1 Distribution Transformers Three-Phase Pad-Mounted Compartmental Type Functional Specification Guide Functional Specification for Three-Phase Pad-Mounted Distribution Transformers 45 10,000 kva 1.0 Scope 1.1. This specification covers the electrical and mechanical characteristics of Eaton s Cooper Power series 45-10,000 kva Three-Phase Step-Down Pad-Mounted Distribution Transformers. KVA ratings for transformers with secondary voltages not exceeding 700V are 45-3,750 kva, while kva ratings for transformers with secondary voltages greater than 700V are 1,000-10,000 kva. Product is per Catalog Data CA202003EN. 2.0 Applicable Standards 2.1. All characteristics, definitions, and terminology, except as specifically covered in this specification, shall be in accordance with the latest revision of the following ANSI, IEEE, NEMA, and Department of Energy standards. IEEE Std C standard Standard for Standard General Requirements for Liquid-Immersed Distribution, Power, and Regulating Transformers. IEEE Std C standard Pad-Mounted Equipment - Enclosure Integrity. IEEE Std C standard Standard Requirements for Pad-Mounted, Compartmental-Type, Self-Cooled, Three-Phase Distribution Transformers (2500 kva and Smaller) - High Voltage: 34500GrdY/19920 Volts and Below; Low-Voltage: 480 Volt 2500 kva and Smaller (issued in March combines IEEE Std C and IEEE Std C standards). IEEE Std C standard Standard Test Code for Liquid-Immersed Distribution, Power, and Regulating Transformers and IEEE Guide for Short-Circuit Testing of Distribution and Power Transformers. IEEE Std C standard Guide for Loading Mineral-Oil-Immersed Transformers. NEMA TR (R2000) Transformers, Regulators and Reactors, Table 0-2 Audible Sound Levels for Liquid-Immersed Power Transformers. 1 of 15 September 2015 Replaces G August 2013
2 3.0 Ratings NEMA (2004) Safety Labels for Pad-Mounted Switchgear and Transformers Sited in Public Areas. 10 CFR Part 431 Department of Energy Energy Conservation Program: Energy Conservation Standards for Distribution Transformers; Final Rule The transformer shall be designed in accordance with this specification and the kva rating shall be: 45, 75, 112.5, 150, 225, 300, 500, 750, 1000, 1500, 2000, 2500, 3000, 3750, 5000, 7500, 10,000 (range may also be specified) The primary voltage, configuration, and the basic lightning impulse insulation level (BIL) shall be, {make a selection from Table 1} Dual voltages are also available The secondary voltage, configuration, and the basic insulation level (BIL) of the secondary voltage shall be, {make a selection from Table 1} 2 of 15 September 2015 Replaces G August 2013 Table 1 Ratings for Three-Phase Transformers (Single Ratio) Primary Voltage BIL (kv) Secondary Voltage BIL (kv) 2400 Delta 4160 Delta 4800 Delta 7200 Delta Delta Delta Delta Delta Delta Delta Delta Delta 4160GrdY/ GrdY/ GrdY/ GrdY/ GrdY/ GrdY/ GrdY/ GrdY/ GrdY/ GrdY/ Y/ Y/ Y/ Y/ Y/ Delta 480 Delta 240 Delta with 120 Mid-Tap 480 Delta with 240 Mid-Tap See left column for voltages over 700 V All 30 kv For complete connector rating, see IEEE Std standard. Transformers are suitable for connectors with phase-to-ground or phase-to-ground/phase-tophase high-voltage ratings as listed.
3 Arrester coordination may require higher BIL on multiple connections than indicated to achieve a minimum protection level of 20% The transformer may be furnished with full capacity high-voltage taps. The tap changer shall be clearly labeled to reflect that the transformer must be de-energized before operating the tap changer as required in Section 4.3 of IEEE Std C standard. The tap changer shall be operable on the higher voltage only for transformers with dual voltage primaries. The unit shall have one of the following tap configurations: No Taps Two 2 ½% taps above and below rated voltage (split taps) Four 2 ½% taps below rated voltage (four below) NEMA taps (14400, 13800, 13200, 12470, 12540) Non-standard tap configuration The applicable tap configuration shall be specified on the inquiry The average winding temperature rise above ambient temperature, when tested at the transformer rating, shall not exceed 65 C OR shall not exceed 55 C OR at the base transformer rating, shall not exceed 55 C, and when tested at 112% of the base rating, shall not exceed 65 C The percent impedance voltage, as measured on the rated voltage connection, shall be per Table 2. For target impedances, the tolerance on the impedance shall be +/- 7.5% of nominal value for impedance values greater than 2.5%. The tolerance on the impedance shall be +/- 10.0% for impedance values less than or equal to 2.5%. Table 2 Percent Impedance Voltage KVA Rating (Low voltage < 700 V) Impedance nominal KVA Rating Low voltage > 700 V (all nominal values) 150 kv BIL 200 kv BIL 250 kv BIL Construction 3 of 15 September 2015 Replaces G August 2013
4 4.1. The core and coil shall be vacuum processed to ensure maximum penetration of insulating fluid into the coil insulation system. While under vacuum, the windings will be energized to heat the coils and drive out moisture, and the transformer will be filled with preheated filtered degassed insulating fluid. The core shall be manufactured from burrfree, grain-oriented silicon steel and shall be precisely stacked to eliminate gaps in the corner joints. The coil shall be insulated with B-stage, epoxy coated, diamond pattern, insulating paper, which shall be thermally cured under pressure to ensure proper bonding of conductor and paper. Coils shall be either aluminum or copper (eliminate a metal if one is required over the other) The dielectric coolant shall be listed less-flammable fluid meeting the requirements of National Electrical Code Section and the requirements of the National Electrical Safety Code (IEEE Std C standard), Section 15. The dielectric coolant shall be non-toxic*, non-bioaccumulating and be readily and completely biodegradable per EPA OPPTS The base fluid shall be 100% derived from edible seed oils and food grade performance enhancing additives. The fluid shall not require genetically altered seeds for its base oil. The fluid shall result in zero mortality when tested on trout fry *. The fluid shall be certified to comply with the US EPA Environmental Technology Verification (ETV) requirements, and tested for compatibility with transformer components. The fluid shall be Factory Mutual Approved, UL Classified Dielectric Medium (UL-EOUV) and UL Classified Transformer Fluid (UL-EOVK), Envirotemp FR3 fluid. *(Per OECD G.L. 203) 4.3. Tank and Cabinet Enclosure The high-voltage and low-voltage compartments, separated by a metal barrier, shall be located side-by-side on one side of the transformer tank. When viewed from the front, the low-voltage compartment shall be on the right. Each compartment shall have a door that is constructed so as to provide access to the high-voltage compartment only after the door to the low-voltage compartment has been opened. There shall be one or more additional fastening devices that must be removed before the high-voltage door can be opened. Where the low-voltage compartment door is of a flat panel design, the compartment door shall have three-point latching with a handle provided for a locking device. Hinge pins and associated barrels shall be constructed of corrosion-resistant material, passivated ANSI Type 304 or the equivalent A recessed, captive, penta-head or hex-head bolt that meets the dimensions per IEEE Std C standard shall secure all access doors The compartment depth shall be in accordance with IEEE Std C standard, unless additional depth is specified The tank base must be designed to allow skidding or rolling in any direction. Lifting provisions shall consist of four lifting lugs welded to the tank. 4 of 15 September 2015 Replaces G August 2013
5 The tank shall be constructed to withstand 7 psi without permanent deformation, and 15 psi without rupture. The tank shall include a 15 psig pressure relief valve with a flow rate of minimum 35 SCFM The exterior of the unit shall be painted Munsell 7GY3.29/1.5 green (STD), ANSI 70 gray, or ANSI 61 gray in color. If a special paint color is specified, a federal spec number or paint chip must be provided at the time of order. The cabinet interior and front plate shall be painted gray for ease of viewing the inside compartment The tank shall be complete with an anodized aluminum laser engraved nameplate. This nameplate shall meet Nameplate B per IEEE Std C standard High Voltage Bushings and Terminals High voltage bushings will be installed in the high voltage termination compartment located on the front left of the transformer and requiring access via the low voltage termination compartment on the front right Bushing Style [ ] 15/25 KV DEADFRONT, CURRENTS BELOW 200 AMPS: The high voltage bushings shall be 15/25 kv 200A bushing wells with bushing well inserts installed. The bushings shall be externally removable and be supplied with a removable stud (Re: Catalog Data CA800016EN, , and ). [ ] 35 KV DEADFRONT, CURRENTS BELOW 200 AMPS: The high voltage bushing shall be a one-piece, 150 kv, 200-amp large interface load-break bushing (Re: Catalog Data CA800021EN). [ ] 15/25/35 KV DEADFRONT, CURRENTS ABOVE 200 AMPS: The high voltage bushing shall be a 600A dead-break primary one-piece bushing externally removable, 3Ø rated, integral design. An optional 900 A bushing is available upon request (Re: Catalog Data CA800025EN and CA800020EN). [ ] 36 KV TO 46 kv (250 KV BIL) DEADFRONT APPLICATIONS: The high voltage bushing shall be a CONNEX Plug-in Cable Termination System, size 3S. The male and female portions of the bushing shall be supplied with the transformer. Available in radial feed only. [ ] 15/25/35 KV LIVEFRONT, 200 KV BIL MAX: The high voltage bushing shall be a porcelain bushing with a two, four, or six-hole spade or an eyebolt connector Bushing Configuration [ ] 15/25 KV RADIAL FEED DEADFRONT: The transformer shall be provided with three (3) high voltage bushings in accordance with Figure 1 dimensions (Figure 4a dimensions may be specified when a larger termination compartment for greater working space is desired) from IEEE Std C standard for 5 of 15 September 2015 Replaces G August 2013
6 radial feed configurations. The bushing heights shall be in accordance with Figure 3 dimensions (Figure 6 dimensions may be specified for greater bushing height) of IEEE Std C standard. [ ] 15/25 KV LOOP FEED DEADFRONT: The transformer shall be provided with six (6) high voltage bushings in accordance Figure 2 dimensions (Figure 5a dimensions may be specified when a larger termination compartment for greater working space is desired) of IEEE Std C standard for loop feed configurations. The bushing heights shall be in accordance with Figure 3 minimum dimensions (Figure 6 dimensions may be specified for greater bushing height) of IEEE Std C standard. [ ] 35 KV RADIAL FEED DEADFRONT: The transformer shall be provided with three (3) high voltage bushings in accordance with Figure 4b dimensions of IEEE Std C standard for radial feed configurations. The bushing heights shall be in accordance with Figure 6 dimensions of IEEE Std C standard. [ ] 35 KV LOOP FEED DEADFRONT: The transformer shall be provided with six (6) high voltage bushings in accordance with Figure 5c dimensions of IEEE Std C standard for loop feed configurations. The bushing heights shall be in accordance with Figure 6 dimensions of IEEE Std C standard. [ ] 46 KV / 250 KV BIL DEADFRONT: The transformer shall be provided with three (3) bushings mounted 45 down from the horizontal, 60 from the ground, and 12 apart from each other. [ ] 15/25/35 KV LIVEFRONT, 150 KV BIL MAX: The transformer shall be provided with three (3) bushings in accordance with Figure 9 of IEEE Std C standard for radial feed configurations. The bushing heights shall be in accordance with Figure 10 of IEEE Std C standard. [ ] 200 KV BIL LIVEFRONT: The transformer shall be provided with three (3) bushings with phase-to-phase and phase-to-ground clearances adequate for 200 kv BIL Low Voltage Bushings and Terminals Bushing Style Voltages less than 700 Volts: The transformer shall be provided with tinplated spade-type bushings for vertical takeoff. The spacing of the connection holes shall be 1.75 on center, per IEEE Std C standard Figure 13a. The quantity of connection holes shall be 4, 6, 8, 12, 16, or 20 holes. 6 of 15 September 2015 Replaces G August 2013
7 Transformers 300 kva and below, and 500 kva with 480Y/277 secondary will have two-piece low voltage bushings with studs and screw on spades. Transformers 500 kva with 208Y/120 secondary and all transformers above 500 kva will have one-piece bushings. Table 3 Standard / Maximum Bushing Hole Quantities KVA 208Y/ Y/277 and higher standard, 16 maximum 4 standard, 16 maximum standard, 12 maximum 4 standard, 16 maximum standard, 20 maximum 6 standard, 12 maximum N/A 12 standard, 20 maximum (Re: Catalog Data CA800017EN, CA800023EN, and CA800018EN) Bushing supports shall be provided for transformers requiring 10 or more connection holes. Bushing supports shall be affixed to the cabinet sidewalls; tank-mounted supports mountings are not acceptable Bushing Configuration The transformer shall be provided with bushings in a staggered arrangement in accordance with Figure 11a dimensions (Figure 12a dimensions may be specified when a larger termination compartment for greater working space is desired) of IEEE Std C standard Voltages greater than 700 Volts: Refer to section 3.1 for the bushing type. Secondary arrangements shall be live-front or dead-front. Dead-front application with a required neutral shall have a porcelain X0 bushing. Dead-front application may be loop feed when specified. Provide additional front barrier for high voltage live front secondary, creating an additional barrier after the low voltage door has been opened Switching [ ] Primary Switching: The primary switching scheme provided with the transformer shall be one (only available option for radial feed), two, or three on-off under-oil load-break switch(s), or one four-position V or T-blade load-break sectionalizing switch. Refer to Appendix 1 for the schematics of these switching options (Re: Catalog Data CA800005EN and CA800019EN). [ ] Make-before-break option for four-position, sectionalizing switch: This switch option provides improved system reliability by eliminating momentary interruptions during switching operations. [ ] External Visible Loadbreak On/Off switch: 7 of 15 September 2015 Replaces G August 2013
8 4.7. Overcurrent Protection The external visible loadbreak switch allows customers to visibly confirm that the transformer is de-energized without having to expose themselves to dangerous arc flash in the transformer compartment. [ ] External Visible Loadbreak On/Off/Ground switch The external visible loadbreak switch allows customers to visibly confirm that the transformer is de-energized without having to expose themselves to dangerous arc flash in the transformer compartment. This feature also allows the end user to ground the transformer using the load break switch. Note: The external load-break switch can also be supplied with external gauges mounted outside of the transformer cabinet. Refer to Section 9 for the gauges included with this option. [ ] BAY-O-NET WITH BACK-UP CURRENT LIMITING FUSES: (available up to 130 amps of full-load transformer current, up to 34.5 kv grounded wye, or 23 kv delta). The high-voltage overcurrent protection scheme provided with the transformer shall be an externally removable loadbreak expulsion Bay-O-Net fuse assembly with a flapper valve to minimize oil spillage. The bayonet fuses shall be in series with ELSP under-oil partial-range current-limiting back-up fuses with an interrupting rating of 50,000 A. (Re: Catalog Data CA132015EN, CA132009EN, CA132010EN, CA132012EN, CA132011EN, CA132007EN, and CA132013EN) For voltages 23000Y or Delta and above (which must also take into account any higher tap settings), bayonet fuses are not available. [ ] Cartridge fusing, >23kV: Under-oil cartridge fusing shall be utilized (available up to 208 amps of full-load transformer current, up to 34.5kV delta). The high-voltage overcurrent protection scheme provided with the transformer shall be under-oil cartridge fusing. Cartridge fuses shall be in series with ELSP under-oil partial-range current-limiting back-up fuses with an interrupting rating of 50,000 A. [ ] Optional Accessory: An interlock shall be required between the loadbreak switch scheme specified and the bayonet fuses, such that the fuses may not be removed unless the transformer has been deenergized via the load-break switch scheme. [ ] MAGNEX INTERRUPTER: (available up to 42 amps of full-load transformer current, up to 35 KV grounded wye, or 17.1 KV delta), The high-voltage overcurrent protection scheme provided with the transformer shall be a threephase trip MagneX interrupter. This externally resettable device may also be used as an on-off switch. The three-phase MagneX interrupter shall be in series with ELSP under-oil partial-range current-limiting back-up fuses with an interrupting rating of 50,000 A (Re: Catalog Data CA132017EN and CA132013EN). 8 of 15 September 2015 Replaces G August 2013
9 [ ] INTEGRAL VACCUUM, FAULT INTERRUPTER (VFI): (available from 13 amps up to 900 amps of full-load transformer current, up to 34.5 kv, grounded wye or delta, maximum 150 KV BIL) The high-voltage or low-voltage overcurrent protection scheme provided with the transformer shall be an integral Vacuum Fault Interrupter (VFI). The VFI shall have a maximum interrupting rating of 12,000A RMS symmetrical (optional 16,000 A RMS symmetrical available at 15 KV) with resettable fault protection up through 35 kv. The VFI shall also include a Tri-Phase electronic breaker control with over 100 minimum trip settings and five (5) selectable time current curves. The minimum trip setting shall be XX amps, and curve profile shall be the EF, KF, TF, F, or H (Re: Bulletin B and Service Information S for the electronic control) Overvoltage Protection [ ] Optional ELSP Accessory: VFI shall be in series with ELSP under-oil partial-range current-limiting back-up fuses with an interrupting rating of 50,000 A. [ ] Optional VFI Accessories: SCADA board; Ground fault detection; Motor operator assembly; Visible break window The overvoltage protection scheme provided with the transformer shall protect the high-voltage or low voltage winding. [ ] DEAD-FRONT BUSHINGS: (maximum 150 kv BIL, for voltages up to 18 kv delta and 35 kv grounded wye). Externally mounted, Distribution Class M.O.V.E. Deadfront elbow arresters shall be supplied. (Re: Catalog Data ) M.O.V.E. arresters are for installation on 200 A rated dead-front bushing interfaces only. If transformer bushings are rated 600 A or 900 A, BT-TAP elbow connectors, T-OP II elbow connectors, or 600 A bushing adapters, each with a load-reducing tap plug for arrester connection, are required (Re: Catalog Data CA235018EN and CA235012EN). [ ] LIVEFRONT BUSHINGS: (up to 200 KV BIL). Distribution- and Intermediate- Class arresters shall be supplied beneath the high-voltage bushings (Re: Catalog Data CA235018EN and CA235012EN). [ ] UNDER OIL: (for voltages up to 27 kv delta and 35 KV grounded wye). Internally mounted, Distribution Class MOV under-oil surge arresters shall be supplied (Re Catalog Data CA235023EN). [ ] Optional Accessory: Three (3) disconnect switches shall be included to disconnect the under-oil arresters from ground for transformer testing (Re: Catalog Data ). 5.0 Optional features to reduce exposure to arc flash 9 of 15 September 2015 Replaces G August 2013
10 5.1. Additional transformer rating nameplate In addition to the standard nameplate located on the transformer tank, a second nameplate shall be included. The nameplate shall be mounted external to the termination compartments with an industrial grade double-sided adhesive. Its location shall be identified on the data sheet External drain valve with sampler A 1.0 drain valve with sampling device shall be located outside of the cable compartment on the [low voltage] [high voltage] side of the tank. The valve shall be protected by a hinged cover with padlock provisions External instrumentation package All included gauges and instrumentation devices shall be located outside of the cable compartments such that access to them does not require exposure to any live circuits. They shall be located inside a separate NEMA 4 rated enclosure on the [low voltage] [high voltage] side of the tank. Devices shall include the following: liquid level gauge, dial-type thermometer, pressure/vacuum gauge, pressure relief valve, ½ fluid sampling valve, [temperature transducer], [pressure transducer], [winding temperature indicator], [rapid rise relay], [upper fill plug/valve] Alarm contacts [shall] [shall not] be included on the liquid level gauge, dial-type thermometer, and pressure/vacuum gauges. Any of the accessories above with contacts shall be wired [to terminal blocks located within the enclosure] [via liquidtight flexible conduit to a terminal block in a [NEMA 4] [NEMA 4X] control box located below the instrument box] External load break switch The high voltage switch handle shall be located on the exterior tank wall on the high voltage side of the transformer. The switch shall be operable without exposure to any live circuits. The handle shall be protected by a hinged cover with padlock provisions External visible load break (EVLB) switch The high voltage switch shall be located on the exterior tank wall on the high voltage side of the transformer and shall include a viewing window that provides visible confirmation of the switch blade position. The switch shall be of a [2-position, on/off] [3-position, on/off/ground] configuration and shall be operable without exposure to any live circuits. Hinged covers with padlock provisions shall be provided over the window and over the switch handle. Properly sized currentlimiting fuses shall be included in the transformer for additional safety. Note: The EVLB option is limited to the following ratings: Line voltage (kv) Maximum kva < < of 15 September 2015 Replaces G August 2013
11 For additional safety and ease of maintenance, the following instrumentation devices shall be located on the front of the external load break switch compartment: liquid level gauge, dial-type thermometer, pressure/vacuum gauge, pressure relief valve and ½ fluid sampling valve. These devices shall be protected by a hinged cover with padlock provisions. Note: If alarm contacts are required a second set of gauges shall be provided in the low voltage cable compartment with the contacts wired to a terminal block on the metal divider between the compartments Infrared (IR) inspection windows To monitor connections in the high voltage and low voltage compartments without opening the compartment doors, IR window shall be provided. The window(s) shall be IRISS model VPFR-75 or approved equal. The quantity and location of the window(s) shall be indicated on the data sheets. 6.0 Labeling 6.1. A temporary bar code label shall be attached to the exterior of the transformer in accordance with IEEE Std C standard. 7.0 Finish Performance Requirements 7.1. The tank coating shall meet all requirements in IEEE Std C standard including: Salt Spray Crosshatch adhesion Humidity Impact Oil resistance Ultraviolet accelerated weathering Abrasion resistance taber abraser 7.2. The enclosure integrity of the tank and cabinet shall meet the requirements for tamper resistance set forth in IEEE Std C standard including but not limited to the pry test, pull test, and wire probe test. 8.0 Production Testing 8.1. All units shall be tested for the following: No-Load (85 C or 20 C) losses at rated current Total (85 C) losses at rated current Percent Impedance (85 C) at rated current Excitation current (100% voltage) test Winding resistance measurement tests Ratio tests using all tap settings 11 of 15 September 2015 Replaces G August 2013
12 Polarity and phase relation tests Induced potential tests Full wave and reduced wave impulse test 8.2. Transformers shall conform to efficiency levels for liquid immersed distribution transformers, as specified in the Department of Energy ruling 10 CFR Part 431 Energy Conservation Program: Energy Conservation Standards for Distribution Transformers; Final Rule; April 18, Manufacturer shall comply with the intent of all regulations set forth in noted ruling In addition, the manufacturer shall provide certification upon request for all design and other tests listed in IEEE Std C standard, including verification that the design has passed short circuit criteria per IEEE Std C standard and IEEE Std C standard In the event of proposal bid evaluated with guaranteed losses due to a loss evaluation (see section 10.0), manufacturer shall conform to guaranteed average losses as specified in IEEE Std C standard. The no-load losses of a transformer shall not exceed the specified no-load losses by more than 10%, and the total losses of a transformer shall not exceed the specified total losses by more than 6%. 9.0 Approved Manufacturers 9.1. Eaton Waukesha WI 10.0 Accessories The following accessories and options shall be provided: [ ] Bolted main tank cover (1000 kva & below) [ ] Welded main tank cover with bolted handhole (1500 kva & above) [ ] 1.0 upper fill plug [ ] 1.0 drain plug in LV compartment (500 kva & below) [ ] 1.0 drain valve w/ sampling device in LV compartment (750 kva & above) [ ] Automatic pressure relief valve [ ] Metal drip shield (when bayonets specified) [ ] 20 deep cabinet (2500 kva & below) [ ] 24 deep cabinet (3000 kva & above) [ ] Ground provisions per IEEE Std C standard section [ ] Meet NEMA TR-1 sound levels [ ] Liquid level gauge [ ] Dial-type thermometer gauge [ ] Pressure vacuum gauge [ ] 1.0 drain valve w/ sampling device in (LV or HV) compartment (500 kva & below) [ ] Upper fill valve [ ] Pressure vacuum bleeder [ ] 24 deep cabinet 12 of 15 September 2015 Replaces G August 2013
13 [ ] 30 deep cabinet [ ] 36 deep cabinet [ ] 40 deep cabinet [ ] Spare bayonet fuse links [ ] Fault indicator provisions [ ] Ground connectors [ ] Mr. Ouch warning & danger signs [ ] Danger high voltage warning signs [ ] Miscellaneous stenciling [ ] Non-PCB decal [ ] Touch-up paint [ ] Interphase barriers (for live front primary units only) [ ] Seismic zone 3 and 4 tank anchoring [ ] Complete 304L stainless steel tank and cabinet [ ] 304L stainless steel tank base and cabinet sides & sill (partial) [ ] Liquid level gauge with auxiliary contacts [ ] Dial-type thermometer gauge with auxiliary contacts [ ] Pressure vacuum gauge with auxiliary contacts [ ] Current or potential transformers [ ] Rapid rise relay with seal-in panel [ ] Winding temperature indicator [ ] Watt-hour meter package includes GE kv2c Encompass Electronic Meter. Factory supplied wiring shall be internal to the cabinet, not in conduit. Communication connection shall be the OPTOCOM port. [ ] Harmonic resistant K-factor design, K=4, 9, 13, or 20 [ ] Forced air ONAF (mineral oil) or KNAF (Envirotemp FR3 fluid) rating. Forced air rating requires documentation from Eaton s customer that they are aware this transformer is no longer tamper resistant and is no longer in compliance with ANSI standards. [ ] Future forced air rating [ ] Forced Air Fan Control Package [ ] FM Global (FM) Approved transformer (to comply with NEC listing restrictions for installations on, near, or inside of buildings) [ ] Combination UL Listed & Classified transformer (to comply with NEC listing restrictions for installations on, near, or inside of buildings) per UL XPLH [ ] UL Listed transformer (certifying compliance with ANSI standards only) per UL XPLH [ ] External visible break with gauges: Gauges include liquid level, dial-type thermometer gauge, pressure/vacuum, pressure relief valve, and a 1.0 oil sampler valve, and fill plug Optional Transformer Evaluation [ ] No unit evaluation, but include quote losses as reference only on bid. [ ] Unit loss evaluation, guaranteed average losses. Criteria to properly evaluate quoted losses: Core loss evaluation (A-factor) $/watt 13 of 15 September 2015 Replaces G August 2013
14 Winding loss evaluation (B-factor) $/watt (Eaton may be contacted for sample loss evaluation method) 12.0 Shipping Transformers, 1000 kva and below, shall be palletized. Transformers, 1500 kva and larger, shall be loaded and unloaded with overhead cranes, so a pallet is not to be provided for these transformers Data With Proposal The following data shall be submitted with the proposal: 14.0 Service Core losses (when requested per Sections 7.4 and 10.0). Winding losses (when requested per Sections 7.4 and 10.0). Percent Impedance Typical bid drawing Approval drawing drawings shall show final dimensions and features. When requested, approval drawings shall be provided per quoted leadtime. Record Drawing drawings shall show final dimensions and features. When requested, record drawings shall be provided The manufacturer of the transformer shall have regional service centers located within two (2) hours flight time of all contiguous 48 states. Service personnel shall be factory trained in commissioning and routine service of quoted transformers. 14 of 15 September 2015 Replaces G August 2013
15 APPENDIX 1: Switching Options and Schematics 1 On/Off Switch 2 On/Off Switches 3 On/Off Switches (Re: Catalog Data CA800019EN) 4-position sectionalizing switches: V-blade switch Description of positions: Feed from A & B Feed from A only Feed from B only Open the loop is open and the transformer is de-energized T-blade switch Description of positions: Feed from A & B Feed from A only Feed from B only Open the loop is closed and the transformer is de-energized (Re: Catalog Data CA800005EN) 15 of 15 September 2015 Replaces G August 2013
Multi-tap Transformers
Multi-tap Transformers Three-Phase Multi-tap Transformer for Electrical Submersible Applications Functional Specification Guide Functional Specification for Multi-tap Transformers for Electrical Submersible
S. C. Electric Cooperative s Specification for a Three-Phase, Padmounted URD Transformer (Revised 12/2014)
1.0 GENERAL S. C. Electric Cooperative s Specification for a Three-Phase, Padmounted URD Transformer (Revised 12/2014) 1.1 This specification covers the electrical and mechanical characteristics of Three-Phase,
Submit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
TRANSFORMER DICTIONARY
TRANSFORMER DICTIONARY AUTOTRANSFORMER A transformer that has only one winding per phase; part of the winding is shared between the primary and secondary CONDITION New - All materials and components are
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to
261000 Medium Voltage Electrical Distribution
Sections Included In This Standard: 1.1 General 1.2 Underground Cable 1.3 Medium Voltage Switches 1.4 Transformers 1.5 Electrical Manholes 1.6 Switch Vaults 1.7 Distribution Switchgear/Switchboards This
This section applies to the design and installation of transformers.
ELECTRICAL: TRANSFORMERS BASIS OF DESIGN This section applies to the design and installation of transformers. Design Criteria 13.8-kV equipment shall be 15-kV class. Coordinate with short-circuit studies
Secondary Unit Substations
14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically
Instructions for Secondary Unit Substation Transformers 150-3000 KVA, Three Phase
ABB Inc. Instruction Booklet Distribution Transformers Jefferson City, MO ISO 9001 Certified I.B. 46-060-1, Section E ILUJ000004-BLE Effective: January, 2008 Instructions for Secondary Unit Substation
SECTION 16322 SUBSTATION TRANSFORMERS
SUBSTATION TRANSFORMERS PART 1 GENERAL 1.01 1.02 1.03 1.04 SCOPE The Contractor shall furnish and install the primary and/or secondary substation transformers as specified herein and as shown on the contract
BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET
BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET Berthold Electric Company s Generator Connection Cabinet provides a quick and convenient station to connect a portable generator to a facility s main service
Unified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
Sample - No Commercial Use
COMPLETE REVISION October 2010 Electrical PIP ELSSG01 Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort
Primary and Secondary Electrical Distribution Systems
Primary and Secondary Electrical Distribution Systems Critical Facilities Round Table 12th Quarterly Membership Meeting June 2, 2006 David D. Roybal. P.E. Eaton Electrical Cutler-Hammer Products Utility
Type MOST oil switch. Technical Data 285-20. Contents. Effective October 2013 Supersedes March 2000
echnical Data 285-20 Supersedes March 2000 ype MOS oil switch Contents Description Page General...2 Ordering information....2 Features and detailed description.... 6 Fuse assemblies....7 MOS switching
Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components
Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Course No: E02-010 Credit: 2 PDH Boris Shvartsberg, Ph.D., P.E., P.M.P. Continuing Education
25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp
Page 1 2015 Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other Component 15 kv or 25 kv Separable Insulated Connector (elbow) Equipment Connection Power Cable Power Cable Grounded Metal
HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80
Buck-Boost Transformers Single and Three Phase Potted Buck-Boost Transformers Buck-Boost Applications & Standard Specification... 80 Selecting Buck-Boost Transformers... 81 Single Phase Selection Tables...
METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D
12 - ELECTRIC SERVICE HANDBOOK SECTION D METER REQUIREMENTS This chapter gives you information on Central Lincoln s metering requirements. It's divided into three sections: General requirements This section
Data Center Solutions. Envirotran HDC Transformers Deliver Superior Reliability and Efficiency for Substantial Savings Everyday
Data Center Solutions Envirotran HDC Transformers Deliver Superior Reliability and Efficiency for Substantial Savings Everyday Data Center Solutions As the demand for data centers grows, the industry s
All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
ELECTRIC METERING COMMERCIAL & INDUSTRIAL
ELECTRIC METERING COMMERCIAL & 1.0 INDEX 1.0 INDEX 2.0 SCOPE 3.0 GENERAL REQUIREMENTS 4.0 METER LOCATIONS 5.0 UNDERGROUND TERMINATIONS 6.0 METERING TRANSFORMER ENCLOSURES 7.0 SINGLE CUSTOMER METER INSTALLATIONS
SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A
SURGE PROTECTIVE DEVICES (SPDs) INTEGRATED UNITS LOW VOLTAGE AC SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS PART 1 GENERAL 01 02 03 SCOPE The Contractor shall furnish and install the Surge Protective
Step Voltage Regulators
Step Voltage Regulators Don Wareham Field Application Engineer Today s Agenda Introduction Voltage Regulator theory Voltage Regulator application considerations Installation and proper bypassing Wrap-up/questions
Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers
Specification Guide for RVAC Direct Replacement AC Medium Voltage Circuit Breakers Table of Contents 1.0 General Work Scope...3 2.0 Standards...3 3.0 Supplier Qualifications...4 4.0 Circuit Breaker Element
Hyperlinks are Inactive
Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)
Customer Substation Manual 08/05/02
Customer Substation Manual Table of Contents Section Page 2 of 85 Description 0 Preface 010.00 General 010.10 Information Required for the Review of New Customer Substations 010.20 New Customer Substation
16300 MEDIUM VOLTAGE DISTRIBUTION
16300 MEDIUM VOLTAGE PART 1: GENERAL 1.01 SYSTEM DESCRIPTION A. Most new loads will be served from the underground electric distribution system. This system is a primary open loop configuration served
FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid
Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars Presented By: Greg Pelster & Robert Schmid FFI Ferrie, Franzmann Industries LOW VOLTAGE SWITCHGEAR & LOW VOLTAGE
Switchgear and Metal-Enclosed Bus
Section 18 Switchgear and Metal-Enclosed Bus 180. SWITCHGEAR ASSEMBLIES 180A. General Requirements for All Switchgear. This rule covers general requirements for all switchgear. Examples of switchgear found
3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance
SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132
IRRIGATION PUMPING Table of Contents - Section 900
IRRIGATION PUMPING Table of Contents - Section 900 PARAGRAPH 900.1 GENERAL 1 900.2 METERING REQUIREMENTS 1 900.3 CUSTOMER S CONTROL EQUIPMENT 2 900.4 SERVICE CONDUCTOR REQUIREMENTS 2 900.5 RECOMMENDATIONS
Doc Ref: 2015.06.01.002. 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC
TM 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC TM D400E Data Module (60Hz) The EDGE D400E is designed to meet high power density requirements for both the HPC and Web Scale environments while
337500 MEDIUM VOLTAGE DISTRIBUTION
337500 MEDIUM VOLTAGE DISTRIBUTION PART 1: GENERAL 1.01 SYSTEM DESCRIPTION A. Most new loads will be served from the underground electric distribution system. This system is a primary selective open loop
ELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC
ELECTRICAL SERVICE REQUIREMENTS ELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC TABLE OF CONTENTS TITLE SECTION NO. List of Approved Electric Utility Service Equipment Requirements Committee
Explosion-Proof Electric Unit Heaters
Type FX4 FX4 Explosion-Proof Electric Air Heaters FX4 heaters are UL listed and/or CSA certified for use in hazardous locations. They are designed for dry indoor industrial applications such as oil refineries,
SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less.
PART 1 - GENERAL SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less. RELATED SECTIONS Division 16 Section "Basic Electrical Materials and Methods" for general
Short Circuit Current Calculations
Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that
Digital Energy ITI. Instrument Transformer Basic Technical Information and Application
g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER
MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4
CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,
Overhead Distribution Transformers 5-833 kva Single Phase 30-500 kva Three Phase
X62292-Brochure 8/20/03 1:15 PM Page 1 Overhead Distribution Transformers 5-833 kva Single Phase 30-500 kva Three Phase Represented by and Nameplated for ABB Inc. X62292-Brochure 8/20/03 1:15 PM Page 2
ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013
ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 READ CAREFULLY These instructions are intended to cover good practices in
Presentation of the France Transfo factories
Presentation of the France Transfo factories France Transfo's internationally recognised and highly esteemed expertise is today exported to more than 80 countries throughout the world. Over the past 15
SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL
SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated
Liquid Filled Transformers Load Tap Changing Transformers Three-Phase Voltage Regulators
Liquid Filled Transformers Load Tap Changing Transformers Three-Phase Voltage Regulators Virginia Transformer is a leader in custom power transformers engineered precisely for your application and optimized
Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1
How to configure Part Numbers: Step : Select Switch Amperage Power Module Switch Rating (Amps) Power Module Switch Catalog No. 30 3 60 6 00 200 2 400 4 Step 2: Select Options Needed 5 Bussmann Power Module
HVL 5 38 kv Load Interrupter Switchgear. The Standard for Performance, Protection and Dependability
HVL 5 38 kv Load Interrupter Switchgear The Standard for Performance, Protection and Dependability For a generation of engineers, Square D High Voltage Load (HVL ) Interrupter Switchgear by Schneider Electric
Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services
Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services Introduction Power Distribution Equipment is a term generally used to describe any apparatus used for the generation,
SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC EXTERNAL SIDEMOUNT SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671B SECTION 16671B
SURGE PROTECTIVE DEVICES (SPDs) EXTERNAL SIDEMOUNT UNITS LOW VOLTAGE AC SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION PART 1 GENERAL 01 02 03 SCOPE The Contractor shall furnish and install the Surge Protective
SUPPLEMENT TO SPECIFICATIONS FOR ELECTRICAL INSTALLATIONS
SUPPLEMENT TO SPECIFICATIONS FOR ELECTRICAL INSTALLATIONS PRIMARY METER POLE ELECTRIC SYSTEM BULLETIN No. 753 JUNE 1993, 2 ND PRINTING APRIL 2002 (Supersedes issue dated March 1983 and incorporates Nov.
Distribution Voltage Regulators
Distribution Voltage Regulators Type JFR Single Phase 2.5 to 19.9 kv Type SFR Three Phase 13.2 to 34.5 kv Power Transmission & Distribution Siemens JFR & SFR Voltage Regulators Improving Quality of Service
SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions
SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS POWER DISTRIBUTION RACKS IN A MISSION CRITICAL SYSTEM MODULES IN A MISSION CRITICAL SYSTEM UPS Convertor Main Inverter Load Battery BPC UPS & BATTERY
TERMINATION ENCLOSURE OPTIONS
TERMINATION ENCLOSURE OPTIONS Add suffix: R - Reverse Stagger the Bus Bars (to run cable in from the top) CU - Copper NEMA Mount Bus Bars C - Plastisol Covers for Bus Bars DF - Dead Fronts T - Tin Plated
PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:
PREFACE UL developed the Dead-Front Switchboard Marking Guide for code authorities, electric utilities, contractors, installers, users, designers, and other interested parties to aid in understanding deadfront
MEDIUM VOLTAGE METAL CLAD SWITCHGEAR
MEDIUM VOLTAGE METAL CLAD SWITCHGEAR PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, installation, connection and testing of the medium voltage switchgear. 1.2 SWITCHGEAR FEATURES
Customer Low-Voltage Switchboards Service Cable Terminal Compartment Arrangements and Clearances
Page 50 of 100 Customer Low-Voltage Switchboards Service Cable Terminal Compartment Arrangements and Clearances (Replaces A-190556) THIS CUSTOMER REFERENCE SPECIFICATION (CRS) IS PART OF THE RULES FOR
UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation
Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers
James M. Pleasants Company
James M. Pleasants Company SUBMITTAL DATA GAINESVILLE MECHANICAL DECEMBER 20, 2013 PROJECT: GSU: J-183 HUMANITIES LAW BLDG. QUOTE NO:12116 ENGINEER: STEVENS & WILKINSON GASKETED PLATE HEAT EXCHANGER Tag:
Metallic and Non-Metallic Air Conditioning Disconnects. A Complete Family of. Disconnects with Exclusive Time Saving Features
Metallic and Non-Metallic Air Conditioning Disconnects A Complete Family of Disconnects with Exclusive Time Saving Features Enclosed Molded Case Disconnect Switch Not-Fusible The preferred molded case
Transformer Design & Design Parameters
Transformer Design & Design Parameters - Ronnie Minhaz, P.Eng. Power Transmission + Distribution GENERATION TRANSMISSION SUB-TRANSMISSION DISTRIBUTION DISTRIBUTED POWER 115/10 or 20 kv 500/230 230/13.8
Issued 06-01-07 E.C.S. Section WTR00 INFORMATION SECTION Page 1 of 1
Issued 06-01-07 E.C.S. Section WTR00 INFORMATION SECTION Page 1 of 1 INDEX SECTION WTR01: ELECTRICAL CONNECTIONS PRIMARY.. Page 1 SERVICE DROPS FROM THREE-PHASE TRANSFORMER BANKS.. Page 9 SECTION WTR02:
Table of Contents. TransformerIQ FAQs 1
[12/12] FAQs Table of Contents FAQ 1. What size transformer will TransformerIQ monitor?... 2 FAQ 2. Are there different TransformerIQ versions?... 2 FAQ 3. How are the units powered?... 2 FAQ 4. What is
OVR Three-Phase Recloser and PCD Control Style Guide 1VAL264001-SG October 13, 2009 Revision F
OVR Three-Phase Recloser and PCD Control Style Guide 1VAL264001-SG October 13, 2009 Revision F The OVR three-phase recloser style guide aids in the proper selection of your OVR three-phase style number.
RAY-MAX Integrated Solar Power Strip
RAY-MAX Integrated Solar Power Strip 600008, 600009, 600010, 600208, 600209, 600210 Owner s Manual NEXTRONEX, INC. Revision Date: 10/27/14 Contents 1. Safety Instructions... 3 2. General Equipment Warnings...
SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches
SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Optional Standby Power Generator Systems A. Furnish and install automatic transfer switches
SECTION 16341 MEDIUM VOLTAGE SWITCHGEAR
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes metal-enclosed
PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS
PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS TESTS ON TRANSFORMERS 1. IR Values a) For 33/11 KV Power Transformer 2500 V megger is to be need. b) Power Transformer neutral Earthing is
SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS
SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section
CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH
CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH Cat transfer switches are designed for a variety of standby power applications. They provide flexibility, reliability and value in a
26 3213.13 Diesel Engine Driven Generators Page 1 of 6
Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled
Generator DoCKInG StatIonS
Generator DOCKING STATIONS TRYSTAR Portable Power Cable Cam to cam cable extensions 2000V, 100A-400A rated to NEC table 400.5 (B) All portable power cable sold is highly flexible and UL & C-UL or CSA Listed
3. TYPES OF SERVICE AVAILABLE. 3.1 Scope
3. TYPES OF SERVICE AVAILABLE 3.1 Scope UI supplies 60 hertz, alternating current with different voltage and ampere ratings. Not all voltage and ampere ratings are available throughout the entire service
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 SCOPE A. Furnish and install individual freestanding variable frequency AC drives (VFD) as shown on the Drawings and specified herein. 1.02
Lightning Arresters P30027 18 KVA P30038 10 KVA. Description & Installation
Lightning Arresters P30027 18 KVA P30038 10 KVA Description & Installation Printed in USA 09/11 TO330 Rev. B Table of Contents Page 1.0 SCOPE 2 2.0 PRODUCT OVERVIEW 2 2.1 Intended Uses 2 2.2 Lightning
Technical Specification for Oil insulated Transformers U m < 24 kv up to 1250 kva
to 1250 kva Page 1/10 Technical Specification for Oil insulated Transformers U m < 24 kv up to 1250 kva This technical specification is valid for the business unit E.ON Sweden of the market unit E.ON Nordic.
01.4IB.51200B PowlVac-AR Arc Resistant Switchgear. 5kV & 15kV 1200A, 2000A, 3000A, & 4000A Forced Cooled. Powered by Safety
PowlVac-AR Arc Resistant Switchgear 1200A, 2000A, 3000A, & 4000A Forced Cooled Powered by Safety PowlVac-AR Arc Resistant Switchgear 01.4IB.51200B Contact Information Powell Electrical Systems, Inc. www.powellind.com
What are the basic electrical safety issues and remedies in solar photovoltaic installations?
What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic
TSn SERIES Surge Protective Device
Page: 1 of 8 TSn SERIES Surge Protective Installation & Operation Manual 3621 Saunders Avenue www.systems.us Ph 804.355.1100 Richmond, VA 23227 4354 [email protected] Fax 804.355.8900 Page: 2 of 8 Quick
Vertical Break Parallel (VBP) / Vertical Break Slant (VBS)
August, 2009 Vertical Break Parallel (VBP) / Vertical Break Slant (VBS) Type VBPA (Aluminum) / Type VBPC (Copper) Type VBSA (Aluminum) / Type VBSC (Copper) PASCOR Air Break Switch Technology PASCOR offers
CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION
CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION SPECIFICATION EO-5023 REVISION 3 MARCH 2003 REQUIREMENTS FOR
Atlanta Chapter IEEE Industry Applications Society
Atlanta Chapter IEEE Industry Applications Society Electrical Equipment Room Design Considerations presented at the Sheraton Buckhead Hotel Atlanta, Georgia November 20, 2006 Outline 1. Definitions 2.
Learning Module 13: Panelboards and Switchboards. 101 Basic Series
Learning Module 13: Panelboards and Switchboards 101 Basic Series What You Will Learn We ll step through each of these topics in detail: Introduction 4 Definitions 4 Similarities Between Panelboards and
TP-C2 Motor Operator CLEAVELAND / PRICE INC. Bulletin DB-111B12
Bulletin DB-111B12 TP-C2 Motor Operator CLEAVELAND / PRICE INC. 14000 Rt. 993, Trafford, PA 15085 (724) 864-4177 FAX (724) 864-9040 Email: [email protected] Cleaveland/Price Type TP-C2 Motor Operator
OVR-3SP Recloser with PCD Control Style Guide 1VAL263901-SG March 30, 2009 Revision B
OVR-3SP Recloser with PCD Control Style Guide 1VAL263901-SG March 30, 2009 Revision B The OVR-3SP three-phase recloser style guide aids in the proper selection of your OVR-3SP style number. The OVR-3SP
Dead Tank Outdoor Vacuum Circuit Breaker, Type VOX
Dead Tank Outdoor Vacuum Circuit Breaker, Type VOX Class 6065 Instruction Bulletin 6065-13 11/2011 Retain for future use. Hazard Categories and Special Symbols Read these instructions carefully and look
Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC
Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC Project name: Customer: Address, location of the system: Serial number
Low Voltage Transformers Sealed, General Purpose, Dry Type
Low Voltage Transformers Sealed, General Purpose, Dry Type Catalog 7400CT9601R4/08 08 Class 7400 CONTENTS Description..............................................Page Introduction.................................................
SECTION 16461 DRY-TYPE TRANSFORMERS
SECTION 16461 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Furnishing and installation of and testing of cast resin dry type MV/LV distribution transformer in accordance with specifications and drawings. Any
MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation
MTE SERIES RLW World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930 2009 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RLW reactors are components designed to improve the reliability
Distribution Dry Type Transformers
8 TRASFORMERS Distribution Dry Type Transformers Table (Contact Sales office for List Price) (commonly used) 1a. 115 C Rise F 1b. 80 C Rise B 4. Wall Brackets1 W 6. Low noise XdB below std. LX Type bg
Evaluating Water-Damaged Electrical Equipment
Evaluating Water-Damaged Electrical Equipment 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been exposed to water through flooding, fire
ABB ! CAUTION. Type COQ Negative Sequence Generator Relay. (50/60 Hertz) 41-161J. Instruction Leaflet
ABB Instruction Leaflet 41-161J Effective: May 1997 Supersedes I.L. 41-161H Dated July 1984 ( ) Denotes Change Since Previous Issue Type COQ Negative Sequence Generator Relay (50/60 Hertz)! CAUTION Before
Power-Zone 4 Arc Resistant Low Voltage Switchgear
Power-Zone 4 Arc Resistant Low Voltage Switchgear with ArcBlok Technology Make the most of your energy SM Workplace safety 2 I Power-Zone 4 Arc Resistant Low Voltage Switchgear Five to ten arc flash explosions
-1- SPECIFICATIONS 002085 CONE SETTER PLATFORM ATTACHMENT INDEX
-1-002085 CONE SETTER PLATFORM ATTACHMENT INDEX I. GENERAL EQUIPMENT : A. Intent Statement B. Cone Setter Platform II. III. 1. Understructure Frame 2. Mounting Components 3. Paint 4. Basket 5. Labels 6.
ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS
Prepared by: ABB1 ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS 052521 Asset Type: Electric Metering Function: Construction Issued by: Quoc Hoang (QxH1) Date: 07-01-16 Rev. #06: This document
AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle
Scope This specification stipulates the minimum requirements for mechanically linked three-phase electronic sectionalizers, for use on outdoor medium voltage overhead lines of 15, 27, and 38 kv. Electronic
MCC Ratings. Voltage Rating
MCC Ratings In addition to the various ratings of individual components used in motor control centers, the overall ratings of the motor control center must also be considered. Voltage Rating Motor control
SECTION 16426C ARC RESISTANT DRAWOUT SWITCHGEAR (MAGNUM DS) LOW VOLTAGE
ARC RESISTANT DRAWOUT SWITCHGEAR (MAGNUM DS) LOW VOLTAGE PART 1 GENERAL 1.01 1.02 1.03 1.04 SCOPE The Contractor shall furnish and install, where indicated on the drawings, a deadfront type, arc resistant