1 UL 580 TEST REPORT Rendered to: ARMSTRONG WORLD INDUSTRIES SERIES/MODEL: MW Vector PRODUCT TYPE: Ceiling System, 3' OC Report No.: Test Dates: 12/14/09 Through: 12/22/09 Report Date: 03/12/10 Expiration Date: 12/22/ Derry Court York, PA phone: fax:

2 UL 580 TEST REPORT Rendered to: ARMSTRONG WORLD INDUSTRIES P.O. Box 3511 Lancaster, Pennsylvania Report No.: Test Dates: 12/14/09 Through: 12/22/09 Report Date: 03/12/10 Expiration Date: 12/22/13 Project Summary: Architectural Testing, Inc. was contracted by Armstrong World Industries to perform testing on a Series/Model MW Vector, ceiling system, 3' OC. The test specimen area, measuring 10' x 10', was tested in accordance with Underwriters Laboratories, Inc., Standard for Safety for Tests for Uplift Resistance of Roof Assemblies, UL 580 (Fourth Edition, May 31, 1994). The purpose of this test is to evaluate the comparative resistance of roof assemblies to positive and negative pressures. This test simulates the effects of wind gusts by use of oscillating exterior pressure and constant interior pressures. Reference Chart #1 for test duration times, positive and negative pressures, Photo Nos. 1 and 2 for test equipment, Photo Nos. 3 through 9 for installation, and Sketch #1 for indicator locations. The sample was provided by the client. Test Specimen Description: Series/Model: MW Vector Chamber Construction: The test chamber was constructed of steel C-channel that measured 10' long. The C-channels were stacked and welded to form one side of a four sided chamber that measured 60" deep. Five W6 x 31 steel "I" beams were flush at the top of the chamber and equally spaced, welded at each end to the chamber. 2x6 Spruce-Pine-Fir wood was secured to the underside of the "I" beams with #12 x 2-1/2" long self-drilling Tek-screws, spaced 18" on center. The lumber was attached to the beams to facilitate securing one end of the compression post. The sides of the chamber utilized 2x6 Spruce-Pine-Fir wood, flush with the bottom of the chamber, secured with #12 x 2-1/2" long self-drilling Tek-screws, spaced 18" on center. A bead of silicone was located on the top side of the 2x6, between the steel test chamber and the 2x6 wood. The top closure was provided by the pyramidal shaped UL 580 chamber roof, (reference Photo No. 1). 130 Derry Court York, PA phone: fax:

3 Page 2 of 4 Test Specimen Description: (Continued) Ceiling Construction: The 7/8" by 7/8" wall molding, was fastened to the inside wood perimeter of the test chamber with #8 x 1" long truss head drywall screws, located 3" from each corner and spaced 16" on center. Four horizontal acoustical T-bar main beams were fitted onto the wall molding located 22-1/2" from each end and spaced 24" on center. The horizontal cross-tees were installed perpendicular to the horizontal main beams and located 22-1/2" from each end and spaced 24" on center. The grid was secured to the wall structure along the perimeter using wall anchors. Twelve U-shaped, 20 gauge, 2-1/2" steel studs were utilized as vertical compression posts. The compression posts were located on each main beam at the first main/cross-tee intersection and then every 3' on center. The compression post was attached to the main beam with four #8 x 1/2" long self-drilling screws, fastened through a bracing clip. The top of the post was fastened to the chamber beam with two #8 x 1" long sheet metal screws. The 2' x 2' metal panels were cut to fit the border dimension. Border panels were fastened to the grid using a #7 x 7/16" long framing screw through the border tab. The cut edge of the panel was held tight to the 7/8" wall molding using a 23-1/4" long section of 1" x 2" angle fastened to the wall molding with four #8 x 1/2"long truss head sheet metal screws. All full 2' x 2' metal panels were installed as per the manufacturer's recommendation. The ceiling was constructed with a 29" plenum depth. Peripheral Support: The test apparatus frame was fabricated from C15 by 33.9 steel channels, measuring 10' 0" wide by 10' 0" long by 1' 3" deep. A loose fitting pleated 4-mil plastic film was utilized to assist in obtaining uniform pressure on the underside of the ceiling system. Note: One assembly was tested per UL 580. The following summarizes observations made during the test at each class rating. Deflection measurements are included within tables attached to this report. Reference the attached Sketch #1 for location of deflection measurement devices. Test Results: The results are tabulated as follows: Class 30: Phases 1-5 PASSED No visible damage to system. Reference Table #1 for deflection measurements. Note: Testing stopped after Class 30 at client's request.

4 Page 3 of 4 General Test Note: Plastic film was used to assist in obtaining pressures. In our opinion, this did not influence test results. Witnesses: The following representatives witnessed all or part of the testing. Name Barry Buhay Michael D. Stremmel, P.E. Jeremy R. Bender Company Armstrong World Industries Architectural Testing, Inc. Architectural Testing, Inc. Detailed drawings, data sheets, representative samples of test specimens, a copy of this report, or other pertinent project documentation will be retained by Architectural Testing, Inc. for a period of four years from the original test date. At the end of this retention period, such materials shall be discarded without notice and the service life of this report will expire. Results obtained are tested values and were secured by using the designated test methods. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the specimen(s) tested. This report may not be reproduced, except in full, without the written approval of Architectural Testing, Inc. For ARCHITECTURAL TESTING, INC. Jeremy R. Bender Technician Michael D. Stremmel, P.E. Senior Project Engineer JRB:vlm/dem Attachments (pages): This report is complete only when all attachments listed are included. Appendix-A: Test Equipment (1) Appendix-B: Table (1) Appendix-C: Chart (1) Appendix-D: Sketch (1) Appendix-E: Photographs (5) Appendix-F: Drawings (6)

5 Page 4 of 4 Revision Log Rev. # Date Page(s) Revision(s) 0 03/12/10 N/A Original report issue This report produced from controlled document template ATI 00351, revised 03/05/09.

6 Appendix A Test Equipment Instrument Manufacturer Asset # Blower System Architectural Testing, Inc Blower System Architectural Testing, Inc Multi-Use Laboratory Equipment Architectural Testing, Inc " Linear Transducer Celesco " Linear Transducer Celesco " Linear Transducer Celesco " Linear Transducer Celesco " Linear Transducer Celesco " Linear Transducer Celesco " Linear Transducer Celesco " Linear Transducer Celesco " Linear Transducer Celesco

7 Appendix B TABLE Table #1 Class 30 Deflection Measurements (inches) Phase #1 #2 #3 #4 #5 #6 #7 #8 #9 Initial (0.0 psf)* Minimum Maximum Final (0.0 psf)** <0.01 <0.01 <0.01 <0.01 <0.01 <0.01 <0.01 <0.01 <0.01 *The measurements are taken via a transit and steel scales mounted to the roof panels. The initial measurements are "zero" point, not actual deflection. Actual deflection is Phase 1, 2, 3 minimum, 3 maximum, 4 or 5 reading less the initial (0.0 psf) reading. **The final reading is taken after the completion of an entire class has been completed and becomes the initial reading for the following class test.

8 Appendix C CHART #1 UL 580 Load Table Test Pressures Test Phase Time Duration (minutes) Negative Pressure Pounds Per Square Foot psf (kpa) Inches (mm) of Water Positive Pressure Pounds Per Square Foot psf (kpa) Inches (mm) of Water Class (0.79) 3.1 (79) 0.0 (0.00) 0.0 (0) (0.79) 3.1 (79) 13.8 (0.66) 2.7 (69) ( ) (38-135) 13.8 (0.66) 2.7 (69) (1.16) 4.7 (119) 0.0 (0.00) 0.0 (0) (1.16) 4.7 (119) 20.8 (1.00) 4.0 (102)

9 Appendix D Sketch

10

11 Appendix E Photographs Photo No. 1 Test Equipment Photo No. 2 Test Equipment

12 Photo No. 3 Border Grid Connection Photo No. 4 Border Panel Connection

13 Photo No. 5 Compression Post 3' On Center Photo No. 6 Post Connection Front

14 Photo No. 7 Post Connection Back Photo No. 8 Border Panel Hold Down

15 Photo No. 9 Full View of All Connections

16 Appendix F Drawings

17

18

19

20

21

22

ASTM E 1886 and ASTM E 1996 TEST REPORT. Rendered to: NORSE, INC.

ASTM E 1886 and ASTM E 1996 TEST REPORT. Rendered to: NORSE, INC. Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: NORSE, INC. SERIES/MODEL: Flush Mount/Surface Mount PRODUCT TYPE: Hurricane Shutter Fastening System This report contains in its

More information

PERFORMANCE TEST REPORT. Rendered to: BAMCO INC. PRODUCT TYPE: ACM Wall Panel Systems

PERFORMANCE TEST REPORT. Rendered to: BAMCO INC. PRODUCT TYPE: ACM Wall Panel Systems PERFORMANCE TEST REPORT Rendered to: BAMCO INC. PRODUCT TYPE: ACM Wall Panel Systems Summary of Results Title Test Specimen #1 Test Specimen #2 Air Infiltration

More information

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B9460.01-109-18. Rendered to: CAPTIVEAIRE, INC. Blue Bell, Pennsylvania

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B9460.01-109-18. Rendered to: CAPTIVEAIRE, INC. Blue Bell, Pennsylvania Architectural Testing MIAMI-DADE COUNTY PERFORMANCE TEST REPORT Report No.: B9460.01-109-18 Rendered to: CAPTIVEAIRE, INC. Blue Bell, Pennsylvania PRODUCT TYPE: Roof Mounted Exhaust Fan SERIES/MODEL: CASRE

More information

PERFORMANCE TEST REPORT. Rendered to: TREMCO INCORPORATED. SERIES/MODEL: Proglaze ETA PRODUCT TYPE: Engineered Transition Assembly

PERFORMANCE TEST REPORT. Rendered to: TREMCO INCORPORATED. SERIES/MODEL: Proglaze ETA PRODUCT TYPE: Engineered Transition Assembly PERFORMANCE TEST REPORT Rendered to: TREMCO INCORPORATED SERIES/MODEL: Proglaze ETA PRODUCT TYPE: Engineered Transition Assembly Title Summary of Results Air Infiltration

More information

PERFORMANCE TEST REPORT. Rendered to: ARCHITECTURAL METAL SOLUTIONS, INC.

PERFORMANCE TEST REPORT. Rendered to: ARCHITECTURAL METAL SOLUTIONS, INC. PERFORMANCE TEST REPORT Rendered to: ARCHITECTURAL METAL SOLUTIONS, INC. SERIES/MODEL: AMS ARMOR-LOCK PRODUCT TYPE: STANDING SEAM METAL ROOF PANEL SYSTEM Report No: 97123.02-901-44 Test Date: 05/17/10

More information

ASTM E 1886 and ASTM E 1996 TEST REPORT. Rendered to: CORAL ARCHITECTURAL PRODUCTS

ASTM E 1886 and ASTM E 1996 TEST REPORT. Rendered to: CORAL ARCHITECTURAL PRODUCTS Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: CORAL ARCHITECTURAL PRODUCTS SERIES/MODEL: PW 256 with Door Openings PRODUCT TYPE: Aluminum Impact Resistant Curtain Wall System

More information

ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT. Rendered to: BEKAERT SPECIALTY FILMS, LLC

ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT. Rendered to: BEKAERT SPECIALTY FILMS, LLC ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT Rendered to: BEKAERT SPECIALTY FILMS, LLC SERIES/MODEL: Panorama 8-mil Film PRODUCT TYPE: Fixed Window with Applied Film This

More information

MOCK-UP TEST REPORT. Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up

MOCK-UP TEST REPORT. Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up MOCK-UP TEST REPORT Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up Report No: 85616.01-120-32 Test Completion Date: 01/15/09 Report Date: 02/11/09 Record Retention End Date: 01/15/13

More information

TEST REPORT. Report No.: A9814.01 109 44. Rendered to: BAMCO INC. Middlesex, New Jersey. PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept

TEST REPORT. Report No.: A9814.01 109 44. Rendered to: BAMCO INC. Middlesex, New Jersey. PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept Architectural Testing TEST REPORT Report No.: A9814.01 109 44 Rendered to: BAMCO INC. Middlesex, New Jersey PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept AAMA 508 07, Voluntary Test Method

More information

AST M F 1642-04/GSA TS01 T EST R EPO R T. Rendered to: UNI T E D ST A T ES A L U M INU M

AST M F 1642-04/GSA TS01 T EST R EPO R T. Rendered to: UNI T E D ST A T ES A L U M INU M AST M F 1642-04/GSA TS01 T EST R EPO R T Rendered to: UNI T E D ST A T ES A L U M INU M SE RI ES/M O D E L : B W3250 PR O DU C T T YPE : Aluminum Combination Fixed Window Summary of Results Title Test

More information

PERFORMANCE TEST REPORT. Rendered to: UNITED STATES ALUMINUM CORPORATION. SERIES/MODEL: 450 Center Glaze PRODUCT TYPE: Aluminum Curtain Wall

PERFORMANCE TEST REPORT. Rendered to: UNITED STATES ALUMINUM CORPORATION. SERIES/MODEL: 450 Center Glaze PRODUCT TYPE: Aluminum Curtain Wall Architectural Testing PERFORMANCE TEST REPORT Rendered to: UNITED STATES ALUMINUM CORPORATION SERIES/MODEL: 450 Center Glaze PRODUCT TYPE: Aluminum Curtain Wall Title Summary of Results Air Infiltration

More information

ASTM E 1886 and ASTM E 1996 TEST REPORT. Rendered to: Atrium Companies, Inc. SERIES/MODEL: 50/305 HS PRODUCT TYPE: Vinyl Horizontal Slider

ASTM E 1886 and ASTM E 1996 TEST REPORT. Rendered to: Atrium Companies, Inc. SERIES/MODEL: 50/305 HS PRODUCT TYPE: Vinyl Horizontal Slider ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: Atrium Companies, Inc. SERIES/MODEL: 50/305 HS PRODUCT TYPE: Vinyl Horizontal Slider Report No.: Test Date: 5/21/07 Through: 5/23/07 Report Date: 5/30/07

More information

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY PERFORMANCE TEST REPORT Rendered to: GLASSCRAFT DOOR COMPANY SERIES/MODEL: Buffalo Forge Steel Doors / Round Top Single PRODUCT TYPE: In-swing Round Top Single Door RH-4 Title Uniform Load Deflection Test

More information

TEST REPORT. Rendered to: DEXERDRY. For: Deck Weatherproofing System Installed with AZEK Deck Boards

TEST REPORT. Rendered to: DEXERDRY. For: Deck Weatherproofing System Installed with AZEK Deck Boards TEST REPORT Rendered to: DEXERDRY For: Deck Weatherproofing System Installed with AZEK Deck Boards Report No.: E8122.01-119-19 Revision 1: 08/18/15 Report Date: 08/14/15 Test Record Retention Date: 07/16/19

More information

TEST REPORT. Rendered to: HOMELAND VINYL PRODUCTS, INC. For:

TEST REPORT. Rendered to: HOMELAND VINYL PRODUCTS, INC. For: TEST REPORT Rendered to: HOMELAND VINYL PRODUCTS, INC. For: PRODUCT: Gorilla Column PVC Porch Post System with PVC Base / Cap Plates, PVC Bushings and 2-3/8 in Diameter and 3-1/2 in Diameter Galvanized

More information

FM 4473 TEST REPORT. Rendered to: VTECH INDUSTRIES, LLP. SERIES/MODEL: 4 x 4 CMC Hurricane PRODUCT TYPE: Skylight

FM 4473 TEST REPORT. Rendered to: VTECH INDUSTRIES, LLP. SERIES/MODEL: 4 x 4 CMC Hurricane PRODUCT TYPE: Skylight FM 4473 TEST REPORT Rendered to: VTECH INDUSTRIES, LLP SERIES/MODEL: 4 x 4 CMC Hurricane PRODUCT TYPE: Skylight Report No.: 92240.01-801-75 Test Date: 08/27/09 Report Date: 08/31/09 Expiration Date: 08/27/13

More information

BLOWING DUST INFILTRATION TEST REPORT. Rendered to: TEX-STAR WINDOWS, INC. PROJECT: Blowing Dust Test SERIES: 3000 Horizontal Sliding Window

BLOWING DUST INFILTRATION TEST REPORT. Rendered to: TEX-STAR WINDOWS, INC. PROJECT: Blowing Dust Test SERIES: 3000 Horizontal Sliding Window BLOWING DUST INFILTRATION TEST REPORT Rendered to: TEX-STAR WINDOWS, INC. PROJECT: Blowing Dust Test SERIES: 3000 Horizontal Sliding Window Report No: 99463.01-801-44 Test Completion Date: 03/24/10 Report

More information

AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT. Rendered to: EAGLE WINDOW & DOOR COMPANY

AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT. Rendered to: EAGLE WINDOW & DOOR COMPANY Architectural Testing AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT Rendered to: EAGLE WINDOW & DOOR COMPANY SERIES/MODEL: Series 01 Axiom Clad One-Piece Casement Fixed 6060 PRODUCT TYPE: Aluminum Clad Fixed

More information

TEST REPORT. Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana

TEST REPORT. Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana Architectural Testing TEST REPORT Report No.: D0162.02-201-44 Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana PRODUCT TYPE: Pressure Equalized Rainscreen SERIES/MODEL: 4 mm Composite

More information

PERFORMANCE TEST REPORT. Rendered to: FORMTECH ENTERPRISES, INC. SERIES/MODEL: Truline PRODUCT TYPE: PVC Seawall

PERFORMANCE TEST REPORT. Rendered to: FORMTECH ENTERPRISES, INC. SERIES/MODEL: Truline PRODUCT TYPE: PVC Seawall PERFORMANCE TEST REPORT Rendered to: FORMTECH ENTERPRISES, INC. SERIES/MODEL: Truline PRODUCT TYPE: PVC Seawall Report No.: Test Dates: 04/17/12 Through: 04/18/12 Report Date: 06/13/12 130 Derry Court

More information

PERFORMANCE TEST REPORT. Rendered to: PROGRESSIVE FOAM TECHNOLOGIES, INC PRODUCT: EPS FOAM

PERFORMANCE TEST REPORT. Rendered to: PROGRESSIVE FOAM TECHNOLOGIES, INC PRODUCT: EPS FOAM PERFORMANCE TEST REPORT Rendered to: PROGRESSIVE FOAM TECHNOLOGIES, INC PRODUCT: EPS FOAM Report No: Report Date: 01/31/11 Expiration Date: 01/19/15 130 Derry Court York, PA 17406-8405 phone: 717-764-7700

More information

PERFORMANCE EVALUATION TEST REPORT. Rendered to: HANDI-SHIM, LLC. SERIES/MODEL: Handi-Shim 1/32", 1/16", 1/8" and 1/4" PRODUCT: Plastic Shims

PERFORMANCE EVALUATION TEST REPORT. Rendered to: HANDI-SHIM, LLC. SERIES/MODEL: Handi-Shim 1/32, 1/16, 1/8 and 1/4 PRODUCT: Plastic Shims PERFORMANCE EVALUATION TEST REPORT Rendered to: HANDI-SHIM, LLC SERIES/MODEL: Handi-Shim 1/32", 1/16", 1/8" and 1/4" PRODUCT: Plastic Shims Report No: Report Date: 11/04/08 Expiration Date: 10/26/12 130

More information

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B8049.01-401-18. Rendered to: AMERICAN PRODUCTS, INC Tampa, Florida

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B8049.01-401-18. Rendered to: AMERICAN PRODUCTS, INC Tampa, Florida Architectural Testing MIAMI-DADE COUNTY PERFORMANCE TEST REPORT Report No.: B8049.01-401-18 Rendered to: AMERICAN PRODUCTS, INC Tampa, Florida PRODUCT TYPE: Aluminum Storefront with Double Doors SERIES/MODEL:

More information

TEST REPORT. Report No.: B3404.01-801-47. Rendered to: CROFT, LLC. Magnolia, Mississippi. PRODUCT TYPE: Aluminum Single Hung Window SERIES/MODEL: 95

TEST REPORT. Report No.: B3404.01-801-47. Rendered to: CROFT, LLC. Magnolia, Mississippi. PRODUCT TYPE: Aluminum Single Hung Window SERIES/MODEL: 95 Architectural Testing TEST REPORT Report No.: B3404.01-801-47 Rendered to: CROFT, LLC. Magnolia, Mississippi PRODUCT TYPE: Aluminum Single Hung Window SERIES/MODEL: 95 SPECIFICATION: AAMA/WDMA/CSA 101/I.S.2/A440-08,

More information

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY Architectural Testing PERFORMANCE TEST REPORT Rendered to: GLASSCRAFT DOOR COMPANY SERIES/MODEL: Mahogany Entry Door PRODUCT TYPE: 6' x 8' Double Outswing Hardwood TDL Door with Half Circle TDL Transom

More information

TEST REPORT. Rendered to: INTEX MILLWORK SOLUTIONS, LLC. For: Rigid Cellular PVC Guardrail System Hampton RS40

TEST REPORT. Rendered to: INTEX MILLWORK SOLUTIONS, LLC. For: Rigid Cellular PVC Guardrail System Hampton RS40 TEST REPORT Rendered to: INTEX MILLWORK SOLUTIONS, LLC For: Rigid Cellular PVC Guardrail System Hampton RS40 Report No: Report Date: 07/26/13 130 Derry Court York, PA 17406-8405 phone: 717-764-7700 fax:

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MGM INDUSTRIES SERIES/MODEL: 6010. TYPE: Single Hung Window

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MGM INDUSTRIES SERIES/MODEL: 6010. TYPE: Single Hung Window ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: MGM INDUSTRIES SERIES/MODEL: 6010 TYPE: Single Hung Window Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC OITC B2706.01

More information

BLOWING DUST INFILTRATION TEST REPORT. Rendered to: TEX-STAR WINDOWS, INC. PROJECT: Blowing Dust Test SERIES: 3000 Double Hung Window

BLOWING DUST INFILTRATION TEST REPORT. Rendered to: TEX-STAR WINDOWS, INC. PROJECT: Blowing Dust Test SERIES: 3000 Double Hung Window Architectural Testing BLOWING DUST INFILTRATION TEST REPORT Rendered to: TEX-STAR WINDOWS, INC. PROJECT: Blowing Dust Test SERIES: 3000 Double Hung Window Report No: 99462.01-801-44 Test Completion Date:

More information

TEST REPORT. Rendered to: INTERNATIONAL WINDOW Hayward, California. PRODUCT TYPE: Aluminum Hopper SERIES/MODEL: 7222

TEST REPORT. Rendered to: INTERNATIONAL WINDOW Hayward, California. PRODUCT TYPE: Aluminum Hopper SERIES/MODEL: 7222 Architectural Testing TEST REPORT Report No.: C2375.01-301-44 Rendered to: INTERNATIONAL WINDOW Hayward, California PRODUCT TYPE: Aluminum Hopper SERIES/MODEL: 7222 SPECIFICATIONS: AAMA/WDMA/CSA 101/I.S.2/A440-05,

More information

E6211.02-113-11-R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: TREX COMPANY, LLC. Series/Model: Trex Seclusion

E6211.02-113-11-R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: TREX COMPANY, LLC. Series/Model: Trex Seclusion ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: TREX COMPANY, LLC Series/Model: Trex Seclusion Type: Sound Barrier Fence Summary of Test Results Data File No. Description STC OITC E6211.01 Trex

More information

TEST REPORT. Rendered to: LMT-Mercer Group, Inc. For: PRODUCT: 4" x 4" and 5" x 5" PVC Porch Posts with Aluminum Reinforcing

TEST REPORT. Rendered to: LMT-Mercer Group, Inc. For: PRODUCT: 4 x 4 and 5 x 5 PVC Porch Posts with Aluminum Reinforcing TEST REPORT Rendered to: LMT-Mercer Group, Inc. For: PRODUCT: 4" x 4" and 5" x 5" PVC Porch Posts with Aluminum Reinforcing Report No.: Report Date: 01/28/14 Test Record Retention Date: 12/20/17 130 Derry

More information

NFRC 102-2010 THERMAL PERFORMANCE TEST REPORT. Rendered to: CR LAURENCE CO., INC. SERIES/MODEL: 7500 Concealed Vent TYPE: Projecting (Awning)

NFRC 102-2010 THERMAL PERFORMANCE TEST REPORT. Rendered to: CR LAURENCE CO., INC. SERIES/MODEL: 7500 Concealed Vent TYPE: Projecting (Awning) NFRC 102-2010 THERMAL PERFORMANCE TEST REPORT Rendered to: CR LAURENCE CO., INC. SERIES/MODEL: 7500 Concealed Vent TYPE: Projecting (Awning) Summary of Results Standardized Thermal Transmittance (U-Factor)

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: TUBELITE, INC. SERIES/MODEL: T24000. TYPE: Two-Lite Storefront

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: TUBELITE, INC. SERIES/MODEL: T24000. TYPE: Two-Lite Storefront ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: TUBELITE, INC. SERIES/MODEL: T24000 TYPE: Two-Lite Storefront Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC OITC C5774.01

More information

HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES

HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES 101 Retrofits Required. Pursuant to Section 553.844 553.884, Florida Statutes, strengthening of existing site-built,

More information

TEST REPORT. Rendered to: FAIRWAY BUILDING PRODUCTS, LP. For: LandMarke Railing System. PVC Guardrail System "Patent Number 7,487,941"

TEST REPORT. Rendered to: FAIRWAY BUILDING PRODUCTS, LP. For: LandMarke Railing System. PVC Guardrail System Patent Number 7,487,941 TEST REPORT Rendered to: FAIRWAY BUILDING PRODUCTS, LP For: LandMarke Railing System PVC Guardrail System "Patent Number 7,487,941" Report No: Report Date: 05/25/10 130 Derry Court York, PA 17406-8405

More information

LISTING INFORMATION OF Alucoil - larson by Alucoil FR 4 mm and 6 mm ACM Panels SPEC ID: 29074. Alucoil North America LLC 1976 Joe Rogers Jr Blvd

LISTING INFORMATION OF Alucoil - larson by Alucoil FR 4 mm and 6 mm ACM Panels SPEC ID: 29074. Alucoil North America LLC 1976 Joe Rogers Jr Blvd LISTING INFORMATION OF Alucoil - larson by Alucoil FR 4 mm and 6 mm ACM Panels SPEC ID: 29074 Alucoil North America LLC 1976 Joe Rogers Jr Blvd Manning, SC 29102 This report is for the exclusive use of

More information

POST AND FRAME STRUCTURES (Pole Barns)

POST AND FRAME STRUCTURES (Pole Barns) POST AND FRAME STRUCTURES (Pole Barns) Post and frame structures. The following requirements serve as minimum standards for post and frame structures within all of the following structural limitations:

More information

Truss Fabrication with Light Gage Steel Framing

Truss Fabrication with Light Gage Steel Framing FROM THE FOUNDATION Truss Fabrication with Light Gage Steel Framing By Richard H. Kapp, P.E. Note: Italicized portions contributed by Brad Beczkalo. See article, p. 15. L ight gage steel trusses have been

More information

LLOYD INDUSTRIES INC. DAMPER INSTALLATION INSTRUCTIONS

LLOYD INDUSTRIES INC.  DAMPER INSTALLATION INSTRUCTIONS DAMPER Installation and Maintenance Instructions 1-1/2 Hour Rated, UL Classified model 75 fire dampers For use in fire barriers with ratings of less than 3 hours INSPECTION 1. Inspect for shipping damage.

More information

PART 1 GENERAL 1.1 SECTION INCLUDES

PART 1 GENERAL 1.1 SECTION INCLUDES J-1 Section 09110 Long Form Specification INTERIOR METAL STUD FRAMING This section includes lightweight, usually 0.036 inch (0.9 mm) thick or lighter, non-axial load bearing metal stud framing including

More information

1. Mark out the starting line To ensure starting line and level as per approved shop drawings.

1. Mark out the starting line To ensure starting line and level as per approved shop drawings. 6. INSTALLATION It is essential to identify location of openings, mechanical and electrical (M&E) services, and other fixtures before installation of drywall. The setting out of the framing system, openings

More information

METALWORKS PLANK. Installation Instructions. Ceiling. 2. Suspension System Installation. 1. Description

METALWORKS PLANK. Installation Instructions. Ceiling. 2. Suspension System Installation. 1. Description Ceiling Systems Between us, ideas become reality METALWORKS PLANK Installation Instructions 1. Description 1.1. is a ceiling system made up of standard sized hook-on planks fabricated from galvanized steel

More information

SECTION 07400 STANDING SEAM METAL ROOF

SECTION 07400 STANDING SEAM METAL ROOF SECTION 07400 STANDING SEAM METAL ROOF PART 1 - GENERAL 1.01 SECTION INCLUDES A. Work described in this section includes pre-formed standing seam metal roofing system complete with clips, perimeter and

More information

PERFORMANCE TEST REPORT. Rendered to: FIBERLOCK TECHNOLOGIES, INC.

PERFORMANCE TEST REPORT. Rendered to: FIBERLOCK TECHNOLOGIES, INC. PERFORMANCE TEST REPORT Rendered to: FIBERLOCK TECHNOLOGIES, INC. PRODUCT: Recon Smoke Odor Sealer - White (#3090) TYPES: Water Based Fluid Applied Membrane for Smoke Odor Sealing and Stain Blocking Report

More information

BXUV.P523 - Fire Resistance Ratings - ANSI/UL 263. Fire Resistance Ratings - ANSI/UL 263

BXUV.P523 - Fire Resistance Ratings - ANSI/UL 263. Fire Resistance Ratings - ANSI/UL 263 Page 1 of 5 Page Bottom BXUV.P523 Fire Resistance Ratings - ANSI/UL 263 Fire Resistance Ratings - ANSI/UL 263 See General Information for Fire Resistance Ratings - ANSI/UL 263 Design No. P523 March 21,

More information

Chapter 4 FLOOR CONSTRUCTION

Chapter 4 FLOOR CONSTRUCTION Chapter 4 FLOOR CONSTRUCTION Woodframe floor systems and concrete slab-on-grade floors are discussed in this chapter. Although cold-formed steel framing for floor systems also is permitted by the IRC,

More information

APRIL 2013 AMENDMENTS LEGISLATIVE FORMAT

APRIL 2013 AMENDMENTS LEGISLATIVE FORMAT TABLE 2308.8(1) FLOOR JOIST SPANS FOR COMMON LUMBER SPECIES (Residential Sleeping Areas, Live Load = 30 psf, L/ = 360) JOIST 12 16 19.2 DEAD LOAD = 10 psf DEAD LOAD = 20 psf 2x6 2x8 2x10 2x12 2x6 2x8 2x10

More information

WINDOW PANNING AND TRIMS

WINDOW PANNING AND TRIMS OCTOBER, 2010 PANNING AND TRIMS GENERAL INFORMATION 1 EXTERIOR PANNING Panning is primarily used to cover the perimeters of existing building openings prior to the installation of replacement windows.

More information

Exterior Research & Design, L.L.C. Building Science and Envelope Consultants

Exterior Research & Design, L.L.C. Building Science and Envelope Consultants Exterior Research & Design, L.L.C. Building Science and Envelope Consultants Certificate of Authorization #9503 Evaluation Report 4540.11.04-2 Evaluation of R-Mer Span and R-Mer Loc Structural Metal Roofing

More information

Mark Cramer Inspection Services, Inc.

Mark Cramer Inspection Services, Inc. Mark Cramer Inspection Services, Inc. 492 Twentieth Avenue, Indian Rocks Beach, FL 34635-2970 (727) 595-4211 Fax (727) 596-7583 Certified Member #12085 American Society of Home Inspectors Construction

More information

Fire Resistance Bulletin

Fire Resistance Bulletin New 1-hr Rated Exterior Wall Assembly Includes Allowances for Various Insulation Options and Much Wider Maximum Girt Spacing Under the auspices of the MBMA Committee on Fire Protection and Related Insurance

More information

CONSTRUCTION DETAILS & LOAD DESIGN CHARTS

CONSTRUCTION DETAILS & LOAD DESIGN CHARTS Office and Production 126 New Pace Rd., PO Box 279 Newcomerstown, OH 43832 1-800-446-2188, Fax: 740-498-4184 www.buildwithsips.com CONSTRUCTION DETAILS & LOAD DESIGN CHARTS Table of Contents Description

More information

This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.

This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances. Residential Decks Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org

More information

Since the Steel Joist Institute

Since the Steel Joist Institute SELECTING and SPECIFYING Wesley B. Myers, P.E. An insider s guide to selecting and specifying K-series, LH, DLH-series joists and joist girders Since the Steel Joist Institute adopted the first standard

More information

Stock sizes are nominal sizes(see glossary) Excludes hardware such as nails and other fixing or fastening components.

Stock sizes are nominal sizes(see glossary) Excludes hardware such as nails and other fixing or fastening components. 2400 x 3000 (8ft x 10ft) Storage Shed Plans Page 1: Introduction and Contents This detailed shed plan-set is in both Standard and metric dimensions. It is built on skids, meaning that there are no footings

More information

REPORT NUMBER: 100900226COQ-003 ORIGINAL ISSUE DATE: July 19, 2013

REPORT NUMBER: 100900226COQ-003 ORIGINAL ISSUE DATE: July 19, 2013 REPORT NUMBER: 100900226COQ-003 ORIGINAL ISSUE DATE: July 19, 2013 TEST REPORT EVALUATION CENTER INTERTEK TESTING SERVICES NA LTD. 1500 BRIGANTINE DRIVE COQUITLAM, BC V3K 7C1 CANADA RENDERED TO PHOENIX

More information

REPORT NUMBER: COQ-001 ORIGINAL ISSUE DATE: March 28, 2013

REPORT NUMBER: COQ-001 ORIGINAL ISSUE DATE: March 28, 2013 REPORT NUMBER: 101028759COQ-001 ORIGINAL ISSUE DATE: March 28, 2013 TEST REPORT EVALUATION CENTER INTERTEK TESTING SERVICES NA LTD. 1500 BRIGANTINE DRIVE COQUITLAM, BC V3K 7C1 CANADA RENDERED TO LENMAK

More information

HOW TO ESTIMATE THE COST OF T-BAR

HOW TO ESTIMATE THE COST OF T-BAR HOW TO ESTIMATE THE COST OF T-BAR ACOUSTICAL CEILINGS MICHAEL HILL DATE WRITTEN: MAY OF 2007 The author is Michael Hill, Estimator with Kaiser Foundation Hospitals, National Facilities Services Cost Engineering

More information

Seismic Installation for Attic Storage System

Seismic Installation for Attic Storage System Your Performance Partner Seismic Installation for Storage System CONTENTS SSafety Precautions................................. 2 Required Tools..................................... 2 Parts and Fastener

More information

SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS. System 402 Flush-Glazed Screw Spline Storefront

SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS. System 402 Flush-Glazed Screw Spline Storefront PART 1 GENERAL 1.01 Work Included SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS System 402 Flush-Glazed Screw Spline Storefront A. Furnish and install aluminum architectural storefront system

More information

STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM

STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM Chapter 9 STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM 9.1 BACKGROUND Steel is widely used in the construction of multi-storey buildings. However, steel construction is seldom used and is traditionally

More information

Requirements for Fire Protection of Light Weight Floor Systems **Act 1 Revisited**

Requirements for Fire Protection of Light Weight Floor Systems **Act 1 Revisited** PHRC Webinar Series Tuesday, September 9, 2014 1:00 pm Requirements for Fire Protection of Light Weight Floor Systems **Act 1 Revisited** Presented by: Bryan Heitzmann Credit(s) earned on completion of

More information

Sundance Supply, LLC. Greca Corrugated Polycarbonate Design & Install. To order Polycarbonate see >

Sundance Supply, LLC. Greca Corrugated Polycarbonate Design & Install. To order Polycarbonate see > Sundance Supply, LLC Greca Corrugated Polycarbonate Design & Install To order Polycarbonate see > http://www.sundancesupply.com Corrugated polycarbonate is sold in 1 ft. Increments. (1) (2) 30ʼ x 48ʼ Greenhouse

More information

SECTION 07723 RIDGE, SOFFIT AND SIDING VENTS. ** NOTE TO SPECIFIER ** Cor-A-Vent; high-density polypropylene ridge and soffit vents.

SECTION 07723 RIDGE, SOFFIT AND SIDING VENTS. ** NOTE TO SPECIFIER ** Cor-A-Vent; high-density polypropylene ridge and soffit vents. SECTION 07723 RIDGE, SOFFIT AND SIDING VENTS ** NOTE TO SPECIFIER ** Cor-A-Vent; high-density polypropylene ridge and soffit vents. This section is based on products manufactured by Cor-A-Vent, Inc., which

More information

How to Use this Guide

How to Use this Guide How to Use this Guide Provide two sets of plans, drawn to scale and complete the following (hint: use graph paper with 1/4" squares. Example: 1/4" =1'): Check with your jurisdiction for additional requirements.

More information

Chapter 36 - STRAW BALE CONSTRUCTION SECTION 3601 - PURPOSE. SECTION 3602 - SCOPE. SECTION 3603 - DEFINITIONS.

Chapter 36 - STRAW BALE CONSTRUCTION SECTION 3601 - PURPOSE. SECTION 3602 - SCOPE. SECTION 3603 - DEFINITIONS. Austin City Code - Volume II TITLE 25 LAND DEVELOPMENT\CHAPTER 25-12 TECHNICAL CODES\ARTICLE 1: UNIFORM BUILDING CODE\25-12-3 LOCAL AMENDMENTS TO THE BUILDING CODE Chapter 36 - STRAW BALE CONSTRUCTION

More information

Structural Assessment Report

Structural Assessment Report Report Dallas Township Elementary School Dallas, Pennsylvania (JBCI Project No. 144911) 1655 Suburban Station Building 1617 John F. Kennedy Boulevard Philadelphia PA 19103 215 665 0497 5 Sandwood Drive

More information

INSTALLATION OF A BAY WINDOW

INSTALLATION OF A BAY WINDOW INSTALLATION OF A BAY WINDOW Installation of a Bay Window These instructions relate to the replacement of an existing bay window or replacement of a straight window with a new bay window, in an opening

More information

Residential Deck Safety, Construction, and Repair

Residential Deck Safety, Construction, and Repair Juneau Permit Center, 4 th Floor Marine View Center, (907)586-0770 This handout is designed to help you build your deck to comply with the 2006 International Residential Building code as modified by the

More information

Superform Products Ltd.

Superform Products Ltd. TYPICAL CORNER REINFORCING NOTE : SEE ENGINEERED REBAR SCHEDULES SUPPLIED BY THE MANUFACTURER STEEL REINFORCEMENT WALL CORNER 90 Copyright 2012 Sept. 2012 5.1.1 Rebar Spacing 6" 12" Max. Load LB./FT. 2000

More information

CEILING SYSTEMS. Between us, ideas become reality. Installing. Suspended Ceilings. North America Version

CEILING SYSTEMS. Between us, ideas become reality. Installing. Suspended Ceilings. North America Version CEILING SYSTEMS Between us, ideas become reality Installing Suspended Ceilings North America Version 1 Installing Armstrong Suspended Ceilings An Armstrong suspended mineral fiber ceiling is functional,

More information

Introduction. Required Materials

Introduction. Required Materials C e r t a i n Te e d Air Barrier Installation Instructions for Wood Framing Introduction In addition to performing as an interior vapor retarder, MemBrain may be installed as a continuous, interior air

More information

CH. 2 LOADS ON BUILDINGS

CH. 2 LOADS ON BUILDINGS CH. 2 LOADS ON BUILDINGS GRAVITY LOADS Dead loads Vertical loads due to weight of building and any permanent equipment Dead loads of structural elements cannot be readily determined b/c weight depends

More information

ICC-ES Evaluation Report Reissued July 1, 2009 This report is subject to re-examination in two years.

ICC-ES Evaluation Report Reissued July 1, 2009 This report is subject to re-examination in two years. ICC-ES Evaluation Report ESR-1566* Reissued July 1, 2009 This report is subject to re-examination in two years. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council

More information

Metal Roofing Practical Design

Metal Roofing Practical Design Metal Roofing Practical Design Metal Roofing Practical Design Learning Outcomes Minimum Requirements Design Resources Low Slope Metal Roofing Design Details Continuously Insulated (Ci) Systems Minimum

More information

Section A Roof Truss

Section A Roof Truss Section A Roof Truss Truss Types Wisconsin Truss, Inc. can build a variety of truss types, pictured below are some common examples. Common Bobtail Scissor Mono Studio Dual Slope Cathedral Tray Vault Parallel

More information

Canvas Office Landscape Wall Strip Installation and Disassembly for Recycling Instructions

Canvas Office Landscape Wall Strip Installation and Disassembly for Recycling Instructions Y Parts Included: Canvas Office Landscape Wall Strip Installation and Disassembly for Recycling Instructions Tools Required: Power Driver Drill Bit (Determined by fastener) Driver Bit (Determined by fastener)

More information

DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 41 13 METAL ROOF PANELS REPORT HOLDER: FIRESTONE BUILDING PRODUCTS COMPANY, LLC

DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 41 13 METAL ROOF PANELS REPORT HOLDER: FIRESTONE BUILDING PRODUCTS COMPANY, LLC 0 ICC ES Report ICC ES (800) 423 687 (62) 699 043 www.icc es.org 000 Most Widely Accepted and Trusted ESR 3422 Reissued 09/201 This report is subject to renewal 09/2016. DIVISION: 07 00 00 THERMAL AND

More information

Installation Instructions for Wall & Frame Mounted Overhead Cabinets

Installation Instructions for Wall & Frame Mounted Overhead Cabinets Installation Instructions for Wall & Frame Mounted Overhead Cabinets CAUTION MAKE SURE THE WALL MEETS THE LOAD CAPACITY REQUIREMENTS FOR THE OVERHEAD CABINET BEING INSTALLED. REFER TO LOCAL BUILDING CODES

More information

INDACO METALS, LLC. RIGID BUILDING SYSTEMS 3 AMERICAN WAY, SHAWNEE, OKLA PH: FAX:

INDACO METALS, LLC. RIGID BUILDING SYSTEMS 3 AMERICAN WAY, SHAWNEE, OKLA PH: FAX: METAL BUILDING INFORMATION GUIDE This bulletin is designed to aid the metal building buyer in the purchase of a rigid building system. What is a rigid building? A rigid building is a building that most

More information

SLIDING DOORS. 3. For doors fitted to the eave side of the building this header takes the form of an additional eave purlin.

SLIDING DOORS. 3. For doors fitted to the eave side of the building this header takes the form of an additional eave purlin. 1 SLIDING DOORS AGS/DR/03 The aim of this instruction is to guide you through the process of construction and fitting of Sliding Doors. Due to the number of sizes available this instruction is written

More information

Chapter 3 Pre-Installation, Foundations and Piers

Chapter 3 Pre-Installation, Foundations and Piers Chapter 3 Pre-Installation, Foundations and Piers 3-1 Pre-Installation Establishes the minimum requirements for the siting, design, materials, access, and installation of manufactured dwellings, accessory

More information

Residential Decks. Planning and Development Services Department

Residential Decks. Planning and Development Services Department Building Safety Division 8500 Santa Fe Drive Overland Park, KS 66212 (913) 895-6225 Fax (913) 895-5016 Email: permitservices@opkansas.org Planning and Development Services Department Residential Decks

More information

glass entrance systems

glass entrance systems All Glass Entrance Systems: Entrance Configurations/Fitting Designations og-43410 og-47210 og-43410 og-43410 og-43410 og-44610 og-43410 og-44010 og-46700 og-46700 og-47210 og-47210 og-44010 og-43410 og-44610

More information

Discipline: Structural Issued 04-26-06

Discipline: Structural Issued 04-26-06 California Department of General Services. Division of the State Architect. Product Acceptance Report STRUCTURAL SHEAR PANEL SURE-BOARD SERIES 200 PANELS PA-132 Discipline: Structural Issued 04-26-06 This

More information

6 RETROFITTING POST & PIER HOUSES

6 RETROFITTING POST & PIER HOUSES Retrofitting Post & Pier Houses 71 6 RETROFITTING POST & PIER HOUSES by James E. Russell, P.E. 72 Retrofitting Post & Pier Houses Retrofitting Post & Pier Houses 73 RETROFITTING POST AND PIER HOUSES This

More information

TREX TRANSCEND RAILING Installation Instructions

TREX TRANSCEND RAILING Installation Instructions NoteS:» trex Transcend Railings are designed to be installed OVER the decking frame or on inside of rim joist. Notching of pressure treated posts or posts installed on outside of rim joist are not allowed.»

More information

WINDOW FRAMES FIRE WINDOWS FIRE RATED PRODUCTS

WINDOW FRAMES FIRE WINDOWS FIRE RATED PRODUCTS FIRE WINDOWS FIRE RATED PRODUCTS WINDOW FRAMES s FIRE RATED WINDOW FRAMES: The fire window (borrowed light) frames covered in this section, have been tested in accordance with NFPA 257, and UL9 and listed

More information

STANDARD PROCEDURES FOR INSTALLATION OF METAL ROOF SYSTEMS

STANDARD PROCEDURES FOR INSTALLATION OF METAL ROOF SYSTEMS ROOFING APPLICATION STANDARD (RAS) No. 133 STANDARD PROCEDURES FOR INSTALLATION OF METAL ROOF SYSTEMS 1. Scope 1.1 This application standard has been developed to provide consistent information for the

More information

Chapter 6 ROOF-CEILING SYSTEMS

Chapter 6 ROOF-CEILING SYSTEMS Chapter 6 ROOF-CEILING SYSTEMS Woodframe roof-ceiling systems are the focus of this chapter. Cold-formed steel framing for a roof-ceiling system also is permitted by the IRC but will not be discussed;

More information

Light Gauge Steel Framing:

Light Gauge Steel Framing: Light gauge steel framing provides an effective support method for interior finishes: gypsum drywall systems, veneer plaster systems, and conventional plaster systems. These systems help satisfy the performance

More information

Replacement of HVAC Systems February 20, 2015 Cranford Campus

Replacement of HVAC Systems February 20, 2015 Cranford Campus SECTION 092116 - GYPSUM BOARD ASSEMBLIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Product Installation Guide

Product Installation Guide Perpendicular to Deck/Parallel Beam Gap for Gypsum Board - Full Height Wall - Flute Fill stuff "oversized plugs" before stud and bottom track - 6" and wider cut plug in half and install from each side

More information

VA25014B0516 VA CINCINNATI PROJECT NO. 539-328 INPATIENT BED TOWER ADDITION (4 TH AND 5 TH FLOORS) SECTION 09 29 00 GYPSUM BOARD

VA25014B0516 VA CINCINNATI PROJECT NO. 539-328 INPATIENT BED TOWER ADDITION (4 TH AND 5 TH FLOORS) SECTION 09 29 00 GYPSUM BOARD SECTION 09 29 00 GYPSUM BOARD PART 1 - GENERAL 1.1 DESCRIPTION This section specifies installation and finishing of gypsum board, vapor retarder and air and moisture barrrier. 1.2 RELATED WORK A. Installation

More information

CRASH RAIL INSTALLATION HEIGHT

CRASH RAIL INSTALLATION HEIGHT PLEASE READ PLEASE READ THESE INSTRUCTIONS THOROUGHLY PRIOR TO BEGINNING THE INSTALLATION! THIS INSTRUCTION SHEET IS INTENDED TO PROVIDE A SPECIFIC GUIDE TO FOLLOW FOR THE INSTALLATION OF THIS. CONTAINED

More information

Florida Building Code, 5 th Edition SHINGLE ROOFING

Florida Building Code, 5 th Edition SHINGLE ROOFING Florida Building Code, 5 th Edition SHINGLE ROOFING Date Issued/Updated: July 6, 2015 This bulletin addresses the current Building Code roofing and re roofing requirements for shingle roofing systems.

More information

1036 Parkway Ct. Phone: 770-932-0202 Buford, GA 30518 Fax: 770-945-0041

1036 Parkway Ct. Phone: 770-932-0202 Buford, GA 30518 Fax: 770-945-0041 CONSTRUCTION 1. A. GENERAL 1.A.1. The intent of this specification is to set forth construction and design standards that will result in an installation of modular cabinetry requiring FLUSH OVERLAY CONSTRUCTION.

More information

ANSI/SPRI WD-1 Wind Design Standard Practice for Roofing Assemblies. Table of Contents. 1.0 Introduction...2. 2.0 Methodology...2

ANSI/SPRI WD-1 Wind Design Standard Practice for Roofing Assemblies. Table of Contents. 1.0 Introduction...2. 2.0 Methodology...2 Standard Practice f Table of Contents 1.0 Introduction...2 2.0 Methodology...2 Appendix A...7 Insulation Board Fastening Patterns 4 feet 4 feet Boards Adhered Membranes...8 Insulation Board Fastening Patterns

More information

FCA CARPENTRY & JOINERY THEORY 13 PARTITIONS

FCA CARPENTRY & JOINERY THEORY 13 PARTITIONS CARPENTRY & JOINERY FCA CARPENTRY & JOINERY THEORY 13 PARTITIONS Introduction Partitions are the vertical walls or panels used to divide rooms or portions of buildings The diagram below shows how existing

More information

DIVISION: FINISHES SECTION: SUSPENSION SYSTEMS SECTION: ACOUSTICAL CEILING SUSPENSION ASSEMBLIES REPORT HOLDER:

DIVISION: FINISHES SECTION: SUSPENSION SYSTEMS SECTION: ACOUSTICAL CEILING SUSPENSION ASSEMBLIES REPORT HOLDER: 0 ICC-ES Report ICC-ES (800) 42-6587 (562) 699-054 www.icc-es.org 000 Most Widely Accepted and Trusted ESR-261 Reissued 06/2016 This report is subject to renewal 06/2017. DIVISION: 09 00 00 FINISHES SECTION:

More information