Trouble Shooting Guide

Size: px
Start display at page:

Download "Trouble Shooting Guide"

Transcription

1 Trouble Shooting Guide WWTP - Control Panel CP-1 & Remote Annunciator Panel Reference: Schematics SCOPE The following trouble shooting guide has been specifically prepared for this system and primarily relates to electrical failures. When problems develop, a good trouble shooting technique is most important because the following guide will not cover all circumstances. Many mechanical functions are beyond the scope of this guide, and should be dealt with by people knowledgeable of the equipment. For example, a pump overload can be caused by mechanical problems relating to the pump and motor: bad bearings, foreign material in pump, binding seals, misalignment, etc. 1.0 GENERAL 1.1 Organization The trouble shooting guide format is arranged in four general areas: Section A discussion of common problems. Section A discussion of problem isolation techniques. Section A list of symptoms with associated possible causes. Section Alarm System In most cases, the identification of the cause will be self explanatory and the corrective action will be obvious. 1.2 SUGGESTIONS The identification of any other changes that may be associated with the problem can be helpful. Any unusual visuals, noise, smell, vibration, etc., may give a clue as to the ultimate cause. A routine inspection of the panel to look for any changes involving noise, humming, excessive dust, discoloration, smoke-burning smell, disconnected wires, vibration, chattering, heat, burning, extra screw-loose parts, etc. File: Trouble Shoot Final.doc Page 1 of 23

2 A useful test on an energized system is to check for the presence of power directly on a suspected component. On a de-energized system, test the suspected components with an ohmmeter to determine that the resistance is in the expected range. 1.3 ADJUSTMENTS Don't touch or adjust anything without being sure you know what you're doing. All adjustable components have either been factory set, or set upon first start-up. A change that requires a field re-adjustment is unusual. If a change is made, care should be exercised to make note of settings before changing so that original settings can be duplicated. 1.4 SAFETY When working on the equipment, assume that all electrical parts are energized. Even though all direct connections normally supplying power to a panel are broken, some parts may still be "hot". All work involving entry into an electrical panel should only be done by a knowledgeable technician. 2.0 COMMON PROBLEMS 2.1 MOTOR OVERLOAD Cause may be electrical, mechanical, worn bearings, something wrong on motor shaft of impeller, foreign objects in the impeller, shorted windings in motor, etc. Suggest resetting the overload and trying again. A second overload trip should be investigated before resetting. 2.2 MOTOR CIRCUIT PROTECTOR TRIP The most common causes of MCP trips occur because of winding insulation failure in the motor. If possible, inspect the motor before resetting and attempting to run again. Persistent "nuisance" tripping indicates a problem or too low a setting on the MCP trip point. Under normal conditions, setting MCP trip point 1 or 2 notch settings above trip point will be sufficient to eliminate nuisance trips. File: Trouble Shoot Final.doc Page 2 of 23

3 2.3 FIELD LOCATED SWITCH FAILURE (Level, Flow, Computer) Action of the field switches may be simulated with test switches TS1 through TS43 and SW1, SW2 and SW3 for CP-1 and TS1 through TS24 and SW1 for the Remote Annunciator Panel. If operation is not normal see operation instructions. Field transmitters (LT-1, PT-3, etc.) are tested through the use of test points (TP1, TP2, etc.) as described in the section below. Only digital field switch (FS3, TS1, FS4, etc.) operations can be checked with the test switches (TS1, TS2, etc.) also as described below: Test Switches (Digital Circuits) A field switch that should be closed but is not can be tested by moving the test switch to C (CLOSE). If the desired function takes place, this indicates a field switch or field wiring has failed. If not, a problem in the control panel may be indicated A field switch that should be opened but is not, can be tested by moving the test switch to O (OPEN). If the desired function takes place, this indicates field switch failure, or a problem in the field wiring. If not, a problem in the panel may be indicated Normal function test. Sequential operation of the test switches can be used to simulate automatic cycling of the system Be sure to return test switches to proper setting after testing. Normally, the switches should be on A (AUTOMATIC). However, there are cases where either an open or closed setting may be desired for abnormal conditions. Test Points (Analog Loop Circuits) By removing the installed jumper between test switch points to isolate field transmitters and by connecting a signal generator through test point connections, analog loop circuits may be tested. File: Trouble Shoot Final.doc Page 3 of 23

4 The procedure for performing this test is given in the Operating Instructions Manual under the section Setpoint Controller Loop Setup/ Calibration. The directions for calibration of each loop are given there and can be used to ensure the panel mounted portion of the circuit is calibrated and functioning properly. If the circuit does not function properly after calibration checks, the problem is then obviously in the field transmitter and/or field wires. Reference the narrative directly below to troubleshoot field instrumentation. 2.4 PUMP MOTOR RUN CYCLE ALTERNATION FAILURE Failure of motors to alternate running cycles can be due to primarily three basic reasons assuming all other conditions are met (circuit breaker closed, no motor overload, etc.): Faulty Alternator Relay Check to see if 24VAC power is available to the relay coil. If so, when the power is removed (by opening one of the control relay contacts or wires that connect to the coil), the alternator relay contacts shift position to enable the other alternate motor to run the next time a motor run cycle is initiated. If the contacts do not shift, replace the relay Hand-Off-Auto Switch If one of the two HOA switches associated with the alternating motor system is in the Off position, the connected motor starter will not turn on and the other motor will run each time a motor run cycle is called for. Ensure both HOA switches are in the Auto position for alternating motor run cycles Faulty Alternator Relay Contacts If all running conditions are met (alternator relay contacts shift, run cycles are enabled, HOA switches in Auto, etc.) and a motor connected to an alternating relay doesn t run but the other motor does, check the wiring connected to the set of alternator relay contacts connected to the faulted motor and repair any bad connections. If the motor still doesn t run, the alternator relay contacts are faulty and the relay needs to be replaced. File: Trouble Shoot Final.doc Page 4 of 23

5 2.4.4 Alternating Motors Motors with alternating relays are as listed below: 1- Aeration Basin Blowers B-01 and B Digester Blowers DB-01 and DB Septic Tank Pumps STEP-01 and STEP Return Activated Sludge Pumps RAS-1 and RAS PROBLEM ISOLATION The alarm indicator lights included with this system are self explanatory. The detailed isolation of a problem can also be associated with general areas of power supply: CP-1 PANEL 3.1 There are three 24 VDC power buses. PS1 supplies power for the +1/-1 bus, PS2 supplies power for the +2/-2 bus and PS3 supplies power for the +3/-3 bus. These 24VDC busses supply the power required to energize the coils of relays R1 through R6 and VDC supply for the field transmitters. PS1 power supply trickle charges the 12V gel cells through resistor RES1 and diode D1 to make sure that if there is a loss of DC Bus the strobe and horn have enough power to operate VAC fed from transformer CPT-2 through circuit breakers CB23 through CB26, involves all other relays, starter/contactor coils, counters, run time meters and associated indicating lights VAC power is fed from transformer CPT-1 through circuit breakers CB17, CB18, CB20 and a ground fault interrupter. This is also the power for power supply PS1, PS2, set point controllers, chart recorder, time clocks and all other instrumentation including the UPS which is protected by circuit breaker CB17. File: Trouble Shoot Final.doc Page 5 of 23

6 /208 VAC power is fed from circuit breaker CB7. This is power for RAS-01/02 pumps, WAS-01 pump, Heat Tape, panel heating and cooling, UV system, site/plant lighting and the duplex outlet in the control panel VAC power is fed from the main circuit breaker CB1. This is power for Septic Tank STEP- 01/02 pumps, Aeration Basin B-01/02 blowers, Digester DB-01/02 blowers, Secondary Clarifier SCO-01 drive, Digested Sludge DSP-01 pump, Unit Heater UH-1 and the 120/208VAC power transformer T-1. REMOTE ANNUNCIATOR PANEL / 120 VAC power is fed from the main circuit breaker CB1. This is power for control transformer CPT-1 which in turn provides 120 VAC power for the entire panel. 3.7 There is one 120 VAC power bus, A2/N2 that supplies power to the voltage monitor relay MR1, SPC-11 (line 4263) and the control power transformer CPT-2 (line 4301). No indicating lights are connected to this bus. However, both IL1 (24 VDC bus) and IL27 (24 VAC bus) indicating lights will not be illuminated if bus A2/N2 has lost power. 3.8 There is one 24 VDC power bus. PS1 supplies power for the +1/-1 bus. This 24VDC bus supplies the power required to energize the Annunciator Panel alarm circuits as shown on the schematic drawings from lines 4020 to The bus also provides 24 VDC power for the Water Tank analog loop at line Indicating lights IL1 (line 4021) and LED1 at the Remote Light Box are illuminated when power is available from PS1 for this bus. File: Trouble Shoot Final.doc Page 6 of 23

7 VAC fed from transformer CPT-2 through circuit breaker CB3 provides power for 24 VAC bus B/C which services the Well Pump Call control circuits. Indicating light IL27 (line 4308) is illuminated when power is available on this bus. Note that although a problem may be isolated to one of the general areas of power, some components may cause problems that are involved with more than one section. For example, relay R3 has a coil in the D.C. circuit but operating contact in the A.C. circuitry. Relays that are alike may be swapped in order to help trouble shoot. A malfunction that appears associated with a given function can be tested by swapping its relay with another identical relay. If the malfunction follows the relay, the apparent cause is a problem with the relay. For help in determining what relays to try swapping, refer to the ladder schematic diagram. Also refer to the schematic diagram to understand the function of the test switches. There is a panel mounted test switch associated with each digital field switch so that operation can be completely checked as though the field switches were operating. Please note that on Automatic operation, the total hours and number of starts on the Septic Tank STEP-01/02 pumps, Aeration Basin B-01/02 blowers, Digester DB-01/02 blowers and RAS-01/02 pumps should be approximately equal because of the operation of the alternating relays. As described in the Operating Instructions, a log of the run time meter and operation counter should be kept so that any unusual change can be noted. The panel mounted test switches can also be used to test the field switches if the malfunction is being caused by an inoperative field switch. For analog field instruments, the panel mounted circuit should be checked first as described in the narrative directly above under Test Points (Analog Loop Circuits). After ascertaining that the panel mounted portion is functioning properly, proceed to the field location of the instrument and disconnect the transmitter from the instrument loop wiring and connect the test meter with its positive lead attached to the positive field wire and File: Trouble Shoot Final.doc Page 7 of 23

8 the meter negative lead to the remaining circuit wire. Simulate a functioning instrument by running the output of the meter from 4ma to 20ma and observe the results. If the circuit operates according to circuit parameters, the field wiring is good and the problem is with the instrument itself. If the problem is with the instrument, refer to the manufacturer s operating manuals for instrument troubleshooting. File: Trouble Shoot Final.doc Page 8 of 23

9 4.0 SYMPTOMS AND POSSIBLE CAUSES Control Panel (CP-1) - Digital GENERAL CIRCUIT SYMPTOMS Septic Tank STEP-01/ 02 pumps: Step-01 won't run on HAND Step-01 won't run on AUTO (No Flow Alarm) Step-01 won't run on AUTO (Flow Alarm) Step-02 won't run on HAND Step-02 won't run on AUTO (No Flow Alarm) Step-02 won't run on AUTO (Flow Alarm) Step-01/ Step-02 won t Alternate in Auto POSSIBLE CAUSES MCP1, OL1, R28, SS12, R28A and M1 (lines 1132 through 1139). R28A, SS12, R75B, RA3B/C, TD37A, R24A, R23B, R23D, TD17A, TS21, TS22, R25C, TS23, SPC-1, SPC-2, LT-1, LT-2, F9, F10, SS-20, F11 and. F12 (lines 1139 through 1148). R75B, TD18A, TS25, R31A, SPC-7 and M1A. (lines 1105, 1110, 1144 and 1427). MCP2, OL2, R30, SS13, R30A and M2 (lines 1155 through 1162). R30A, SS13, R78B, RA3A/D, TD37A, R24A, R23B, R23D, TD17A, TS21, TS22, and R25C TS23, SPC-1, SPC-2, LT-1, LT-2, F9, F10, SS-20, F11 and F12. (lines 1148 through 1156). R78B, TD19A, TS26, R31D, SPC-7 and M2A. (lines 1152, 1118, 1152 and 1537) RA3, SS12, SS13, RA3A, RA3B, RA3C and RA3D. (lines 1140, 1146, 1147, 1149, 1150 & 1156) Aeration Basin B-01/ 02 blowers: B-01 won't run on HAND CB4, VFD-OL1, R12, SS7, R12A and R21 (lines 876 through 883). File: Trouble Shoot Final.doc Page 9 of 23

10 B-01 won't run on AUTO (No Blower Alarm) R12A, SS7, R53B, RA1B/C, TD35A, R8A, SS5, SW3, SS6, SS20, TC1A, TC1B, TC1C, M1-D, M2- D. (lines 800 through 808 and 883 through 892). B-01 won't run on AUTO (Blower Alarm) R53B, R9A, TD1A, TD2A, TD3A, TD4A, R11E, TS4, TS5, TS6, TS7, FS1, SPC-3, TS1, F13 F14, PT1, TP8, and TP9. (lines 550, 811 through 839, 888, and 1442). B-02 won't run on HAND CB5, VFD-OL2, R14, SS8, R14A and R22 (lines 899 through 904). B-02 won't run on AUTO (No Blower Alarm) R14A, SS8, R58B, RA1A/D, TD35A, R8A, SS5, SW3, SS6, SS20, TC1A, TC1B, TC1C, M1-D, M2- D. (lines 800 through 808 and 892 through 900). B-02 won't run on AUTO (Blower Alarm) R58B, R10A, TD5A, TD6A, TD7A, TD8A, R13E, TS8, TS9, TS10, TS11, FS2, SPC-4, TS2, F15 F16, PT2, TP11 and TP12. (lines 568, 844 through 871, 896, and 1462). B-01/ B-02 won t Alternate in Auto RA1, SS7, SS8, RA1A, RA1B, RA1C and RA1D. (lines 884, 888, 890 through 894 and 900) Digester DB-01/02 blowers: DB-01 won't run on HAND DB-01 won't run on AUTO (No Blower Fault) DB-01 won't run on AUTO (Blower Faulted) DB-02 won't run on HAND MCP5, OL5, R18, SS9, R18A and M5 (lines 1004 through 1011). R18A, SS9, R63B, RA2B/C, TC1D/E/F, SS10, and TD36A. (lines 1011 through 1022). R63B, R15A, TD9A, TD10A, TD11A, TD12A, R17E, TS12, TS13, TS14, TS15, SPC-5, FS3, TS3, F17, F18, PT-3, TP14 and TP15. (lines 594, 916 through 951, 1016 and 1484). MCP6, OL6, R20, SS11, R20A and M6 (lines 1027 through 1034). File: Trouble Shoot Final.doc Page 10 of 23

11 DB-02 won't run on AUTO (No Blower Fault) DB-02 won't run on AUTO (Blower Faulted) DB-01/ DB-02 won t Alternate in Auto R20A, SS11, R68B, RA2A/D, TC1D/E/F, SS10, TD36A (lines 1016 through 1028). R68B, R16A, TD13A, TD14A, TD15A, TD16A, R19E, TS16, TS17, TS18, TS19, SPC-6, FS4, TS4, F19, F20, PT-4, TP17 and TP18. (lines 612, 960 through 995, 1024 and 1499). RA2, SS9, SS11, RA2A, RA2B, RA2C and RA2D (lines 1012, 1018, 1019, 1021, 1022 & 1028). Return Activated Sludge RAS-01/02 pumps: RAS-01 won't run on HAND MCP9, OL9, R36, SS15, R36A and M9. (lines 1260 through 1267). RAS -01 won't run on AUTO (No Alarms) RAS-01 won't run on AUTO (Flow Alarm) RAS-01 won't run on AUTO (Low Level Cutout) RAS -02 won't run on HAND R33B, R36A, SS15, R84B, RA4B/C, TD38A, SS14, TC2A, R122A, TS42 and computer interface contact. (lines 1267 through 1276 and lines 1180 through 1182). SS15, R33B, R84B, TD21, R32A, M9A, TS-28 and LS-7. (lines 1189, 1198, 1268 and 1272). SS15, R33B, TS29 and LS-9. (lines 1220, and 1268). MCP10, OL10, R38, SS16, R38A and M10 (lines 1283 through 1289). RAS -02 won't run on AUTO (No alarms) RAS-02 won't run on AUTO (Flow Alarm) R38A, SS16, R87B, RA4A/D, TD38A, SS14, TC2A, R122A TS42 and computer interface contact. (lines 1276 through 1284 and lines 1180 through 1182). SS16, R34B, R87B, TD22, R32D, M10A, TS-28 and LS-7. (lines 1189, 1204, 1280 and 1284). File: Trouble Shoot Final.doc Page 11 of 23

12 RAS-02 won't run on AUTO (Low Level Cutout) RAS-01/ RAW-02 won t Alternate in Auto R34B, TS30 and LS-10. (lines 1227, and 1284). RA4, SS15, SS16, RA4A, RA4B, RA4C and RA4D. (lines 1012, 1018, 1019, 1021, 1022 & 1028) Waste Activated Sludge WAS-01 pump: WAS-01 won't run Secondary Clarifier SCO-01 drive: SCO-01 won't run Digested Sludge DSP-01 pump: DSP-01 won't run in HAND DSP-01 won't run in REMOTE Heat Tape HT-01: HT-01 won't run UV Alarms: UV Major Alarm MCP11, OL11, R39, TD38D, PB2, TD26A, PB3, TD25A, M11, TS33, LS-12 (lines 1305 through 1315). MCP7, OL7, R44, R44A, TD37D, SS18, Over-torque Limit Switch, M7, TD-29 (lines 1353 through 1361). MCP8, OL8, R41, R41A, SS17, TD28A, M8, TS34, LS-13 (lines 1326 through 1346). MCP8, OL8, R41, R41A, TD36D, SS17, Remote Start/Stop Station, TD28A, M8, TS34, LS-13 (lines 1326 through 1346). R121A, R45, R45A, SS19, Heat Stat, C2 R42A, TS43, SPC-10, TT-3, F27 and F28 (lines 1388 through 1392). UV System Fail contact, TS39, R47B TD39 (lines 1400 and 1410). UV High Level Alarm LS-4, TS38, TD33A (lines 1404 and 1622). Generator Alarm: Generator Run Alarm Generator Running contact, TS40, R48 (line 1415). Generator Ground Fault Alarm GFR, IL90, R129, R130 (lines 777 through 784). File: Trouble Shoot Final.doc Page 12 of 23

13 Scada Functions: Remote Scada Reset Remote Scada contact, TS41, R49 (line 1420). Aeration Basin Alarms: Aeration Basin No.1 High Level Alarm LS-1, TS31, TD23 (line 1235). Aeration Basin No.2 High Level Alarm LS-2, TS32, TD24 (line 1242). Clarifier Alarms: Secondary Clarifier Over Torque Alarm Clarifier High Level Alarm MCP-7, OL-7, R44, R44A, TD37D SS18, Over Torque Limit Switch and TD29, TD29A, R91 and R92 (lines 1353, 1359, 1360, 1361 and 1592). LS-3, TS35, TD30, TD30A, R95 and R96 (lines 1366, 1600, and 1602). Aerobic Digester Alarms: High Level No.1 Alarm LS-5, TS36, TD31, TD31A, R97, R98 (lines 1373, 1606 and 1609). High Level No.2 Alarm LS-6, TS37, TD32, TD32A, R99, R100 (lines 1380, 1613 and 1615). File: Trouble Shoot Final.doc Page 13 of 23

14 Control Panel (CP-1) - Analog CIRCUIT SYMPTOMS POSSIBLE CAUSES Septic Tank STEP-01/02, SPC-1/ 2: Alarms occurring at erroneous levels Control output open/close at erroneous levels SPC-1/ 2 calibration error, fault in circuit wiring, wrong alarm setpoints LT-1/ 2 error SPC-1/ 2 calibration error, fault in circuit wiring, wrong setpoints LT-1/ 2 error Error OVR/ OVR displayed on SPC-1/ 2 Open circuit wire including blown fuses (F9, F10, F11 F12) and open test point connections (TP2, TP3, TP5, TP6), SS-20 fault, LT-1/ 2 error Autodialer reading high/ low Autodialer calibration/ setup error, fault or calibration error, LT-1/ 2 error. Autodialer reading zero Open circuit wire including blown fuses (F9, F10, F11 F12) and open test point connections (TP2, TP3, TP5, TP6). Aeration Blowers B-01/ 02, SPC-3/ 4: Alarms occurring at erroneous levels Control output open/close at erroneous levels SPC-3/ 4 calibration error, wrong setpoints fault in circuit wiring, PT-1/ 2 error SPC-3/ 4 calibration error, fault in circuit wiring, wrong setpoints PT-1/ 2 error Error OVR/ OVR displayed on SPC-3/ 4 Open circuit wire including blown fuses (F13, F14, F15, F16) and open test point connections (TP8, TP9, TP11, TP12), PT-1/ 2 error Autodialer reading high/ low Autodialer calibration/ setup error, fault or calibration error, PT-1/2. File: Trouble Shoot Final.doc Page 14 of 23

15 Autodialer reading zero Open circuit wire including blown fuses (F13, F14, F15, F16) and test points (TP8, TP9, TP11, TP12). Digester Blowers DB-01/ 02, SPC-5/ 6: Alarms occurring at erroneous levels SPC-5/ 6 calibration error, fault in circuit wiring, PT-3/ 4 error Error OVR/ OVR displayed on SPC-5/ 6 Open circuit wire including blown fuses (F17, F18, F19, F20) and open test point connections (TP14, TP15, TP17, TP18), PT-3/ 4 error. Autodialer reading high/ low Autodialer calibration/ setup error, fault or calibration error, PT-3/4. Autodialer reading zero Open circuit wire including blown fuses (F17, F18, F19, F20) and open test point connections (TP14, TP15, TP17, TP18). Influent Flow, SPC-7: Alarms occurring at erroneous levels SPC-7 calibration error, fault in circuit wiring, FM-1 error Error OVR/ OVR displayed on SPC-7 Open circuit wire including blown fuses (F21, F22) and open test point connections (TP20 TP21), SS-4 fault, FM-1 error Autodialer reading high/ low Autodialer calibration/ setup error, fault or calibration error Autodialer reading zero Open circuit wire including blown fuses (F21, F22) and open test point connections (TP20 TP21) Integrator fault, Signal repeater (I/I) fault. Flow totalizer count in error Flow totalizer not counting Chart recorder high/ low Integrator faulted or calibration error, OC13 faulted Integrator faulted or calibration error, OC13 Faulted, open circuit in wires to counter Chart recorder calibration/ setup error File: Trouble Shoot Final.doc Page 15 of 23

16 Chart recorder not recording Both samplers cycling too much/ little Both samplers not cycling One sampler cycling too much/ little One sampler not cycling Chart recorder calibration/ setup error, SS-4 in Bypass, chart recorder failed I/I (signal repeater) calibration error, Sampler calibration/ setup error I/I (signal repeater) faulted, wiring to Samplers fault, F29 or F30 blown, DSP-3 fault Sampler calibration/ setup error Sampler faulted Influent Flow Fail Alarms: One Pump (STEP-01) Flow Failed One Pump (STEP-02) Flow Failed Both Pumps Flow Failed SPC-7, R31, R31A, M1A, TS25, TD18 SPC-7, R31, R31D, M2A, TS26, TD19 SPC-7, M1C, M2C, TS27, TD20 Lab Room Temperature, SPC-8: Alarms occurring at erroneous levels Error OVR/ OVR displayed on SPC-8 Autodialer reading high/ low SPC-8 calibration error, fault in circuit wiring, TT-1 error Open circuit wire including blown fuses (F23, F24,) and open test point connections (TP23, TP24), TT-1 error Autodialer calibration/ setup error, fault or calibration error, TT-1 error. Autodialer reading zero Open circuit wire including blown fuses (F23, F24) and open test point connections (TP23, TP24). File: Trouble Shoot Final.doc Page 16 of 23

17 Equipment Room Temperature, SPC-9: Alarms occurring at erroneous levels SPC-9 calibration error, fault in circuit wiring, TT-2 error Error OVR/ OVR displayed on SPC-9 Open circuit wire including blown fuses (F25, F26) and open test point connections (TP26, TP27), TT-2 error. Autodialer reading high/ low Autodialer calibration/ setup error, fault or calibration error, TT-2 error. Autodialer reading zero Open circuit wire including blown fuses (F25, F26) and open test point connections (TP26, TP27). Outside Air Temperature, SPC-10: Alarms occurring at erroneous levels SPC-10 calibration error, fault in circuit wiring, TT-3 error Error OVR/ OVR displayed on SPC-10 Open circuit wire including blown fuses (F27, F28) and open test point connections (TP29, TP30), TT-3 error. Autodialer reading high/ low Autodialer calibration/ setup error, fault or calibration error, TT-3 error. Autodialer reading zero Open circuit wire including blown fuses (F27, F28) and open test point connections (TP29, TP30). UV Intensity, SPC-11: (See UV Manual for controller operation) Reading high/ low at Autodialer SPC-11 calibration error, UV Controller error Error OVR/ OVR displayed on SPC-11 Open circuit wire including blown fuses (F31, F32) and open test point connections (TP35, TP36), SS-21 fault, UV controller error, DSP-4 fault. Autodialer reading high/ low Autodialer calibration/ setup error, fault or calibration error, UV Controller error. File: Trouble Shoot Final.doc Page 17 of 23

18 Autodialer reading zero Open circuit wire including blown fuses (F31, F32) and open test point connections (TP35, TP36), DSP-4 error Chart recorder high/ low Chart recorder not recording Chart recorder calibration/ setup error, UV Controller error Chart recorder calibration/ setup error, SS-21 in Bypass, chart recorder failed File: Trouble Shoot Final.doc Page 18 of 23

19 Annunciator Panel (CP-1) - Digital CIRCUIT SYMPTOMS POSSIBLE CAUSES Well Pump: Well Pump Running relay R2 not energized Fuses F5/ 6, test switch TS1 and/or remote Well Pump On contact open (line 4014) Well Pump run meter/ counter not working Well Pump Call relay not on RTM1/ OC1 fault, R2A (line 4310) SS3, SPC-11, R8A/ R9A or R10A (line 4319) or Float switches in tank not working Water Tank: Water Tank high level not on No high level alarm, R4A (line 4313) Water Tank low level not on No low level alarm, R5A (line 4315) Annunciator Panel Alarms: Note: Normal status of alarm circuits is off with relays and lights de-energized. The below narrative describes alarm circuits that are in an alarm state but have faulted. Well House R3, IL3 & LED3 not on Fuses F7/ 8, test switch TS2 and/or remote Pump House Gen. Alarm contact open (line 4050) Water Tank High R4, IL4 & LED4 not on Fuse F9/10, test switch TS3 and/or both remote float switch and SPC-11 contact open (line 4058) File: Trouble Shoot Final.doc Page 19 of 23

20 Water Tank Low R5, IL5 & LED5 not on STEP-01 IL6 & LED6 not on STEP-02 IL7 & LED7 not on Septic Tank high level IL8 & LED8 not on Septic Tank low level IL9 & LED9 not on Generator Running IL10 & LED10 not on Blower Fail IL11 & LED11 not on Fuse F9/11, test switch TS4 and/or both remote float switch and SPC-11 contacts open (line 4066) Fuse F12/13, test switch TS5 and/or remote R75F contact open (line 4075) Fuse F14/15, test switch TS6 and/or remote R78F contact open (line 4081) Fuse F16/17, test switch TS7 and/or remote R73A contact open (line 4081) Fuse F18/19, test switch TS8 and/or remote R71A contact open (line 4101) Fuse F20/21, test switch TS9 and/or remote R48D contact open (line 4108) Fuse F22/23, test switch TS10 and/or remote R70A contact open (line 4115) 24 VAC LED11A not on Fuse F24, and/or contact R11D open (line 4120) Aeration Basin 1 high IL12 & LED12 not on Aeration Basin 2 high IL13 & LED13 not on SCO-1 drive over torque IL14 & LED14 not on RAS pumps failed IL15 & LED15 not on Fuse F26/27, test switch TS11 and/or remote R89D contact open (line 4134) Fuse F28/29, test switch TS12 and/or remote R91D contact open (line 4141) Fuse F30/31, test switch TS13 and/or remote R93A contact open (line 4148) Fuse F32/33, test switch TS14 and/or remote R112D contact open (line 4155) File: Trouble Shoot Final.doc Page 20 of 23

21 UV system failed IL16 & LED16 not on ATS transferred IL17 & LED17 not on CP-1 24AC/DC Power Loss IL18/ LED18 not on Intrusion alarm IL19/ LED19 not on Fire alarm IL20/ LED20 not on CP-1 general alarm IL21/ LED21 not on Fuse F34/35, test switch TS15 and/or remote R101A contact open (line 4162) Fuse F36/37, test switch TS16 and/or remote R109A contact open (line 4179) Fuse F38/39, test switch TS17 and/or remote R6C and R7E contact open (line 4186) Fuse F40/41, test switch TS18 and/or remote TD40D contact open (line 4193) Fuse F42/43, test switch TS19 and/or remote R125D contact open (line 4200) Fuse F44/45, test switch TS20 and/or remote R111D contact open (line 4207) Annunciator general alarm R6 & R7 not on Fuse F54, no current alarms on (line 4252 File: Trouble Shoot Final.doc Page 21 of 23

22 Annunciator Panel (CP-1) - Analog CIRCUIT SYMPTOMS POSSIBLE CAUSES Water Tank Level, SPC-11: Alarms occurring at erroneous levels SPC-11 calibration error, fault in circuit wiring, LT-3 error Error OVR/ OVR displayed on SPC-11 Open circuit wire including blown fuses (F55, F56, F57, F58) and open test point connections (TP2, TP3), LT-3 error, faulted signal repeater, DSP-1 faulted. Autodialer reading high/ low Autodialer reading zero Remote display DD-1 reading high/ low Autodialer calibration/ setup error, SR-1 fault or calibration error, LT-3 error. Open circuit wire, blown fuses, DSP-2 error DD-1 calibration/ setup error Remote display DD-1 reading zero or off Open circuit wire including blown fuses, (F55, F56, F57, F58) and open test point connections (TP2, TP3), faulted signal repeater SR ALARM SYSTEM The pilot lights and alarm system included in this system should be of great assistance in trouble shooting. Occasionally, a pilot light will burn out and trouble shooting will be difficult because of the burned out light. Frequent checking of the lights to make sure that they are not burned out will be a help in operating this system. The test switches can be used to check light functions. File: Trouble Shoot Final.doc Page 22 of 23

23 In the event of D.C. power failure, the alarm horns will be automatically sounded by battery power. Because power supply PS3 and 120VAC bus A3/N3 is fed from the uninterruptible power supply, these circuits will continue to have power enabling continued setpoint controller operation. File: Trouble Shoot Final.doc Page 23 of 23

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... ..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... TIME MARK CORPORATION 11440 EAST PINE STREET TULSA, OK 74116 USA tel 918 438-1220 fax 918 437-7584 www.time-mark.com

More information

TROUBLESHOOTING PRELIMINARY

TROUBLESHOOTING PRELIMINARY TROUBLESHOOTING PRELIMINARY To troubleshoot, one must first have a working knowledge of the individual parts and their relation to one another. Must have adequate hand tools Must have basic instrumentation:

More information

PARAGON ELECTRIC, INC. LIQUID LEVEL CONTROLLER USER MANUAL MODELS: LLC-I, LLC-II AND TELEMETRY OPTIONS

PARAGON ELECTRIC, INC. LIQUID LEVEL CONTROLLER USER MANUAL MODELS: LLC-I, LLC-II AND TELEMETRY OPTIONS PARAGON ELECTRIC, INC. LIQUID LEVEL CONTROLLER USER MANUAL MODELS: LLC-I, LLC-II AND TELEMETRY OPTIONS 2 Table of Contents Safety... 4 Introduction... 5 Features and Benefits... 6 Control Overview... 7

More information

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE DESCRIPTION MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE DESCRIPTION The SST Model 5010 Two Channel Smoke/Fire Detection Module provides two independent detection input channels for the NOVA-5000

More information

543-0032-00, 943-0032-00. User s Manual

543-0032-00, 943-0032-00. User s Manual 543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and

More information

Use your troubleshooting superpowers for good Application Note

Use your troubleshooting superpowers for good Application Note Use your troubleshooting superpowers for good Application Note Unleash your full troubleshooting powers with innovative new tools from Fluke. You ve got skill. You ve got experience. Now you have some

More information

INSTALLATION INSTRUCTIONS MC95HAE-1 MASTER CONTROLLER

INSTALLATION INSTRUCTIONS MC95HAE-1 MASTER CONTROLLER INSTALLATION INSTRUCTIONS MC95HAE-1 MASTER CONTROLLER Bard Manufacturing Company, Inc. Bryan, Ohio 43506 Since 1914...Moving ahead just as planned. Manual : 2100-360B Supersedes: 2100-360A File: Volume

More information

The Charging System. Section 5. Charging System. Charging System. The charging system has two essential functions:

The Charging System. Section 5. Charging System. Charging System. The charging system has two essential functions: The Charging System Charging System The charging system has two essential functions: Generate electrical power to run the vehicle s electrical systems Generate current to recharge the vehicle s battery

More information

Chapter 5. Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams

Chapter 5. Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams Chapter 5 Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams Objectives Upon completion of this course, you will be able to: Explain what electrical loads are and their general purpose

More information

26 3213.13 Diesel Engine Driven Generators Page 1 of 6

26 3213.13 Diesel Engine Driven Generators Page 1 of 6 Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at

More information

COOL-01, Cooling Fan Operation and Troubleshooting

COOL-01, Cooling Fan Operation and Troubleshooting COOL-01, Cooling Fan Operation and Troubleshooting Table of Contents Introduction Early 944s With Air Conditioning Cooling Fan Operation On Early 944s With Air Conditioning Testing Fan Relay One Early

More information

A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps

A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps Troubleshooting Submersible Pumps Fuse overload or circuit breaker trips when motor is started 1. Incorrect line voltage. Check the line

More information

DC LOAD TESTING Gian Trento June 18 th, 2004

DC LOAD TESTING Gian Trento June 18 th, 2004 DC LOAD TESTING Gian Trento June 18 th, 2004 THIS TECHNICAL NOTE DESCRIBES THE PROCESS OF CONNECTING THE UNIVERSAL VOLTRONICS CORPORATION (UVC) POWER SYSTEM TO THE DC LOAD AS WELL AS OPERATING THE UVC

More information

Oil and Coolant Circulating Heating System. Model - OCSM

Oil and Coolant Circulating Heating System. Model - OCSM Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine

More information

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASYG07LECA ASYG09LECA ASYG12LECA ASYG14LECA AOYG07LEC AOYG09LEC AOYG12LEC AOYG14LEC R410A CONTENTS

More information

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting

More information

CENTERLINE Motor Control Centers Bulletin 2100 Smoke Detector Unit

CENTERLINE Motor Control Centers Bulletin 2100 Smoke Detector Unit Instructions CENTERLINE Motor Control Centers Bulletin 2100 Smoke Detector Unit Catalog Number 2100-SD1 Description The Bulletin 2100 smoke detector unit is a 0.5 space factor unit for use in Bulletin

More information

City of Dallas 1.5 MGD WWTP

City of Dallas 1.5 MGD WWTP LCP NO. EQUIPMENT DESCRIPTION SIGNAL OPERATOR NOTE REV NO TYPE INTERFACE DATE SCADA LCP1 LE751 EXISTING DIGESTER LEVEL AI I, R, C SCADA LCP1 FIT548 RAS FLOW RATE AI I, R, C SCADA LCP1 FIT549 WAS FLOW RATE

More information

ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE

ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE Protected by one or more of the following U.S. Patents (3,507,354; 3,575,234; 3,596,936; 3,605,797; 3,685,329; 4,045,977; 4,698,982; 926,673 and

More information

Hydraulic Trouble Shooting

Hydraulic Trouble Shooting Hydraulic Trouble Shooting Hydraulic systems can be very simple, such as a hand pump pumping up a small hydraulic jack, or very complex, with several pumps, complex valving, accumulators, and many cylinders

More information

Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6

More information

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fi re pumps

More information

SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY

SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY! WARNING - SHOCK HAZARD! TO PREVENT THE POSSIBILITY OF SEVERE PERSONAL INJURY, DEATH, OR EQUIPMENT DAMAGE DUE TO ELECTRICAL

More information

i ChatterBox! Motorcycle Security

i ChatterBox! Motorcycle Security i Before you Start the Installation * Please read this manual to become familiar with the requirements necessary to complete the installation. * Use a high quality multi-meter to test all wires before

More information

KBIC Solid State SCR DC Motor Speed Controls See table 2 page 4 for KBIC models covered by this manual

KBIC Solid State SCR DC Motor Speed Controls See table 2 page 4 for KBIC models covered by this manual KBIC Solid State SCR DC Motor Speed Controls See table 2 page 4 for KBIC models covered by this manual Patented Ultra Fast CL Circuit Prevents Demagnetization in PM Motors Installation and Operating Instructions

More information

Chapter 7 Hydraulic System Troubleshooting

Chapter 7 Hydraulic System Troubleshooting Chapter 7 Hydraulic System Troubleshooting General The following troubleshooting information is provided as a general guide to identify, locate and correct problems that may be experienced with the hydraulic

More information

What is a multimeter?

What is a multimeter? What is a multimeter? A multimeter is a devise used to measure voltage, resistance and current in electronics & electrical equipment It is also used to test continuity between to 2 points to verify if

More information

A/C-HEATER SYSTEM - AUTOMATIC

A/C-HEATER SYSTEM - AUTOMATIC A/C-HEATER SYSTEM - AUTOMATIC 1995 Volvo 850 1995-96 Auto. A/C-Heater Systems Volvo 850 * PLEASE READ THIS FIRST * WARNING: To avoid injury from accidental air bag deployment, read and carefully follow

More information

Operational Overview and Controls Guide

Operational Overview and Controls Guide DOCUMENT: ECSEQ2-1 EFFECTIVE: 02/14/07 SUPERSEDES: 02/26/03 Operational Overview and Controls Guide Standard Two or Three Pump Type VFD Booster Controls 6700 Best Friend Road. Norcross, GA 30071. (770)

More information

Inverter / Charger Installation General Operations and AC and DC Connections

Inverter / Charger Installation General Operations and AC and DC Connections Inverter / Charger Installation General Operations and AC and DC Connections The Inverter is just one piece. Sometimes, a tendency is to mount the inverter and batteries, and make it work It is better

More information

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short

More information

Table Z. Troubleshooting Chart for Air Conditioners. Cause

Table Z. Troubleshooting Chart for Air Conditioners. Cause Troubleshooting Chart for Air Conditioners Type of Unit Complaint Cause With open-type compressor Electric motor will not start Power failure Check circuit for power source Compressor stuck Locate cause

More information

Operational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives

Operational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives DOCUMENT: ECSEQ6-0 EFFECTIVE: 09/23/10 SUPERSEDES: Operational Overview and Controls Guide Two or Three Pump IronHeart Lite with Variable Frequency Drives 6700 Best Friend Road. Norcross, GA 30071. (770)

More information

6. Diagnostics for A/C System Malfunction

6. Diagnostics for A/C System Malfunction 6. A: A/C OR SELF-DIAGNOSIS SYSTEMS DO NOT OPERATE TROUBLE SYMPTOM: Set temperature is not indicated on the display, switch LEDs are faulty or switches do not operate. Self-diagnosis system does not operate.

More information

conventional system operation

conventional system operation conventional system operation detection line operation Conventional detection systems normally operate on a 24VDC line. In the standby condition, the detectors will draw a low current, typically less than

More information

ANTI-THEFT SYSTEM. 1995 Volvo 850 DESCRIPTION & OPERATION BASIC ALARM. 1995-96 ACCESSORIES & EQUIPMENT Volvo Anti-Theft Systems

ANTI-THEFT SYSTEM. 1995 Volvo 850 DESCRIPTION & OPERATION BASIC ALARM. 1995-96 ACCESSORIES & EQUIPMENT Volvo Anti-Theft Systems ANTI-THEFT SYSTEM 1995 Volvo 850 1995-96 ACCESSORIES & EQUIPMENT Volvo Anti-Theft Systems 850 DESCRIPTION & OPERATION WARNING: Deactivate air bag system before performing any service operation. For 1995

More information

1 General Responsibility. 1.1 Participants. 1.2 Documentation. 1.3 Lockout/Tagout

1 General Responsibility. 1.1 Participants. 1.2 Documentation. 1.3 Lockout/Tagout Electrical Safety Plan This plan establishes rules for both the design and operation of the LPRDS. These rules are intended to enhance the safety of the participants in the initial project and future users

More information

FUEL-16, Troubleshooting Fuel Supply Problems

FUEL-16, Troubleshooting Fuel Supply Problems FUEL-16, Troubleshooting Fuel Supply Problems Introduction This procedure is used to troubleshooting fuel supply problems including failure of the fuel pump to start during engine cranking. Fuel Pump Not

More information

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS TABLE OF CONTENTS 1. Warnings...2 2. Accessibility Of Appliance...3 3. Unit Dimensions And Specifications...3 4. Unit Specifications

More information

CONTROL PANEL INSTALLATION INSTRUCTIONS. Single Phase Simplex Page 2-7. 3-Phase Simplex Page 8-13

CONTROL PANEL INSTALLATION INSTRUCTIONS. Single Phase Simplex Page 2-7. 3-Phase Simplex Page 8-13 CONTROL PANEL INSTALLATION INSTRUCTIONS Single Phase Simplex Page 2-7 3-Phase Simplex Page 8-13 Single Phase Simplex SXL21=3, SXL24=3, SXH21=3, and SXH24=3 Manufactured by SJE-Rhombus Installation Instructions

More information

EET272 Worksheet Week 8

EET272 Worksheet Week 8 EET272 Worksheet Week 8 answer questions 1-5 in preparation for discussion for the quiz on Monday. Finish the rest of the questions for discussion in class on Wednesday. Question 1 Questions We will now

More information

14. Troubleshooting Guide

14. Troubleshooting Guide 14. Guide 14.1 Refrigeration Cycle System In order to diagnose malfunctions, ensure the air conditioner is free from electrical problems before inspecting the refrigeration cycle. Such problems include

More information

Troubleshooting accelerometer installations

Troubleshooting accelerometer installations Troubleshooting accelerometer installations Accelerometer based monitoring systems can be tested to verify proper installation and operation. Testing ensures data integrity and can identify most problems.

More information

HVAC SYSTEM (AUTO A/C) (DIAGNOSTICS) AC

HVAC SYSTEM (AUTO A/C) (DIAGNOSTICS) AC HVAC SYSTEM (AUTO A/C) (DIAGNOSTICS) AC Page. Basic Diagnostic Procedure.... General Description...3 3. Electrical Components Location...6 4. A/C Control Module I/O Signal...8 5. Self-diagnosis...0 6.

More information

Pump Maintenance - Repair

Pump Maintenance - Repair Pump Maintenance - Repair Brian Trombly Mo Droppers Cummins Bridgeway, Gaylord, Mi The basic centrifugal pump consists of two main elements: 1. The rotating element which includes an impeller and a shaft.

More information

DTW Works Master Specification Version 2006

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section 13852 Multiplex Fire Alarm System Page 1 of 10 PART 1 GENERAL 1.1 RELATED WORK.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Procedures..3 Section 01810 Commissioning..4

More information

Configuring Alarms & Relays in the Enhanced Transformer Advantage

Configuring Alarms & Relays in the Enhanced Transformer Advantage Configuring s & Relays in the Enhanced Transformer Advantage The Transformer Advantage product family offers a variety of relay options. Some choices are made when the Advantage is specified and ordered.

More information

Thermostatic Wiring Principles by Bob Scaringe Ph.D., P.E.

Thermostatic Wiring Principles by Bob Scaringe Ph.D., P.E. Thermostatic Wiring Principles by Bob Scaringe Ph.D., P.E. Basic Thermostat Types Many technicians have great difficulty understanding how to properly wire a thermostat or how to replace a thermostat with

More information

Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches

Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches Downtime Is Not An Option The industrial uninterruptible power supply (UPS) is the foundation of your

More information

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification 08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and

More information

SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE

SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE for solar energy management LEATEC Delivering Solutions for Energy Management SOLAR ENERGY DATA CENTER BUILDING 4 to8 String Monitoring with 0.% Accuracy

More information

SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS

SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS SECTION 16721 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire Alarm Control Panels B. Manual Fire Alarm Stations C. Automatic Smoke D. Fire Alarm Notification Appliances E. Auxiliary Fire Alarm Equipment

More information

HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER:

HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER: HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER: It is normal for a heat pump to have a build up of white frost on the outside coil during cold damp weather. The

More information

User s Manual AURORA 1.2K/2.2K

User s Manual AURORA 1.2K/2.2K User s Manual AURORA 1.2K/2.2K Uninterruptible Power System Safety CAUTION This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user serviceable

More information

rpsa FIRE PROTECTION ENGINEERS

rpsa FIRE PROTECTION ENGINEERS R.P. SCHIFILITI ASSOCIATES, INC. P.O. Box 297 Reading, Massachusetts 01867-0497 USA 781.944.9300 Fax / Data 781.942.7500 Telephone Sample Fire Alarm System Calculations 1. A fire alarm manufacturer specifies

More information

Section 7. Evaporator thermistor. Under-and-over pressure safety switches. Connections to the ECU

Section 7. Evaporator thermistor. Under-and-over pressure safety switches. Connections to the ECU Automatic Temperature Control Diagnosis and Repair Diagnosis of Automatic A/C Systems The most common automatic A/C system malfunctions tend to be the result of basic air conditioning problems. These problems

More information

1 4. 3 4-2 ABNORMAL OPERATION. 4-2-1 Error code Display. Specifics Error Code. Subsection Error Code. Subsection and Specifics Error code target

1 4. 3 4-2 ABNORMAL OPERATION. 4-2-1 Error code Display. Specifics Error Code. Subsection Error Code. Subsection and Specifics Error code target 4-2 ABNORMAL OPERATI 4-2-1 An is represented by 3 digit characters. The first 2 digit means the subsection, and the last 1 digit means the specifics. Ex.) Indoor unit Network communication Error Subsection

More information

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original A motor starter is a combination of devices to allow an induction motor to start, run and stop according

More information

SECTION 13XXX CONTROL DESCRIPTION (DICP Models 02-412NC, 412, 622, 826, 1030)

SECTION 13XXX CONTROL DESCRIPTION (DICP Models 02-412NC, 412, 622, 826, 1030) PART 1 - GENERAL SECTION 13XXX CONTROL DESCRIPTION (DICP Models 02-412NC, 412, 622, 826, 1030) 1.01 SUMMARY This section describes the operation and control of a drip irrigation system. The major components

More information

Trouble Shooting. Pump

Trouble Shooting. Pump Trouble Shooting Pump Trouble Possible Cause Remedy Oil leaking in the area of water pump crankshaft Worn crankshaft seal, bad bearing, grooved shaft, or failure of retainer o-ring. Excessive play on crankshaft

More information

SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT

SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled

More information

HP 5 Microprocessor Control for Mammoth Water Source Heat Pumps

HP 5 Microprocessor Control for Mammoth Water Source Heat Pumps HP 5 Microprocessor Control for Mammoth Water Source Heat Pumps Operation and Maintenance Manual Model: 71028004 Applies to: Single Circuit Water-to-Water Twin Circuit Units Without DDC Controls MAMM WHSP

More information

Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy

Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy Reyrolle Protection Devices 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy Siemens Protection Devices Limited 2 7PG17 XR101 & XR102 Intertripping Relay

More information

Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500

Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500 Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500 Description Firetrol FTA1500 Primary Resistance Fire Pump Controllers use resistors in the line to reduce line voltage

More information

INSTALLATION & SERVICE MANUAL. Display Panel

INSTALLATION & SERVICE MANUAL. Display Panel INSTALLATION & SERVICE MANUAL Display Panel The PowerLine EMS TM is a specialized power distribution and energy management system intended to be used in recreational vehicles. The Control Module is housed

More information

Fan Coil EC Motor Control

Fan Coil EC Motor Control Fan Coil EC Motor Control G3 PWM BARD The Enviro-Tec Generation 3 PWM (G3 PWM) board provides a pulse-width modulated (PWM) signal to the EC motor to control fan speed. The board is factory programmed

More information

ABC-1000 Automatic Boiler Level Controller Operation and Installation Manual

ABC-1000 Automatic Boiler Level Controller Operation and Installation Manual QUALITY STEAM SPECIALTIES SINCE ABC-1000 Automatic Boiler Level Controller Operation and Installation Manual Section: C500 Bulletin: C500.40 Date: 06-26-01 Supersedes: New PRODUCT DESCRIPTION: The Clark-Reliance

More information

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL RANCO INSTALLATION INSTRUCTIONS ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL Relay Electrical Ratings PRODUCT DESCRIPTION The Ranco ETC is a microprocessor-based family of electronic temperature controls,

More information

Chapter 9 N.C. C. N.O. Single-Pole Double-Throw

Chapter 9 N.C. C. N.O. Single-Pole Double-Throw rather than providing multiple choices. The sensor modules used may only be suitable for use with the matching controller so it is wise to read the specifications to make sure the unit suits your application.

More information

How To Use A Power Supply Unit (Upu)

How To Use A Power Supply Unit (Upu) BRAVER UPS (Uninterruptible Power System) User s Manual Safety CAUTION! This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user replaceable parts.

More information

MANUAL FOR MODEL MP30 ELECTRIC MOTOR DRIVEN LIMITED SERVICE CONTROLLER

MANUAL FOR MODEL MP30 ELECTRIC MOTOR DRIVEN LIMITED SERVICE CONTROLLER MANUAL FOR MODEL MP30 ELECTRIC MOTOR DRIVEN LIMITED SERVICE CONTROLLER Starting Serial No. "LA" This manual provides General Information, Installation, Operation, Maintenance and System Set-Up Information

More information

Help protect your home, possessions and family.

Help protect your home, possessions and family. Help protect your home, possessions and family. A guide to your Square D electrical distribution system SM Make the most of your energy Understanding your home s electrical distribution system As one of

More information

BIOMEDICAL ENGINEERING TECHNICIAN SERIES

BIOMEDICAL ENGINEERING TECHNICIAN SERIES BIOMEDICAL ENGINEERING TECHNICIAN SERIES Occ. Work Prob. Effective Last Code No. Class Title Area Area Period Date Action 4549 Biomedical Engineering Technician I 02 032 6 mo. 07/15/11 Rev. 4550 Biomedical

More information

HM-W536 Install Guide

HM-W536 Install Guide HM-W536 Install Guide 9/13/2013 IMPORTANT SAFETY INSTRUCTIONS Warning - When using electrical devices, basic safety precautions should be followed to reduce the risk of fire, electrical shock or injury.

More information

SECTION 26 29 23 VARIABLE FREQUENCY DRIVES

SECTION 26 29 23 VARIABLE FREQUENCY DRIVES SECTION 26 29 23 VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 SCOPE A. Furnish and install individual freestanding variable frequency AC drives (VFD) as shown on the Drawings and specified herein. 1.02

More information

TMS TANK MANAGEMENT SYSTEM

TMS TANK MANAGEMENT SYSTEM TMS TANK MANAGEMENT SYSTEM Page 1 of 9 Operating Instructions GENERAL The Tank Management System is a bespoke design to control, monitor and accommodate efficient storage and dispensing of TMS. FUNCTIONS

More information

LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems

LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems Universal Split Systems If there is a fault on any LG Universal unit, a two digit number will appear on the remote controllers led display. If the unit does not have a remote controller the fault will

More information

HQ Series ¼ Turn Actuator

HQ Series ¼ Turn Actuator HQ Series ¼ Turn Actuator HQ-015 thru HQ-300 Installation & Maintenance Manual HQ Series I&M Manual HQ-400-1005 1 Table of Contents: General 1.0 Actuator Mounting 2.0 External Construction 3.0 Wiring Diagrams

More information

USER S MANUAL. MaxPower 400-600 UPS. Uninterruptible Power System 28-2MAXPO0018

USER S MANUAL. MaxPower 400-600 UPS. Uninterruptible Power System 28-2MAXPO0018 USER S MANUAL MaxPower 400-600 UPS Uninterruptible Power System 28-2MAXPO0018 IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions for models MaxPower 400 and

More information

ELECTRONIC BOARDS - SUPRA

ELECTRONIC BOARDS - SUPRA ELECTRONIC BOARDS - SUPRA INDEX TROUBLESHOOTING BOARD SOURCE INTERCONNECTION C.E. INTERFACE PH INTERFACE HARD SWITCH RELAYS 32-OUTPUT CARD BOARD # 7520 # TROUBLESHOOTING BOARD 12V CONNECTIONS: CONNECTOR

More information

INTRODUCTION. The data provided is for The Standard Products and any variation will be dealt with at the end of this manual.

INTRODUCTION. The data provided is for The Standard Products and any variation will be dealt with at the end of this manual. INTRODUCTION The information provided herein covers the range of products known as the 'Sensor 901' series. The range of equipment is designed to meet the requirements of BS 5839 parts 1 & 4 1988. The

More information

CONSTRUCTION STANDARDS DIVISION 23 HEATING VENTILATING AND AIR CONDITIONING

CONSTRUCTION STANDARDS DIVISION 23 HEATING VENTILATING AND AIR CONDITIONING PART 1-GENERAL 1.01 DESCRIPTION A. This specification is to cover a complete Variable Frequency motor Drive (VFD) consisting of a pulse width modulated (PWM) inverter designed for use on a standard NEMA

More information

ALARM ANNUNCIATOR ME - 3010 INSTRUCTION MANUAL

ALARM ANNUNCIATOR ME - 3010 INSTRUCTION MANUAL ALARM ANNUNCIATOR ME - 3010 INSTRUCTION MANUAL INTRODUCTION... 2.. TECHNICAL DATA... 3 ACCESSORIES... 5. INSTALLATION... 7 OPERATION... 12. TECHNICAL INFORMATION... 13 MAINTENANCE... 14. CONFIGURATIONS...

More information

F2400 FOM II Series Fiber Optic Modem Technical Manual

F2400 FOM II Series Fiber Optic Modem Technical Manual F2400 FOM II Series Fiber Optic Modem Technical Manual T1 Revision B Copyright April 2003 VERSITRON, Inc. 83 Albe Drive / Suite C Newark, DE 19702 www.versitron.com A030430283T PROPRIETARY DATA All data

More information

NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL

NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL CONTENTS GENERAL INFORMATION...3 INSTALLATION...3 FIELD WIRING...4 PROGRAMMING...4 Circuit Monitor Options...5 Power Frequency...5 Alarm Silence

More information

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the different types of open single-phase motors used to drive

More information

Fire Alarm Control Panel. Family. Operating Manual

Fire Alarm Control Panel. Family. Operating Manual Fire Alarm Control Panel Family Operating Manual CONTENTS System Description AH-03312 System Characteristics... Fire Signal Receiving Board Description-4L... Fire Signal Receiving Board Description-8L...

More information

CDS TROUBLESHOOTING SECTION I. VACUUM. 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg)

CDS TROUBLESHOOTING SECTION I. VACUUM. 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg) CDS TROUBLESHOOTING SECTION I. VACUUM 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg) 1.1. Clogged hoses or wand tube. Disconnect hoses and carefully check for an obstruction. 1.2. Excessive

More information

Streaming Potential System (SPT1000, SPD1000)

Streaming Potential System (SPT1000, SPD1000) Streaming Potential System (SPT1000, SPD1000) User's Manual Sentrol Systems, Inc. 3949 Cotswold Dr. SW, Lilburn, GA 30047-2371 Tel: 770-564-1541, Fax: 770-564-8605 www.sentrolsystems.com Since the streaming

More information

Air Conditioning Sign-Off Sheet

Air Conditioning Sign-Off Sheet Air Conditioning Sign-Off Sheet Printed Technician Name Address Social Security Number Telephone Number City State Zip Code Install Or Verify The Accuracy Of An Air Conditioner s Installation The candidate

More information

Dyeing Programmer DP - 01

Dyeing Programmer DP - 01 Dyeing Programmer DP - 01 Display and Controls. 1) Display: 16/2 alphanumeric display 2) Temperature range: 0 to 150 degree. 3) Resolution: 1 degree. 4) Accuracy: +/- 1 degree. 5) Temperature control setting:

More information

Automatic taper of charge rate for superior battery life through good equalization of cells and low water use rate.

Automatic taper of charge rate for superior battery life through good equalization of cells and low water use rate. *00151* FEATURES Automatic taper of charge rate for superior battery life through good equalization of cells and low water use rate. Silicon diodes with inherent surge protection operated at a conservative

More information

RI-215A Operator s Manual. Part Number: 71-0045RK Revision 0 Released: 10/3/05

RI-215A Operator s Manual. Part Number: 71-0045RK Revision 0 Released: 10/3/05 RI-215A Operator s Manual Part Number: 71-0045RK Revision 0 Released: 10/3/05 Warranty RKI Instruments, Inc., warrants gas alarm equipment sold by us to be free from defects in materials and workmanship,

More information

Transport Air Conditioning TRANSPORT AIR CONDITIONING OPERATOR S MANUAL. for SPLIT SYSTEM. Bus Air Conditioning Units.

Transport Air Conditioning TRANSPORT AIR CONDITIONING OPERATOR S MANUAL. for SPLIT SYSTEM. Bus Air Conditioning Units. R Transport Air Conditioning TRANSPORT AIR CONDITIONING OPERATOR S MANUAL for SPLIT SYSTEM Bus Air Conditioning Units T--326 Rev -- OPERATOR S MANUAL BUS AIR CONDITIONING UNITS GEN IV & GEN V CONTENTS

More information

GPD 506/P5 Start-up Procedure and Checklist

GPD 506/P5 Start-up Procedure and Checklist GPD 506/P5 Start-up Procedure and Checklist Preparation for GPD506/P5 Drive Start-Up...2 HVAC Start-Up Procedure for GPD 506/P5 WITH Bypass Option:...4 HVAC Start-Up Procedure for GPD 506/P5 WITHOUT Bypass

More information

Manual for Fire Suppression & Methane Detection System

Manual for Fire Suppression & Methane Detection System Manual for Fire Suppression & Methane Detection System Fogmaker North America Post address: 150 Gordon Dr Exton, PA 19341 Delivery address: 150 Gordon Dr Exton, PA 19341 Tel: 610-265-3610 Fax: 610-265-8327

More information

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety

More information

SmartVFD Frame 4 Wiring Diagrams and Dimensional Drawings

SmartVFD Frame 4 Wiring Diagrams and Dimensional Drawings Smart Frame Wiring Diagrams and Dimensional Drawings Smart Frame Size 60 Vac:.5-7.5 HP 08/0 Vac: 0.75- HP SPECIFICATION DATA CONTENTS Smart Frame Wiring Diagrams... Frame, Fused Disconnect Wiring Diagrams...

More information

Hoshizaki America, Inc.

Hoshizaki America, Inc. Hoshizaki America, Inc. Stackable Crescent Cuber Models KM-1301SAH/3, SWH/3, SRH/3 KM-1400SWH-M, SWH3-M KM-1601SAH/3, SWH/3, SRH/3 KM-1900SAH/3, SWH/3, SRH/3 KM-2100SWH3, SRH3 KM-2500SWH3, SRH3 KMH-2000SWH/3,

More information

Hydraulic Troubleshooting PRESENTED BY

Hydraulic Troubleshooting PRESENTED BY Hydraulic Troubleshooting PRESENTED BY NORMAN KRONOWITZ Introduction Welcome to the CMA/Flodyne/Hydradyne s Hydraulic Troubleshooting presentation. We will introduce many aspects of troubleshooting hydraulic

More information