Lateral load testing and analysis of manufactured homes

Size: px
Start display at page:

Download "Lateral load testing and analysis of manufactured homes"

Transcription

1 Lateral load testing and analysis of manufactured homes Koerner, Brian D. 1, Schmidt, Richard J. 2, Goodman, James R. 3, and Richins, William D. 4 ABSTRACT The lateral-load behavior of a single-wide manufactured home was studied by both experimental and numerical methods. Experimental testing consisted of the application of lateral loads using a pressurized air bag. The response of the home was measured with a detailed instrumentation package. A finite element model of the home was built to predict the behavior of the structure under these loads. The results from the full-scale tests were used to validate the finite element model. This research demonstrates that the finite element method can be effectively applied to the analysis of manufactured homes to predict both global and local behavior mechanisms. However, physical testing of components and interfaces from the home is needed to provide reliable data for the analysis model. INTRODUCTION The research reported in this paper is the result of a joint effort by researchers at the University of Wyoming (UW), the Idaho National Engineering and Environmental Laboratory (INEEL), and EDM International (a structural engineering consulting firm in Ft. Collins, CO). The INEEL and the Manufactured Housing Institute (MHI) sponsored this research program to address the nation s need to improve the ability of manufactured housing to withstand high winds. INEEL, UW, EDM, and MHI teamed together to perform a series of full-scale static load tests and structural analyses on a singlewide manufactured home. The tests provided information to advance the process of structural modeling and simulation of manufactured housing subjected to high winds. With data from the full-scale tests, the research team has developed and calibrated finite element modeling techniques for eventual use in the design and analysis of improved manufactured housing. This paper includes a brief review of the lateral-load test program, a description of the finite element model, and a comparison of the finite element results with those from the experimental tests. Additional details of the full-scale tests can be found in a companion paper (Richins, et al, 2) and in the complete test report (Richins et al, 1999). A more general overview of the research effort, as well as an examination of research needs in the area of affordable housing is contained in (Schmidt et al, 2). A detailed report of the finite element analysis is contained in (Schmidt et al, 1999). LATERAL LOAD TESTS A structurally complete manufactured home was tested using uniformly distributed and concentrated loads. The purpose of these tests was to measure displacements and forces on the home and its structural components at design-level lateral loads, such as those due to wind. The forces and displacements consist of tiedown strap forces, global displacements, slip at the interface between components, and wall and ceiling racking deformations. A 14 ft by 62 ft (4.3 m by 18.9 m) single-wide home, manufactured by Oakwood Homes of Fort Morgan, CO, was installed and tested at EDM s research facility in Ft. Collins, CO. The home was installed on concrete masonry piers and anchored using steel tiedown straps to a concrete footing according to manufacturer s recommendations. A floor plan of the home is shown in Figure 1. 1 Structural Engineer, Nelson Engineering, Jackson, WY 832 USA 2 Professor, Dept. of Civil and Architectural Engineering, University of Wyoming, Laramie, WY 8271 USA 3 Research Professor, Dept. of Civil and Architectural Engineering, University of Wyoming, Laramie, WY 8271 USA 4 Idaho National Engineering and Environmental Lab, Idaho Falls, ID 834 USA

2 Figure 1 Floor plan of the test home Inside the home, scissors trusses formed a cathedral ceiling over the central portion of the home, including the kitchen, living room, and dining room. All other areas of the home had a flat ceiling with horizontal bottom chord trusses. Longitudinal walls support the roof trusses. The home contained two shear walls, one at each end wall, and several interior partition walls (see Fig. 1). Shear walls and partition walls are similar in materials and assembly, but differ in the way they are placed in the home during construction. A partition wall is nailed to the floor and ceiling to provide a divider between rooms. Partition walls may be placed on the floor sheathing, between joists. Since a shear wall is intended to distribute the lateral force in the home, it is always located over a floor joist. Also, it is attached to the floor using lag bolts and nails. The spacing between fasteners in shear walls is smaller than that in partition walls. All walls are sheathed with gypsum board on the inside of the home. Exterior walls have gypsum board on the interior surface with exterior siding on the other side. The gypsum board wall sheathing and oriented strand board (OSB) floor sheathing are attached to the wood framing members using glue and staples. The glue provides a rigid attachment of the sheathing to its frame and contributes to increased stiffness and improved serviceability by reducing cracking in walls and along component interfaces. Staples are used to provide short term attachment of the sheathing panels until the glue cures. The floor system of the manufactured home consists of several different parts. A conventionally framed floor joist system is placed on two steel beams used as chassis rails that run the full length of the home. Perpendicular to these chassis rails are outriggers. The outriggers provide support for the floor system and transfer the load from the floor to the chassis rails, which in turn are supported by concrete masonry piers and anchored by steel tiedown straps. Three air bag tests were performed. The first air bag test was performed to check out the instrumentation system and remove initial slack from the building. Next, the tiedown straps were pretensioned and a second test was performed. For the third test, greased steel plates were placed between the chassis rails and the masonry piers to act as bearings. The objective of this change in the installation was to reduce the friction between the chassis and the piers, thus improving the ability to do computer modeling. The second air bag test is referred to here as the high friction test and the third test, with the greased bearing plates, is referred to as the low friction test. Both of these tests involved monotonic ramp loading up to approximately 3 psf (1.44 kpa) of air bag pressure. Instrumentation focused on four response mechanisms: tiedown strap forces, global displacements, wall racking, and component interface slip. Figure 2 shows a typical cross section of the home with instrumentation. Global displacements of the home at this section, which happened to be at the tongueend of the home, were recorded with LVDTs on channels 9, 1, 11, and 12 of the data acquisition system. Global displacements were measured at six such sections along the length of the home. Also at the section Figure 2 - Typical cross section with instrumentation

3 shown, shear wall racking was measured by channel 33 using a cable extensiometer with an extension wire, and wall to wall interface slip was recorded on channels 8 and 6 with linear potentiometers. Ceiling-to-wall interface slip was measured on channels 4 and 6, while channels 46 and 48 measured wall-to-floor interface slip. Finally, tiedown straps extended from the top of the chassis rail on the windward side of the home to the base of the airbag support frame. Each tiedown strap was attached to a load cell, such as that on channel 16 (Fig. 2), for direct measurement of strap force. Tiedown straps were spaced at 1 ft (3. m) intervals along the length of the home; masonry piers were placed at 8 ft (2.4 m) intervals. FINITE ELEMENT MODEL The finite element mesh for the manufactured home, shown in Fig. 3, contained 3693 nodes and 219 elements. Quadratic (8-node) orthotropic shell elements were used to model the individual wall, floor, and ceiling components of the structure. Since these components in a manufactured home consist of OSB panels, wood framing, and gypsum board, fastened with rigid glue and staples, full composite behavior of these subassemblies can be assumed; this assumption has been verified by physical tests (Goodman and Klasi, 1996). The model also includes space truss elements for the roof framing and tiedown straps, and 3-node Lagrangian space frame elements for the chassis rails and outriggers. Finally, the interface (connection) between the individual components is modeled with specially designed link elements. The link elements model the inelastic interface between shell elements and retain displacement compatibility with the shells. The link element, shown in Fig. 4, contains six nodes, each with four degrees of freedom (three translations and one rotation). To reduce model complexity, the finite element model was laid out on a regular grid, upon which the node points were located. To align structural components to this grid, it was necessary to shift the locations of some components as well as door and window openings. Grid spacing was 2. ft (.61 m) in the x and z directions (in the horizontal plane) and 1. ft (.46 m) in the y direction (vertically). This grid spacing was chosen based on a convergence study performed in previous research (Jablin and Schmidt, 1996). The models were analyzed using FINITE, a general-purpose structural analysis system for static and dynamic, nonlinear analysis (Dodds and Lopez, 198). Linear analyses were performed in this research. Since the physical testing of components and joints is still pending, material properties for the various finite elements were based on estimates from previous work (Jablin, 199; Creighton, 1997). In those studies, data for the orthotropic shell elements was generated from a laminate theory for the wall, floor, and ceiling components. Link element properties were taken from physical test data of mocked-up joint specimens. Properties for the other elements were selected as typical for the materials used in their construction. Complete tables of the material property data used in this study can be found in (Schmidt et al, 1999). The finite element model was analyzed for two sets of material properties in a limited parameter study to examine the effects of changing material properties. The first analysis used material properties from previous research, as described above. In the second analysis, wall, floor, and ceiling elements were stiffened to reduce deflections in the model. In the first analysis, exterior walls, partition walls, and shear walls all had different properties. For the second analysis, all walls were given the same properties. The partition wall material stiffnesses were increased by two orders of magnitude and used for all wall elements. Properties of the links, floor, and ceiling were not changed. These modified properties were chosen arbitrarily to examine the sensitivity of the model to changes in material stiffness. The modified properties do not represent any specific construction material or method. Figure 3 Manufactured home finite element mesh Wall - shell element Interface - link element 4 6 Floor - shell element (a) Component interface (b) Link element Figure 4 - Detail of interface between components

4 In the full-scale tests, two different support conditions were examined. For the first support condition, the manufactured home was placed on concrete masonry piers, as in a conventional installation. During the physical tests with the highfriction support conditions, the piers were observed to tip slightly under lateral load. No attempt was made to model friction or tipping of the piers. The second support condition involved use of greased plates between the home and the piers. The greased plates were intended to reduce friction between the home and the piers, thus enabling simplified modeling that did not include friction or tipping of the piers. The second of these two support conditions was modeled by finite elements using simulated roller supports beneath the chassis rails at the pier locations. COMPARISON OF RESULTS In this section, results of two finite element analyses are compared to those from the lateral load tests. In the comparisons that follow, the labels High Friction and Low Friction identify the experimental results. The labels FEM and FEM Modified identify the initial and the second analyses, respectively. Again, the initial analysis used material properties from previous research and the second analysis used properties with artificially high stiffness for the wall elements. Global Displacements The global displacements from the high-friction test and finite element analyses are shown in Fig.. The global displacements during the full-scale testing involved two distinct parts: rigid-body translation and racking deformation. The rigid-body translation can be attributed to flexibility (initial slack) in the tiedown system. During installation of the home, a steel strap was wrapped in a coil around a steel pin to secure the system. As lateral load was introduced into the system, the coil was tightened around the steel pin allowing the strap to lengthen under relatively low load. The manufactured home continued to translate until the steel strap was wrapped tightly against the pin. No attempt was made with the finite element model to represent slack or initial gaps in the foundation system. Instead, the finite element model responded immediately to load by deformation of the home. Therefore, when comparing the displacements of the fullscale tests to the computer model, it is necessary to compare only the response quantities associated with deformation response of the home. Global Displacement Displacement (inches) High Friction, Bottom Transducer, 3 psf FEM, Top Tansducers, 3 psf FEM Mod., Top Transducers, 3 psf 4 3 Station (inches) High Friction, Top Transducer, 3 psf FEM, Bottom Transducers, 3 psf FEM Mod., Bottom Transducers, 3 psf 2 1 Figure Global Displacements

5 Examination of Fig. shows that the racking deflection, given by the difference between the displacements measured by the top transducers and those measured by the bottom transducers, is reasonably well predicted by the initial finite element model. The modified finite element model, with its artificially high wall stiffnesses, substantially under predicts global racking deformation. In the test at station 12, the top transducer recorded less horizontal displacement than the bottom transducer. This behavior was observed in both the high-friction and the low-friction tests. The reason for this anomalous behavior is not known. However, several possibilities exist, including localized flexibility in the floor diaphragm due to a splice in the chord, placement of the partition wall at that location between two floor joists, or some initial gaps between components that may have contributed to unusual flexibility at that location. Tiedown Strap Forces The tiedown forces are shown in Fig. 6. Results from the FEM contained higher values than were observed during the low friction test. This can be attributed to the friction that still existed in the full-scale test. Even in the low friction test with the greased plates, there is still some strap force lost to friction. In the physical tests, the total lateral load on the building was 13,9 lb (62.1 kn). The total horizontal component of the strap forces was 69 lb (3.7 kn) in the highfriction test and 12,2 lb (4.3 kn) in the low-friction test. Hence, about 13% of the horizontal load on the building was resisted by pier friction in the low-friction test. In some cases, the modified FEM exhibited higher strap forces than the original FEM. While in other cases, it was just the opposite. As with the comparison to global displacements, the initial FEM analysis more accurately predicted strap forces than the modified analysis. 3 Strap Forces 3 Air Bag Load (psf) Strap Force (lbs) Channel 2 Channel 3 Channel 4 Channel Channel 6 Channel 7 Channel Ch. 2 FEM Ch. 3 FEM Ch. 4 FEM Ch. FEM Ch. 6 FEM Ch. 7 FEM Ch. 8 FE Figure 6 Tiedown Strap Forces Wall Racking As expected, increasing the stiffness in the walls decreases the racking strains. Some walls in the finite element model exhibit close to the same racking strain as was found experimentally. Nevertheless, it is imperative to look at the slope of the load-deflection plots, rather than the specific data points at 3 psf (1.44 kpa). A majority of the data obtained from the full-scale tests displays little response until the lateral load reached from psf (.24 kpa) to 1 psf (.48 kpa). This is due to the slack in the system. The FEM contains no such slack, so it responds immediately to load. Hence, the slopes of the lines are better indicators of model performance than are the data values themselves. The racking strains in the front shear wall (at the tongue end of the home) are shown in Fig. 7. Those in the kitchen partition wall at station 482 are shown in Fig. 8. In both cases, the initial analysis greatly over-predicts wall racking, even though global displacements are reasonably accurate. This suggests a mismatch in material properties between the wall elements and the component interfaces. Certainly, physical testing is needed to develop appropriate material properties for these components.

6 3 Channel 33 Front Shear Wall At Sta '-" Racking Strain 3 Lo ad (ps f) Strain (in/in) Low Friction High Friction FEM FEM Modified Figure 7 Front Shear Wall Racking Strains 3 Channel 3 Kitchen Wall At Sta 4'-2" Racking Strain 3 Load (psf) Strain (in/in) Low Friction High Friction FEM FEM Modified Figure 8 Partition Wall Racking Strains Interface Slip Interface slip results for the high-friction and low-friction tests were nearly identical. Prediction of interface slip by finite element analysis was reasonably successful, considering the small contribution made to overall response by the interfaces. The initial analysis resulted in good matches to measured response. Since it stiffened the walls of the structure and not the interfaces, the modified analysis produced markedly higher slips than did the initial analysis. In many cases, such as the response shown in Fig. 9, the interface responded to load immediately. In others, such as that in Fig. 1, no interface slip occurred until a relatively high lateral load was on the building. This suggests that a static friction mechanism in the interface had to be overcome before the interface could respond to load. Precompression between two components, caused by tightly installed lag screws, could cause such a mechanism.

7 3 Channel Master Bedroom Wall (Sta. 62'-") - Ceiling Interface Slip 3 Load (psf) Displacement (in) Low Friction High Friction FEM FEM Modified Figure 9 Master Bedroom Wall Interface Slip 3 Channel 8 Bedroom #2 - South W all Interface Slip 3 Load (psf) Displacem ent (in) Low Friction High Friction FEM FEM Modified Figure 1 Bedroom #2 Wall Interface Slip CONCLUSIONS The full-scale tests of the manufactured home provided excellent results. The tests provided accurate data, produced in a controlled laboratory setting. The data yielded plots that aided in finite element model refinement and verification. After testing this home, it is apparent that some of the channels can be moved to other locations to record potentially significant response. For instance, the research team did not instrument the building to measure interface separation. Only slip along the interface was monitored. Separation of one component from another due to tension across the interface could also be significant at certain locations on shear walls. Several trends can be seen in this data. It is apparent that interface slip is not affected by the pier support conditions. This is important to consider when modeling the manufactured home in a finite element program. Even though the chassis rail and piers may have a high coefficient of friction between them, this friction had little effect on interface slip.

8 Therefore, if a model is analyzed and interface slip output is desired, boundary conditions should not be a major concern. Also, the largest racking strain was.333. If one were to assume a nominal value of 9, psi (62 MPa) as the shear modulus for the shear wall, this strain would correspond to a shear stress of approximately 3 psi (27 kpa). Once again, this result was the same for both the high-friction and low-friction tests. This reinforces the conclusion that internal deformation, and hence forces, are not highly dependent on external boundary conditions. As expected, boundary conditions had a big influence on global displacements. The home moved twice as far horizontally during the low friction test than the high friction test. Finite element analysis of a manufactured home to obtain both global and localized response is feasible for manufactured homes. However, better component and interface data is needed in order to seed the model. Additional parameter studies are needed to identify which material parameters create the greatest sensitivity. Then physical testing can be emphasized in those key areas. ACKNOWLEDGEMENTS The United States Department of Energy under DOE Idaho Operations Office, Contract DE-AC7-99ID13727, sponsored this work. Financial support received from the Manufactured Housing Institute is also acknowledged. The leadership and guidance of Frank Walter, Technical Director of the MHI is also greatly appreciated. REFERENCES Creighton, John, Finite Element Structural Analysis for Manufactured Homes Under Lateral Loading, Master of Science Thesis for Colorado State University. Dodds, Robert H., and Lopez, L. A., 198. "A Generalized Software System for Nonlinear Analysis," Advance Engineering Software, Vol. 2, No. 4, ppg Goodman, James R.; Klasi, Melvin L., Testing of Wall Stiffness in the Crownpointe Manufactured Home, South Dakota School of Mines & Technology, February. Jablin, M. C. and Schmidt, R. J., 1996 Finite Element Modeling of Manufactured Homes, Proceedings, International Wood Engineering Conference, Vol. 3, pp , New Orleans, LA October. Jablin, Mark C., 199. Finite Element Modeling of Manufactured Homes Using Interface Elements, Master of Science Thesis for University of Wyoming. Richins, W. D., Lacy, J. M., Larson, T. K., Rahl, T. E., Goodman, J. R., Schmidt, R. J., Koerner, B. D., & Pandey, A. K., 2. Full-Scale Structural Testing of a Single-Wide Manufactured Home, Proceedings World Conference on Timber Engineering, 31 July 3 Aug. Richins, W. D., Rahl, T. E., Lacy, J. M., Larson, T. K., Flood, M. N., Goodman, J. R., Schmidt, R. J., Koerner, B. D., Pandey, A. K., Stewart, A. H., and Walters, F "Full-Scale Structural Testing of a Single-Wide Manufactured Home, Oakwood Model 132; 13ft x 62ft," INEEL Test Report, INEEL/EXT , March. Schmidt, R. J., Koerner, B. D. and Goodman, J. R Methods for Manufactured Home Testing and Analysis, Contract Report, Contract Report to Idaho National Engineering and Environmental Laboratory, Idaho Falls, ID and Manufactured Housing Institute, Arlington, VA, Dec. Schmidt, R. J., Goodman, J. R., Richins, W. D., and Pandy, A., 2. Improved Design of Manufactured Homes for Hazardous Winds, Proceedings World Conference on Timber Engineering, 31 July 3 Aug.

POST AND FRAME STRUCTURES (Pole Barns)

POST AND FRAME STRUCTURES (Pole Barns) POST AND FRAME STRUCTURES (Pole Barns) Post and frame structures. The following requirements serve as minimum standards for post and frame structures within all of the following structural limitations:

More information

Chapter 6 ROOF-CEILING SYSTEMS

Chapter 6 ROOF-CEILING SYSTEMS Chapter 6 ROOF-CEILING SYSTEMS Woodframe roof-ceiling systems are the focus of this chapter. Cold-formed steel framing for a roof-ceiling system also is permitted by the IRC but will not be discussed;

More information

Introduction to Solid Modeling Using SolidWorks 2012 SolidWorks Simulation Tutorial Page 1

Introduction to Solid Modeling Using SolidWorks 2012 SolidWorks Simulation Tutorial Page 1 Introduction to Solid Modeling Using SolidWorks 2012 SolidWorks Simulation Tutorial Page 1 In this tutorial, we will use the SolidWorks Simulation finite element analysis (FEA) program to analyze the response

More information

bi directional loading). Prototype ten story

bi directional loading). Prototype ten story NEESR SG: Behavior, Analysis and Design of Complex Wall Systems The laboratory testing presented here was conducted as part of a larger effort that employed laboratory testing and numerical simulation

More information

Optimum proportions for the design of suspension bridge

Optimum proportions for the design of suspension bridge Journal of Civil Engineering (IEB), 34 (1) (26) 1-14 Optimum proportions for the design of suspension bridge Tanvir Manzur and Alamgir Habib Department of Civil Engineering Bangladesh University of Engineering

More information

The elements used in commercial codes can be classified in two basic categories:

The elements used in commercial codes can be classified in two basic categories: CHAPTER 3 Truss Element 3.1 Introduction The single most important concept in understanding FEA, is the basic understanding of various finite elements that we employ in an analysis. Elements are used for

More information

4B-2. 2. The stiffness of the floor and roof diaphragms. 3. The relative flexural and shear stiffness of the shear walls and of connections.

4B-2. 2. The stiffness of the floor and roof diaphragms. 3. The relative flexural and shear stiffness of the shear walls and of connections. Shear Walls Buildings that use shear walls as the lateral force-resisting system can be designed to provide a safe, serviceable, and economical solution for wind and earthquake resistance. Shear walls

More information

Numerical modelling of shear connection between concrete slab and sheeting deck

Numerical modelling of shear connection between concrete slab and sheeting deck 7th fib International PhD Symposium in Civil Engineering 2008 September 10-13, Universität Stuttgart, Germany Numerical modelling of shear connection between concrete slab and sheeting deck Noémi Seres

More information

STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM

STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM Chapter 9 STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM 9.1 BACKGROUND Steel is widely used in the construction of multi-storey buildings. However, steel construction is seldom used and is traditionally

More information

Wisconsin Building Products Evaluation

Wisconsin Building Products Evaluation Safety & Buildings Division 201 West Washington Avenue P.O. Box 2658 Madison, WI 53701-2658 Evaluation # 200813-O Wisconsin Building Products Evaluation Material Best Management Standards for Foundation

More information

4.3.5 - Breakaway Walls

4.3.5 - Breakaway Walls 4.3.5 - Breakaway Walls Elevation of a structure on a properly designed foundation reduces the potential for water damage from flooding. When the space below the lowest elevated floor is maintained free

More information

Post and Beam Construction

Post and Beam Construction Post and Beam Construction A Presentation By the Canadian Wood Council Canadian Conseil Wood canadien Council du bois Early settlers introduced the concept of post and beam construction in North America

More information

6 RETROFITTING POST & PIER HOUSES

6 RETROFITTING POST & PIER HOUSES Retrofitting Post & Pier Houses 71 6 RETROFITTING POST & PIER HOUSES by James E. Russell, P.E. 72 Retrofitting Post & Pier Houses Retrofitting Post & Pier Houses 73 RETROFITTING POST AND PIER HOUSES This

More information

Chapter 36 - STRAW BALE CONSTRUCTION SECTION 3601 - PURPOSE. SECTION 3602 - SCOPE. SECTION 3603 - DEFINITIONS.

Chapter 36 - STRAW BALE CONSTRUCTION SECTION 3601 - PURPOSE. SECTION 3602 - SCOPE. SECTION 3603 - DEFINITIONS. Austin City Code - Volume II TITLE 25 LAND DEVELOPMENT\CHAPTER 25-12 TECHNICAL CODES\ARTICLE 1: UNIFORM BUILDING CODE\25-12-3 LOCAL AMENDMENTS TO THE BUILDING CODE Chapter 36 - STRAW BALE CONSTRUCTION

More information

Mark Cramer Inspection Services, Inc.

Mark Cramer Inspection Services, Inc. Mark Cramer Inspection Services, Inc. 492 Twentieth Avenue, Indian Rocks Beach, FL 34635-2970 (727) 595-4211 Fax (727) 596-7583 Certified Member #12085 American Society of Home Inspectors Construction

More information

COMPUTATIONAL ENGINEERING OF FINITE ELEMENT MODELLING FOR AUTOMOTIVE APPLICATION USING ABAQUS

COMPUTATIONAL ENGINEERING OF FINITE ELEMENT MODELLING FOR AUTOMOTIVE APPLICATION USING ABAQUS International Journal of Advanced Research in Engineering and Technology (IJARET) Volume 7, Issue 2, March-April 2016, pp. 30 52, Article ID: IJARET_07_02_004 Available online at http://www.iaeme.com/ijaret/issues.asp?jtype=ijaret&vtype=7&itype=2

More information

Design of Cold-Formed Steel Shear Walls

Design of Cold-Formed Steel Shear Walls DESIGN GUIDE 2 Design of Cold-Formed Steel Shear Walls March 1998 The following publication was developed by R.L. Brockenbrough & Associates for the American Iron and Steel Institute (AISI), In the production

More information

Retrofitting By Means Of Post Tensioning. Khaled Nahlawi 1

Retrofitting By Means Of Post Tensioning. Khaled Nahlawi 1 Retrofitting By Means Of Post Tensioning Khaled Nahlawi 1 Abstract An analytical program was prepared to retrofit the Holy Cross Church in Santa Cruz, California. An inelastic analysis was perfonned on

More information

Section A Roof Truss

Section A Roof Truss Section A Roof Truss Truss Types Wisconsin Truss, Inc. can build a variety of truss types, pictured below are some common examples. Common Bobtail Scissor Mono Studio Dual Slope Cathedral Tray Vault Parallel

More information

Perforated Shearwall Design Method 1

Perforated Shearwall Design Method 1 Perforated Shearwall Design Method 1 Philip Line, P.E., Bradford K. Douglas, P.E., American Forest & Paper Association, USA Abstract Wood frame shearwalls are traditionally designed using full-height shearwall

More information

Draft Table of Contents. Building Code Requirements for Structural Concrete and Commentary ACI 318-14

Draft Table of Contents. Building Code Requirements for Structural Concrete and Commentary ACI 318-14 Draft Table of Contents Building Code Requirements for Structural Concrete and Commentary ACI 318-14 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE (ACI 318 14) Chapter 1 General 1.1 Scope of ACI 318

More information

ANALYSIS OF A LAP JOINT FRICTION CONNECTION USING HIGH STRENGTH BOLTS

ANALYSIS OF A LAP JOINT FRICTION CONNECTION USING HIGH STRENGTH BOLTS Nordic Steel Construction Conference 212 Hotel Bristol, Oslo, Norway 5-7 September 212 ANALYSIS OF A LAP JOINT FRICTION CONNECTION USING HIGH STRENGTH BOLTS Marouene Limam a, Christine Heistermann a and

More information

Structural Axial, Shear and Bending Moments

Structural Axial, Shear and Bending Moments Structural Axial, Shear and Bending Moments Positive Internal Forces Acting Recall from mechanics of materials that the internal forces P (generic axial), V (shear) and M (moment) represent resultants

More information

National Council of Examiners for Engineering and Surveying. Principles and Practice of Engineering Structural Examination

National Council of Examiners for Engineering and Surveying. Principles and Practice of Engineering Structural Examination Structural Effective Beginning with the April 2011 The structural engineering exam is a breadth and exam examination offered in two components on successive days. The 8-hour Vertical Forces (Gravity/Other)

More information

Bracing Webs in Trusses that have Dissimilar Configurations

Bracing Webs in Trusses that have Dissimilar Configurations Bracing Webs in Trusses that have Dissimilar Configurations Released April 25, 2006 Issue: Truss Design Drawings (TDD) that are prepared in accordance with ANSI/TPI 1, National Design Standard for Metal

More information

Finite Element Method (ENGC 6321) Syllabus. Second Semester 2013-2014

Finite Element Method (ENGC 6321) Syllabus. Second Semester 2013-2014 Finite Element Method Finite Element Method (ENGC 6321) Syllabus Second Semester 2013-2014 Objectives Understand the basic theory of the FEM Know the behaviour and usage of each type of elements covered

More information

Timber Frame Construction

Timber Frame Construction Timber Frame Construction Introduction Design and Detailing What is timber? Failure modes History of timber frame construction Forms of timber frame construction Live and dead loads Wind loads Roof construction

More information

1997 Uniform Administrative Code Amendment for Earthen Material and Straw Bale Structures Tucson/Pima County, Arizona

1997 Uniform Administrative Code Amendment for Earthen Material and Straw Bale Structures Tucson/Pima County, Arizona for Earthen Material and Straw Bale Structures SECTION 70 - GENERAL "APPENDIX CHAPTER 7 - EARTHEN MATERIAL STRUCTURES 70. Purpose. The purpose of this chapter is to establish minimum standards of safety

More information

4. ANCHOR BOLTS AND STRAPS a. ½" anchor bolts shall be embedded 7" into concrete a maximum of 6' on center and 12" from corners and ends of plates.

4. ANCHOR BOLTS AND STRAPS a. ½ anchor bolts shall be embedded 7 into concrete a maximum of 6' on center and 12 from corners and ends of plates. GENERAL CODE REQUIREMENTS (BASEMENTS) 1. FOOTINGS a. Footings shall be below frost line depth (42"). b. For an 8" foundation wall, footings shall be no less than 8" deep and 16" wide. c. Steel reinforcement

More information

Walls. Add Strength and Water Resistance When Repairing Your. Replace damaged framing members when walls are open

Walls. Add Strength and Water Resistance When Repairing Your. Replace damaged framing members when walls are open Add Strength and Water Resistance When Repairing Your Walls Any home repair or remodeling work you do presents an opportunity to make your home fare better in the next storm. Whether you are just replacing

More information

CF-Mesa, CF-Light Mesa, CF-Flute, CF-Metl-Plank, CF-Striated, CF-Santa Fe, CF-Architectural Flat, CF...

CF-Mesa, CF-Light Mesa, CF-Flute, CF-Metl-Plank, CF-Striated, CF-Santa Fe, CF-Architectural Flat, CF... Building Insulations - Walls and Ceilings (FM Approval Numbers 4411, 4651, 4880, 4881, 4882) Insulating materials may occur in building construction to reduce heat or sound transmission through a wall,

More information

METHODS FOR ACHIEVEMENT UNIFORM STRESSES DISTRIBUTION UNDER THE FOUNDATION

METHODS FOR ACHIEVEMENT UNIFORM STRESSES DISTRIBUTION UNDER THE FOUNDATION International Journal of Civil Engineering and Technology (IJCIET) Volume 7, Issue 2, March-April 2016, pp. 45-66, Article ID: IJCIET_07_02_004 Available online at http://www.iaeme.com/ijciet/issues.asp?jtype=ijciet&vtype=7&itype=2

More information

Formwork for Concrete

Formwork for Concrete UNIVERSITY OF WASHINGTON DEPARTMENT OF CONSTRUCTION MANAGEMENT CM 420 TEMPORARY STRUCTURES Winter Quarter 2007 Professor Kamran M. Nemati Formwork for Concrete Horizontal Formwork Design and Formwork Design

More information

Compression load testing straw bale walls. Peter Walker Dept. Architecture & Civil Engineering University of Bath Bath BA2 7AY.

Compression load testing straw bale walls. Peter Walker Dept. Architecture & Civil Engineering University of Bath Bath BA2 7AY. Compression load testing straw bale walls Peter Walker Dept. Architecture & Civil Engineering University of Bath Bath BA2 7AY May 2004 1. Introduction Over the last 10 years a growing number of loadbearing

More information

Beginning on Friday, Jan 22, and on subsequent investigations, the following issues were identified:

Beginning on Friday, Jan 22, and on subsequent investigations, the following issues were identified: Date: 2/15/2016 Project: To: Middleton Public Library Roof Repair Pamela K. Westby Library Director Middleton Public Library 7425 Hubbard Avenue Middleton WI 53562 Pamela, Strategic Structural Design,

More information

Validation of Cable Bolt Support Design in Weak Rock Using SMART Instruments and Phase 2

Validation of Cable Bolt Support Design in Weak Rock Using SMART Instruments and Phase 2 Validation of Cable Bolt Support Design in Weak Rock Using SMART Instruments and Phase 2 W.F. Bawden, Chair Lassonde Mineral Engineering Program, U. of Toronto, Canada J.D. Tod, Senior Engineer, Mine Design

More information

In-situ Load Testing to Evaluate New Repair Techniques

In-situ Load Testing to Evaluate New Repair Techniques In-situ Load Testing to Evaluate New Repair Techniques W.J. Gold 1 and A. Nanni 2 1 Assistant Research Engineer, Univ. of Missouri Rolla, Dept. of Civil Engineering 2 V&M Jones Professor, Univ. of Missouri

More information

CH. 2 LOADS ON BUILDINGS

CH. 2 LOADS ON BUILDINGS CH. 2 LOADS ON BUILDINGS GRAVITY LOADS Dead loads Vertical loads due to weight of building and any permanent equipment Dead loads of structural elements cannot be readily determined b/c weight depends

More information

Eurocode 5: Design of timber structures

Eurocode 5: Design of timber structures Eurocode 5: Design of timber structures Arnold Page, BSc, BD, MIWSc. Structural timber engineering consultant Introduction BS EN 1995 consists of three parts: Part 1-1: General. Common rules and rules

More information

CHAPTER 4 4 NUMERICAL ANALYSIS

CHAPTER 4 4 NUMERICAL ANALYSIS 41 CHAPTER 4 4 NUMERICAL ANALYSIS Simulation is a powerful tool that engineers use to predict the result of a phenomenon or to simulate the working situation in which a part or machine will perform in

More information

UL 580 TEST REPORT. Rendered to: ARMSTRONG WORLD INDUSTRIES. SERIES/MODEL: MW Vector PRODUCT TYPE: Ceiling System, 3' OC

UL 580 TEST REPORT. Rendered to: ARMSTRONG WORLD INDUSTRIES. SERIES/MODEL: MW Vector PRODUCT TYPE: Ceiling System, 3' OC UL 580 TEST REPORT Rendered to: ARMSTRONG WORLD INDUSTRIES SERIES/MODEL: MW Vector PRODUCT TYPE: Ceiling System, 3' OC Report No.: Test Dates: 12/14/09 Through: 12/22/09 Report Date: 03/12/10 Expiration

More information

Expected Performance Rating System

Expected Performance Rating System Expected Performance Rating System In researching seismic rating systems to determine how to best classify the facilities within the Portland Public School system, we searched out what was used by other

More information

Type of Force 1 Axial (tension / compression) Shear. 3 Bending 4 Torsion 5 Images 6 Symbol (+ -)

Type of Force 1 Axial (tension / compression) Shear. 3 Bending 4 Torsion 5 Images 6 Symbol (+ -) Cause: external force P Force vs. Stress Effect: internal stress f 05 Force vs. Stress Copyright G G Schierle, 2001-05 press Esc to end, for next, for previous slide 1 Type of Force 1 Axial (tension /

More information

Lab for Deflection and Moment of Inertia

Lab for Deflection and Moment of Inertia Deflection and Moment of Inertia Subject Area(s) Associated Unit Lesson Title Physics Wind Effects on Model Building Lab for Deflection and Moment of Inertia Grade Level (11-12) Part # 2 of 3 Lesson #

More information

Numerical Analysis of the Moving Formwork Bracket Stress during Construction of a Curved Continuous Box Girder Bridge with Variable Width

Numerical Analysis of the Moving Formwork Bracket Stress during Construction of a Curved Continuous Box Girder Bridge with Variable Width Modern Applied Science; Vol. 9, No. 6; 2015 ISSN 1913-1844 E-ISSN 1913-1852 Published by Canadian Center of Science and Education Numerical Analysis of the Moving Formwork Bracket Stress during Construction

More information

Introduction...COMB-2 Design Considerations and Examples...COMB-3

Introduction...COMB-2 Design Considerations and Examples...COMB-3 SECTION DIRECTORY General Information Introduction...COMB-2 Design Considerations and Examples...COMB-3 Combination Assembly Recommendations and Limitations Composite Configurations...COMB-4 Typical Sealant

More information

DESIGN OF PRESTRESSED BARRIER CABLE SYSTEMS

DESIGN OF PRESTRESSED BARRIER CABLE SYSTEMS 8601 North Black Canyon Highway Suite 103 Phoenix, AZ 8501 For Professionals Engaged in Post-Tensioning Design Issue 14 December 004 DESIGN OF PRESTRESSED BARRIER CABLE SYSTEMS by James D. Rogers 1 1.0

More information

This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.

This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances. Residential Decks Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org

More information

The University of Birmingham (Live System)

The University of Birmingham (Live System) The University of Birmingham (Live System) Behaviour of Structural Insulated Panels (SIPs) under both short-term and long-term loadings Yang, Jian; Rungthonkit, Prathan Document Version Author final version

More information

Featuring TJ Rim Board and TimberStrand LSL

Featuring TJ Rim Board and TimberStrand LSL #TJ-8000 SPECIFIER S GUIDE TRUS JOIST RIM BOARD Featuring TJ Rim Board and TimberStrand LSL Multiple thicknesses, grades, and products to cover all your rim board needs 1¼" Thickness matches lateral load

More information

Handling, Erection and Bracing of Wood Trusses

Handling, Erection and Bracing of Wood Trusses Handling, Erection and Bracing of Wood Trusses Follow these guidelines for safe installation of Wood Trusses. These guidelines should not be considered to be the only method for erecting and bracing of

More information

HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES

HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES 101 Retrofits Required. Pursuant to Section 553.844 553.884, Florida Statutes, strengthening of existing site-built,

More information

INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES. Interpretations of the FTP

INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES. Interpretations of the FTP INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES Interpretations of the FTP CONTENTS FTP1 Adhesives used in A or B class divisions (FTP Code 3.1, Res A.754 para. 3.2.3) June 2000 FTP2 Pipe and duct

More information

Building Construction. Lightweight construction. Conventional Construction

Building Construction. Lightweight construction. Conventional Construction Ventilation 53 Building Construction The firefighter s ability to safely and efficiently ventilate a building through its roof will depend to some degree on the firefighter s understanding of roof construction.

More information

Report on. Wind Resistance of Signs supported by. Glass Fiber Reinforced Concrete (GFRC) Pillars

Report on. Wind Resistance of Signs supported by. Glass Fiber Reinforced Concrete (GFRC) Pillars Report on Wind Resistance of Signs supported by Glass Fiber Reinforced Concrete (GFRC) Pillars Prepared for US Sign and Fabrication Corporation January, 2006 SUMMARY This study found the attachment of

More information

CONSTRUCTION DETAILS & LOAD DESIGN CHARTS

CONSTRUCTION DETAILS & LOAD DESIGN CHARTS Office and Production 126 New Pace Rd., PO Box 279 Newcomerstown, OH 43832 1-800-446-2188, Fax: 740-498-4184 www.buildwithsips.com CONSTRUCTION DETAILS & LOAD DESIGN CHARTS Table of Contents Description

More information

SEISMIC RETROFITTING TECHNIQUE USING CARBON FIBERS FOR REINFORCED CONCRETE BUILDINGS

SEISMIC RETROFITTING TECHNIQUE USING CARBON FIBERS FOR REINFORCED CONCRETE BUILDINGS Fracture Mechanics of Concrete Structures Proceedings FRAMCOS-3 AEDIFICA TIO Publishers, D-79104 Freiburg, Germany SEISMIC RETROFITTING TECHNIQUE USING CARBON FIBERS FOR REINFORCED CONCRETE BUILDINGS H.

More information

EFFECTS ON NUMBER OF CABLES FOR MODAL ANALYSIS OF CABLE-STAYED BRIDGES

EFFECTS ON NUMBER OF CABLES FOR MODAL ANALYSIS OF CABLE-STAYED BRIDGES EFFECTS ON NUMBER OF CABLES FOR MODAL ANALYSIS OF CABLE-STAYED BRIDGES Yang-Cheng Wang Associate Professor & Chairman Department of Civil Engineering Chinese Military Academy Feng-Shan 83000,Taiwan Republic

More information

INTRODUCTION TO BEAMS

INTRODUCTION TO BEAMS CHAPTER Structural Steel Design LRFD Method INTRODUCTION TO BEAMS Third Edition A. J. Clark School of Engineering Department of Civil and Environmental Engineering Part II Structural Steel Design and Analysis

More information

Project Report. Structural Investigations Hotel del Sol Yuma, Arizona

Project Report. Structural Investigations Hotel del Sol Yuma, Arizona Project Report Structural Investigations Yuma, Arizona Prepared by: 2619 Spruce Street Boulder, CO 80302 303-444-3620 Prepared for: Principle Engineering Group, Inc. 833 East Plaza Circle, Suite 100 Yuma,

More information

Residential Deck Safety, Construction, and Repair

Residential Deck Safety, Construction, and Repair Juneau Permit Center, 4 th Floor Marine View Center, (907)586-0770 This handout is designed to help you build your deck to comply with the 2006 International Residential Building code as modified by the

More information

Numerical Analysis of Independent Wire Strand Core (IWSC) Wire Rope

Numerical Analysis of Independent Wire Strand Core (IWSC) Wire Rope Numerical Analysis of Independent Wire Strand Core (IWSC) Wire Rope Rakesh Sidharthan 1 Gnanavel B K 2 Assistant professor Mechanical, Department Professor, Mechanical Department, Gojan engineering college,

More information

Chapter 3 Pre-Installation, Foundations and Piers

Chapter 3 Pre-Installation, Foundations and Piers Chapter 3 Pre-Installation, Foundations and Piers 3-1 Pre-Installation Establishes the minimum requirements for the siting, design, materials, access, and installation of manufactured dwellings, accessory

More information

MANUFACTURED HOUSING USED AS DWELLINGS

MANUFACTURED HOUSING USED AS DWELLINGS MANUFACTURED HOUSING USED AS DWELLINGS SECTION AE101 SCOPE AE101.1 General. These provisions shall be applicable only to a manufactured home used as a single dwelling unit and shall apply to the following:

More information

EXPERIMENTAL/NUMERICAL TECHNIQUES FOR AIRCRAFT FUSELAGE STRUCTURES CONTAINING DAMAGE

EXPERIMENTAL/NUMERICAL TECHNIQUES FOR AIRCRAFT FUSELAGE STRUCTURES CONTAINING DAMAGE EXPERIMENTAL/NUMERICAL TECHNIQUES FOR AIRCRAFT FUSELAGE STRUCTURES CONTAINING DAMAGE Abstract Padraic E. O Donoghue, Jinsan Ju Dept. Civil Engineering National University of Ireland Galway, Ireland padraic.odonoghue@nuigalway.ie,

More information

PDmB, Inc. Definitions

PDmB, Inc. Definitions Page 1 of 11 Definitions S Satisfactory Meets industry standards for proper material and installation NP Not Present Condition or item was not present at time of inspection NI Not Inspected Condition or

More information

Laying the First Course. 1. Excavate the site and construct the footing.

Laying the First Course. 1. Excavate the site and construct the footing. Use QUIKRETE Mortar Mix or Mason Mix lay up a concrete block wall as shown. QUIKRETE Mortar Mix or Mason Mix Concrete block Mason's line Line blocks 4' level brick trowel Jointer Mason's hammer Stiff brush

More information

LEGACY REPORT. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council. *Corrected March 2014

LEGACY REPORT. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council. *Corrected March 2014 ICC-ES Legacy Report PFC-3700* Issued October 2003 www.icc-es.org (00) 423-57 (52) 99-0543 A Subsidiary of the International Code Council Legacy report on the 1997 Uniform Building Code and the 2000 International

More information

Connection Solutions

Connection Solutions Connection Solutions DESIGN BUILD SYSTEM Connection Solutions for Cold formed Steel Construction Complies with; AS/NZS 4600:2005 AISI S100:2007 AS/NZ 1397 ASTM A653 DESIGN & BUILD SYSTEM FRAMECAD Construction

More information

Back to Elements - Tetrahedra vs. Hexahedra

Back to Elements - Tetrahedra vs. Hexahedra Back to Elements - Tetrahedra vs. Hexahedra Erke Wang, Thomas Nelson, Rainer Rauch CAD-FEM GmbH, Munich, Germany Abstract This paper presents some analytical results and some test results for different

More information

DEVELOPMENT OF A NEW TEST FOR DETERMINATION OF TENSILE STRENGTH OF CONCRETE BLOCKS

DEVELOPMENT OF A NEW TEST FOR DETERMINATION OF TENSILE STRENGTH OF CONCRETE BLOCKS 1 th Canadian Masonry Symposium Vancouver, British Columbia, June -5, 013 DEVELOPMENT OF A NEW TEST FOR DETERMINATION OF TENSILE STRENGTH OF CONCRETE BLOCKS Vladimir G. Haach 1, Graça Vasconcelos and Paulo

More information

SECTION 3 ONM & J STRUCTURAL ANALYSIS

SECTION 3 ONM & J STRUCTURAL ANALYSIS Historic Boynton Beach High School Existing Building Assessment City of Boynton Beach February 10, 2011 SECTION 3 ONM & J STRUCTURAL ANALYSIS STRUCTURAL ENGINEERS SPECIAL INSPECTORS STRUCTURAL CONDITION

More information

Design of Steel Structures Prof. S.R.Satish Kumar and Prof. A.R.Santha Kumar. Fig. 7.21 some of the trusses that are used in steel bridges

Design of Steel Structures Prof. S.R.Satish Kumar and Prof. A.R.Santha Kumar. Fig. 7.21 some of the trusses that are used in steel bridges 7.7 Truss bridges Fig. 7.21 some of the trusses that are used in steel bridges Truss Girders, lattice girders or open web girders are efficient and economical structural systems, since the members experience

More information

Stress Strain Relationships

Stress Strain Relationships Stress Strain Relationships Tensile Testing One basic ingredient in the study of the mechanics of deformable bodies is the resistive properties of materials. These properties relate the stresses to the

More information

PART 1 GENERAL 1.1 SECTION INCLUDES

PART 1 GENERAL 1.1 SECTION INCLUDES J-1 Section 09110 Long Form Specification INTERIOR METAL STUD FRAMING This section includes lightweight, usually 0.036 inch (0.9 mm) thick or lighter, non-axial load bearing metal stud framing including

More information

DESIGN OF SLABS. 3) Based on support or boundary condition: Simply supported, Cantilever slab,

DESIGN OF SLABS. 3) Based on support or boundary condition: Simply supported, Cantilever slab, DESIGN OF SLABS Dr. G. P. Chandradhara Professor of Civil Engineering S. J. College of Engineering Mysore 1. GENERAL A slab is a flat two dimensional planar structural element having thickness small compared

More information

Common Errors in Truss Design

Common Errors in Truss Design In today s competitive world of trusses, component manufacturers are always looking for ways to generate more efficient truss designs. Occasionally, truss designs need to be changed in order to be sealed

More information

Practical Approach to Designing Wood Roof Truss Assemblies

Practical Approach to Designing Wood Roof Truss Assemblies Practical Approach to Designing Wood Roof Truss Assemblies Rakesh Gupta, M.ASCE 1 ; and Pranueng Limkatanyoo2 Abstract: The objective of this research was to use a three-dimensional (3D) analysis method

More information

Protecting Your Home From Hurricane Wind Damage

Protecting Your Home From Hurricane Wind Damage T H E W I N D Protecting Your Home From Hurricane Wind Damage During a hurricane, homes may be damaged or destroyed by high winds and high waves. Debris can break windows and doors, allowing high winds

More information

Seismic Technical Guide

Seismic Technical Guide Technical Document Seismic Technical Guide Hanger Wire Attachment Code Requirements 1 The International Building Code (IBC) defines the requirement for hanger wire and their supports and attachment methods.

More information

Structural Foundation System

Structural Foundation System Structural Foundation System SLABTEK, a technological advancement in foundation designs for residential and lightweight commercial structures SlabTek is a patent allowed process for concrete foundations

More information

CHAPTER 6 CONSTRUCTION TYPES

CHAPTER 6 CONSTRUCTION TYPES CHAPTER 6 CONSTRUCTION TYPES SECTION 601 GENERAL 601.1 Scope. Provisions of this chapter shall govern the classification of construction type by materials and fire resistance of its elements and the use

More information

Guide for SOLID CONCRETE BLOCK SEALS

Guide for SOLID CONCRETE BLOCK SEALS Guide for SOLID CONCRETE BLOCK SEALS July, 2006 Mine Safety and Health Administration SOLID CONCRETE BLOCK SEAL Formersection 30 CFR 75.335(a)(1) specifies requirements for seals constructed using solid

More information

CPA Steel Stud Framing Page 1 of 11

CPA Steel Stud Framing Page 1 of 11 CPA Steel Stud Framing Page 1 of 11 STEEL STUD FRAMING General Requirements City of Palo Alto (CPA) Building Inspection Division 285 Hamilton Ave. Inspection Request: 650 329-2496 Building Division IVR#

More information

Magnetic / Gravity Loading Analysis

Magnetic / Gravity Loading Analysis Magnetic / Gravity Loading Analysis 2 ELEMENTS JUL 7 2006 ELEMENTS MAT NUM 2:5:0 MAT NUM POR Design JUL 7 2006 2:5:0 L2 L L q Assumed Location of Gap Encoder(s) ELEMENTS MAT NUM JUL 7 2006 2:5:0 Materials:

More information

THE DOW CHEMICAL COMPANY Issued: August 1, 2008 200 LARKIN CENTER 1605 JOSEPH DRIVE MIDLAND MICHIGAN 48674 (989) 638-8655 www.dowbuildingmaterials.

THE DOW CHEMICAL COMPANY Issued: August 1, 2008 200 LARKIN CENTER 1605 JOSEPH DRIVE MIDLAND MICHIGAN 48674 (989) 638-8655 www.dowbuildingmaterials. ICC EVALUATION SERVICE, INC. EvaluateP InformP Protect Los Angeles Business/Regional OfficeP 5360 Workman Mill RoadP Whittier, CA 90601 (562) 699-0543 phonep (562) 695-4694 fax DIVISION: Section: 6 WOOD

More information

Seismic analysis of a 2-storey log house Jorge M. Branco a, Paulo B. Lourenço b, Chrysl A. Aranha c

Seismic analysis of a 2-storey log house Jorge M. Branco a, Paulo B. Lourenço b, Chrysl A. Aranha c Seismic analysis of a 2-storey log house Jorge M. Branco a, Paulo B. Lourenço b, Chrysl A. Aranha c ISISE, Department of Civil Engineering, University of Minho, Guimarães, Portugal a jbranco@civil.uminho.pt,

More information

SECTION 7 Engineered Buildings Field Investigation

SECTION 7 Engineered Buildings Field Investigation SECTION 7 Engineered Buildings Field Investigation Types of Data to Be Collected and Recorded A field investigator looking at engineered buildings is expected to assess the type of damage to buildings.

More information

Protecting Your Home from Wind Damage

Protecting Your Home from Wind Damage Protecting Your Home from Wind Damage During severe thunderstorms or hurricanes, homes may be damaged or destroyed by high winds. Debris flying through the air can break windows and doors, allowing high

More information

Engineered, Time-Tested Foundation Repairs for Settlement in Residential and Light Commercial Structures. The Leading Edge.

Engineered, Time-Tested Foundation Repairs for Settlement in Residential and Light Commercial Structures. The Leading Edge. TM TM Engineered, Time-Tested Foundation Repairs for Settlement in Residential and Light Commercial Structures. SM The Leading Edge. 10 One Major Causes of foundation settlement or more conditions may

More information

Residential Decks. Planning and Development Services Department

Residential Decks. Planning and Development Services Department Building Safety Division 8500 Santa Fe Drive Overland Park, KS 66212 (913) 895-6225 Fax (913) 895-5016 Email: permitservices@opkansas.org Planning and Development Services Department Residential Decks

More information

609 West Rock Road, Radford,VA 24141 540-633-5000 / (fax) 540-731-3712 RECOMMENDED ATTACHMENTS & CONNECTION DETAILS

609 West Rock Road, Radford,VA 24141 540-633-5000 / (fax) 540-731-3712 RECOMMENDED ATTACHMENTS & CONNECTION DETAILS 609 West Rock Road, Radford,VA 24141 540-633-5000 / (fax) 540-731-3712 RECOMMENDED ATTACHMENTS & CONNECTION DETAILS INDEX OF DRAWINGS SECTION A: A-1 = METAL TRACK TO PANEL ATTACHMENT A-2 = WOOD PLATE TO

More information

What is Seismic Retrofitting?

What is Seismic Retrofitting? What is Seismic Retrofitting? SEISMIC RETROFITTING A Seismic Retrofit provides existing structures with more resistance to seismic activity due to earthquakes. In buildings, this process typically includes

More information

research report Residential Hip Roof Framing Using Cold-Formed Steel Members RESEARCH REPORT RP06-2 American Iron and Steel Institute

research report Residential Hip Roof Framing Using Cold-Formed Steel Members RESEARCH REPORT RP06-2 American Iron and Steel Institute research report Residential Hip Roof Framing Using Cold-Formed Steel Members RESEARCH REPORT RP06-2 2006 American Iron and Steel Institute Residential Hip Roof Framing Using Cold-Formed Steel Members i

More information

Envelope INSULATION BATT (2) Avoid Using Batt Insulation With Metal Framing. Pressure or Friction Fit

Envelope INSULATION BATT (2) Avoid Using Batt Insulation With Metal Framing. Pressure or Friction Fit R-H-DI1 INSULATION BATT NR-E-IB1 Avoid Using Batt Insulation With Metal Framing Batt insulation should not be used with metal framing systems. Although it is common to see fiberglass batt insulation installed

More information

Guidelines for Earthquake Bracing Residential Water Heaters

Guidelines for Earthquake Bracing Residential Water Heaters Guidelines for Earthquake Bracing Residential Water Heaters Department of General Services Division of the State Architect In accordance with the Health and Safety Code Section 19215, the Division of the

More information

ASTM E 1886 and ASTM E 1996 TEST REPORT. Rendered to: NORSE, INC.

ASTM E 1886 and ASTM E 1996 TEST REPORT. Rendered to: NORSE, INC. Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: NORSE, INC. SERIES/MODEL: Flush Mount/Surface Mount PRODUCT TYPE: Hurricane Shutter Fastening System This report contains in its

More information

For the purposes of this Part, the following words shall have the following meanings:

For the purposes of this Part, the following words shall have the following meanings: LOUISIANA REVISED STATUTES TITLE 51. TRADE AND COMMERCE CHAPTER 2. PARTICULAR GOODS PART XIV-B. MINIMUM STANDARDS FOR INSTALLATION OF MANUFACTURED HOMES Current through all 2010 Regular Session Acts 912.21.

More information

Plates and Shells: Theory and Computation - 4D9 - Dr Fehmi Cirak (fc286@) Office: Inglis building mezzanine level (INO 31)

Plates and Shells: Theory and Computation - 4D9 - Dr Fehmi Cirak (fc286@) Office: Inglis building mezzanine level (INO 31) Plates and Shells: Theory and Computation - 4D9 - Dr Fehmi Cirak (fc286@) Office: Inglis building mezzanine level (INO 31) Outline -1-! This part of the module consists of seven lectures and will focus

More information