Rocky Mountain Power Transmission Five Year Study Findings Meeting

Size: px
Start display at page:

Download "Rocky Mountain Power Transmission Five Year Study Findings Meeting"

Transcription

1 Rocky Mountain Power Transmission Five Year Study Findings Meeting

2 Study Areas for 2009 Goshen Idaho Study Area encompasses parts of Bingham, Bonneville, Butte, Clark, Fremont, Jefferson, Lemhi, Madison and Teton Counties Southwest Utah Study Area encompasses parts of Iron and Washington Counties, Utah Utah Valley Study Area encompasses Utah County in the north to Spanish Fork in the South Nebo Study Area encompasses from Spanish Fork to parts of Juab County and Sanpete County, Utah

3 Goshen, Idaho Study Area Planner Greg Hansen Prepared by: Scott Murdock

4 Goshen, Idaho Study Blue outlined area is an approximation of the Rocky Mountain Power's Service territory as shown by Power Map. Goshen Substation

5 Goshen, Idaho Study Urban and agricultural areas: Service to portions of Bingham, Bonneville, Butte, Clark, Fremont, Jefferson, Lemhi, Madison and Teton counties Larger Communities served: Ammon, Rexburg, Rigby, Shelley & Sugar City Largest population center is Idaho Falls City, which has its own municipality

6 Goshen, Idaho Study Utilities, Municipalities, Rural Electric Associations (REA) in the area: Bonneville Power Administration (BPA) Fall River Electric Association Idaho Falls City Power Idaho Power Lost River Electric Cooperative Lower Valley Electric Rocky Mountain Power (RMP)

7 Load Growth 2009 Demand Total Area load: summer 755 MVA Growth Rate: 2.6% summer & 2.7% winter Anticipated 2014 Demand Total Area load: 917 MVA

8 250 MVA of participating Load

9 Sub-Transmission Substations Goshen, Idaho study has eight operating areas: Amps, Scoville (Antelope), Big Grassy, Bonneville, Goshen, Jefferson, Rigby and Sugarmill

10 Big Grassy Amps Jefferson Rigby Bonneville Antelope (Scoville) Sugarmill Goshen

11 N-0 Conditions Idaho Falls Power : kv, 25MVA transformer at Westside substation kv, 25MVA mobile.

12 N-0 Conditions Problem: Low voltage on the 69 kv bus at Hamer in Solution: Change source for Hamer by transferring to Jefferson.

13 N-0 Conditions Problem: Excessive voltage swings at Big Grassy. Transmission path, load swings and phase shifter largely effect voltage. Solution: New cap bank at Big Grassy: 33 Mvar Install 69kV, (3) steps of 11 Mvar each cap bank, In-service spring, Arrangement and controls, similar to Amps Cap Bank 2. Voltage control on Circuit Switchers 3. SCADA on new circuit breaker and circuit switchers. 4. Proper Protection and Control. To Jefferson 3 Ci r* 3 cui Circuit t Br eaker Switchers s Mobile Connection Big Grassy Substation 69 kv To Dillon 161 kv kv 3-11 MVAR To Sandune * Review cost of circuit switchers and regular switch. If switch is less can install 2 circuit switches and one switch. S. Murdock, Area Planning S. Smith, Planning Technologies BigGrasseyCapBank.cdr 2/27/2009

14 N-0 Conditions Problem: Dubois, Hamer, Mud Lake, Ririe, South Fork and Thornton have regulators which will overload. Solution: Upgrade regulators at Dubois (2012), South Fork (2013) and Thornton (2009). Distribution load transfers* mitigate the other substations overloads. *The Mud Lake Transfer (2011) will require distribution circuit upgrades.

15 N-0 Conditions Problem: Moody (2013), Goshen #7 (2011) and Ucon (2014) transformers will overload. Solution: Distribution load transfers*. *The Moody Transfer will require distribution circuit upgrades.

16 N-0 Conditions Problem: Rigby-Ucon 69 kv line overloaded in last study year. Solution: Change Ucon source to Goshen. Solution: Ririe 69 kv Tap Line overload in last year Solution: Distribution Load transfers. P A G E - 16

17 N-1 Conditions Problem: Loss of a kV transformer at Goshen may result in overload of the remaining transformer up to 107% today, 113% in 2014*. Solution: Third party work at Three Mile Knoll shifts load from Goshen. *This is anticipating the local generation output is average.

18 N-1 Conditions Problem: Loss of a Rigby kv transformer Solution: Using a mobile back-up transformer (located at Goshen substation) corrects the Problem through the study period. Some load (10 MVA to 30 MVA throughout the study period) will be out during the installation of the mobile.

19 N-1 Conditions Problem: Loss of Goshen-Bonneville 161 kv line overloads the Goshen-Sugarmill 161 kv line. In 2014 this overload is three percent over the emergency rating. Solution: Reconductor the existing line (16.5 miles) with a 400 MVA rated conductor in 2014.

20 N-1 Conditions Underrated Fault Duty Equipment Problem: Total number is 6 pieces of equipment are underrated for fault duty Solution: Goshen CB 165, Goshen CS167I, Goshen CS169I, Goshen CS 189I, Goshen 199I and the Goshen #7 High side fuses Replace Circuit Switchers, fuses and Breaker during regular maintenance to insure proper fault interrupting. Underrated Switch Problem: Switches at Jeffco: 61A, 63A; Osgood: 1, 3; Rexburg Jct. 67A, 68A; and Ucon 61A, 62A have no capability to break parallel. Solution: Replace switch with air break switch that have loop opening and line dropping attachments.

21 Construction Schedule 2009 Construction 7-1 Thornton Upgrade regulators to 509 kva units $96, Construction - In service by May 1 of this year Replace CB11 & CB12 for maintenance and 7-2 Anderson $111,000 reliability Problems 7-3 Canyon Creek 7Xfr-1T Hamer Replace Transformer high-side fuses. (This will require review of protection to ensure proper coordination) Transfer Hamer from Big Grassy CB 67 to Jefferson CB 65. This is until cap bank is installed at Big Grassy. $9,500 subtotal $216,500 n/a

22 Construction Schedule 2011 Construction - In service before May 1 of this year 7-4 Big Grassy Install 69 kv, 3 steps of 11 Mvar ea. (33 MVAr total) Approved job May $1,669,935 7Xfr-2D Goshen #7 Transfer Load to Shelley. n/a 7Xfr-3T Hamer Transfer Hamer to Big Grassy from Jefferson n/a 7D-1 Mud Lake Distribution Transfer from Mud Lake to Anderson. Will require line work. $750, Various Install bottles or replace switches with bottles to improve system operability $640,000 subtotal $3,059, Construction - In service before May 1 of this year 7-6 Dubois Replace regulators with 509 kva units to get full capacity from transformer. $100,000 subtotal $125,000

23 Construction Schedule 2013 Construction - In service before May 1 of this year 7D-2 Moody Transfer distribution load to Newdale (may require distribution line regulators) $80, South Fork Replace regulators with 509 kva units to get full capacity from transformer. $100,000 subtotal $180, Construction - In service before May 1 of this year 7-8 Goshen to Reconductor 16.5 miles of ACSR with high Sugarmill temperature conductor good for 400 MVA. $6,500,000 7Xfr-4D Hamer Transfer 500 kw to Anderson. Switching only n/a 7Xfr-5T Rigby Move Ucon to Goshen. n/a subtotal $6,500,000 Grand total $10,081,435

24 Questions?

25 Prepared by: Seth Riding Area Planner: Nathan Powell

26 Primary Sources Washington Co kv line from Sigurd to Red Butte /138 kv at Red Butte and Central /69 kv at Middleton Iron Co kv line from Sigurd to West Cedar kv line from Cameron to Coleman /138 kv at Parowan /138 kv at West Cedar /69 kv at Coleman 3

27 Summer 2009 Load: 462 MVA Average Growth Rate: 5.6% (34 MVA per year) Projected Summer 2014 Load: 773 MVA

28 Coleman Transformer #4 Problem 2013 the area utilization for Coleman and Crosshollow is projected to be over 90%. Solution Replace Transformer #4 with a 40 MVA transformer and replace the 12.5 kv bus with 2000A rated bus. Estimated Cost: $3.25 million

29 Parowan Coleman Substation Coleman 138 kv breaker Problem An outage on the 138 kv line between Coleman and West Cedar will result in a loss of Crosshollow substation and all four transformers at Coleman. Solution Install a 138 kv breaker where switch 107A is located. Estimated Cost: $400, kv 69 kv and below West Cedar

30 Middleton 138 kv breaker Problem An outage to either 138/69 kv transformer results in a loss of both transformers and all 69 kv loads fed from Middleton. Solution Install a 138 kv breaker and 138 kv bus to separate transformers #4 and #5. Estimated Cost: $1.5 million

31 Middleton to St George 138 kv line Problem An outage on the 138 kv line between Middleton and St George will cause a loss of Middleton substation and approximately 50 MW. Solution Install a second 138 kv line between Middleton and St George with added breaker positions at each substation. Estimated Cost: $3 million

32 Parowan 230 kv switch 138 kv 230 kv Cameron and Coleman Problem An outage on the 230 kv line between Sigurd and Parowan will cause an outage to West Cedar resulting in the 138 kv voltage between Coleman and Cameron to fall below.95 pu. The 230 kv line from Sigurd to Parowan to West Cedar will be out until repairs are complete. West Cedar Solution Install a 230 kv switch at Parowan on the line to Sigurd. Sigurd Estimated Cost: $200,000

33 West Cedar 138 kv breaker Problem An outage to the 230/138 kv transformer at West Cedar will result in a loss of the north side of the 138 kv bus and the 138/34.5 kv transformer which feeds the 34.5 kv in Iron County. Solution Install a 138 kv breaker on the low side of the 230/138 kv transformer. Sigurd Estimated Cost: $900, kv 138 kv 230 kv West Cedar Substation Red Butte Parowan Commerce

34 Three Peaks and Parowan Substations Problem Limited sources to Iron county with low voltage on the 138 kv system in steady-state conditions. To Red Butte Solution Completed 138 kv breaker at Cameron and a 138 kv two stage 30 MVAr capacitor bank at Parowan. Under construction 345/138 kv substation with a 30 MVAr capacitor bank at Three Peaks, a new 138 kv line from WECCO to Three Peaks and a four breaker ring bus at Parowan. This construction to be completed by summer Estimated Cost: $60 million

35 To Sigurd To Parowan Red Butte to St. George Rebuild 138 kv line to 345 kv double circuit To Harry Allen Problem The 138 kv lines from Red Butte and Central to St George are the main sources for Washington county. The growth in will require an additional 345 kv source to St George and this is the first phase of the project. Solution Rebuild existing 138 kv line between Red Butte and St George to double circuit 345 kv and initially operate single circuit 138 kv. Construction to be completed in Estimated Cost: $15.7 million

36 Windy Ridge Substation To Middleton Problem In 2009 RMP purchased a 69 kv line from Garkane Energy feeding the Twin Cities area. The line will be fed through Hurricane City s Clifton Wilson facility until a new facility is constructed. Solution Build Windy Ridge substation with a 69 kv breaker to feed from the Gateway to Toquerville 69 kv line. Construction to be completed in Estimated Cost: $2 million

37 Middleton to Gateway, rebuild 2.2 miles Problem A 2.2 miles section of 4/0 ACSR between Middleton and Gateway is projected to overloaded by summer Solution The long term plan for this line is to convert to 138 kv. Rebuild this section of line with 1272 ACSR at 138 kv construction. Estimated Cost: $1.2 million

38 Red Butte to St George Operate double circuit 138 kv Problem The growth in Washington county is causing the existing 138 kv lines to be insufficient in an outage condition. Also the long term plan is to bring 345 kv to St George substation. Solution Finish the 345 kv double circuit line from Red Butte to St George and operate double circuit 138 kv. Projected to be operated 345 kv around 2017 to Estimated Cost: $2 million

39 Middleton to Gateway, finish 138 kv conversion Problem The single delivery point at St George substation for Washington county provides a reliability issue for the area. Also, by 2012 Middleton #4 138/69 kv transformer will not be able to support the 69 kv load with an outage to the Middleton #5 138/69 kv transformer. Solution Complete 138 kv conversion of 69 kv line from Middleton to Gateway in 2013 removing part of the 69 kv load fed from Middleton. Connect with proposed 345/138 kv substation in west Hurricane to provide an alternate source to the area. Estimated Cost: $15 million

40 Projects proposed by Main Grid Planning during the study period. Install an SVC connected to the 345 kv bus at Red Butte in Estimated cost is $26.5 million Construct second 345 kv line from Sigurd to Red Butte by Estimated cost is $153 million.

41 N-0 Project Coleman Install a 40 MVA kv transformer to replace transformer #4 $ 3,250,000 subtotal $ 3,250,000 N-1 Projects Coleman Install a 138 kv breaker protecting line to West Cedar $ 400,000 Parowan Install a 230 kv switch at Parowan on line to Sigurd $ 200,000 Middleton Install a new 138 kv breaker $ 1,500,000 Middleton Construct a second 138 kv line to St George $ 3,000,000 West Cedar Install a 138 kv breaker on the kv transformer #1 $ 900,000 subtotal $ 6,000,000 Projects Under Construction Three Peaks Construct a kv substation with 30 MVAr capacitor bank $ 60,000,000 Parowan Install a 138 kv four breaker ring bus (part of Three Peaks) $ 15,700,000 Red Butte - St George Rebuild existing 138 kv line to double circuit 345 kv (operate single circuit 138 kv) Windy Ridge Install a 69 kv breaker station with metering for the line to Twin Cities $ 2,000,000 subtotal $ 77,700,000 SWTTF Identified Projects Middleton - Gateway Rebuild 2.2 miles of 4/0 ACSR at 138 kv with 1272 ACSR $ 1,200,000 Red Butte - St George Operate the 345 kv double circuit line as 138 kv double circuit $ 2,000,000 Middleton - Gateway Finish 138 kv conversion and connect with new Hurricane West substation $ 15,000,000 subtotal $ 18,200,000 Main Grid Identified Projects Red Butte Install a 345 kv SVC $ 26,500,000 Sigurd - Red Butte Install a second 345 kv line from Sigurd to Red Butte $ 153,000,000 subtotal $ 179,500,000 Total $ 284,650,000

42

43 Utah Valley Study Prepared by: Tim Reynolds Area Planner: Nathan Powell

44 Utah Valley Study Utah County in the North Wallsburg Substation to the East Part of Utah Lake to the West Spanish Fork and Benjamin in the South

45 Utah Valley Study UAMPS Members Encompassed in Area Lehi, Eagle Mountain, Springville, Strawberry ESD, and Payson UMPA Members Encompassed in Area Spanish Fork, Salem, and Provo

46 Load Growth Base System Loads Summer 2008: 865 MW Growth Average Percentage 4.5% Average growth of 43 MW per year Projected System Loads Summer 2014: 1166 MW

47 N-0 Conditions Saratoga Transformer Problem In 2011: Saratoga #1 XFMR at 101% Most feeders are projected to be close to or over 100% of their rating Solution: (Approved project) Install a second LTC transformer at Saratoga substation. Estimated cost at $7.6 Million

48 N-0 Conditions American Fork Transformer Problem In 2012: American Fork #1 XFMR at 98% Utilization for American Fork, Tri-City #1, and Highland #2 will be at 93% By 2014, upon a loss of one of the Hale to Highland or Highland to West Field 138 kv line, the Tri-City to American Fork 138 kv line loads to 93% Solution Install a second 40 MVA LTC transformer at American Fork substation Perform transmission work to utilize a unused 46 kv line to put American Fork on another source. Estimated cost at $8.5 Million

49 N-0 Conditions West Field Transformer Problem In 2013: West Field #1 XFMR at 101% Transfers are maxed out with existing distribution feeders Solution: Install a second 40 MVA LTC transformer at West Field substation. Estimated cost at $6 Million

50 N-1 Conditions Vineyard substation Problem In 2013: Under the loss of the kv transformer at Hale or the Hale to Willow Ridge 46 kv line Timp to Vinyard Tap line loaded to 100%. Timp kv XFMR at 107% Weak 46 kv system prevents looping Sharon (Overloads are only transferred to another line). Solution: Rebuild ~4 miles of 46 kv line to 1272 ACSR at 138 kv construction Convert Vineyard to kv substation with a LTC, 40 MVAR XFMR Estimated cost at $6 Million

51 N-1 Conditions Spanish Fork kv Transformer & Spanish Fork to Dry Creek 138 kv line Problem In 2014: Estimated that the loss of one kv transformer at Spanish Fork will overload the other one after switching to 100% of name plate rating. Loss of the Dry Creek to Spanish Fork 138 kv line overloads the kv transformers at Spanish Fork and loss of power to the Nebo Study Area. There are extremely few to no load transfers available to correct this issue Solution: Build a new kv substation named Clover in the Nebo Study Area Estimated cost at $44 Million

52 N-1 Conditions Underrated Fault Duty Equipment Problem Total number is 12 pieces of equipment are underrated for fault duty Solution: Cherrywood CS134I, Hale CB102, Highland CS134I, Orem CS44I, Spanish Fork CS141I, Spanish Fork CS143I, Spanish Fork 139I, Spanish Fork CB46, Spanish Fork CB49, Spanish Fork CB50, Spanish Fork CB51, and Timp CS130I. Replace Transrupters, Circuit Switchers, and Breaker to insure proper fault interrupting Underrated Switch Problem Switch 133A at Wallsbug substation is not rated to loop open or line drop Solution: Replace switch with air break switch that has loop opening and line dropping attachments

53 Total Construction Costs 2010 Saratoga 2 nd kv XFMR $7.6 Million 2012 American Fork 2 nd kv XFMR and Transmission Work $8.5 Million Vineyard Convert to kv Substation and Transmission Work $6 Million 2013 West Field 2 nd kv XFMR $6 Million 2014 Build Clover Substation, a kv Substation $44 Million Total - $52.1 Million ($28.1 Million without Clover substation)

54 Questions?

55 Nebo Utah Study Prepared by: Jeremy Viula Area Planner: Nathan Powell

56 System Overview Primary Sources kv lines from Spanish Fork kv line from Spanish Fork Normally Open / Limited Back-up Sources kv lines from Utah Valley kv lines from Gunnison kv lines from Scipio kv lines from Delta

57 Load Growth Base System Loads Summer 2008: 89 MW Growth Average Percentage 3.7% Average growth of 3 MW per year Projected System Loads Summer 2013: 120 MW

58 N-0 Conditions Spanish Fork Substation Problem In 2010: Jerusalem 138-kV bus voltage projected to sag to 0.88 p.u. Vickers, Nephi City, Comnet, Levan, Juab, Fayette, Fool Creek, North Field, and Oak City 46-kV bus voltages lower than 0.90 p.u. Solution: Change both Spanish Fork kv transformers high side no load tap from 345 to

59 N-0 Conditions North Fields Substation Problem In 2010: Oak City and North Fields substation 46-kV bus voltage projected to sag to 0.89 p.u. Solution: Install 600-kVAR of distribution power factor correction at North Fields substation. (Included in the Vickers increase line capacity project) Estimated cost: $45,000

60 N-0 Conditions Ockey Substation Problem In 2010: Ockey XFMR at 110% of normal summer rating Solution: Replace the existing Ockey transformer with 500-kVA kv transformer Estimated cost: $88,800

61 N-0 Conditions Vickers Substation Problem In 2010 The Nebo-Vickers B 46-kV line is projected to load to 124% normal summer rating with the 46-kV voltages dropping to 0.86 p.u. at Oak City, Fayette, and Nephi City The Vickers-Nephi City 46-kV line will be loaded to 100% normal summer rating) The Vickers kv transformer is projected to overload to 100% of normal summer rating Solution: Add four 46- kv line circuit breakers at the Vickers substation Connect the Scipio 46-kV line to the Vickers bus by building 1,000 feet of 46-kV line Rebuild the Vickers-Nephi City 46-kV line (1.0 mile) with 795 ACSR conductor Add 600-kVAR of distribution capacitors to the North Fields substation kV feeder Install fans on the existing Vickers substation transformer to increase capacity to 2.3 MVA Estimated cost: $4.3 Million

62 N-0 Conditions Vickers Substation (Continued) Problem In 2013: The Vickers kv transformer (with fans added in 2010) is projected to overload to 104% of normal summer rating Solution: Replace existing transformer with a surplus kv 3.75-MVA (or higher) transformer Estimated cost: $300,000

63 N-0 Conditions Vickers Substation (Continued)

64 N-0 Conditions North Fields Substation Problem In 2011: North Fields XFMR at 100% normal summer rating Solution: Fit the existing North Fields transformer with fans to increase capacity to 2.3- MVA Estimated cost: $10,000

65 N-0 Conditions Elberta Substation Problem In 2012: Elberta XFMR at 100% of normal summer rating Solution: Replace Elberta XFMR with a surplus kv 10- MVA (or higher) transformer Estimated cost: $300,000

66 N-0 Conditions Rasmusson Substation Problem In 2012: Rasmusson XFMRs at 103% of normal summer rating Solution: Replace T-4510, 4527,4728 with a single surplus kv 2-MVA (or higher) transformer Estimated cost: $300,000

67 N-0 Conditions Nebo Substation Problem In 2012: The Jerusalem and Ashgrove 138-kV bus voltage is projected to sag to 0.89 p.u. The Vickers, Soma, Moroni Feed Nephi, Nephi City, Comnet, Levan, Juab, Fayette, Fool Creek, North Field, Canyon Fuel, and Oak City 46 kv buses also experiencing voltages under 0.9 p.u. Solution: Add second step of 12 MVAR to the existing 11- MVAR capacitor bank Estimated cost: $900,000

68 N-1 Conditions Spanish Fork kv Transformer & Spanish Fork to Dry Creek to Nebo 138 kv line Problem Today: Loss of power the Nebo Study Area In 2014: Estimated that the loss of one kv transformer at Spanish Fork will overload the other one after switching to 100% of name plate rating. Loss of the Dry Creek to Spanish Fork 138 kv line overloads the kv transformers at Spanish Fork and loss of power to the Nebo Study Area. Solution: Build a new kv substation named Clover near the Nebo Substation Estimated cost at $44 Million

69 Total Construction Costs North Fields Install Distribution Power Factor Correction $45,000 Ockey Replace Transformer $88,800 Vickers Add Four Breakers and Transmission Work $4.2 Million Vickers Install Transformer Fans $10,000 North Fields Install Transformer Fans $10,000 Elberta Replace Transformer $300,000 Rasmusson Replace Transformer $300,000 Nebo Second Step12 MVAR Capacitor Bank $900,000 Vickers Replace Transformer $300,000 Build Clover Substation, a kv Substation $44 Million Total - $50.2 Million ($6.2 Million without Clover substation)

70 Thank You For Your Time Questions?

SOUTHERN MARYLAND ELECTRIC COOPERATIVE, INC. HUGHESVILLE, MD

SOUTHERN MARYLAND ELECTRIC COOPERATIVE, INC. HUGHESVILLE, MD SOUTHERN MARYLAND ELECTRIC COOPERATIVE, INC. HUGHESVILLE, MD HOLLAND CLIFF HEWITT ROAD 230 KV TRANSMISSION LINE PROJECT ELECTRIC ALTERNATIVE EVALUATION STUDY BLACK & VEATCH CORPORATION B&V Project 146026(G)

More information

NTTG Study Plan for the 2014-2015 Public Policy Consideration Scenario

NTTG Study Plan for the 2014-2015 Public Policy Consideration Scenario NTTG Study Plan for the 2014-2015 Public Policy Consideration Scenario Table of Contents NTTG Study Plan for the 2014-2015 Public Policy Consideration Scenario Table of Contents... 2 1. Executive Summary...

More information

Treasure Valley Electrical Plan

Treasure Valley Electrical Plan Treasure Valley Electrical Plan Community Advisory Committee January 25, 2006 Agenda 10 a.m. Welcome 10:10 a.m. Follow up DSM discussion 10:30 a.m. TVEP CAC process update 10:40 a.m. Transmission Presentation

More information

16 West Coast Regional Plan

16 West Coast Regional Plan 16 West Coast Regional Plan 16.1 Regional overview 16.2 West Coast transmission system 16.3 West Coast demand 16.4 West Coast generation 16.5 West Coast significant maintenance work 16.6 Future West Coast

More information

Rule 5.500 Fast Track Analysis for National Life Insurance Co.

Rule 5.500 Fast Track Analysis for National Life Insurance Co. Rule 5.500 Fast Track Analysis for National Life Insurance Co. For a 500 kw Solar array to be located at 155 Northfield Street in Montpelier, Vermont Green Mountain Power Pam Allen Date: 5/31/13 SECTION

More information

How To Operate The Williston Uvls

How To Operate The Williston Uvls WND Winter Operating Guide 2012/2013 1 WND Operating Study Using EQ-890-2012WIN- FINAL.sav developed through the 890 process Got load updates from MDU, Central Power, UM G&T Made several topology updates

More information

Emera Maine Proposed Potential Transmission Projects. Line Identification Line 75 - KR Sub. Estimated Cost $201,464 $0 $3,200,000

Emera Maine Proposed Potential Transmission Projects. Line Identification Line 75 - KR Sub. Estimated Cost $201,464 $0 $3,200,000 L75 & BW3 Rebuild ROW Phase I Keene Rd. Expansion for Oakfield Wind KR Transformer Addition Line Identification Line 75 - KR Sub Location Bangor Chester Chester Estimated Cost $201,464 $0 $3,200,000 Voltage

More information

Star Ratings From Medicare For Utah Nursing Homes 2014

Star Ratings From Medicare For Utah Nursing Homes 2014 Federal Provider Number Provider Name 6003 HERITAGE PARK CARE CENTER 6006 MT OLYMPUS REHABILITATION CENTER 6009 KINDRED NURSING & REHABILITATION - WASATCH CARE 6020 PIONEER CARE CENTER 609 SPRING CREEK

More information

Cross-Tie Transmission Line. Ravikanth Varanasi Principal Transmission Planner

Cross-Tie Transmission Line. Ravikanth Varanasi Principal Transmission Planner Cross-Tie Transmission Line Ravikanth Varanasi Principal Transmission Planner Overview ~213 mile 500-kV transmission line between PacifiCorp s proposed Clover 500 kv substation with NV Energy s Robinson

More information

Chapter 1. Network Structures

Chapter 1. Network Structures Chapter 1 Network Structures Definition Standard IEC 60038 defines voltage ratings as follows: Low voltage (): for a phase-to-phase voltage of between 100 V and 1,000 V, the standard ratings are: 400 V

More information

Generation Interconnection Feasibility Study Report-Web Version. PJM Generation Interconnection Request Queue Position Z1-055

Generation Interconnection Feasibility Study Report-Web Version. PJM Generation Interconnection Request Queue Position Z1-055 Generation Interconnection Feasibility Study Report-Web Version For PJM Generation Interconnection Request Queue Position Z1-055 South Bend Generation Project March 2014 PJM Interconnection 2014. All rights

More information

Transmission Planning Study (Year 2022) for Cherokee 4 Replacement Alternatives. Final Report

Transmission Planning Study (Year 2022) for Cherokee 4 Replacement Alternatives. Final Report Transmission Planning Study (Year 2022) for Cherokee 4 Replacement Alternatives (Required per CPUC Decision No. C10-1328) Final Report (Submitted with Public Service s 2011 ERP) Executive Summary The objective

More information

Green Power Connection Net Energy Metering Engineering Review Process in Delaware and Speeding Up the Application Fee Process

Green Power Connection Net Energy Metering Engineering Review Process in Delaware and Speeding Up the Application Fee Process Green Power Connection Net Energy Metering Engineering Review Process in Delaware and Speeding Up the Application Fee Process Presented by: Marianne Mannschreck Date: Welcome A Look at the Net Energy Metering

More information

85 South 400 East; St. George, UT Northeast Corner of Building

85 South 400 East; St. George, UT Northeast Corner of Building ST. George, UT & vicinity Sunday 2:45 PM Purgatory Correctional Facility Hurricane, UT Men's ARP Group 2:45 AM Purgatory Correctional Facility Hurricane, UT Women's ARP Group 7:30 PM Buena Vista Stake

More information

Treasure Valley Electric Plan - Community Advisory Committee

Treasure Valley Electric Plan - Community Advisory Committee Treasure Valley Electric Plan - Community Advisory Committee What is a transmission line and why are they necessary? A transmission line is used to conduct electricity between two points. Without high

More information

Chapter 7 - Appendix A

Chapter 7 - Appendix A Chapter 7 - Appendix A Transmission and Distribution Supplemental Information Table 7A.1 MTEP Transmission Projects in Missouri 1 Project Approved Project Title Project Description Category Estimated Cost

More information

Q140 Cluster Addendum

Q140 Cluster Addendum Cluster Addendum 1. INTRODUCTION This Interconnection Customer (IC), submitted a Small Generator Interconnection Request (IR) to Arizona Public Service Company (APS) for their proposed project, located

More information

Houston Region Import Capacity Project

Houston Region Import Capacity Project Houston Region Import Capacity Project July 25, 2013 Prepared by: CenterPoint Energy Transmission Planning Executive Summary 3 1. Introduction 5 2. Methodology and Study Assumptions 7 2.1 Case Description

More information

BL20A0501 Electricity distribution technology. Introduction Jarmo Partanen

BL20A0501 Electricity distribution technology. Introduction Jarmo Partanen BL20A0501 Electricity distribution technology Introduction Jarmo Partanen Introduction to ED Prof. Jarmo Partanen, D.Sc Jukka Lassila Topics of lectures Introduction to Electricity Distribution, 27.10

More information

6. The estimated costs here do not include any applicable ITCC tax

6. The estimated costs here do not include any applicable ITCC tax General Notes and Clarifications: 1. The following estimated costs are based on past experiences and are intended to provide an order of magnitude of the total project cost given the major system components.

More information

Updated SYSTEM IMPACT STUDY OF NEW ENGLAND AREA

Updated SYSTEM IMPACT STUDY OF NEW ENGLAND AREA CROSS SOUND CABLE PROJECT 330MW HVdc INTERCONNECTION BETWEEN NEW HAVEN, CONNECTICUT AND SHOREHAM, NY Updated SYSTEM IMPACT STUDY OF NEW ENGLAND AREA Subordinate Status Removal and Amendment of Approved

More information

Distributed Generation and the Impact on a Distribution System. Brian Lassiter Technical Sales Engineer

Distributed Generation and the Impact on a Distribution System. Brian Lassiter Technical Sales Engineer Distributed Generation and the Impact on a Distribution System Brian Lassiter Technical Sales Engineer Company Overview Founded in 1989 in Abilene, TX Industry leader in Engineering and Operations Utility

More information

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Course No: E02-010 Credit: 2 PDH Boris Shvartsberg, Ph.D., P.E., P.M.P. Continuing Education

More information

Guideline for Energy Efficient Electrical systems for building. Presentation by TERI

Guideline for Energy Efficient Electrical systems for building. Presentation by TERI Guideline for Energy Efficient Electrical systems for building Presentation by TERI Objective of study The study highlights how BBMP can implement energy efficiency measures in building in co-ordination

More information

Generation Interconnection System Impact Study Report. For. PJM Generation Interconnection Request Queue Position X1-114.

Generation Interconnection System Impact Study Report. For. PJM Generation Interconnection Request Queue Position X1-114. Generation Interconnection System Impact Study Report For PJM Generation Interconnection Request Queue Position X1-114 Sandyston January 2012 Preface The intent of the System Impact Study is to determine

More information

PJM Merchant Transmission Request. Queue #R75. Mitchell Shepler Hill 138 Kv Feasibility / System Impact Study

PJM Merchant Transmission Request. Queue #R75. Mitchell Shepler Hill 138 Kv Feasibility / System Impact Study PJM Merchant Transmission Request Queue #R75 Mitchell Shepler Hill 138 Kv Feasibility / System Impact Study 413038v1a March 2007 PJM Interconnection 2007. All rights reserved. Preface The intent of the

More information

School District Design and Project Management For Rochester, NY

School District Design and Project Management For Rochester, NY The following is a list of projects completed by Engineered Solutions or its President Eric Sheffer, P.E.: Medium Voltage Design and project management for replacement of 1500KVA double ended substation

More information

Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE

Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE Understanding Power Factor and How it Affects Your Electric Bill Presented by Scott Peele PE Understanding Power Factor Definitions kva, kvar, kw, Apparent Power vs. True Power Calculations Measurements

More information

FINAL. Alternative Evaluation. for the. Proposed Burlington-Wray 230-kilovolt Transmission Project

FINAL. Alternative Evaluation. for the. Proposed Burlington-Wray 230-kilovolt Transmission Project FINAL Alternative Evaluation for the Proposed Burlington-Wray 230-kilovolt Transmission Project Prepared by Tri-State Generation and Transmission Association, Inc. 1100 W. 116th Avenue Westminster, Colorado

More information

D.3 South Minneapolis Electric Distribution Delivery System Long-Term Study

D.3 South Minneapolis Electric Distribution Delivery System Long-Term Study D.3 South Minneapolis Electric Distribution Delivery System Long-Term Study Xcel Energy April 2009 Hiawatha Project SOUTH MINNEAPOLIS ELECTRIC DISTRIBUTION DELIVERY SYSTEM LONG-TERM STUDY Scott Zima Distribution

More information

PG&E Transmission Interconnection Handbook. Section L3: SUBSTATION DESIGN FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES

PG&E Transmission Interconnection Handbook. Section L3: SUBSTATION DESIGN FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES Section L3: SUBSTATION DESIGN FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES PURPOSE This section provides substation design information for Load Entities interconnected at transmission voltage

More information

RELIABILITY PLANNING CRITERIA

RELIABILITY PLANNING CRITERIA RELIABILITY PLANNING CRITERIA Version 4.0 01/20/2016 Date Rev. No. Individual Making Edits REVISION HISTORY Reason / Comments 07/01/2013 1 J. Johnson Initial document 06/06/2014 2 R. Chapman Document review;

More information

EMS Certficate Companies Utah

EMS Certficate Companies Utah County Service # Agency BEAVER 0101L BEAVER AMBULANCE SERVICE BEAVER 0102L MILFORD VALLEY AMBULANCE SERVICE BOX ELDER 0201L BRIGHAM CITY AMBULANCE BOX ELDER 0202L TREMONTON CITY FIRE DEPARTMENT BOX ELDER

More information

3. TYPES OF SERVICE AVAILABLE. 3.1 Scope

3. TYPES OF SERVICE AVAILABLE. 3.1 Scope 3. TYPES OF SERVICE AVAILABLE 3.1 Scope UI supplies 60 hertz, alternating current with different voltage and ampere ratings. Not all voltage and ampere ratings are available throughout the entire service

More information

F.C. Chan General Manager, CLP Engineering Ltd., Hong Kong SAR, China

F.C. Chan General Manager, CLP Engineering Ltd., Hong Kong SAR, China ELECTRIC POWER DISTRIBUTION SYSTEMS F.C. Chan General Manager, CLP Engineering Ltd., Hong Kong SAR, China Keywords: Distribution system planning, Load characteristics, Subtransmission Lines, Distribution

More information

Conservation Voltage Reduction (CVR)

Conservation Voltage Reduction (CVR) Conservation Voltage Reduction (CVR) Nicholas Abi-Samra Senior Vice President October 15, 2013 DNV GL Energy Table of Contents What does CVR do? Why Does CVR Work? DNV GL s CVR Project Experience Needs

More information

For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz)

For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz) 24 1. NETWORK CONFIGURATIONS definition Standard IEC 38 defines voltage ratings as follows: - Low voltage () For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690

More information

State of Utah DEPARTMENT OF COMMERCE Division of Corporations & Commercial Code BUSINESS LICENSING & REGISTRATION GUIDE

State of Utah DEPARTMENT OF COMMERCE Division of Corporations & Commercial Code BUSINESS LICENSING & REGISTRATION GUIDE State of Utah DEPARTMENT OF COMMERCE Division of Corporations & Commercial Code BUSINESS LICENSING & REGISTRATION GUIDE All businesses operating in Utah must be registered with the Department of Commerce

More information

Transmission Planning Standards for the Baltimore Gas & Electric Company Transmission System

Transmission Planning Standards for the Baltimore Gas & Electric Company Transmission System Transmission Planning Standards for the Baltimore Gas & Electric Company Transmission System Prepared By: Transmission Planning Unit Baltimore Gas & Electric Company Table of Contents 1. INTRODUCTION

More information

Minimizing Impact of Electric Utility Outages with Backup Generation

Minimizing Impact of Electric Utility Outages with Backup Generation Minimizing Impact of Electric Utility Outages with Backup Generation Introduction of the Speaker Michael Dempsey, PE Senior Electrical Engineer Carter & Burgess, Inc. Energy & Power Solutions Facility

More information

GPS Interfacing of Banediya Feeder (M.P) Using MI Power Software

GPS Interfacing of Banediya Feeder (M.P) Using MI Power Software GPS Interfacing of Banediya Feeder (M.P) Using MI Power Software Swati Paliwal 1, V.K Tayal 2, H.P Singh 3 Assistant professor, Department of Electrical & Electronics Engineering, Northern India Engineering

More information

PA PUC AERS & Metropolitan Edison Company Site Visit

PA PUC AERS & Metropolitan Edison Company Site Visit PA PUC AERS & Metropolitan Edison Company Site Visit October 26, 2010 Scott Lowry Director-Operation Services, Met-Ed Andrew Zulkosky Manager-Engineering, Met-Ed Curt Christenson Manager-York Customer

More information

LOCAL EMERGENCY RESPONSE AUTHORITY PHONE ROSTER BY COUNTY*

LOCAL EMERGENCY RESPONSE AUTHORITY PHONE ROSTER BY COUNTY* LOCAL EMERGENCY RESPONSE AUTHORITY PHONE ROSTER BY COUNTY* County LERA Office / Cell Ada County ISP all areas outside the fire districts 846-7500 Boise Boise F.D. Division Chief 570-6544 / 941-0746 Eagle

More information

Generation Interconnection Facilities Study Report. For. PJM Generation Interconnection Request Queue Position R11. South River

Generation Interconnection Facilities Study Report. For. PJM Generation Interconnection Request Queue Position R11. South River Generation Interconnection Facilities Study Report For PJM Generation Interconnection Request Queue Position R11 South River May 2012 Transmission Owner Facilities Study Summary Description of Project

More information

Unitil Energy Systems, Inc. Interconnection Standards For Inverters Sized Up To 100 kva

Unitil Energy Systems, Inc. Interconnection Standards For Inverters Sized Up To 100 kva Unitil Energy Systems, Inc. Interconnection Standards For Inverters Sized Up To 100 kva Issued: August 2009 SIZED UP TO 100 KVA TABLE OF CONTENTS 1.0 Introduction... 1 1.1 Applicability... 1 1.2 Definitions...

More information

Idaho Trauma Registry - ITR EMS Agency Codes

Idaho Trauma Registry - ITR EMS Agency Codes EMS Agency License Number EMS Agency Name 5601 Aberdeen / Springfield Fire District 8405 Ada Boi, Inc. 8407 Ada County Paramedics 8728 Air Idaho Rescue 8426 Air Saint Lukes Boise 8515 Air Saint Lukes Magic

More information

Monitoring Underground Power Networks

Monitoring Underground Power Networks Monitoring Underground Power Networks By Mark Stiles Merve Cankaya ABSTRACT Underground electric distribution systems are common in large cities throughout the United States. Power usage for the entire

More information

CyberFortress Data Center at Innovation Park Infrastructure and Topology Guide. Innovation Park Charlotte. NC 28262. DRAFT V0.

CyberFortress Data Center at Innovation Park Infrastructure and Topology Guide. Innovation Park Charlotte. NC 28262. DRAFT V0. Innovation Park Charlotte. NC 28262 DRAFT V0.1 Page 2 CyberFortress Data Center at Innovation Park BECO South purchased Innovation Park in March 2010 and immediately launched a dramatic top-to-bottom $30M

More information

VOLTAGE CONTROL IN DISTRIBUTION SYSTEMS AS A LIMITATION OF THE HOSTING CAPACITY FOR DISTRIBUTED ENERGY RESOURCES

VOLTAGE CONTROL IN DISTRIBUTION SYSTEMS AS A LIMITATION OF THE HOSTING CAPACITY FOR DISTRIBUTED ENERGY RESOURCES VOLTAGE CONTROL IN DISTRIBUTION SYSTEMS AS A LIMITATION OF THE HOSTING CAPACITY FOR DISTRIBUTED ENERGY RESOURCES C. Schwaegerl*, M.H.J. Bollen, K. Karoui #, A. Yagmur + *Siemens AG, # Tractebel STRI AB

More information

UT Based on Home Health Care - Patient survey (HHCAHPS)

UT Based on Home Health Care - Patient survey (HHCAHPS) State CMS Certification Number (CCN)* Provider Name UT 467001 COMMUNITY NURSING SERVICES WEST VALLEY CITY UT 467004 INTERMOUNTAIN HOMECARE OGDEN OGDEN UT 467012 IRON COUNTY HOME HEALTH AGENCY CEDAR CITY

More information

Size template. Grid Connection Masterclass Energex John Lansley Senior Network Solutions Engineer

Size template. Grid Connection Masterclass Energex John Lansley Senior Network Solutions Engineer Size template Grid Connection Masterclass Energex John Lansley Senior Network Solutions Engineer The average system size has doubled since 2010 Key Network Issues Reverse power on up to 12 off 11 kv feeders

More information

Step Voltage Regulators

Step Voltage Regulators Step Voltage Regulators Don Wareham Field Application Engineer Today s Agenda Introduction Voltage Regulator theory Voltage Regulator application considerations Installation and proper bypassing Wrap-up/questions

More information

Iron Hill Corporate Center Newark, DE

Iron Hill Corporate Center Newark, DE Iron Hill Corporate Center Newark, DE Delaware s Premier Suburban Office Park Contact: John Kaczowka (302) 661-6709 or Brian Hopkins (302) 661-6712 Total Project Size 463,085 RSF Red Wing Built in 1988

More information

INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012

INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012 INTRODUCTION TO SYSTEM PROTECTION Hands-On Relay School 2012 CONGRATULATIONS On choosing the field of system protection. It is an exciting, challenging profession. System protection has changed considerably

More information

FY 2009 Economic Stimulus List

FY 2009 Economic Stimulus List FY 2009 Economic Stimulus List The Projects in this List are "Ready to Advertise" within 30-90 days of a Bills Enactment Pavement Preservation Projects Region County PIN Project Location Concept Estimate

More information

How the National Grid System Operates. Chris Gorman Lead Account Executive Syracuse

How the National Grid System Operates. Chris Gorman Lead Account Executive Syracuse How the National Grid System Operates Chris Gorman Lead Account Executive Syracuse 2 Parts of the Electric System Parts of the Electric System 1. Generating Station: Produces Electricity. 2. Transmission

More information

Bill is the author of 15 papers and lectures on transmission lines and other power system topics.

Bill is the author of 15 papers and lectures on transmission lines and other power system topics. Transmission Lines Electricity s Highway This talk starts with an explanation of Surge Impedance Loading and demonstrates how it is used for transmission line work. The St. Clair Curve widely used in transmission

More information

David Payne, P.E. Associate Director February 18, 2014

David Payne, P.E. Associate Director February 18, 2014 David Payne, P.E. Associate Director February 18, 2014 Overview of Texas A&M University State's first public institution of higher education, was opened on Oct. 4, 1876 as the Agricultural and Mechanical

More information

Joint Con Edison LIPA Offshore Wind Power Integration Project Feasibility Assessment

Joint Con Edison LIPA Offshore Wind Power Integration Project Feasibility Assessment Joint Con Edison LIPA Offshore Wind Power Integration Project Feasibility Assessment March 20, 2009 Joint Con Edison LIPA Offshore Wind Power Integration Project Feasibility Assessment Table of Contents:

More information

ESB Networks Response. ERGEG Consultation. Voltage Quality Regulation in Europe

ESB Networks Response. ERGEG Consultation. Voltage Quality Regulation in Europe NETWORKS ESB Networks Response to ERGEG Consultation on Voltage Quality Regulation in Europe Date: 22 February 2007 Distribution System Operator ESB Networks Page 1 of 12 Contents 1.0 INTRODUCTION...3

More information

EL PASO ELECTRIC COMPANY (EPE) GENERATOR INTERCONNECTION FEASIBILITY STUDY FOR PROPOSED XXXXXXXX GENERATION ON THE SIERRA BLANCA-FARMER 69 KV LINE

EL PASO ELECTRIC COMPANY (EPE) GENERATOR INTERCONNECTION FEASIBILITY STUDY FOR PROPOSED XXXXXXXX GENERATION ON THE SIERRA BLANCA-FARMER 69 KV LINE EL PASO ELECTRIC COMPANY (EPE) GENERATOR INTERCONNECTION FEASIBILITY STUDY FOR PROPOSED XXXXXXXX GENERATION ON THE SIERRA BLANCA-FARMER 69 KV LINE El Paso Electric Company System Planning Department April

More information

IESO Supply Deliverability Guidelines

IESO Supply Deliverability Guidelines PUBLIC IMO_GDL_0021 IESO Supply Deliverability Guidelines Issue 3.0 This document is to be used to evaluate long-term system adequacy and connection assessments Public Disclaimer The posting of documents

More information

FIXED CHARGE: This is a cost that goes towards making the service available, including

FIXED CHARGE: This is a cost that goes towards making the service available, including ELECTRICITY BILL COMPONENTS FIXED CHARGE: This is a cost that goes towards making the service available, including installation and maintenance of poles, power lines and equipment, and 24-hour customer

More information

Underground vs. Overhead Transmission and Distribution

Underground vs. Overhead Transmission and Distribution electric power engineering Underground vs. Overhead Transmission and Distribution Your Power System Specialists June 9, 2009 1 NATIONAL TRENDS Municipalities have passed laws requiring new distribution

More information

Western Area Power Administration Rocky Mountain Region (LAPT) Network Integrated Transmission Service. Designated Network Resources

Western Area Power Administration Rocky Mountain Region (LAPT) Network Integrated Transmission Service. Designated Network Resources Customer Name Basin Electric Cheyenne Power and Light City of Fort Morgan & Estimated Maximum Resource MW Point of Receipt Delivering Party & Voltage Antelope Valley 2 Yellowtail Basin Electric 115 kv

More information

SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks

SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks Introduction SCADA (Supervisory Controlled and Data Acquisition) controlled multi-step metalenclosed automatic capacitor

More information

Item 8: Houston Import RPG Project

Item 8: Houston Import RPG Project : Houston Import RPG Project Jeff Billo Manager, Transmission Planning Board of Directors Meeting April 8, 2014 Study Overview ERCOT has determined that there will be a need for additional import capacity

More information

How To Choose A Transformer

How To Choose A Transformer Consider open loop MV network as an example source 1 source 2 NC NC NC or NO main MV switchboard A B Detail design of substation NC NC NC NO NC NC switchboard 1 switchboard 2 switchboard 3 MV MV MV LV

More information

New Supervisory Control and Data Acquisition (SCADA) Based Fault Isolation System for Low Voltage Distribution Systems

New Supervisory Control and Data Acquisition (SCADA) Based Fault Isolation System for Low Voltage Distribution Systems International Conference on Computer and Communication Engineering (ICCCE 2010), 11-13 May 2010, Kuala Lumpur, Malaysia New Supervisory Control and Data Acquisition (SCADA) Based Fault Isolation System

More information

Treasure Valley Electrical Plan

Treasure Valley Electrical Plan Treasure Valley Electrical Plan Prepared by System Planning Department Idaho Power Company Boise, ID Table of Contents Table of Contents... i Executive Summary... 1 Introduction... 3 Technical Input...

More information

Topics. HVDC Fundamentals

Topics. HVDC Fundamentals Topics HVDC Fundamentals Conventional Converters Capacitor Commutated Converters Voltage Source Converters Reactive Power Requirements System Configurations Tapping Control basics High Power Transmission

More information

Future of Electric Distribution Dialogue

Future of Electric Distribution Dialogue Future of Electric Distribution Dialogue Webinar Series Session I: State of U.S. Electric Distribution July 11, 2012 2:00 3:30 p.m. EDT Session I: State of U.S. Electric Distribution 2:00 p.m. Opening

More information

Understanding Delta Conversion Online "Output Power Factor Ratings" - Part 7

Understanding Delta Conversion Online Output Power Factor Ratings - Part 7 Application Note #45 Understanding Delta Conversion Online "Output Power Factor Ratings" - Part 7 Introduction This application note is the seventh in a series on delta conversion theory of operation.

More information

UTILITIES DEPARTMENT NORTH CAMPUS DISASTER RECOVERY PLAN

UTILITIES DEPARTMENT NORTH CAMPUS DISASTER RECOVERY PLAN Page 1 of 27 UTILITIES DEPARTMENT NORTH CAMPUS DISASTER RECOVERY PLAN Page 2 of 27 Table of Contents 1. OBJECTIVE... 4 2. SCOPE... 4 3. COMMUNICATION... 4 4. LOSS OF NATURAL GAS SUPPLY... 5 5. LOSS OF

More information

SALT RIVER PROJECT AGRICULTURAL IMPROVEMENT AND POWER DISTRICT E-33 EXPERIMENTAL PRICE PLAN FOR SUPER PEAK TIME-OF-USE GENERAL SERVICE

SALT RIVER PROJECT AGRICULTURAL IMPROVEMENT AND POWER DISTRICT E-33 EXPERIMENTAL PRICE PLAN FOR SUPER PEAK TIME-OF-USE GENERAL SERVICE SALT RIVER PROJECT AGRICULTURAL IMPROVEMENT AND POWER DISTRICT E-33 EXPERIMENTAL PRICE PLAN FOR SUPER PEAK TIME-OF-USE GENERAL SERVICE Effective: April 2015 Billing Cycle Supersedes: November 2012 Billing

More information

Health Savings Account Eligible Plans

Health Savings Account Eligible Plans Health Savings Account Eligible Plans Secure WELL TH Choices 100% PLAN PREMIUM SAVER NO WORRIES KNOW YOUR COSTS $0 copay yearly women s health checkup $0 copay routine pap smear and mammogram $0 copay

More information

Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer

Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer A Short Circuit analysis is used to determine the magnitude of short

More information

SHE Transmission. 2015_10_30 Transmission Losses Strategy Rev 2.0 October 2015

SHE Transmission. 2015_10_30 Transmission Losses Strategy Rev 2.0 October 2015 SHE Transmission 2015_10_30 Transmission Losses Strategy Rev 2.0 October 2015 Summary This paper presents SHE Transmission s views and approach on the impact of transmission losses on the transmission

More information

Request for Payment Instructions Wholesale Distribution Access Tariff (WDAT) Attachment I - GIP

Request for Payment Instructions Wholesale Distribution Access Tariff (WDAT) Attachment I - GIP Grid Interconnection & Contract Development Request for Payment Instructions Wholesale Distribution Access Tariff (WDAT) Attachment I - GIP Submittal Instructions Prior to submitting your application and

More information

Reactive Power and Importance to Bulk Power System OAK RIDGE NATIONAL LABORATORY ENGINEERING SCIENCE & TECHNOLOGY DIVISION

Reactive Power and Importance to Bulk Power System OAK RIDGE NATIONAL LABORATORY ENGINEERING SCIENCE & TECHNOLOGY DIVISION Reactive Power and Importance to Bulk Power System OAK RIDGE NATIONAL LABORATORY ENGINEERING SCIENCE & TECHNOLOGY DIVISION Outline What is Reactive Power and where does it come from? Why is it important?

More information

Achieving Operational Efficiencies through On-Line Substation Monitoring. Vince Polsoni Powerstream Inc. Manager Station Sustainment EDIST 2016

Achieving Operational Efficiencies through On-Line Substation Monitoring. Vince Polsoni Powerstream Inc. Manager Station Sustainment EDIST 2016 Achieving Operational Efficiencies through On-Line Substation Monitoring Vince Polsoni Powerstream Inc. Manager Station Sustainment EDIST 2016 1 Agenda Maintenance Monitoring Equipment CMMS Data Historian

More information

A Tariff for Reactive Power Christopher Tufon, Alan Isemonger, Brendan Kirby, Senior Member, John Kueck, Senior Member, and Fangxing Li, Senior Member

A Tariff for Reactive Power Christopher Tufon, Alan Isemonger, Brendan Kirby, Senior Member, John Kueck, Senior Member, and Fangxing Li, Senior Member 1 A Tariff for Reactive Power Christopher Tufon, Alan Isemonger, Brendan Kirby, Senior Member, John Kueck, Senior Member, and Fangxing Li, Senior Member Abstract-- This paper describes a suggested tariff

More information

ABB Power Systems. Substations References

ABB Power Systems. Substations References ABB Power Systems Substations References Jingzhou, China BA PTPS - 2 - Connection of power from the 3-Gorges-Project to Guandong province (940km away) HVDC Transmission station, Filter banks and GIS Extremely

More information

CITY OF GLENDALE CALIFORNIA REPORT TO CITY COUNCIL

CITY OF GLENDALE CALIFORNIA REPORT TO CITY COUNCIL FORM CM-36 CITY OF GLENDALE CALIFORNIA REPORT TO CITY COUNCIL February 7,2012 AGENDA ITEM Request for Approval to Issue a Request for Qualification (RFQ) of Firms, and Request for Proposal (RFP) to Engineer,

More information

BASIC NEC CODE RULES AND DESIGN PRACTICE

BASIC NEC CODE RULES AND DESIGN PRACTICE BASIC NEC CODE RULES AND DESIGN PRACTICE Wire Ampacity and Size Circuit Breaker Size 1. Maximum loading for any branch circuit is 80% of rating of circuit for ampacity of wire for any load. NEC 220-2,

More information

Syed Ahmed Richard Krause Southern California Edison

Syed Ahmed Richard Krause Southern California Edison An Electric Utility s Power Transmission Modernization Needs Syed Ahmed Richard Krause Southern California Edison 2 Presentation Outline Existing System Electric System Components, Basic Power System,

More information

the amount of data will grow. It is projected by the industry that utilities will go from moving and managing 7 terabytes of data to 800 terabytes.

the amount of data will grow. It is projected by the industry that utilities will go from moving and managing 7 terabytes of data to 800 terabytes. Before the Department of Energy Washington, D.C. 20585 In the Matter of Implementing the National Broadband Plan by Studying the Communications Requirements of Electric Utilities To Inform Federal Smart

More information

Distribution Operations with High-penetration of Beyond the Meter Intermittent Renewables. Bob Yinger Southern California Edison April 15, 2014

Distribution Operations with High-penetration of Beyond the Meter Intermittent Renewables. Bob Yinger Southern California Edison April 15, 2014 1 Distribution Operations with High-penetration of Beyond the Meter Intermittent Renewables Bob Yinger Southern California Edison April 15, 2014 Southern California Edison SCE provides power to: Nearly

More information

PPL Electric Utilities Summer Readiness Overview June 2016

PPL Electric Utilities Summer Readiness Overview June 2016 SUMMARY PPL Electric Utilities Summer Readiness Overview June 2016 For PPL Electric Utilities (PPL Electric), summer readiness means the company must respond effectively to summer storms as well as provide

More information

Hyperlinks are Inactive

Hyperlinks are Inactive Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)

More information

Oncor s Pioneering Transmission Dynamic Line Rating (DLR) Demonstration Lays Foundation for Follow-On Deployments

Oncor s Pioneering Transmission Dynamic Line Rating (DLR) Demonstration Lays Foundation for Follow-On Deployments Oncor s Pioneering Transmission Dynamic Line Rating (DLR) Demonstration Lays Foundation for Follow-On Deployments 1. Summary Oncor Electric Delivery Company (Oncor) successfully demonstrated a fully integrated

More information

Full Network Model Scope for FNM DB2015Q4

Full Network Model Scope for FNM DB2015Q4 Transmission Projects PG&E SCE 1. Build Shepherd Substation (MWC 60) Install 115 kv ring bus and loop 115 kv line, phase # 4 2. CDCR Mule Creek Prison Load Interconnection, phase # 1 3. Chowchilla Solar

More information

4. The Transmission & Distribution of Electricity

4. The Transmission & Distribution of Electricity 4. The Transmission & Distribution of Electricity 4.1 System Overview Green Mountain Power provides electric service to approximately 260,000 customers in 202 towns in Vermont. In 2013, the GMP transmission

More information

FRCC Standards Handbook. FRCC Automatic Underfrequency Load Shedding Program. Revision Date: July 2003

FRCC Standards Handbook. FRCC Automatic Underfrequency Load Shedding Program. Revision Date: July 2003 F R C C FRCC Standards Handbook FRCC Automatic Underfrequency Load Shedding Program Revision Date: July 2003 FRCC Underfrequency Load Shedding Program Modification and Approval Process Requests to modify

More information

Electric Power Systems An Overview. Y. Baghzouz Professor of Electrical Engineering University of Nevada, Las Vegas

Electric Power Systems An Overview. Y. Baghzouz Professor of Electrical Engineering University of Nevada, Las Vegas Electric Power Systems An Overview Y. Baghzouz Professor of Electrical Engineering University of Nevada, Las Vegas Overview Power Generation Conventional power generation Power generation from renewables

More information

Modeling the Financial and System Benefits of Energy Storage Applications in Distribution Systems

Modeling the Financial and System Benefits of Energy Storage Applications in Distribution Systems Modeling the Financial and System Benefits of Energy Storage Applications in Distribution Systems Patrick Balducci, Senior Economist, Pacific NW National Laboratory Hydrogen Energy Storage for Grid and

More information

Federal Wage System Job Grading Standards for Electric Power Controlling, 5407. Table of Contents

Federal Wage System Job Grading Standards for Electric Power Controlling, 5407. Table of Contents Federal Wage System Job Grading Standards for Electric Power Controlling, 5407 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 TITLES... 2 GRADE LEVELS... 2 SPECIAL ADDITIONAL RESPONSIBILITIES...

More information

TRANSMISSION AND SUBSTATION PROJECTS

TRANSMISSION AND SUBSTATION PROJECTS TRANSMISSION AND SUBSTATION PROJECTS OPERATING COMPANY: EMI CUSTOMER: WARREN POWER, LLC EJO # MS0010 SCOPE DOCUMENT FOR 340 MW, IPP PROJECT at VICKSBURG, MS WITH INTERCONNECTION AT BAXTER WILSON 500kV

More information

Implementing Low-Cost Distribution Automation Programs

Implementing Low-Cost Distribution Automation Programs Implementing Low-Cost Distribution Automation Programs By: Jai Belagur, P.E. Contact: Jai Belagur Power System Engineering, Inc. 1532 West Broadway, Suite 100, Madison, WI 53713 Phone: 608-268-3544 E-mail:

More information

Pacific Mort hwest National Laboratory. Operated by Battelle for the U.S. Department of Energy

Pacific Mort hwest National Laboratory. Operated by Battelle for the U.S. Department of Energy 3 Pacific Mort hwest National Laboratory Operated by Battelle for the U.S. Department of Energy PNNL-11815 UC-9. Electric Power Substation Capital Costs J.E. Dagle D.R. Brown DSTRBUTON OF TH\S DOCUMENT

More information