Honeywell Programmer Control Cross Reference

Size: px
Start display at page:

Download "Honeywell Programmer Control Cross Reference"

Transcription

1 Honeywell Programmer Control Cross Reference CROSS REFERENCE Honeywell has provided proprietary and/ labelled controls to certain Original Equipment Manufacturers (OEM) at their request. Proprietary controls are available only from the OEM, while labelled controls can, in some instances, be purchased directly from Honeywell. Where a control is available only from the OEM, we have placed a footnote in the Replacement Control column. Refer questions about a particular OEM control to the particular OEM (see list below): Cleaver Brooks Div. Aqua Chem Inc. ATTN: Parts Manager P.O. Box 42 Milwaukee, WI Lennox Industries Inc. Lennox Parts Center P.O. Box st Street Urbandale, IA Gdon-Piatt Energy Group Parts Manager C Street and Warehouse Road Winfield, KS Ray Burner Co. Engineering & Sales Dept. 40 Parr Boulevard Richmond, CA Vap Power International 66 S. County Line Road Franklin Park, IL

2 CROSS REFERENCE DATA Page R R PM BC R R SERIES FIREYE

3 Table. HONEYWELL R48 PROGRAMMER CROSS REFERENCE Replacement Prepurge Interlocks Lo- Fire On- Off LHL R48A00 RM7840G4 40 PRV LHL PRV OP Damp X X X X, 4- R48A8 X X X X X X, 4- R48A26 RM7840G4 40 PRV X X X X, 4- R48A34 X X X X X X, 4- R48A42 X X X X X X, X R48A59 55 X X X X X 7 X, X 6 4- See Conversion Wiring Diagram in Modernization Wiring Infmation section

4 Table 2. HONEYWELL R427 PROGRAMMER CROSS REFERENCE Device to be Replacement Prepurge Interlocks Lo-Fire On-Off LHL LHL PRV Op Damp R427A07 RM7840G4 R427A RM7840G4 R427A RM7840G4 R427A3 RM7840G4 R427A49 RM7840G4 R427A56 RM7840G4 R427A64 RM7840G4 X X X X 3- X X X X 3- X X X X 3- X X X X 3- X X X X 3- X X X X, 3- X X X X 3- R427A72 None X X X X 3- R427A80 RM7840G4 R427A98 RM7840G4 X X X X, 3- X X X X With R7253A With Q535 and R7253A With Q536 and R7253A With Q535 With Q With Q535 international model Produced in Canada R427A6 None International model R427A4 None See footnotes on page

5 Table 2. HONEYWELL R427 PROGRAMMER CROSS REFERENCE (Continued) Device to be R427A22 RM7840G4 R427A RM7840G4 R427A48 RM7840G4 R427A5 RM7840G4 R427A63 Replacement X X X X, X X X X 3-90 X X X X, 55 X X X X 8 X, 3-4- None X X X X 3- R427A7 RM7840G4 R427A89 RM7840G4 R427A97 RM7840G4 R427B05 RM7840G4 R427B3 RM7840G4 R427B2 RM7840G4 Prepurge Interlocks X X X X 9 X, 4- X X X X 3- X X X X 9 X, 4- X X X X 3- X X X X 3- X X X X International model 20 Ray Burner RC2D, uses special Q535/ Q With Q535 With Q536 Lo-Fire On-Off LHL LHL PRV Op Damp See footnotes on page

6 Table 2. HONEYWELL R427 PROGRAMMER CROSS REFERENCE (Continued) Device to be Replacement R427B39 RM7840G4 R427B47 RM7840G4 R427B54 RM7840G4 R427C03 RM7840G4 Prepurge Interlocks X X X X 3- X X X X 3- X X X X 3- X X X X 3-20 Ray Burner RC2A with R7254A, Q Ray Burner RC2B with R7254A,Q Ray Burner Lo-Fire On-Off LHL LHL PRV Op Damp FOOTNOTES: 20 Ray Burner with R7255A Refer to conversion wiring diagrams in Modernization Wiring Infmation section. 2 RM7840G meets current UL requirements. 3 RM7840L meets current insurance requirements. 4 See series ST7800A Plug-in Timers f prepurge timings available. 5 R427A,B,C Interlocks become RM7840 Interlocks. 6 No longer available. 7 Replacement controls are 20 Vac, Hz. 8 RM7840G4 is,, seconds. 9 is seconds. RM7840G4 and is 4 seconds. Select proper flame amplfier. 2 Use with existing Honeywell Flame Detects. 3 With selectable air-flow switch check (AFSC). 4 With selectable air-flow switch check (AFSC). Requires Q7800A Q7800B Subbase

7 Table 3. HONEYWELL BC7000 PROGRAMMER REPLACEMENT CROSS REFERENCE Replacement Prepurge Interlocks Program Module Used With Direct Purge Timer PM720G97 BC7000L42 Consult Original Equipment Manufacturer PM720G205 BC7000L42 Consult Original Equipment Manufacturer PM720G2005 BC7000L00 R740G2008 RM7800G8 ST7800A 47 PM720G203 BC7000L00 R740G2008 RM7800G8 ST7800A 47 PM720G202 BC7000L00 Consult Original Equipment Manufacturer PM720G2039 BC7000L00 R740G2008 RM7800G8 ST7800A 47 PM720L22 BC7000L8 Consult Original Equipment Manufacturer PM720L BC7000L00 R740L2007 RM7800L2 ST7800A 39 PM720L63 BC7000L34 Consult Original Equipment Manufacturer PM720L89 NEVER PRODUCED 40 LHL, 40 LHL, 40 LHL, 40 LHL, LHL, 40 LHL, 8 LHL, HF- LHL, HF- LHL, HF- X X X X X, X X X X X, X X X X,, 4-20 Proprietary to Yk-Shipley, LWCO annunciation on terminal 8" 4-20 Proprietary to Yk-Shipley, LWCO annunciation on terminal 8 X 4-20 X X X X * X 4-20 sec intermittent pilot X X X 7 X 3* sec intermittent pilot proprietary to Lennox X X X X,, X X X X X 7 X Proprietary to Cleaver Brooks X X X X X, X 4-20 X X X X 7 X Proprietary to Vap Cpation See footnotes on page

8 Table 3. HONEYWELL BC7000 PROGRAMMER REPLACEMENT CROSS REFERENCE (Continued) Replacement Prepurge Interlocks Program Module Used With Direct PM720L97 BC7000L8 Consult Original Equipment Manufacturer PM720L5 BC7000L34 Consult Original Equipment Manufacturer PM720L5 BC7000L34 Consult Original Equipment Manufacturer PM720L3 BC7000L42 Consult Original Equipment Manufacturer PM720L2 BC7000L42 Consult Original Equipment Manufacturer Purge Timer PM720L39 BC7000L00 R740L2007 RM7800L2 ST7800A 39 PM720L2004 BC7000L00 None RM7800E ST7800A 39 PM720L202 BC7000L00 R740L2007 RM7800L2 ST7800A 39 PM720L2020 BC7000L00 R740L2007 RM7800L2 ST7800A 2 8 LHL, HF- 8 LHL, HF- 8 LHL, HF- LHL, HF- LHL, HF- LHL, HF- LHL, HF- LHL, HF- LHL, HF- X X X X 7 X Proprietary to Cleaver Brooks X X X X 7 X Proprietary to Vap Cpation X X X X 7 X Proprietary to Vap Cpation X X X X X, "X X X X X, X X X X X, X X X X X, X X X X X, X X X X X, 4-20 Proprietary to Yk-Shipley, LWCO annunciation on terminal 8" 4-20 Proprietary to Yk-Shipley, LWCO annunciation on terminal 8, energy saving prepurge (ESP) X 4-20 Reduced sensitivity to line noise X 4-20 Energy saving prepurge (ESP) X X 4-20 See footnotes on page

9 Table 3. HONEYWELL BC7000 PROGRAMMER REPLACEMENT CROSS REFERENCE (Continued) Replacement Prepurge Interlocks Program Module Used With PM720M2002 BC7000L00 R740M07 RM7800M ST7800A 39 ( seconds), ST7800A 62 (90 seconds) PM720M20 BC7000L00 R740M07 RM7800M ST7800A 3 (7 seconds) PM720M2036 BC7000L00 R740M07 RM7800M ST7800A 3 (7 seconds), ST7800A 39 ( seconds) PM720M2044 BC7000L00 R740M07 RM7800M ST7800A 39 ( seconds), ST7800A 62 (90 seconds) PM720M205 BC7000L00 R740M07 RM7800M ST7800A 3 (7 seconds), ST7800A 39 ( seconds) BC7000L0 0 BC7000L 8 BC7000L3 4 BC7000L4 2 Direct Purge Timer, 90 On- Off, X X X X * X 2-20 second intermittent pilot 7 X X X X * X 20 second intermittent pilot 7,, 90 7, On- Off, X X X X * X 20 second intermittent pilot X X X X * X second intermittent pilot X X X X * X second intermittent pilot None See Program Module f Current Replacements 2 0 None Consult Original Equipment Manufacturer 2 0 None Consult Original Equipment Manufacturer 2 0 None Consult Original Equipment Manufacturer See footnotes on page

10 FOOTNOTES: 4 second. 2 With S7800A0 Keyboard Display Module. 3 Select proper amplifier: Old Amplifier: Replacement Amplifier: R7247A05 R7847A33 R7247A2 R7847A25 R7247B03 R7847B3 R7247C0 R786A26 See Note 5 R7248A04 R7848A08 R7248B28 R7848B06 R7249A03 R7849A R7476A07 R7886A0 4 With Selectable Airflow Switch Check. 5 Use with existing flame detects, EXCEPT C702E,F Replace with C706A,F and appropriate R786 Amplifier

11 Table 4. HONEYWELL R440 PROGRAMMER CROSS REFERENCE. Replacement Prepurge Interlocks Direct 2, 6, Purge Timer R440D04 None None X X X X R440E0 None None 3 X X 3 4- R440G07 R740G00 RM7840G4 ST7800A54 HL, R440G R740G00 RM7840G4 ST7800A54 LHL, R440G Consult Original Equipment Manufacturer R440G3 R740G2008 R440G49 R740G2008 R440G56 R740G2008 R440G64 R740G2008 R440G72 R740G2008 R440G80 R740G2008 RM7840G4 RM7840G4 RM7840G4 RM7840G4 RM7840G4 RM7840G4 72 LHL, ST7800A54 LHL, ST7800A54 LHL, ST7800A54 LHL, ST7800A54 LHL, ST7800A54 LHL, ST7800A54 LHL, R440G98 None None LHL, R440G6 R740G00 RM7840G4 ST7800A54 LHL, X X X X, X X X X, X X X X, X X X X, X X X X, X 6 4- X 6 4- X X X X X 6 4- X X X X X 6 4- X X X X 6 4- X X X X 6 4- X X X X, X X X X, X See footnotes on page Maxon special sequence f postpurge pilot systems. Uses special Q520A F direct spark ignition systems Proprietary to Cleaver Brooks CB International model

12 Table 4. HONEYWELL R440 PROGRAMMER CROSS REFERENCE. (Continued) R440G4 None None 70 LHL, R440G22 None None 70 LHL, R440G R740G2008 R440G48 R740G2008 RM7840G4 RM7840G4 Replacement Prepurge Interlocks ST7800A54 LHL, ST7800A54 "LHL, R440G5 None EC7850A22 ST7800A54 LHL, X X X X,, X X X X,, X X X X, X X X X, X X X 6 4- X 6 4- X X X X 5 X 5 X 4- R440G63 R740G2008 R440G7 R740G RM7840G4 RM7840G4 3 ST7800A54 LHL, ST7800A62 (90 seconds) 70 LHL, R440G89 R740L09 ST7800A54 LHL, HF- R440G97 None EC7850A22 ST7800A54 LHL, X X X X X 6 4- X X X X,, X X X X X X X 4- X X X 5 X 5,, X 6 4- R440L06 R740L09 ST7800A54 LHL, HF- R440L4 R740L09 ST7800A54 LHL, HF- R440L22 Consult Original Equipment Manufacturer 72 LHL, HF- R440L R740L09 ST7800A54 LHL, HF- R440L48 None EC7850A22 ST7800A47 (40 seconds) 45 LHL, HF- X X X X X, X X X X X, X X X X X, X X X X X, X X X X X 2, 5, X 6 4- X Proprietary to Gdon-Piatt Energy Gdon-Piatt Energy GP20 50 International model Cleaver Brooks CB40 20 With nonrotatable timer International model Direct 2, 6, Purge Timer See footnotes on page

13 Table 4. HONEYWELL R440 PROGRAMMER CROSS REFERENCE. (Continued) R440L55 R740L09 ST7800A54 LHL, HF- R440L63 Consult Original Equipment Manufacturer 9.5 LHL, HF- R440L7 None ST7800A54 LHL, HF- R440L89 R740L09 ST7800A54 LHL, HF- R440L97 R740L09 ST7800A54 LHL, HF- R440L5 R740L09 ST7800A54 LHL, HF- R440L3 None EC7850A22 ST7800A54 LHL, HF- R440L2 Consult Original Equipment Manufacturer 5.5 LHL, HF- R440L39 R740L09 ST7800A54 LHL, HF- R440L47 R740L09 ST7800A54 LHL, HF- R440L4 None EC7850A22 Check R440 f purge timing R440L62 Consult Original Equipment Manufacturer Replacement Prepurge Interlocks Direct Sel ect abl e LHL, HF- LHL, HF- R440L70 None EC7850A22 ST7800A54 LHL, HF- X X X X X, " 4- X X X X 6.5 X X X X X X,, X 4- X X X X X X 4- X X X X X, X X X X X, X X X X 5 X 5,, X 4- X 6 4- X Vap Cpation 50 International model 20 Gdon-Piatt Energy GP International model X X X X 8 ICI Model X X X X X, X X X X X,, X X X X X 5, X X X X X 5, X X X X X 5, X 4- X 4- X X 50 2, 6, Purge Timer 50 Approved by Australian Gas Association 20 Fulton Special See footnotes on page

14 Table 4. HONEYWELL R440 PROGRAMMER CROSS REFERENCE. (Continued) Replacement Prepurge Interlocks Direct 2, 6, Purge Timer R440M04 R740M07 R440M2 R740M07 R440M20 R740M R440M38 R740M R440M46 R740M R440M53 R740M RM7840M7 RM7840M7 RM7840M7 4 RM7840M7 4 RM7840M7 4 RM7840M7 4 ST7800A39 ( seconds) ST7800A39 ( seconds) ST7800A47 (40 seconds) ST7800A47 (40 seconds) ST7800A62 (90 seconds) ST7800A62 (90 seconds) 3 On-Off X X X 20 3 On-Off X X X On-Off, 42 On-Off, 96 On-Off, 96 On-Off, R440M6 R740M07 None 3 On-Off, R440M79 R740M07 RM7840M7 ST7800A62 90 On-Off, X X X X X 20 Isolated damper mot contact X X X X X 20 Isolated damper mot contact X X X X X Isolated damper mot contact X X X X X Isolated damper mot contact X X X 5, R440M87 None None 3 On-Off X X X 5,, R440M95 Never produced R440M3 R740M07 R440M R740M07 R440M29 Never produced R440M37 Never produced R440M45 R740M R440M2 R740M RM7840M7 RM7840M7 RM7840M7 4 RM7840M7 4 ST7800A39 ( seconds) ST7800A39 ( seconds) ST7800A47 (40 seconds) ST7800A47 (40 seconds) X 50 International model "X X X X Gdon-Piatt Energy GP 3 On-Off X X X, 3 On-Off X X X, On-Off, On-Off, 42 On-Off, 42 On-Off, X 50 International model With Selectable Airflow Switch Check (AFC). 8 Used with existing flame detects EXCEPT C702E,F Replace with C706A,F and appropriate R786 Flame Amplifier. 9 Requires Q7800A B Wiring Subbase. Never produced X X X X X X 20 Isolated damper mot contact X X X X X X 20 Isolated damper mot contact See footnotes on page

15 Table 4. HONEYWELL R440 PROGRAMMER CROSS REFERENCE. (Continued) R440M R740M R440M78 R740M R440M86 R740M07 5 R440M94 R740M07 5 RM7840M7 4 RM7840M7 4 RM7840M7 RM7840M7 ST7800A62 (90 seconds) ST7800A62 (90 seconds) ST7800A47 (40 seconds) ST7800A62 (90 seconds) 96 On-Off, 96 On-Off, 42 On-Off, 96 On-Off, R440M202 None None 3 On-Off, R440M2 Consult Original Equipment Manufacturer Replacement Prepurge Interlocks Direct 3 On-Off, X X X X X Isolated damper mot contact X X X X X Isolated damper mot contact X X X X X 20 X X X X X 20 X X X 5 X 5, 2, 6, Purge Timer X 50 Approved by Australian Gas Association X X X Fulton Special R440P07 None RM7896C ST7800A62 90 On-Off X X X 20 Gdon Piatt GP00 R440Y05 None RM7895A4 ST7800A3 7 On-Off X X X 20 R440Y3 None RM7895A4 ST7800A3 7 On-Off X X 4 X 20 R440Y2 None RM7895A4 ST7800A39 On-Off X X X 20 R440Y39 None RM7895A4 ST7800A39 On-Off X X 4 X 20 R440Y47 None RM7895A4 ST7800A54 On-Off X X X 20 R440Y54 None RM7895A4 ST7800A54 On-Off X X 4 X 20 R440Y62 None RM7895A4 ST7800A62 90 On-Off X X X 20 R440Y70 None RM7895A4 ST7800A62 90 On-Off X X 4 X 20 See footnotes on page

16 FOOTNOTES: R440 Interlocks become Pre-Ignition Interlocks (must remain closed throughout Purge). 2 4 second. 3 second is not available with replacement device. 4 Spring return Firing Rate Mot (damper mot). 5 Remove Jumpers J and J2. 6 Select proper amplifier: Old Amplifier New Amplifier R7247A05 R7847A33 R7247A2 R7847A25 R7247B03 R7847B3 R7247C0 R786A26 See Note 8 R7248C04 R7848A08 R7248B28 R7848B06 R7249A03 R7849A R7476A07 R7886A0 7 With Selectable Airflow Switch Check (AFC). 8 Used with existing flame detects EXCEPT C702E,F Replace withc706a,f and appropriate 786 Flame Amplifier. 9 Requires Q7800A Q7800B Wiring Subbase

17 Table 5. HONEYWELL R 40 PROGRAMMER CROSS REFERENCE. Replacement Prepurge Interlocks Direct, 2, 6, 7, 8, 2, 6, 7, 8, 9 Purge Timer R40A07 None RM7840M7 ST7800A39 On-Off X X X 20 Includes R7257 Amplifier. R40A None RM7840M7 ST7800A39 On-Off X X X R40A None RM7840M7 ST7800A39 On-Off X X X 20 R40A3 None RM7840M7 ST7800A39 On-Off X X X, X 20 Kewanee label. R40A49 International Model On-Off X X X 5 X 200 Includes R7257 International model. R40A56 None RM7840M7 ST7800A39 On-Off X X X X 20 R40A64 None RM7840M7 ST7800A39 On-Off X X X, 20 R40A72 International Model On-Off X X X 200 International model. R40A80 None RM7840M7 ST7800A39 On-Off X X X, X 20 Kewanee label. R40A98 Never Produced Never produced R40A6 None RM7840M7 ST7800A39 On-Off X X X 5 X 20 R40A4 None RM7840M7 ST7800A54 On-Off X X X 20 R40A22 None RM7840M7 ST7800A62 90 On-Off X X X 20 R40A None RM7840M7 ST7800A54 On-Off X X X, R40A48 None RM7840M7 ST7800A62 90 On-Off X X X, R40A5 None RM7840M7 ST7800A62 90 On-Off X X X, X 20 Kewanee label. R40A63 None RM7840M7 ST7800A39 On-Off X X X X 20 R40A7 None RM7840M7 ST7800A62 90 On-Off X X X X 20 R40A89 None RM7840M7 ST7800A62 90 On-Off X X X X R40A97 None RM7840M7 ST7800A39 On-Off X X X International model R40A205 International Model 37 On-Off X X X International model R40A23 International Model 37 On-Off X X X International model R40A22 International Model 37 On-Off X X X International model R40A9 None RM7840M7 ST7800A62 90 On-Off X X X X See footnotes on page

18 Table 5. HONEYWELL R 40 PROGRAMMER CROSS REFERENCE. (Continued) R40A247 None RM7840M7 ST7800A39 On-Off X X X 20 R40A254 None RM7840M7 ST7800A62 90 On-Off X X X R40A262 International Model On-Off X X X X International model R40A270 None RM7840M7 ST7800A39 On-Off X X X 20 R40A288 None RM7840M7 ST7800A47 (40 seconds) Replacement Prepurge Interlocks Direct, 2, 6, 7, 8, 2, 6, 7, 8, 9 Purge Timer 35 On-Off X X X 20 5 second stabilization befe. R40A296 International Model On-Off X X X International model. Ignition on 3 secs befe pilot valve. R40B05 None RM7840M7 ST7800A39 On-Off X X X 20 R7258A included R40B3 Never Produced Never produced R40C03 None RM7840M7 ST7800A39 On-Off X X X 20 R7259A included R40C Never Produced R40C29 None RM7840M7 ST7800A39 On-Off X X X 20 R7259A included R40D0 Never Produced Never produced R40E08 None None X X 3 20 F direct spark ignition applications R40F06 International Model International - Japan R40F4 International Model International - Japan R40G04 R740G2008 RM7840G4 ST7800A54 ( seconds) R40G2 R740M07 4, 5 RM7840M7 ST7800A62 (90 seconds) 50 LHL, 72 On-Off, X X X 9 X X X X 3 X X 20 See footnotes on page

19 Table 5. HONEYWELL R 40 PROGRAMMER CROSS REFERENCE. (Continued) R40G20 R740G2008 RM7840G4 ST7800A54 ( seconds) 50 LHL, R40G38 International Model 50 LHL, R40G46 R740G2008 RM7840G4 ST7800A54 ( seconds) 50 LHL, R40G53 Consult Original Equipment Manufacturer 72 LHL, R40G6 Consult Original Equipment Manufacturer 72 LHL, R40G79 R740M07 RM7840M7 ST7800A62 (90 seconds) 72 LHL, R40G87 Consult Original Equipment Manufacturer 72 LHL, X X X 9 X 8 3- X X X 9 X 8 3- X X X 9 X 8 3- X X X X, X X X X X, Kewanee label International model 20 X X X 3 X X 20 X X X X, 4-20 Cleaver Brooks CB2 20 Cleaver Brooks CB4, CB4-20 Cleaver Brooks CB2- R40G95 Never Produced Never produced R40G3 R740G2008 RM7840G4 ST7800A54 LHL, R40G Replacement Prepurge Interlocks R740G2008 RM7840G4 ST7800A54 LHL, R40G29 None ST7800A54 LHL, R40G37 R740G2008 RM7840G4 ST7800A54 LHL, R40G45 R740G2008 RM7840G4 ST7800A54 LHL, X X X X, 3- X X X X 4- X X X X X 4- X X X X, 4- X X X X Gdon-Piatt Energy GP Direct, 2, 6, 7, 8, 2, 6, 7, 8, 9 Purge Timer See footnotes on page

20 Table 5. HONEYWELL R 40 PROGRAMMER CROSS REFERENCE. (Continued) Replacement Prepurge Interlocks R40G2 Never Produced Never produced R40G Consult Original Equipment Manufacturer 72 LHL, R40G78 R740G2008 RM7840G4 ST7800A54 LHL, R40G86 R740G00 RM7840G4 ST7800A54 LHL, X X X X, 4- X X X X 4- X X X X, 4-20 Cleaver Brooks CB2- A R40G94 Never Produced Never produced R40G202 International Model 62 LHL, "X X X X X 5 X Direct, 2, 6, 7, 8, 2, 6, 7, 8, 9 Purge Timer 50 International model to Gdon-Piatt Energy Specifications. R40H02 International Model On-Off X X 9 X 3, 58 R40H International Model On-Off X X 9 X 3, 58 R40H28 International Model On-Off X X 9 X 3, 58 R40H36 International Model On-Off X X 9 X 3, International model International model International model R40J07 International Model 37 On-Off X 5 X International model R40K05 International Model 37 On-Off X 5 X International model R40L03 R40L R740L09 ST7800A62 (90 seconds) R740L09 ST7800A62 (90 seconds) 72 LHL, HF- 72 LHL, HF- X X X X X, X X X X X, See footnotes on page

21 Table 5. HONEYWELL R 40 PROGRAMMER CROSS REFERENCE. (Continued) R40L29 R40L37 R40L45 R40L52 R740L09 ST7800A54 LHL, HF- R740L09 ST7800A62 (90 seconds) R740L09 ST7800A62 (90 seconds) 72 LHL, HF- 72 LHL, HF- X X X X X 4- X X X X X, X X X X X, Gdon-Piatt Energy GP0 (iginal) Never Produced Never produced R40L Consult Original Equipment Manufacturer 72 LHL, HF- R40L78 Replacement Prepurge Interlocks R740L09 ST7800A54 LHL, HF- X X X X X, 4- X X X X X 4- Direct, 2, 6, 7, 8, 2, 6, 7, 8, 9 Purge Timer 20 Cleaver Brooks CB4- A 20 Gdon-Piatt Energy GP0 R40M0 R740M07 RM7840M7 ST7800A62 90 On-Off X X X Ray Burner R40M9 None RM7840M7 ST7800A62 90 On-Off X X X Ray Burner - Special Base R40M27 R740M07 RM7840M7 ST7800A39 On-Off X X X 20 R40M35 R740M07 RM7840M7 ST7800A39 On-Off X X X 20 R40M43 R740M07 RM7840M7 ST7800A39 On-Off X X X X 20 R40M50 R740M07 RM7840M7 ST7800A39 On-Off X X X, 20 R40M68 R740M07 RM7840M7 ST7800A62 90 On-Off X X X 20 R40M76 R740M07 RM7840M7 ST7800A62 90 On-Off X X X X 20 R40M84 R740M07 RM7840M7 ST7800A62 90 On-Off X X X 20 R40M92 None RM7840M7 ST7800A62 90 On-Off X X X X Gdon-Piatt Energy GP0 (iginal) R40M0 R740M07 RM7840M7 ST7800A39 On-Off X X X, 20 R40M8 None RM7840M7 ST7800A39 On-Off X X X X 20 R40M26 R740M07 RM7840M7 ST7800A39 On-Off X X X X 20 See footnotes on page

22 Table 5. HONEYWELL R 40 PROGRAMMER CROSS REFERENCE. (Continued) Replacement Prepurge Interlocks Direct, 2, 6, 7, 8, 2, 6, 7, 8, 9 Purge Timer R40M34 R740M07 RM7840M7 ST7800A39 On-Off X X X 20 R40M42 R740M07 RM7840M7 ST7800A62 90 On-Off X X X X R40M9 R740M07 RM7840M7 ST7800A62 90 On-Off X X X R40M67 Never Produced Never produced R40M75 None RM7840M7 ST7800A62 90 On-Off X X X X Gdon-Piatt Energy GP0 R40X04 International Model On-Off X X 5 X 5 X International model R40X2 International Model On-Off X X 5 X 5 X 50 International model R40X20 International Model International model FOOTNOTES: R40 Interlocks become Pre-Ignition Interlocks (must remain closed throughout Purge). 2 4 second. 3 Second is not available with replacement device. 4 Spring return Firing Rate Mot (damper mot). 5 Remove Jumpers J and J2. 6 Select proper amplifier: Old Amplifier Replacement Amplifier R7257A28 R7847A33 R7258A0 R7848A08 R7259A00 R7849A 7 With Selectable Air Flow Switch Check (AFC). 8 Use with existing flame detects EXCEPT C702E,F replace with C706A,F and appropriate R786 Flame Amplifier. 9 Requires Q7800A Q7800B Wiring Subbase

23 Table 6. HONEYWELL 7800 SERIES PROGRAMMER, PRIMARY CONTROL CROSS REFERENCE. Prepurge Interlocks Current Replacement Air-Flow SW Check Run/Test Switch Flmae Timer RM7800E02 RM7800E Selectable LHL HF, PRV X X X X X X 4, RM7800E RM7800E Selectable LHL HF, PRV X X X X X X 4, RM7800G00 RM7800G8 Selectable LHL PRV X X X X X 4, RM7800G8 RM7800G8 Selectable LHL PRV X X X X X 4, RM7800L04 RM7800L2 Selectable LHL HF, PRV X X X X X X 4, RM7800L2 RM7800L2 Selectable LHL HF, PRV X X X X X X 4, RM7800L38 RM7800L38 Selectable LHL HF, PRV X X X X X X 4, RM7800L46 RM7800L46 Selectable LHL HF, PRV X X X X X X 4, RM7800L53 RM7800L53 Selectable LHL HF, PRV X X X X X X 4, RM7800L6 RM7800L79 Selectable LHL HF, PRV X X X X X X 4, RM7800L79 RM7800L79 Selectable LHL HF, PRV X X X X X X 4, RM7800M03 RM7800M Selectable LHL PRV X X X X X 4, RM7800M RM7800M Selectable LHL PRV X X X X X 4, RM7800M36 RM7800M36 Selectable LHL PRV X X X X X 4, X, X, X X,, X X,, X, X, X, X, X X, X, X, with Energy Saving Purge and display module 4- with Energy Saving Purge and display module With display module 4- With display module With display module 4- With display module 4- Fulton Proprietary 4- Vap Proprietary ( ) 4- With display module-intermittent Pilot 4- Cleaver Brook Proprietary ( ) 4- Cleaver Brook Proprietary ( ) X X With display module X X X X 2- With display module 2- Fulton Proprietary

24 Table 6. HONEYWELL 7800 SERIES PROGRAMMER, PRIMARY CONTROL CROSS REFERENCE. (Continued) Prepurge Interlocks Current Replacement RM7838A06 RM7838A4 Selectable LHL HF PRV X X 4, RM7838A4 RM7838A4 Selectable LHL HF PRV X X 4, RM7838B05 RM7838B3 Selectable LHL HF, PRV X X X X X X X 4, RM7838B3 RM7838B3 Selectable LHL HF, PRV X X X X X X X 4, RM7838C04 RM7838C04 Selectable LHL HF, PRV X X X X X X X 4, RM7840E08 RM7840E6 Selectable LHL HF, PRV X X X X X X 4, RM7840E6 RM7840E6 Selectable LHL HF, PRV X X X X X X 4, RM7840G06 RM7840G4 Selectable LHL PRV X X X X X 4, RM7840G4 RM7840G4 Selectable LHL PRV X X X X X 4, RM7840L00 Selectable LHL HF, PRV X X X X X X 4, Selectable LHL HF, PRV X X X X X X 4, RM7840L26 RM7840L26 Selectable LHL HF, PRV X X X X X X 4, X Semi-automatic control, with display module X Semi-automatic control, with display module X With display module X X X X X, X, X X,, X X,, X, X, X X, With display module With display module, Alarm sounds only on safety shutdown, Requires ST7800C type Purge Timer with Energy Saving Purge with Energy Saving Purge Intermittent Pilot Air-Flow SW Check Run/Test Switch Flmae Timer

25 Table 6. HONEYWELL 7800 SERIES PROGRAMMER, PRIMARY CONTROL CROSS REFERENCE. (Continued) Prepurge Interlocks Current Replacement RM7840L34 RM7840L42 Selectable LHL HF, PRV X X X X X X 4, RM7840L42 RM7840L42 Selectable LHL HF, PRV X X X X X X 4, RM7840M09 RM7840M7 Selectable LHL PRV X X X X X 4, RM7840M7 RM7840M7 Selectable LHL PRV X X X X X 4, X, X, X X X X 4- Cleaver Brook Proprietary ( ) 4- Cleaver Brook Proprietary ( ) 2- Air-Flow SW Check Run/Test Switch Flmae Timer

26 Table 7. FIREYE TO HONEYWELL PROGRAMMER CROSS REFERENCE. Current Replacement 2 4 Replacement Prepurge Interlocks Lo-Fire On-Off LHL LHL PRV OP Damp 24CJ5 00 None RM7840M7 24CJ5 00 None RM7840M7 24CJ5 None RM7840M7 24CJ5 None RM7840M7 24CJ5 4 None RM7840G4 24CJ5 50 None RM7840M7 24CJ5 50 None RM7840M7 24CJ5 50 None RM7840G4 24CJ5 50A None RM7840G4 33 X X X 7 X 8 4 sec FFRT, rectification type flame sens, vacuum tube X X X 7 X X X sec FFRT, rectification type flame sens." 37 X X X X 7 X X sec FFRT, rectification type flame sens. 98 X X X X 7 X X sec FFRT, rectification type flame sens. X X X X 7 X sec FFRT, rectification type flame sens. 37 X X X X 5 X X 20-4 sec FFRT, rectification type flame sens. 98 X X X X 5 X X sec FFRT, rectification type flame sens. X X X X 7 X, X X X X 7 X, 24PJ8 00 None RM7840G4 0 X, 4-4- X RJ8 00 None None 7 X sec FFRT, rectification type flame sens. 4 sec FFRT, rectification type flame sens. Rectification type flame sens, low voltage. -4 sec FFRT, low voltage special f air heaters, vacuum tube electronics. See footnotes on page

27 Table 7. FIREYE TO HONEYWELL PROGRAMMER CROSS REFERENCE. (Continued) Replacement Prepurge Interlocks Current Replacement 2 4 Lo-Fire On-Off LHL LHL PRV OP Damp 25CU6 50 None RM7840M7 25CU6 62 None RM7840M7 ot 25CU6 63 None RM7840M7 25CU6 65 None RM7840G4 25CU None RM7840M7 25CU None RM7840M7 25CU CU6 5065A 25CU CU6 5066A None None RM7840G4 25CU6 RS-2 None RM7840M7 25CU6 RS-2D None RM7840M7 25CU6 RS-2RE None RM7840M7 X X X 7 X X 20 4 sec FFRT, UV type flame detect. 37 X X X X 7 X X 20-4 sec FFRT, UV type flame detect. 98 X X X X 7 X X sec FFRT, UV type flame detect. X X X X 7 X sec FFRT, UV type flame detect. 37 X X X X 7 X X 20-4 sec FFRT, UV type flame detect. 98 X X X X 7 X X sec FFRT, UV type flame detect. X X X X X 7 X, X X X X 7 X, sec FFRT, UV type flame detect. 4 sec FFRT, UV type flame detect." X X X 7 X X X 20 Ray Burner special, 4 sec FFRT, UV type flame detect. 98 X X X X 7 X X X Ray Burner special, -4 sec FFRT, UV type flame detect. 98 X X X X 5 X X Ray Burner special, -4 sec FFRT, UV type flame detect. See footnotes on page

28 Table 7. FIREYE TO HONEYWELL PROGRAMMER CROSS REFERENCE. (Continued) Replacement RU None RM7800L2 25RU None RM7840G4 RM7800G8 25RU8 65 None RM7800G8 24RU None RM7840G4 25RU None RM7800L2 25RU None RM7800L2 Prepurge Interlocks Current Replacement X X X X X 8 X, 33 X X X X 7 X, X X X 7 X, 40 X X X X, X X X X 7 X, 45 X X X X X X,, X 3- X 4-2- X 4- X Lo-Fire On-Off LHL LHL PRV OP Damp 4 sec FFRT, used with selfcheck UV flame detect 4 sec FFRT, UV type flame detect. -4 sec FFRT, UV type flame detect. 4 sec FFRT, UV type flame detect. 4 sec FFRT, UV type flame detect. -2 sec FFRT, UV type flame detect. 26CF6 00 None RM7840M7 ot 26CF6 None RM7840M7 26CF6 None RM7840M7 26CF6 2 None RM7840G4 26CF None RM7840M7 X X X X 7 X 37 X X X X 7 X X 98 X X X X 7 X X 25 X X X X 7 X X X X X X X -4 sec FFRT, IR type flame detect. -4 sec FFRT, IR type flame detect. -4 sec FFRT, IR type flame detect. -4 sec FFRT, IR type flame detect. -4 sec FFRT, IR type flame detect. See footnotes on page

29 Table 7. FIREYE TO HONEYWELL PROGRAMMER CROSS REFERENCE. (Continued) 26CF6 502 None RM7840M7 26CF CF6 5022A Replacement None Prepurge Interlocks 98 X X X X X X 25 X X X X X 7 X, CF CF6 50A None RM7840G4 26CF6 RC-3A None RM7840G4 X X X X 7 X, X X X X 7 X, RJ8 00 None RM7840G4 RM7800G8 26RJ8 0 None RM7840G4 RM7800G8 26RJ8 02 None Consult OEM f replacement X X X 3- X X X 4- X X X X RJ8 03 None RM7840G4 RM7800G8 X X X RJ8 04 None RM7840G4 RM7800G8 X X X sec FFRT, IR type flame detect. With AUTOCHECK feature, same as Honeywell R7245B AMPLI-CHECK. 4 sec FFRT, IR type flame detect. Ray Burner special, 2 sec FFRT. 4 sec FFRT, IR type flame detect, low voltage controller. Orr and Sewbower special, IR type flame detect, low voltage controller. Cleaver Brooks special, 4 sec FFRT, IR type flame detect, low voltage controller. Nth America special, 4 sec FFRT, IR type flame detect, low voltage controller. 4 sec FFRT, IR type flame detect, B&W FM boiler special, vacuum tube Current Replacement 2 4 Lo-Fire On-Off LHL LHL PRV OP Damp See footnotes on page

30 Table 7. FIREYE TO HONEYWELL PROGRAMMER CROSS REFERENCE. (Continued) Replacement RJ8 05 None RM7840M7 RM7800M Prepurge Interlocks X X X 2 26RJ8 06 None RM7840G4 RM7800G8 X X X X RJ8 08 None RM7840G4 RM7800G8 X X X, RJ8 09 None RM7840M7 RM7800M X X X, 2 26RJ8 None RM7840G4 RM7800G8 0 X X X X, RJ8 2 26RJ8 2T 26RJ8 6 26RJ8 6T None RM7840G4 RM7800G8 None RM7840G4 RM7800G8 26RJ8 8 None RM7840G4 RM7800G8 35 X X X X HL X X 4-45 X X X X, RJ8 4, 26RJ8, 26RJ8 594 None None 45 X X X X X 5, sec FFRT, IR type flame detect, B&W FM boiler special, vacuum tube 4 sec FFRT, IR type flame detect, low voltage 4 sec FFRT, IR type flame detect, low voltage 4 sec FFRT, IR type flame detect, low voltage Nth America special, IR type flame detect, low voltage controller, vacuum tube Nth America special, dual IR type flame detects, vacuum tube sec FFRT, dual IR type flame detects, vacuum tube 2-4 sec FFRT, IR type flame detects, low voltage circuitry U.S. Navy special, no replacement available,voltage controller, vacuum tube Current Replacement 2 4 Lo-Fire On-Off LHL LHL PRV OP Damp See footnotes on page

31 Table 7. FIREYE TO HONEYWELL PROGRAMMER CROSS REFERENCE. (Continued) Replacement RJ8 08 None RM7840G4 RM7800G8 26RJ8 09 None RM7840M7 RM7800M 26RJ8 2 None RM7840G4 RM7800G8 26RJ8 6 None RM7840G4 RM7800G8 26RJ8 8 None RM7840G4 RM7800G8 35 X X X X, X X X X X X 4-65 X X 4-45 X X X X X, 4-26RJ8 26 None X X X 7 X RJ8 58 None RM7840G4 RM7800G8 26RJ8 None RM7800G8 26RJ8 66 None RM7840G4 RM7800G8 Prepurge Interlocks Current Replacement X X X X X, 55 X X X X 7 X, X X X X X, sec FFRT, IR type flame detect, low voltage B&W FM boiler special, -4 sec FFRT, IR type flame detect, low voltage -4 sec FFRT, dual IR type flame detects, low voltage -4 sec FFRT, dual IR type flame detects, low voltage -4 sec FFRT, IR type flame detect, low voltage 20-4 sec FFRT, IR type flame detect, low voltage controller, special f air heaters 20-4 sec FFRT, IR type flame detect, vacuum tube Lo-Fire On-Off LHL LHL PRV OP Damp -4 sec FFRT, IR type flame detect, vacuum tube -4 sec FFRT, IR type flame detect, vacuum tube See footnotes on page

32 Table 7. FIREYE TO HONEYWELL PROGRAMMER CROSS REFERENCE. (Continued) Replacement RJ8 68 None RM7840G4 RM7800G8 26RJ8 70 None RM7800L2 26RJ8 80 None RM7800G8 26RJ8 6 None RM7800G8 Prepurge Interlocks Current Replacement X X X X, 65 X X X X X, 45 X X X X X X,, X X X X 7 X, 4-4- X X RJ8 CB- Consut OEM 45 X X X X 4-26RJ8 CB-3 Consult OEM 45 X X X X X X ",, " sec FFRT, IR type flame detect, vacuum tube circuitry, f Canada sec FFRT, IR type flame detect, vacuum tube Lo-Fire On-Off LHL LHL PRV OP Damp -2 sec FFRT, IR type flame detect, vacuum tube -4 sec FFRT, IR type flame detect, vacuum tube Cleaver Brooks special, IR type flame detect, low voltage controller. Cleaver Brooks special, IR type flame detect, low voltage controller. 29RF5 00 None RM7840G4 RM7800G8 29RF5 0 None RM7840G4 RM7800G8 29RF5 02 None RM7840G4 RM7800G8 X X X 5 X 2 25 X X X 7 X X 3 2 X X X 5 X 2-4 sec FFRT, IR type flame detect, low voltage -4 sec FFRT, IR type flame detect, low voltage -4 sec FFRT, IR type flame detect, low voltage See footnotes on page

33 Table 7. FIREYE TO HONEYWELL PROGRAMMER CROSS REFERENCE. (Continued) Replacement RF5 05 None RM7840G4 RM7800G8 29RF5 09 None RM7840G4 RM7800G8 29RF5 None RM7840G4 RM7800G8 X X 5, X 2 25 X X X 7 X X X X 5, X 2-29RF5 3 None X X 5 X 2 29RF5 4 None RM7840G4 RM7800G8 29RF5 09 None RM7840G4 RM7800G8 29RF5 None RM7840G4 RM7800G8 Prepurge Interlocks Current Replacement X X 5 X 2 25 X X X 7 X X X X 50, 2 X 2 20 Lo-Fire On-Off LHL LHL PRV OP Damp 2-4 sec FFRT, IR type flame detect, low voltage -4 sec FFRT, IR type flame detect, low voltage 2-4 sec FFRT, IR type flame detect, low voltage Military special, IR type flame detect, low voltage A.E.C. Kilns special, IR type flame detect, low voltage -4 sec FFRT, IR type flame detect, low voltage -4 sec FFRT, IR type flame detect, low voltage 29RF5 63 None Military special, IR type flame detect, vacuum tube D-506 See footnotes on page 36. None RM7800L2 X X X X X X, X sec FFRT, rectification type flame detect, solid state

34 Table 7. FIREYE TO HONEYWELL PROGRAMMER CROSS REFERENCE. (Continued) D-5022 Replacement None RM7800L2 Prepurge Interlocks X X X X X X, X 4- D-5065 D20-50 D20-50 D D-50 D-50 D-5020 D-502 D-5062 None RM7800L2 None RM7800L2 None RM7800G8 None RM7800L2 None RM7840M7 None RM7840M7 None RM7840M7 None RM7840M7 None RM7840M7 X X X X X X, X X X X X, PRV PRV X X X X, X X X X, X 4- X 4- X 4- X 4- X X X X X X X 90 X X X X X X X X X X X X X X 90 X X X X X X X X X X X X X X 4 sec FFRT, IR type flame detect, auto check amplifier, solid state 4 sec FFRT, UV type flame detect, solid state 4 sec FFRT, rectification type flame detect, solid state 4 sec FFRT, IR type flame detect, solid state 4 sec FFRT, UV type flame detect, solid state 4 sec FFRT, rectification type flame detect, solid state " 4 sec FFRT, rectification type flame detect, solid state 4 sec FFRT, IR type flame detect, solid state 4 sec FFRT, IR type flame detect, solid state 4 sec FFRT, IR type flame detect, solid state Current Replacement 2 4 Lo-Fire On-Off LHL LHL PRV OP Damp See footnotes on page

35 Table 7. FIREYE TO HONEYWELL PROGRAMMER CROSS REFERENCE. (Continued) D-5063 Replacement None RM7840M7 Prepurge Interlocks 7 X X X EP None RM7800L2 X X X X X X, 4- EP6 None RM7800L2 X X X X X X, EP70 EP2 None RM7800L2 X X X X X 5, None RM7800G8 X X X X X, 4- X X 4-4- EP26 EP270 None RM7800G8 X X X X X, None RM7800G8 X X X X 5, 4- X X 4- EP380 None RM7800M X X X X X X EP38 None RM7800M X X X X 5, X EP390 None RM7800M 90 X X X X 5, X X 4 sec FFRT, IR type flame detect, solid state 4 sec FFRT, rectification type flame detect, solid state 4 sec FFRT, IR type flame detect, solid state 4 sec FFRT, UV type flame detect, solid state 4 sec FFRT, rectification type flame detect, solid state 4 sec FFRT, lr type flame detect, solid state 4 sec FFRT, UV type flame detect, solid state 4 sec FFRT, rectification type flame detect, solid state 4 sec FFRT, rectification type flame detect, solid state 4 sec FFRT, IR type flame detect, solid state Current Replacement 2 4 Lo-Fire On-Off LHL LHL PRV OP Damp See footnotes on page

36 FOOTNOTES: Refer to Modernization Wiring Infmation f conversion wiring infmation. 2 Refer to Modernization Programmer Selection section f proper subbase, amplifier and flame detect. 3 second postpurge. 4 Replacement is 20 Vac, Hz second prepurge. 6 See Series ST7800A Plug-in Timers f prepurge timings available. 7 second second prepurge. 9 6 second postpurge. 4- modulation., second. 2 RM7840G,M meets current UL requirements. 3 RM7840L meets current insurance requirements second prepurge.,, second. 6 second prepurge. 7,, second. 8 second second postpurge second. 2 second prepurge second prepurge. With display module. 24 Existing Fireye UV Senss must be replaced with a Honeywell C7027A interlocks become lockout interlocks after main valve opens second prepurge second on terminal Available from proprietary OEM only second trial f ignition on terminal 6. Early spark termination. 3 EP0, EP200 Series, add a second waiting period after prepurge while mot is driving to low fire position f a total prepurge of seconds. 32 Select proper flame amplifier. 33 Requires Q7800A Q7800B Wiring Subbase. Automation and Control Solutions Honeywell International Inc. Honeywell Limited-Honeywell Limitée 985 Douglas Drive Nth 35 Dynamic Drive Golden Valley, MN Scarbough, Ontario MV 4Z9 customer.honeywell.com U.S. Registered Trademark 2005 Honeywell International Inc G.R. Rev. 0-05

Programmer Control Cross Reference

Programmer Control Cross Reference Programmer Control Cross Reference CROSS REFERENCE Honeywell has provided proprietary and/ labelled controls certain Original Equipment Manufacturers (OEM) at their request. Proprietary controls are available

More information

7800 SERIES EC7895A,C; RM7895A,B,C,D and RM7896A,B,C,D Relay Modules

7800 SERIES EC7895A,C; RM7895A,B,C,D and RM7896A,B,C,D Relay Modules 7800 SERIES EC7895A,C; RM7895A,B,C,D and RM7896A,B,C,D Relay Modules SPECIFICATION DATA FEATURES APPLICATION The Honeywell EC7895/RM7895/RM7896 is a microprocessor based integrated burner control for automatically

More information

7800 SERIES RM7838B,C Relay Module

7800 SERIES RM7838B,C Relay Module 7800 SERIES RM7838B,C Relay Module SPECIFICATION DATA The RM7838B1021 and RM7838C1012 Relay Modules offer VPS, so they differ from the RM7838B1013 and RM7838C1004 in the following ways: 1. Terminal 16

More information

7800 SERIES Relay Modules

7800 SERIES Relay Modules 7800 SERIES Relay Modules This publication provides general checkout and troubleshooting procedures for the 7800 SERIES Relay Modules. CHECKOUT AND TEST SYSTEM CHECKOUT IMPORTANT Perform all Static Checkout

More information

E110 FIREYE FLAME-MONITOR BURNER MANAGEMENT CONTROL FOR USE WITH THE MICROPROCESSOR-BASED EP AND EPD STYLE PROGRAMMER MODULES

E110 FIREYE FLAME-MONITOR BURNER MANAGEMENT CONTROL FOR USE WITH THE MICROPROCESSOR-BASED EP AND EPD STYLE PROGRAMMER MODULES E-11 OCTOBER 30, 2015 E1 FIREYE FLAME-MONITOR BURNER MANAGEMENT CONTROL FOR USE WITH THE MICROPROCESSOR-BASED EP AND EPD STYLE PROGRAMMER MODULES E1 with ED5 Display Module APPROVED DESCRIPTION The Fireye

More information

FIREYE MODULAR MicroM FLAME SAFEGUARD CONTROLS

FIREYE MODULAR MicroM FLAME SAFEGUARD CONTROLS MC-5000 JUNE 9, 2015 FIREYE MODULAR MicroM FLAME SAFEGUARD CONTROLS APPROVED WARNING: Selection of this control for a particular application should be made by a competent professional, licensed by a state

More information

SIL 3 Capable. RM7890A,B,C/EC7890A,B 7800 SERIES Relay Modules SPECIFICATIONS APPLICATION INSTALLATION INSTRUCTIONS

SIL 3 Capable. RM7890A,B,C/EC7890A,B 7800 SERIES Relay Modules SPECIFICATIONS APPLICATION INSTALLATION INSTRUCTIONS RM780A,B,C/EC780A,B 7800 SERIES Relay Modules INSTALLATION INSTRUCTIONS APPLICATION The Honeywell RM780A,B,C/EC780A,B Relay Modules are microprocessor based integrated burner controls for on/off automatically

More information

SIMPLE ELECTRONIC IGNITION WIRE DIAGRAM THERMOSTAT (3) PV PILOT BURNER/IGNITOR - SENSOR Q345A (9) SPARK (4) GND (BURNER) CHASSIS GND

SIMPLE ELECTRONIC IGNITION WIRE DIAGRAM THERMOSTAT (3) PV PILOT BURNER/IGNITOR - SENSOR Q345A (9) SPARK (4) GND (BURNER) CHASSIS GND Honeywell Electronic Ignition Troubleshooting Tech Tip April 2007 The Honeywell S8610H Intermittent Pilot Module provides the ignition sequencing, pilot spark, pilot flame monitoring, Pilot Valve (PV)

More information

7800 SERIES S7800A Keyboard Display Module

7800 SERIES S7800A Keyboard Display Module 7800 SERIES S7800A Keyboard Display Module PRODUCT DATA The KDM provides local or remote annunciation of operation and fault information, remote reset, report generation, burner control data and diagnostic

More information

http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html

http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html APPLY POWER TO APPLIANCE FIELD WIRING CORRECT? DPLAY ERROR CODE 1 OR 2 Intelli-Vent TM Sequence of Operation REQUEST FOR HEAT PRESENT?

More information

S7810M ModBus Module SPECIFICATIONS APPLICATION FEATURES PRODUCT DATA

S7810M ModBus Module SPECIFICATIONS APPLICATION FEATURES PRODUCT DATA S7810M ModBus Module PRODUCT DATA SPECIFICATIONS APPLICATION The Honeywell 7800 SERIES is a microprocessor-based integrated burner control for automatically fired gas, oil or combination fuel single-burner

More information

Inventory Management Guide

Inventory Management Guide NORTH/NORTHWEST Inventory Management Guide Honeywell Residential Combustion is the industry leader in combustion controls for applications including warm air furnaces, boilers, commercial water heaters,

More information

T7079A,B Solid State Remote Temperature Controllers

T7079A,B Solid State Remote Temperature Controllers T7079A,B Solid State Remote Temperature Controllers FEATURES PRODUCT DATA Switch selection of heat or cool mode. Temperature sensing up to 400 feet. Does not require field calibration. 0K NTC temperature

More information

How To Use A Power Supply With A Powerline 2.2 (Powerline) And Powerline 3.2 Power Supply (Powerplant)

How To Use A Power Supply With A Powerline 2.2 (Powerline) And Powerline 3.2 Power Supply (Powerplant) R784, R7847, R7848, R7849, R7851, R785, R7861, R7886 Amplifiers for 7800 SERIES and R7140 Relay Modules PRODUCT DATA indicate the presence of flame when used with 7800 SERIES and R7140 Relay Modules. This

More information

WOYR2.E67774 - Switches, Appliance and Special Use - Component. Switches, Appliance and Special Use - Component

WOYR2.E67774 - Switches, Appliance and Special Use - Component. Switches, Appliance and Special Use - Component Page 1 of 24 02..2014 WOYR2.E67774 Switches, Appliance and Special Use - Component For enhanced search functionality, please visit UL's iq Family of Databases. Click on a product designation for complete

More information

Installation Guide. VisionPRO. TH8000 Series. Need Help? This manual covers the following models. System Types

Installation Guide. VisionPRO. TH8000 Series. Need Help? This manual covers the following models. System Types Installation Guide VisionPRO TH8000 Series Touch-screen Programmable Thermostat This manual covers the following models TH8110U: For 1 Heat/1 Cool systems TH8320U: For up to 3 Heat/2 Cool systems TH8321U:

More information

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin 1-800-432-8373. 2 Inch PowerVent LED Indicator Explanations & Troubleshooting Table

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin 1-800-432-8373. 2 Inch PowerVent LED Indicator Explanations & Troubleshooting Table New Robertshaw control valve was introduced in May 2008 as a replacement part. See last page for troubleshooting this replacement part. All voltage inputs are 120V. All electrical connectors are Molex

More information

TYPE 65UV5-1004 CEX Integrated Flame Scanner with Internal Flame Relay and Analog Output

TYPE 65UV5-1004 CEX Integrated Flame Scanner with Internal Flame Relay and Analog Output 133-683 JUNE 28, 2006 TYPE 65UV5-1004 CEX Integrated Flame Scanner with Internal Flame Relay and Analog Output DESCRIPTION APPLICATION The Fireye 65UV5-1004 flame scanner is a microprocessor based flame

More information

Eclipse Veri-Flame Single Burner Monitoring System Model 5600 Version 1

Eclipse Veri-Flame Single Burner Monitoring System Model 5600 Version 1 Instruction Manual 88 9/5/008 Eclipse Veri-Flame Single Burner Monitoring System Model 5600 Version Modulation Model No Purge Model Purge Model Co p y r i g h t Copyright 008 by Eclipse, Inc. All rights

More information

Model 7586. Description / Applications. Intermittent Pilot Gas Ignition Control

Model 7586. Description / Applications. Intermittent Pilot Gas Ignition Control PARTS & ACCESSORIES Model 7586 Intermittent Pilot Gas Ignition Control Description / Applications The Beckett GeniSys Intermittent Pilot Gas Ignition Control is a 24 Vac gas ignition and safety control.

More information

G670 Intermittent Pilot Ignition Controls

G670 Intermittent Pilot Ignition Controls Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin Issue Date 0300 Intermittent Pilot Ignition Controls Figure 1: Intermittent Pilot Ignition Control

More information

DKG 972 Gas Burner Safety Control

DKG 972 Gas Burner Safety Control A Honeywell Company Gas Burner Safety Control For 2-stage atmospheric gas burners Flame detection: - Ionisation probe - Infrared-flicker detector IRD 1020.1 - UV flame sensor UVD 971 EN1C-0127SZ20 R0305

More information

Veri-Flame Single Burner Monitoring System

Veri-Flame Single Burner Monitoring System Instruction Manual 88 6//06 Veri-Flame Single Burner Monitoring System Model 5600 Version.2 Modulation Model No Purge Model Purge Model Copyright Disclaimer notice Copyright 2006 by Eclipse, Inc. All rights

More information

B I N G O B I N G O. Hf Cd Na Nb Lr. I Fl Fr Mo Si. Ho Bi Ce Eu Ac. Md Co P Pa Tc. Uut Rh K N. Sb At Md H. Bh Cm H Bi Es. Mo Uus Lu P F.

B I N G O B I N G O. Hf Cd Na Nb Lr. I Fl Fr Mo Si. Ho Bi Ce Eu Ac. Md Co P Pa Tc. Uut Rh K N. Sb At Md H. Bh Cm H Bi Es. Mo Uus Lu P F. Hf Cd Na Nb Lr Ho Bi Ce u Ac I Fl Fr Mo i Md Co P Pa Tc Uut Rh K N Dy Cl N Am b At Md H Y Bh Cm H Bi s Mo Uus Lu P F Cu Ar Ag Mg K Thomas Jefferson National Accelerator Facility - Office of cience ducation

More information

Q309A,B; Q335C; Q340A; Q390A Thermocouples and Q313A,B,C,F Thermopile Generators

Q309A,B; Q335C; Q340A; Q390A Thermocouples and Q313A,B,C,F Thermopile Generators Q309A,B; Q335C; Q340A; Q390A Thermocouples and Q313A,B,C,F Thermopile Generators FEATURES PRODUCT DATA Push-in clip, split nut, and adapter assembly for easy pilot burner installation. Q335 Spade or quick-connect

More information

Fossil fuel heating equipment

Fossil fuel heating equipment Fossil fuel heating equipment principles and troubleshooting techniques Application Note This application note was written to provide you with an understanding of the basic principles of fossil fuel heating

More information

Sensi TM. Wi-Fi Programmable Thermostat MANUAL OPERATION. Version: March 2016 2016 Emerson Electric Co. All rights reserved.

Sensi TM. Wi-Fi Programmable Thermostat MANUAL OPERATION. Version: March 2016 2016 Emerson Electric Co. All rights reserved. Sensi TM Wi-Fi Programmable Thermostat MANUAL OPERATION Version: March 2016 2016 Emerson Electric Co. All rights reserved. Contents MANUAL OPERATION GUIDE Buttons and Icons 3 Basic Functionality 4 Manual

More information

SV9501/SV9502/SV9601/SV9602 SmartValve TM System Control

SV9501/SV9502/SV9601/SV9602 SmartValve TM System Control SV950/SV9502/SV960/SV9602 SmartValve TM System Control APPLICATION The Honeywell TRADELINE SmartValve TM System Controls provide easy field replacement of a wide range of SV9500, SV950, SV9502 and SV9602

More information

Valve Proving System VPS 504 Series S06 (120 VAC) Series S05 (24 VDC)

Valve Proving System VPS 504 Series S06 (120 VAC) Series S05 (24 VDC) Valve Proving System VPS 504 Series S06 (120 VAC) Series S05 (24 VDC) VPS 504 S06 (120 VAC) is: CSA Certified File # 1637485 CSA Requirement No. 4-01 (USA) Technical Information Letter R-15 (Canada) UL

More information

Installation Guide. LR-HWLV-HVAC TouchPRO Wireless. System Types

Installation Guide. LR-HWLV-HVAC TouchPRO Wireless. System Types Installation Guide LR-HWLV-HVAC TouchPRO Wireless Touchscreen Thermostat System Types Gas, oil, or electric heat with air conditioning Warm air, hot water, high efficiency furnaces, heat pumps, steam,

More information

Thermostatic Wiring Principles by Bob Scaringe Ph.D., P.E.

Thermostatic Wiring Principles by Bob Scaringe Ph.D., P.E. Thermostatic Wiring Principles by Bob Scaringe Ph.D., P.E. Basic Thermostat Types Many technicians have great difficulty understanding how to properly wire a thermostat or how to replace a thermostat with

More information

Boiler Preparation, Start-Up and Shutdown

Boiler Preparation, Start-Up and Shutdown Boiler Preparation, Start-Up and Shutdown Learning Outcome When you complete this module you will be able to: Describe the basic preparation of a boiler for start-up, and the start-up and shutdown procedures.

More information

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE 2008-36 TSG-PRESTIGE Date revised: 12/6/10

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE 2008-36 TSG-PRESTIGE Date revised: 12/6/10 prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE Date revised: 12/6/10 2008-36 TSG-PRESTIGE Table of Contents INTRODUCTION Page 1-2 SERVICING TIPS AND INSTRUCTIONS Page 3-4

More information

T6570, T8570 Series Digital Fan-Coil Thermostats

T6570, T8570 Series Digital Fan-Coil Thermostats T6570, T8570 Series Digital Fan-Coil Thermostats PRODUCT DATA APPLICATION T6570 Series Digital Fan-Coil thermostats provide line voltage on/off control for fans, valves, compressors or auxiliary electric

More information

SmartVFD Frame 4 Wiring Diagrams and Dimensional Drawings

SmartVFD Frame 4 Wiring Diagrams and Dimensional Drawings Smart Frame Wiring Diagrams and Dimensional Drawings Smart Frame Size 60 Vac:.5-7.5 HP 08/0 Vac: 0.75- HP SPECIFICATION DATA CONTENTS Smart Frame Wiring Diagrams... Frame, Fused Disconnect Wiring Diagrams...

More information

DMG 970. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners

DMG 970. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners A Honeywell Company Gas Burner Safety Control For 2-stage forced draught and combi oil/gas burners Possible flame detectors: - Ionisation probe - Infrared flicker detector 1020 - UV flame sensor UVD 971

More information

RA890F Flame Safeguard Primary Control

RA890F Flame Safeguard Primary Control RA890 lame Safeguard Primary Control INSTALLATION INSTRUCTIONS APPLICATION The RA890 Protectorelay Primary Control is a nonprogramming, amplifying relay that provides solid state electronic flame safeguard

More information

1 QPro HelpFile 01.EN.2010 2010 COPYRIGHT CONTRIVE

1 QPro HelpFile 01.EN.2010 2010 COPYRIGHT CONTRIVE QPro is a free software tool for Burner Management Systems made using Quad and TraxBus TM. Using QPro it s possible to upload and download configuration parameters for the following devices: Quad Quad400

More information

MODEL MAC-3 MULTIPLE APPLIANCE CONTROL

MODEL MAC-3 MULTIPLE APPLIANCE CONTROL TJERNLUND PRODUCTS, INC. 1601 Ninth Street White Bear Lake, MN 55110-6794 PHONE (800) 255-4208 (651) 426-2993 FAX (651) 426-9547 Visit our web site www.tjernlund.com REV. A 5/99 MODEL MAC-3 MULTIPLE APPLIANCE

More information

Honeywell CT3500/CT3595 PROGRAMMABLE THERMOSTAT

Honeywell CT3500/CT3595 PROGRAMMABLE THERMOSTAT Honeywell CT3500/CT3595 PROGRAMMABLE THERMOSTAT Weekday, Saturday and Sunday Programmable Heat and/or Cool Low Voltage (20 to 30 Vac) Thermostat and Wallplate Model CT3500/CT3595 OWNER S GUIDE Para pedir

More information

Trouble Shooting Guide

Trouble Shooting Guide Trouble Shooting Guide WWTP - Control Panel CP-1 & Remote Annunciator Panel Reference: Schematics SCOPE The following trouble shooting guide has been specifically prepared for this system and primarily

More information

Commercial Semi-Instantaneous Water Heaters

Commercial Semi-Instantaneous Water Heaters FEATURES HWI Models A. O. Smith s HWI models are available for operation with steam or boiler water as the energy source. They are factory assembled with components sized, piped and checked at the factory

More information

DUCT SMOKE DETECTOR D4120

DUCT SMOKE DETECTOR D4120 Purpose/Application National and local safety standards and codes recognize the ability of air duct systems to transfer smoke, toxic gases, and flame from area to area. Sometimes smoke can be of such quantity

More information

Manual MPA 41xx. Edition: 02.14. Nr. 257 454 - GB. Printed in Germany Edition 02.14 Nr. 257 454

Manual MPA 41xx. Edition: 02.14. Nr. 257 454 - GB. Printed in Germany Edition 02.14 Nr. 257 454 Manual MPA 41xx Edition: 02.14 GB 1 126 Nr. 257 454 - GB Table of contents Data sheet...3-6 Approval Overview...7 System description/variants/accessories/approvals...8 General technical data...9 Connection

More information

DVI 980/982 (Honeywell Nr. S4865) Gas Burner Safety Control

DVI 980/982 (Honeywell Nr. S4865) Gas Burner Safety Control Gas Burner Safety Control For 1- or 2-stage forced draught and atmospheric gas burners, with DC valves Possible flame detectors: - Ionisation probe - Infrared flicker detector 1020.1 - UV flame sensor

More information

Variable speed drives for synchronous and asynchronous motors

Variable speed drives for synchronous and asynchronous motors Imptant infmation Altivar XXXXXX Variable speed drives f synchronous and asynchronous mots ATEX manual F ATEX applications in explosive gas atmosphere in the presence of combustible dust 0/010 S1A0 www.schneider-electric.com

More information

C. Burner management system to follow requirements of Industrial Risk Insurers (IRI).

C. Burner management system to follow requirements of Industrial Risk Insurers (IRI). SECTION 23 52 30 PART 1 - GENERAL 1.01 RELATED WORK A. Section 23 05 00: Common Work Results for HVAC B. Section 23 25 00: Chemical Water Treatment C. Section 23 51 23: Flue Piping 1.02 QUALITY ASSURANCE

More information

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. DESCRIPTION

More information

80UHG. Service Literature

80UHG. Service Literature Service Literature Corp. 9728 L12 Revised 01 2002 80UHG 80UHG series units are mid efficiency gas furnaces used for upflow or horizontal applications only, manufactured with tubular heat exchangers formed

More information

WARNING CAUTION 21V51U-843 DESCRIPTION PRECAUTIONS

WARNING CAUTION 21V51U-843 DESCRIPTION PRECAUTIONS The kit Includes: CAUTI 21V51U-843 Integrated Two-Stage/Variable Speed Motor Hot Surface Ignition Control Kit INSTALLATI INSTRUCTIS Operator: Save these instructions for future use! FAILURE TO READ AND

More information

TAC I/NETTM MR-VAV-AX. Application Specific MicroRegulator TM

TAC I/NETTM MR-VAV-AX. Application Specific MicroRegulator TM TAC I/NETTM TM TAC s TM has an extensive range ofpre-engineered VAV control sequences, which combined with a fully integrated actuator and airflow transducer, makes it a low Total Installed Cost solution

More information

ONE STAGE GAS BURNERS RIELLO 40 FS SERIES FS3 11 35 kw FS5 23 58 kw FS8 46 93 kw FS10 42 116 kw FS20 81 220 kw

ONE STAGE GAS BURNERS RIELLO 40 FS SERIES FS3 11 35 kw FS5 23 58 kw FS8 46 93 kw FS10 42 116 kw FS20 81 220 kw ONE STAGE GAS BURNERS RIELLO FS SERIES FS3 35 kw FS5 3 5 kw FS 93 kw FS kw FS kw The Riello FS series of one stage gas burners, is a complete range of products developed to respond to any request for light

More information

SKP Series SKP15U.. Gas Valve Actuator with Safety Shutoff Function

SKP Series SKP15U.. Gas Valve Actuator with Safety Shutoff Function SKP Series SKP15U.. Gas Valve Actuator with Safety Shutoff Function Document No. 155-751 SKP15U.. Description Only when assembled to Series VGU Gas valves SKP15 electro-hydraulic actuators combine with

More information

LANDFILL GAS ENCLOSED FLARE SYSTEM

LANDFILL GAS ENCLOSED FLARE SYSTEM LANDFILL GAS ENCLOSED FLARE SYSTEM Part 1. General 1.01 Description A. Information within this specification describes an enclosed flare system designed specifically for the combustion of landfill gas.

More information

TYPE 25SU3-5166/5168 CONTROL SYSTEM DESCRIPTION FLAME AMPLIFIER, WIRING BASE, SCANNERS, AND DISPLAY

TYPE 25SU3-5166/5168 CONTROL SYSTEM DESCRIPTION FLAME AMPLIFIER, WIRING BASE, SCANNERS, AND DISPLAY X-742E MAY 3, 205 TYPE 25SU3-566/568 ONTROL SYSTEM DESRIPTION FLAME AMPLIFIER, WIRING BASE, SANNERS, AND DISPLAY 25SU3-566 /568 SHOWN WITH OPTIONAL DISPLAY MODULE INSTALLED WARNING: This bulletin is directed

More information

PRODUCT DESIGN. 5. Furnace awaits call from thermostat.

PRODUCT DESIGN. 5. Furnace awaits call from thermostat. Goodman / Amana Distinctions Brand Single-Stage 80% or 90% Furnaces White-Rodgers 50A55 Integrated Ignition Control 1. 115 VAC power applied to furnace. 2. Integrated ignition control module performs internal

More information

S8910U Universal Hot Surface Ignition Module

S8910U Universal Hot Surface Ignition Module SUPER TRADELINE Universal Hot Surface Ignition Module INSTALLATION INSTRUCTIONS Installation Instructions for the Trained Service Technician. APPLICATION The SUPER TRADELINE Universal Hot Surface Ignition

More information

PART 8: FIELD WIRING. n WARNING NOTICE. Boiler Manual

PART 8: FIELD WIRING. n WARNING NOTICE. Boiler Manual PART 8: FIELD WIRING A. INSTALLATION MUST COMPLY WITH: 1. National Electrical Code and any other national, state, provincial or local codes or regulations. 2. In Canada, CSA C22.1 Canadian Electrical Code

More information

GeniSys 12V. Model 7556. Description / Applications. Advanced 12 Vdc Burner Control

GeniSys 12V. Model 7556. Description / Applications. Advanced 12 Vdc Burner Control PARTS & ACCESSORIES GeniSys 12V Model 7556 Advanced 12 Vdc Burner Control Description / Applications The Beckett GeniSys TM 12V Advanced Burner Control is a 12 Vdc primary safety control for oil burners

More information

its ELECTRIC POSITION for electric heat, or set the units fan control appropriately to ELECTRIC or another appropriate setting.

its ELECTRIC POSITION for electric heat, or set the units fan control appropriately to ELECTRIC or another appropriate setting. Troubleshooting Poor Temperature Regulation This page lists problems that may affect the temperature performance of your LUX thermostat with suggested resolutions. For more detailed information please

More information

Drive Technology \ Drive Automation \ System Integration \ Services. DR Motor Common Connection Diagrams

Drive Technology \ Drive Automation \ System Integration \ Services. DR Motor Common Connection Diagrams Drive Technology \ Drive Automation \ System Integration \ Services DR Motor Common Connection Diagrams Edition 06/2010 9PD0058 / US SEW-EURODRIVE Driving the world Table of Contents Overview... 5 Important

More information

GUIDELINES FOR LOGBOOKS COMPLIANCE TO BOILER REGULATIONS N.J.A.C. 12:90

GUIDELINES FOR LOGBOOKS COMPLIANCE TO BOILER REGULATIONS N.J.A.C. 12:90 GUIDELINES FOR LOGBOOKS COMPLIANCE TO BOILER REGULATIONS N.J.A.C. 12:90 Department of Labor and Workforce Development Labor Standards & Safety Enforcement Division of Public Safety and Occupational Safety

More information

Model 5511 Filler Controller User s Manual Version 1.1 October 2011

Model 5511 Filler Controller User s Manual Version 1.1 October 2011 Thompson Scale Company WEIGHING SYSTEMS & PACKAGING MACHINERY CONTROLS 2758 Bingle Road Houston, Texas 77055 Phone: 713/932-9071 Fax: 713/932-9379 www.thompsonscale.com Model 5511 Filler Controller User

More information

Communicating Thermostats. Add More Flexibility to Building Automation with New. Communicating Thermostats

Communicating Thermostats. Add More Flexibility to Building Automation with New. Communicating Thermostats Communicating Thermostats Add More Flexibility to Building Automation with New Communicating Thermostats More Choices. More Possibilities. From zone control to rooftop units and nearly everything in between,

More information

TR21, TR22, TR23, and TR24 Wall Modules

TR21, TR22, TR23, and TR24 Wall Modules TR21, TR22, TR23, and TR24 Wall Modules FEATURES INSTALLATI INSTRUCTIS The TR21, TR22, TR23, and TR24 family of wall modules include: Models with setpoint adjustment. Models with humidity output. Models

More information

SuperIOr Controller. Digital Dynamics, Inc., 2014 All Rights Reserved. Patent Pending. Rev: 5-16-14 1

SuperIOr Controller. Digital Dynamics, Inc., 2014 All Rights Reserved. Patent Pending. Rev: 5-16-14 1 SuperIOr Controller The SuperIOr Controller is a game changer in the world of high speed embedded control. The system combines incredible speed of both control and communication with revolutionary configurable

More information

AIS750 Series Alarm Annunciator

AIS750 Series Alarm Annunciator Unparallel, modular, multipoint design with Integrated controllers Two Operation Modes (Stand-alone & Serial) All sizes confi gurable up to 440 Alarm Points RS485 / RS232 Serial Communication Manual &

More information

Maintenance Minder System Reference Guide

Maintenance Minder System Reference Guide Maintenance Minder System Reference Guide PRICE GROUP ACCORD 2006-2009, 4-Cylinder CIVIC 2006-2009 (Includes 2009 GX) CR-V 2007-2009, 2WD ELEMENT 2007-2009, 2WD FIT 2007-2009 PRICE GROUP 2 ACCORD 2006-2009,

More information

INSTALLATION INSTRUCTIONS MC95HAE-1 MASTER CONTROLLER

INSTALLATION INSTRUCTIONS MC95HAE-1 MASTER CONTROLLER INSTALLATION INSTRUCTIONS MC95HAE-1 MASTER CONTROLLER Bard Manufacturing Company, Inc. Bryan, Ohio 43506 Since 1914...Moving ahead just as planned. Manual : 2100-360B Supersedes: 2100-360A File: Volume

More information

This chart is intended for selection purposes only. For complete product application information, refer to individual product specification sheets.

This chart is intended for selection purposes only. For complete product application information, refer to individual product specification sheets. 1/99 Modutrol Motors Selection Guide This chart is intended for selection purposes only. For complete product application information, refer to individual product specification sheets. 2-POSITION SPRING

More information

UV100A Ultraviolet Air Treatment System

UV100A Ultraviolet Air Treatment System UV100A Ultraviolet Air Treatment System INSTALLATION INSTRUCTIONS APPLICATION When installed in forced air heating and cooling systems, the UV100A Ultraviolet Air Treatment System kills airborne microorganism

More information

THERMAL MANAGEMENT SOLUTIONS

THERMAL MANAGEMENT SOLUTIONS t2000 Series Electronic heat-tracing controller Product Overview /COMMUNICATIONS INTERACE CARRIER REQ TO SEND The DigiTrace heat trace controller is designed to provide the benefits associated with single

More information

Features and Benefits

Features and Benefits SPC 1000 Single Point Control ABC-1000 Retropak Section: F100 Bulletin: 100.2 Date: 03/09 Supercedes: 5/01 Features and Benefits Design pressure to 450 WSP Meets ASME, CSD-1 Requirements LED Monitoring

More information

Sanitary Type Electronic Flow Switches

Sanitary Type Electronic Flow Switches Industries Pharmaceutical Sanitary Type Electronic Flow Switches Food and Beverage Biotechnology Semiconductor Water Treatment S Series Ameritrol, Inc. Instruments and Controls Features No Moving Parts

More information

In-Line Electronic Flow Switches

In-Line Electronic Flow Switches In-Line Electronic Flow Switches Industries Petrochemical Refining Oil Production Water Treatment Pharmaceutical Food and Beverage Pulp and Paper Power Production Gas Processing Mining Biotechnology Semiconductor

More information

Munchkin Heat Exchanger Maintenance

Munchkin Heat Exchanger Maintenance Munchkin Heat Exchanger Maintenance By: Mike Granahan *Refer to the appropriate boiler manual for your specific model number. Adjustment procedures will vary. Boiler shown below is an HTP Munchkin 80M

More information

Oil Burner Controls LMO24... LMO44...

Oil Burner Controls LMO24... LMO44... 7 130 Oil Burner Controls LMO14... LMO24... LMO44... Microcontroller-based oil burner controls for the startup, supervision and control of forced draft oil burners in intermittent operation. Standard versions

More information

Heating Basics Gas Valve Systems

Heating Basics Gas Valve Systems Heating Basics Gas Valve Systems UNI-LINE PRODUCT KNOWLEDGE 2010 Invensys. All Rights Reserved. The names, logos, and taglines identifying the products and services of Invensys are proprietary marks of

More information

Y7230A CO 2 Alarm System

Y7230A CO 2 Alarm System Y7230A CO 2 Alarm System FOR CO 2 GAS DETECTION PRODUCT DATA FEATURES APPLICATION Y7230A CO 2 alarm system is used to detect gas leaking from CO 2 beverage dispensing systems and posts an alarm to occupants

More information

UV100E Ultraviolet System

UV100E Ultraviolet System UV100E Ultraviolet System OWNER S GUIDE 69-1573-3 !! UV100E ULTRAVIOLET SYSTEM IMPORTANT Please read these instructions and keep them in your records. HOW YOUR ULTRAVIOLET AIR TREATMENT SYSTEM OR SURFACE

More information

R&D Electronics 8440 N. Waukegan Rd., Morton Grove, IL 60053 -- (847) 583-9080 -- Issue 12/08/06 om_207f.doc --

R&D Electronics 8440 N. Waukegan Rd., Morton Grove, IL 60053 -- (847) 583-9080 -- Issue 12/08/06 om_207f.doc -- R&D Electronics 8440 N. Waukegan Rd., Morton Grove, IL 60053 (847) 5839080 Issue 12/08/06 om_207f.doc MODEL AH 207 Heat Call MICRO PROCESSOR SYSTEM Temperature Averaging OWNERS MANUAL Model AH207, 207M

More information

Installation Guide. Programmable Thermostat TH6220D

Installation Guide. Programmable Thermostat TH6220D Installation Guide Programmable Thermostat TH6220D Product Application This thermostat provides electronic control of 24 VAC single-stage and multi-stage heating and cooling systems, or 750 mv heating

More information

Gas Unit Heaters Duct Furnaces Horizontal - 60 HZ Form No. LF24-100-400 (10/2011) LF24 Standard

Gas Unit Heaters Duct Furnaces Horizontal - 60 HZ Form No. LF24-100-400 (10/2011) LF24 Standard LF Standard Features Horizontal unit heaters are compact in design and easy to install. Steady State Efficiencies of up to 80.%. Ideal for economical commercial heating systems. Shipped completely assembled

More information

Timing, control and counting Zelio Time, Control, Count. Confidence can be measured

Timing, control and counting Zelio Time, Control, Count. Confidence can be measured Timing, control and counting Zelio Time, Control, Count Confidence can be measured Simply Smart! Leveraging ingenuity and intelligence for ease of use Zelio Time, Control and Count Zelio Time A complete

More information

PRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE

PRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE Table of Contents PRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE # Electric Room Comfort Controller NEW! RDY2000 Room Comfort Controller RDY 129-905 D-3 Electric for Specialized Applications Surface

More information

http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html

http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html TECHNICAL SERVICE DEPARTMENT Effective October 2007, we transitioned to the White Rodgers (Intelli-Vent TM )Thermostat Control for

More information

TWO STAGE GAS BURNERS

TWO STAGE GAS BURNERS TWO STAGE GAS BURNERS GAS/2 SERIES GAS 3/2 8/13 3 kw GAS 4/2 12/18 47 kw GAS /2 1/32 66 kw GAS 6/2 3/2 1 kw 4/8 176 kw 1/17 32 kw The GAS/2 series of burners covers a firing range from 8 to 32 kw and they

More information

Corner-Grounded Delta (Grounded B Phase) Systems

Corner-Grounded Delta (Grounded B Phase) Systems Data Bulletin 2700DB0202R03/12 09/2012 Replaces 2700DB0202R2/09 dated 02/2009 Corner-Grounded Delta (Grounded B Phase) Systems Class 2700 Retain for future use. Introduction Corner-grounded delta systems

More information

Burner controls. Building Technologies Division Infrastructure & Cities Sector

Burner controls. Building Technologies Division Infrastructure & Cities Sector 7 101 Burner controls LE... Burner controls for the supervision of 1- or 2-stage gas or gas/oil burners of small to medium capacity, with or without fan in intermittent operation. The LE and this Data

More information

ELECTRIC POSITION for electric heat, then confirm with Fan Test below.

ELECTRIC POSITION for electric heat, then confirm with Fan Test below. Troubleshooting Poor Temperature Regulation This page lists problems that may affect the temperature performance of your LUX thermostat with suggested resolutions. For more detailed information please

More information

For installation guide see reverse of book

For installation guide see reverse of book USERS GUIDE LOGIC Combi 24, 30, 35 For installation guide see reverse of book When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance

More information

Solid Core and Split Core Adjustable Current Status Switches CSS-O, CSS-C; CSP-O, CSP-C

Solid Core and Split Core Adjustable Current Status Switches CSS-O, CSS-C; CSP-O, CSP-C Solid Core and Split Core Adjustable Current Status Switches CSS-O, CSS-C; CSP-O, CSP-C DESCRIPTION FEATURES PRODUCT DATA Very low operating trip points LED status indication Integral DIN rail mounting

More information

FIREYE CG-14E PRICE BOOK EFFECTIVE JANUARY 1, 2012

FIREYE CG-14E PRICE BOOK EFFECTIVE JANUARY 1, 2012 FIREYE CG-14E PRICE BOOK EFFECTIVE JANUARY 1, 2012 Euro List Weight Bulletin E110 Control, consisting of EB700, 48-1836, EC600. 120 VAC. Display ordered separately. UL, FM, UL/c Approved. $1.184 5/2.0

More information

B r u ne n r e Ma M n a a n g a e g m e e m n e t A S t S rai a gh g t h for o wa w r a d A p p r p oa o c a h c h Us U i s ng n g De D l e tav a

B r u ne n r e Ma M n a a n g a e g m e e m n e t A S t S rai a gh g t h for o wa w r a d A p p r p oa o c a h c h Us U i s ng n g De D l e tav a Burner Management A Straightforward Approach Using DeltaV SIS for Typical Systems David Sheppard, CFSE Presentation: SIS, BMS, Why Implement BMS in a SIS State Transition Approach to BMS Design Review

More information

TWO STAGE GAS BURNERS RIELLO 40 GSD SERIES GS10D 29/41 106 kw GS20D 58/81 220 kw

TWO STAGE GAS BURNERS RIELLO 40 GSD SERIES GS10D 29/41 106 kw GS20D 58/81 220 kw TWO STAGE GAS BURNERS RIELLO 4 GSD SERIES 9/4 6 58/8 The Riello 4 GSD series of two stage gas burners, is a complete range of products developed to respond to any request for home heating. The Riello 4

More information

MODULATING LIGHT OIL BURNERS RL/M SERIES

MODULATING LIGHT OIL BURNERS RL/M SERIES MODULATING LIGHT OIL BURNERS RL/M SERIES RL 28/M 95/166 332 kw RL 38/M 11/237 45 kw RL 5/M 13/296 593 kw RL 7/M 261/474 143 kw RL 1/M 332/711 1482 kw RL 13/M 498/948 1779 kw RL 19/M 534/1423 2431 kw The

More information

Vanguard DC /DC-Technology - worldwide -

Vanguard DC /DC-Technology - worldwide - Vanguard DC /DC-Technology - worldwide - Catalogue INTERNATIONAL POWER For new s and latest product updates see: INTERNATIONAL POWER Vanguard DC/DC-Technology - worldwide ECONOLINE INNOLINE POWERLINE When

More information

S4965 SERIES COMBINED VALVE AND BOILER CONTROL SYSTEMS APPLICATION. Contents PRODUCT HANDBOOK. General. Technical. Various

S4965 SERIES COMBINED VALVE AND BOILER CONTROL SYSTEMS APPLICATION. Contents PRODUCT HANDBOOK. General. Technical. Various S4965 SERIES COMBINED VALVE AND BOILER CONTROL SYSTEMS APPLICATION PRODUCT HANDBOOK The S4965 boiler controls have been developed for application in gas fired domestic appliances. The S4965 boiler controls

More information

Gas Valve Proving System

Gas Valve Proving System Gas alve Proving System GY DU... Series... SO 001 The DU... gas valve proving system is designed for use in gas-fired plant equipped with two safety shutoff valves. During each startup cycle, the control

More information