1 MGE TM Galaxy TM kva Battery circuit-breaker enclosures Installation manual
2 EN/AH - Page 2
3 Introduction Thank you for selecting an APC by Schneider Electric product to protect your electrical equipment. The MGE Galaxy 7000 range has been designed with the utmost care. We recommend that you take the time to read this manual to take full advantage of the many features of your UPS (Uninterruptible Power System). APC by Schneider Electric pays great attention to the environmental impact of its products. Measures that have made MGE Galaxy 7000 a reference in environmental protection include: the eco-design approach used in product development, the elimination of harmonic disturbances reinjected into the AC source, production in an ISO certified factory, recycling of the MGE Galaxy 7000 at the end of its service life. To discover the entire range of APC by Schneider Electric products and the options available for the MGE Galaxy 7000 range, we invite you to visit our web site at or contact your local representative. Content 1. Installation of enclosure Circuit-breaker NSX630S DC enclosure Circuit-breakers NSX630S DC enclosure Electrical characteristics of enclosure... 5 Setting the 2 circuit-breakers NSX630S DC enclosure Connections 3.1 Connecting the 1 circuit-breaker NSX630S DC enclosure Connection points... 6 Connection diagrams Connecting the 2 circuit-breakers NSX630S DC enclosure Connection points... 7 Connection diagrams Connecting the enclosure auxiliary cables to MGE Galaxy 7000 UPS cabinets EXPUT board location... 8 All products in the MGE Galaxy 7000 range are protected by patents. They implement original technology not available to competitors of APC by Schneider Electric. To take into account evolving standards and technology, equipment may be modified without notice. Indications concerning technical characteristics and dimensions are not binding unless confirmed by APC by Schneider Electric. This document may be copied only with the written consent of Schneider Electric or its affiliated companies. Authorised copies must be marked "MGE Galaxy 7000 Battery circuit-breaker installation manual no " EN/AH - Page 3
4 1. Installation of enclosure Only qualified persons can install UPS or its auxiliaries. UPS or its auxiliaries must be installed in a room with restricted access. The circuit-breaker enclosure must be located as close to the battery as possible, The enclosure is fixed to a vertical wall by means of 4 screws of diameter 8 using the fastening lugs placed in the vertical or horizontal position Only maintenance persons with a electrical security clearance are authorised to open enclosures Circuit-breaker NSX630S DC enclosure The enclosure door is closed by two lock knobs with a key (405 type) on one of the knobs, cables are fed through the bottom of the enclosure via a 315 x 90 mm opening. enclosure weights : - 35 kg Opening for cable feed-through Fig Circuit-breakers NSX630S DC enclosure The enclosure door is closed by only one point with a key (405 type), cables are fed through the bottom of the enclosure via two 345 x 130 mm openings. enclosure weights : - 65 kg Opening for cable feed-through Fig EN/AH - Page 4
5 2. Electrical characteristics of enclosure the characteristics of the enclosures indicated in the tables below are valid for a linear load charge with power factor of 0.9 and a minimum battery voltage set to 422 V on the UPS side, the recommended cable crosssections are applicable to U1000R02V type copper conductors. They are calculated in relation to permissible temperature rises and take into account a maximum line voltage drop of 1% for a maximum cable length of 25 m. For greater cable lengths, cross-sections will be chosen to keep the voltage drop within 1%. UPS rated power in kva Maximum battery backup times at Sn(1) for a power factor of 0.9 in minutes QF1 circuit-breaker Type Release Magnetic setting Max. cable cross-section in mm All NSX630S DC MP x All NSX630S DC MP x All NSX630S DC MP x mn > 15 mn NSX630S DC 2 X NSX630S DC MP1 MP see below 1x185 1x mn > 5 mn NSX630S DC 2 X NSX630S DC MP1 MP see below 1x240 1x All 2 X NSX630S DC MP1 see below 2x150 (1) Sn = rated power ; for other values, consult the after sales department or your local agency. Setting the 2 circuit-breakers NSX630S DC enclosure UPS rated power in kva Maximum battery backup times Total number of battery strings QF1-1 circuit-breaker QF1-2 circuit-breaker Number of battery strings Magnetic setting (A) Number of battery strings Magnetic setting (A) 300 >15 mn >5 mn Toutes EN/AH - Page 5
6 3. Connections 3.1 Connecting the 1 circuit-breaker NSX630S DC enclosure Connection points enclosure with door open A view AA connection to UPS on 50 x 10 mm copper terminals with two 12,2 mm diameter holes, B- QF1 B+ to battery Vers batterie connection to the battery on 50 x 10 mm copper terminals with two 12,2 mm diameter holes, earth connection on 50 x 5 mm copper terminals with 12,2 mm diameter hole. L- L+ A XR2 XR1 earth to UPS Vers auxiliaires to auxiliaries Vers cellule ASI Connection order: 1 - Connect to earth 2 - Connect to the battery 3 - Connect to UPS 4 - Connect the control-wire cables as described below Put the protective cover back in place after connection operations. Fig. 3 Connection diagrams Connection for a enclosure without insulation monitor (see electrical characteristics table) QF1 battery circuit-breaker to battery B- B+ position contact of QF1 circuitbreaker QF1 tripping: 24V undervoltage coil the cross-section of the power cables is given in the tables in the section entitled "Electrical characteristics of enclosure" page 5; recommended cross-section of auxiliary conductors: 1 mm2 / AWG18 (terminal acceptance capacity: 2 mm2 / AWG16 ); L- L+ to UPS D1 D4 battery circuit- breaker cabinet XR1 terminal block (2) make sure that the auxiliary conductors and power cables do not follow the same path, power cables and auxiliary conductors are not supplied. Important : leave the QF1 circuit-breaker in «off» position until the MGE Galaxy 7000 unit has been commissioned. to XM20 connector on the EXPUT board (1) (1) See MGE Galaxy 7000 n Fig. 4 (2) Strap or one of the contacts of the emergency stop button, if any EN/AH - Page 6
7 3. Connections 3.2 Connecting the 2 circuit-breakers NSX630S DC enclosure A maximum of 2 circuit-breakers NSX630S DC enclosures can be connected for each UPS. Connection points Enclosure with door open A B1- B1+ B2- B2+ QF1-1 QF1-2 To battery string 1 To battery string 2 view AA connection to UPS on 63 x 8 mm copper terminals with four 12.2 mm diameter holes, connection to the battery on 80 x 5 mm copper terminals with four 12.2 mm diameter holes, earth connection on 50 x 8 mm copper terminals with three 12.2 mm diameter holes. earth L+ L- XR10 to auxiliaries Connection order: 1 - Connect to earth 2 - Connect to the battery 3 - Connect to UPS 4 - Connect the control-wire cables as described below A to UPS Put the protective cover back in place after connection operations. Fig. 5 Connection diagrams Connection for a enclosure without insulation monitor (see electrical characteristics table) B1- B1+ B2- B2+ to battery to battery string 1 string 2 position QF1-1 contact of QF1-2 breaker CB tripping: 24V undervoltage coil the cross-section of the power cables is given in the tables in the section entitled "Electrical characteristics of enclosure" page 5; D1 D D1 D4 recommended cross-section of auxiliary conductors: 1 mm2 / AWG18 (terminal acceptance capacity: 2.5 mm2 / AWG16 ); make sure that the auxiliary conductors and power cables do not follow the same path, L- L+ to UPS battery circuit- breaker cabinet XR10 terminal block (2) power cables and auxiliary conductors are not supplied. Important : leave the QF1 circuit-breaker in «off» position until the MGE Galaxy 7000 unit has been commissioned. Fig. 6 to XM20 connector on the EXPUT board (1) (1) Don t use UPS EXPUT board pins 9 to 12 to connect the circuit-breaker enclosure. See MGE Galaxy 7000 n (2) Strap or one of the contacts of the emergency stop button, if any EN/AH - Page 7
8 R Connections 3.2 Connecting the enclosure auxiliary cables to MGE Galaxy 7000 UPS cabinets EXPUT board location 1 XM19 L3 XM23 XB6 R121 VT3 R117 R118 L2 C21 R66 R120 VD10 R95 R80 VZ11 R97 C19 R119 R140 VP2 K1 K2 VP3 R81 C22 VP4 R82 R96 R98 VD2 VD3 VD11 DI1 R48 R68 R67 R64 R65 R69 C32 R70 VP6 R45 R46 R123 R124 C20 R125 R126 R127 C23 R71 R152 VT2 R72 R12 R20 R19 R47 VP5 VD12 VP7 VD4 R73 XM24 XM6 XM18 XM17 XM16 R13 R14 C18 R15 VZ4 R3 XM3 XM5 XM4 R9 R143 R142 VP1 VZ1 R147 R148 R146 C33 VD15 NR2 R139 R39 R41 R43 C17 R8 R10 R11 R137 XM25 XB3 C1 C5 XM1 XM2 R155 R156 R154 R158 R157 R4 C6 R5 R138 R6 R159 L1 VD1 XM20 R16 XM21 VD5 R49 R51 R17 R18 NR3 R44 R42 XB2 VD7 R74 R75 R76 R77 R78 R79 VD8 R85 R86 R87 R88 R99 R101 R103 R100 R102 R104 R135 R136 R134 XB5 C3 C15 R111 R112 R113 C2 R1 R89 R90 R91 R60 R58 R50 R61 R59 XM22 R110 R108 R106 R109 R107 R105 R133 R131 R132 VD13 VD14 R83 R84 XM15 VZ10 R114 R92 R55 R115 R93 R56 R116 R94 R57 VZ9 C24 C16 HE1 XB4 R53 R54 VZ5 XM11 XM14 XM10 VZ8 R52 VZ7 VZ6 R22 R33 R30 R26 R34 R31 R27 R35 R32 R28 PT3 PT2 R29 R23 R24 NR1 EH1 C4 C10 XM8 R25 C13 C11 ET1 C9 VD6 C12 C14 PT1 XB1 XM12 EXPUT board XM7 VT1 R2 XM9 R7 C8 C7 R36 R37 R38 XM13 R62 R63 XM20 connector EN/AH
Installation. Smart-UPS VT MGE Galaxy 3500. Maintenance Bypass Panel. 10-40 kva 400 V
Installation Smart-UPS VT MGE Galaxy 3500 Maintenance Bypass Panel 10-40 kva 400 V Contents Safety.................................................. 1 Save these instructions...................................
More informationTechnical Specifications
Technical Specifications MGE Galaxy 7000 160 500 kva 380/400/415 V Table of Contents Technical Data... 1 Model list... 1 Input Power Factor... 1 Efficiency... 1 Efficiency Curves... 2 Derating due to
More informationMGE TM Galaxy TM 9000 50, 60 Hz 800-900 kva
MGE TM Galaxy TM 9000 50, 60 Hz 800-900 kva Installation manual Single-unit UPS Modular UPS Parallel UPS with SSC Frequency converters Static Switch Cubicle 34006451EN/AC - Page 2 Contents 1. Characteristics
More informationBERTHOLD ELECTRIC GENERATOR CONNECTION CABINET
BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET Berthold Electric Company s Generator Connection Cabinet provides a quick and convenient station to connect a portable generator to a facility s main service
More informationLow voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.
Low voltage Direct Current Network Compact NSX DC PV Circuit breakers and switch disconnectors for solar application Catalogue 2012 Compact NSX DC PV A complete DC offer for solar application from 80
More informationInstallation. Smart-UPS VT and MGE Galaxy 3500. Maintenance Bypass Panel with Power Distribution (wall-mount) 10-30 kva 208 V
Installation Smart-UPS VT and MGE Galaxy 3500 Maintenance Bypass Panel with Power Distribution (wall-mount) 10-30 kva 208 V Contents Safety... 1 SAVE THESE INSTRUCTIONS...............................
More informationSeries 8146/5-V37 and Series 8150/5-V37
www.stahl.de > Clear assignment safe technology easy installation > Intelligent structure only one rotary actuator for frequency-controlled drives ) 20 ms leading auxiliary contact for safe motor disconnection
More information3RT1015-1BB41 CONTACTOR, AC-3 3 KW/400 V,
Automation Technology > Industrial Controls > Switching Devices > Contactors and Contactor Assemblies > Power Contactors for Switching Motors > Contactors SIRIUS 3RT10, 3-pole, 3... 250 kw 3RT1015-1BB41
More informationSIRCOVER. Manual changeover switches from 125 to 3200 A. Changeover switches. Function. Advantages. The solution for.
The solution for Changeover switches svr_099_b_1_cat > Manufacturing industry. > Power distribution. 3200 Strong points svr_059_a_1_cat > complete range. > Easy connections. > Stable positions. > mproved
More informationPositive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous
Safety relay for monitoring E-STOP pushbuttons. Approvals Unit features Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous Safe separation of
More informationINSTALLATION INSTRUCTIONS
LIGHTING CONTROL PANELS 4 AND 8 RELAYS INSTALLATION INSTRUCTIONS INSTALLATION OVERVIEW The installation instructions contained in this document are provided as a guide for proper and reliable installation.
More informationHERZ-Thermal Actuators
HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01
More informationICON Server box installation manual Rev. 1.1
ICON Server box installation manual Rev. 1.1 Contents 1.0 About this manual... 3 2.0 Intended use... 3 2.1 European WEEE directive... 3 3.0 Installation and service instructions... 4 Server box overview...
More informationParallel Redundant Uninterruptible Power Supply
9 315 Parallel Redundant Uninterruptible Power Supply Installation/Operation Manual 164202013 Rev. D ------------------------------------------------------------------------ ------------------------------------------------------------------------
More informationInverter / Charger Installation General Operations and AC and DC Connections
Inverter / Charger Installation General Operations and AC and DC Connections The Inverter is just one piece. Sometimes, a tendency is to mount the inverter and batteries, and make it work It is better
More informationST Series POWER SUPPLIES USER INSTRUCTIONS
Introduction These instructions detail the installation and operation requirements for the ST20 & ST35 power supplies. These have been designed for operation in RV s providing a DC power system, with optional
More informationSolar Home System. User Manual. AEH-SHS01-10W2L Solar Home System 2 Lamps
Solar Home System User Manual AEHSHS0110W2L Solar Home System 2 Lamps All rights reserved Specifications subject to change without prior notice 2 Dear Customer, Thank you for purchasing Schneider Electric
More information33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application
33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application Features Compliant with the IEEE802.3at Standard -40 to +60 C Temperature Range Diagnostic LEDs Full Protection
More informationTmax MCCBs. Molded case circuit breakers. Tmax
Molded case circuit breakers Introduction ABB is once again demonstrating its commitment to new product development and its superiority in product performance. Never before has the industry seen such high
More informationEVC40 EMERGENCY VOICE COMMUNICATION SYSTEM
EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM INSTALLATION MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0) 1282 717273
More informationUPS system for emergency lighting and smoke extraction
UPS system for emergency lighting and smoke extraction Requirements There are a number of standards that apply to emergency lighting and smoke extraction systems (for example: NFS 61-940 [France only]
More informationContractors Guide Central Inverter System Installation
Contractors Guide Central Inverter System Installation Step By Step Procedures 2,200 Watt/VA 6 Step Installation 1. Mount Bottom Cabinet 2. Mount Top Cabinet 3. Install Batteries 4. Install Conduit 5.
More informationOutdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points
Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Features SELV Compliant No Detection Passive Injector Gigabit Compatible Full Protection
More information5SV Residual Current Protective Devices
s Siemens AG 2013 SENTRON 5SV Residual Current Protective Devices New portfolio for reliable personnel, material and fire protection Safe protection against residual currents Residual current protective
More informationMTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation
MTE SERIES RLW World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930 2009 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RLW reactors are components designed to improve the reliability
More informationCatalog. Arc Guard System TM TVOC-2
Catalog Arc Guard System TM TVOC-2 Introduction An even better Arc Guard System TVOC-2, ABB s latest Arc Monitor, builds on the well known TVOC design. Its new functions and features improve an already
More informationPower Management Module 2. Installation
Power Management Module 2 30 300 kva Installation Table of Contents Safety... 1 Safety Instructions... 1 Certification Standards Three Phase... 1 Product Safety... 2 Special Precautions... 2 System Description...
More informationDoc Ref: 2015.06.01.002. 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC
TM 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC TM D400E Data Module (60Hz) The EDGE D400E is designed to meet high power density requirements for both the HPC and Web Scale environments while
More informationSecondary Unit Substations
14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically
More information12V Dimmable Driver EL-TMDRVR
Elemental LED, LLC website: elementalled.com 11 9 5 P a r k A v e., S u i t e 2 11 Emeryville, CA 94608 toll free 877.564.5051 fax 510.740.4457 12V Dimmable Driver EL-TMDRVR ETL Listed #4001928 CSA Listed
More informationAdvantium 2 Plus Alarm
ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia
More informationPlug and Socket Devices CES 63 A Series 8579
www.stahl.de > Switch socket / plug 63 A > Large switch handle with clear switch position indication padlockable in 0- and I-position > Low insertion and withdrawal forces through individually encapsulated
More informationDBS720 / FDS221-R / FDS221-W Sounder base, Alarm sounders
DBS720 / FDS221-R / FDS221-W Sounder base, Alarm sounders For the automatic addressable detector bus C-NET Cerberus PRO Sounder base DBS720 11 selectable tones, 2 programmable activation levels Sound intensity
More information8146/5 Series Breaker Panelboards
8146/5 Series Breaker Panelboards DISTRIBUTION BREAKER PANELBOARDS FOR HAZARDOUS & CORROSIVE ENVIRONMENTS Breaker Panels Features: Wide variety of Flameproof branch circuit breakers for Zone 1 & Division
More informationSquare D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit
Square D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit SLCLE5504AUX for Use with Wired C-Bus Networks Instruction Bulletin Retain for future use. Square D Clipsal DIN-Rail Four-Channel Auxiliary Input
More informationInstruction Bulletin. MCS025 Sync-Check Module Installation Sheet
Instruction Bulletin 63230-216-244B1 LaVergne, TN, USA MCS025 Sync-Check Module Installation Sheet Retain for future use. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Only qualified electrical
More informationSubmit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
More informationGalaxy VM. Three-phase power protection. schneider-electric.com
Galaxy VM Three-phase power protection schneider-electric.com 2 schneider-electric.com schneider-electric.com 3 Galaxy VM trusted partner for your business continuity Features and benefits Highly efficient,
More informationFor a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz)
24 1. NETWORK CONFIGURATIONS definition Standard IEC 38 defines voltage ratings as follows: - Low voltage () For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690
More informationPower factor correction and harmonic filtering. Rectimat 2 Automatic capacitor banks. Catalogue. Building a New Electric World
Catalogue 2002 Automatic capacitor banks Building a New Electric World 0Contents Power factor correction 2 Power factor equipment selection guide 3 General technical data 4 Capacitors and banks 50 z 6
More informationI nstallation. M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications. Tools Needed.
FANs 268.1, 1628.3 Installation Bulletin M100Q Issue Date 1099 M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications I nstallation Parts Included M110QGA-1 and
More informationEmergency lighting units EM powerled
M BASIC 1 W Combined emergency lighting Driver 1 4 W Product description Emergency lighting Driver for manual testing SEV for output voltage < 60 V DC ow-profile casing (21 x 30 mm cross-section) 5-year
More informationMEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4
CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,
More informationSilcon DP300E 208V/480V 10-80kVA Installation Guide
Silcon DP300E 208V/480V 10-80kVA Installation Guide Copyright 1999 APC Denmark A/S Due to continuous product development information given in this guide is subject to change without notice. 1 IMPORTANT
More informationTopvex SX/C, Topvex TX/C. Air Handling Unit
Air Handling Unit Document in original language 131677-EN_GB 23-12-2015 A001 Contents 1 Declaration of Conformity... 1 2 Warnings... 2 3 Product information... 2 3.1 General... 2 3.2 Technical data...
More information12VDC MAGNETIC LED DIMMABLE POWER SUPPLIES SPEC SHEET DIGEST
12VDC MAGNETIC ED DIMMABE POER SUPPIES SPEC SEET DIGEST TM-30-DIM TM-50-DIM T-60-DIM TM100-DIM TM200-DIM TM300-DIM iring Diagram for TM-50-DIM and TM-100-DIM ED 12VDC MAGNETIC DIMMABE 30 POER SUPPY Smallest
More informationExample of use: Fuse for a solenoid valve. If the fuse is defective, no information is sent to the electronic component.
Overview Switch and button modules The dimensions of the switch and button modules are adapted to the electronic components in the integral housing. The modules are equipped with the universal clip-on
More information2013 Wireless Video Intercom INSTALLATION GUIDE
2013 Wireless Video Intercom INSTALLATION GUIDE INDEX System configuration and wiring VL-SWD501 System Component.. 4 VL-SWD501EX wiring schematic diagram VL-SWD501EX wiring type and length... 5.... 6 Door
More informationCurrent valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
More informationLIEBERT VNSA Installation Sheet
LIEBERT VNSA Installation Sheet Description The Liebert vnsa network switch is designed for connecting multiple Ethernet-ready devices and comes in various models. The unit may have: A Liebert icom display
More informationRY2 miniature industrial relays
6 RY2 Relays of general application For plug-in sockets, 35 mm rail mount acc. to PN-EN 60715 or on panel mounting Flat insert connectors - faston x 0,5 mm Recognitions, certifications, directives: RoHS,
More informationE-STOP relays, safety gate monitors
Unit features Safety features Gertebild ][Bildunterschrift_NOT_Sch.tuer_Licht Safety relay for monitoring E-STOP pushbuttons, safety gates and light beam devices Approvals Gertemerkmale Positive-guided
More informationP System Cubicles. Certified for more safety
P System Cubicles Prisma Plus LV Switchboards Certified for more safety Prisma Plus, an offer thought out for greater professionalism With the Prisma Plus P system, Schneider Electric proposes high-performance
More informationBreaking and protection devices
Breaking and protection devices 05 POWER GUIDE 2009 / BOOK 05 INTRO The purpose of selecting a protection device is to perform two essential functions: to protect people and to protect trunking, while
More informationMagnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2...
Magnetic and Hydraulic-Magnetic Circuit Breaker 840-G2... Description Single, two and three pole magnetic circuit breakers with trip-free mechanism and push/pull on/off manual actuation. A choice of fast
More informationMGE Galaxy 7000. 160/200/250/300/400/500 kva Power efficiency for business continuity
MGE Galaxy 7000 160/200/250/300/400/500 kva Power efficiency for business continuity Performance three-phase power protection with high adaptability to meet the unique requirements of medium to large data
More informationHM-W536 Install Guide
HM-W536 Install Guide 9/13/2013 IMPORTANT SAFETY INSTRUCTIONS Warning - When using electrical devices, basic safety precautions should be followed to reduce the risk of fire, electrical shock or injury.
More informationSolid Core and Split Core Adjustable Current Status Switches CSS-O, CSS-C; CSP-O, CSP-C
Solid Core and Split Core Adjustable Current Status Switches CSS-O, CSS-C; CSP-O, CSP-C DESCRIPTION FEATURES PRODUCT DATA Very low operating trip points LED status indication Integral DIN rail mounting
More informationSF 6 Gas Insulated Switchgear Type SDF for 170 kv
Three Phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDF for 170 kv 06B1-E-0001 With Trustworthy Technology, Structure Fuji Electric as a manufacturer of comprehensive substation equipment
More informationBroadway 3D Security System
Broadway 3D Security System USER MANUAL v.1.1.0 Artec Group, Inc. 2012 Table of contents 1. General Information... 3 2. Delivery Package... 4 3.1. B3D BR... 5 3.2. B3D B... 6 3.3. B3D BM... 7 4. Integration
More informationAssisted lift operated 2/2-way solenoid valves Type EV250B
MAKING MODERN LIVING POSSIBLE Data sheet Assisted lift operated 2/2-way solenoid valves Type EV250B EV250B with assisted lift can operate from zero and up to 10 bar differential pressure. This 2/2-way
More informationCHAPTER 2 EXAMPLES AND TABLES
CHAPTER 2 EXAMPLES AND TABLES COMMENTARY AT 210.20(A) EXCEPTION An overcurrent device that supplies continuous and noncontinuous loads must have a rating that is not less than the sum of 100 percent of
More informationRemote Power Panels with Breakers
Remote Power Panels with Breakers 8 Series Panels & Enclosures N/A N/A Remote power panels with breakers are available in two different sizes, each of which may be either surfacemounted or recess-mounted,
More informationTerminal Boxes Series 8146
Series > Enclosures in shock-resistant glass fibre reinforced polyester resin > basic enclosure sizes various heights > Fitted according to the customer's requirements > For terminals up to max. 00 mm
More informationProduct and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.
Product and Applications Description The power supply units N 125/x2 can supply DC 24 V power from an additional pair of terminals (yellowwhite). This DC 24 V output voltage can be used to power e.g. an
More informationElectronic overload relay EF65, EF96 and EF146
Data sheet Electronic overload relay EF65, EF96 and EF146 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays.
More informationMILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)
MILLENIUM Table of contents 1. INTRODUCTION 1 2. HARDWARE DESCRIPTION 2 3. INSTALLATION 5 4. CONNECTION 6 5. USER SAFETY AND PROTECTION OF EQUIPMENT 8 1. Introduction The MILLENIUM series has been designed
More informationML 1012 v.1.2 ML13,8V/1A Buffer power supply module, linear.
ML 1012 v.1.2 ML13,8V/1A Buffer power supply module, linear. EN Edition: 6 from 10.03.2014 Supercedes the edition: 5 from 16.09.2013 Features: uninterrupted supply of 13,8VDC/1A supply voltage: external
More information3.0 CHARACTERISTICS. AR Auxiliary Relay High Speed, High Threshold 41-759.3C
41-759.3C the magnetic core upon energizing of the switch. When the switch closes, the moving contacts bridge two stationary contacts, completing the trip circuit. Also during this operation two fingers
More information1.1 ANNUAL PREVENTIVE MAINTENANCE VISIT
Maintenance Service - 1 - Lead Acid Battery Frame On-Site Warranty Statement of Work 1.0 Executive Summary Lead Acid Battery Frame On-Site Warranty Service Service Table of Contents 1.0 Executive Summary
More informationDORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS
Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short
More informationElectrical auxiliaries 0 For i DPN (DPN), C60 and C120
Circuit protection For i DPN (DPN), C60 and C120 Function They remotely trip or indicate circuit-breakers, with or without Vigi module. Description b They are mounted to the left of the circuit-breaker
More informationResidual current socket 30mA Order No.: 0477..
30mA Order o.: 0477.. 1. Operating description The operating principle of the residual current socket is identical to that of the residual current device. In a fault-free installation, in which no current
More informationRoof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS
Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS Ducted System RECORD THIS UNIT INFORMATION FOR FUTURE REFERENCE: Model Number: Serial Number: Date Purchased: This manual must be read and
More informationAdvantages of Fixed Circuit Breaker Switchgear
Advantages of Fixed Circuit Breaker Switchgear by Lionel Mackay, EDF Energy, and Mike Adams, Schneider Electric Ltd Introduction The purpose of this paper is to review the advantages of fixed circuit breaker
More informationPower Distribution Systems for the Dell PowerEdge M1000e Modular Server Enclosure - Selection and Installation
One Dell Way Round Rock, Texas 78682 www.dell.com Dell Enterprise White Paper Power Distribution Systems for the Dell PowerEdge M1000e Modular Server Enclosure - Selection and Installation January, 2008
More informationPressure Switch for gas and air
Switch for gas and air GAO-A4 GMH-A4 GML-A4 UL Listed UL 353 File # MH 16628 CSA Certified CSA C22.2 No. LR 53222 Certification file # 201527 FM Approved Class 3510, 3530 File # J.I. 1Y919.AF Commonwealth
More informationAPC 3Phase Power Distribution
APC 3Phase Power Distribution North American 3 Phase Business Development Team All content in this presentation is protected 2008 American Power Conversion Corporation Objectives Understand the entire
More informationNEW RANGE OF CABINETS DRIVIATM. Innovation at your service. THE GLOBAL SPECIALIST in electrical and digital building infrastructures
NEW RANGE OF CABINETS DRIVIATM Innovation at your service THE GLOBAL SPECIALIST in electrical and digital building infrastructures Drivia true innovation The new electrical panel for the residential and
More informationDead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms
Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms ABB innovations for changing demands ABB (www.abb.com) is a leader in power and automation technologies that enables utility
More informationElectronic overload relay EF19 and EF45
Data sheet Electronic overload relay EF19 and EF45 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays. Motor
More informationMOTOR PROTECTIVE DEVICES
W MOTOR PROTECTIVE DEVICE, SERIES MP 206 BE400206 BE400306 Inherently stable without back-up fuseup to 4 A at 400 V AC, > 4 A main back-up fuse 100 A gl Thermal and magnetic release Terminal and accessory
More informationSENTRON Switching and Protection Devices Air Circuit Breakers
Siemens AG 9 SENTRON Switching and rotection Devices Air Circuit reakers 5 5/ Introduction 3WL Air Circuit reakers 3WL Air Circuit reakers/ Non-Automatic Air Circuit reakers up to 63 A (AC) 5/6 General
More informationHow To Operate A Gec Transfer Switch Open Transition 40 2000 Amp Power Supply
GTEC Transfer switch open transition 40 2000 amp Description GTEC transfer switches combine reliability and flexibility in a small, economical package for transferring loads between a utility and a generator
More informationABLOY EL614 Motor lock with bolt Abloy Oy An ASSA ABLOY Group company EL614 42/52 25/35 25 22 263.5 225 38.2 17.3 3 10 2 Contents TECHNICAL DATA... 4 INSTALLATION... 5 WIRING DIAGRAM... 6 DRILLING SCHEME...
More informationNo Phone Line II-48 System
Used in conjunction with an EntraGuard Telephone Entry System, the -48 provides No Phone Line communication and door or gate control through existing building telephone lines without the need to purchase
More informationPNOZsigma - Base units
PNOZsigma - Base units Register Login Sensors Control and Communication Electronic monitoring relays Safety Relays PNOZ X PNOZsigma PNOZelog PNOZmulti PNOZpower Configurable control systems Programmable
More informationMinimum Standards for Data/Voice Infrastructure in New Building Construction
UNIVERSITY OF WATERLOO Minimum Standards for Data/Voice Infrastructure in New Building Construction 12/17/2012 Offices 1. Two Work Area Outlets (WAO) on opposite walls, each with 2 jacks 2. Each WAO shall
More informationELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA
MRO Modularne Razdelilne Omare d.o.o. ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 2, 000 Ljubljana, LOVENIA MC GENERAL When to use? MC - modular switchgear cabinets are type-tested, factory built switchgears,
More informationPSACH 01246 v.1.0 PSACH 24VAC/6A/1x6A HERMETIC AC power supply for CCTV
PSACH 01246 v.1.0 PSACH 24VAC/6A/1x6A HERMETIC AC power supply for CCTV EN Edition: 2 from 12.12.2013 Supersedes the edition: 1 from 18.06.2013 Features: power output 24V AC/6A or 27V AC/ 5,5A power voltage
More informationBETA Switching. Switching Devices. 5TT5 8 Insta contactors, AC technology. Overview
BETA Switching Siemens AG 200 5TT5 Insta contactors, AC technology Overview The 5TT5 Insta contactors are equipped with an AC magnetic system and are ideal for use under harsh conditions. The auxiliary
More informationRemote Monitoring and REC 501 Control Unit Product Guide
Remote Monitoring and Control Unit REC 501 Product Guide Issued: May 1999 Status: Updated Version: B/06.11.2001 Data subject to change without notice Features Remote control and monitoring unit for the
More informationAll work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
More informationOLI. Oil level indicator
OLI Oil level indicator Oil level indicator Unexpected or accidental oil leakages may occur randomly along transformer s lifetime. Clear indication of oil level inside transformer tank and on load tap
More informationCDGRD-10. Grounding. Solutions For Comm/Data Applications
CDGRD-10 Grounding Solutions For Comm/Data Applications Overview & Table of Contents Cooper B-Line s Grounding products for rack & runway provide a complete solution for grounding metal supports. The offering
More informationpicomax The Pluggable Connection System
picomax The Pluggable Connection System TECHNOLOGY THIS SPECIALIZED CAN T MEET ALL REQUIREMENTS. YES IT CAN. CONTENTS picomax Pin spacing: 3. mm/0.138 in;.0 mm/0.197 in; 7. mm/0.29 in Versatile Pluggable
More information3RV Motor Starter Protectors up to 100 A
General data Overview S0 motor 3RV1 motor are compact, current limiting motor which are optimized for load feeders. The motor are used for switching and protecting three-phase induction motors of up to
More informationBack-UPS 650 VA 120 V with AVR (BX650CI-LM)
Back-UPS 650 VA 120 V with AVR (BX650CI-LM) Overview Do not install the unit in direct sunlight, in areas of excessive heat or humidity, or in contact with fluids ON/OFF button Battery connector Circuit
More informationHEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR
HEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR 2 MB 103 TRANSFORMER TEMPERATURE CONTROL UNIT WITH CONTROL SIGNAL Recent approval of new
More information1756 ControlLogix Chassis Specifications
Technical Data 1756 ControlLogix Chassis Specifications Catalog Numbers 1756-A4/B, 1756-A4K/B, 1756-A4/C, 1756-A4K/C, 1756-A7/B, 1756-A7K/B, 1756-A7/C, 1756-A7K/C, 1756-A10/B, 1756-A10K/B, 1756-A10/C,
More information