1 REV: WAD Guidelines INFORMATION/COMMUNICATIONS RESOURCE REQUIREMENTS VOICE/DATA/VIDEO COMMUNICATION STANDARDS UNIVERSITY BUILDING STANDARDS All wiring will be in accordance with the ANSI/TIA/EIA-568-B and its addenda standard for telecommunications wiring. All copper RJ45 jacks will be wired in accordance with T568A wiring pattern. The campus telecommunications systems derive from Perry Paige (data), Coleman Library Complex (video), and Foote-Hilyer (voice). The standard wiring plan for the University is to provide an acceptable outlet for any communications device (voice, data or video) which requires connection to other devices, networks, or information services serving general university needs. All new and upgrade work at the University should meet these guidelines unless otherwise directed. NOTE: All backbone fiber patch cords must be Corning or Belden products. All infrastructure products for retrofitting or new construction, (ex. wall outlets, category 6 patch cords, etc.) must be a product of Corning or Belden. These requirements are a must to stay in accordance and maintain the University's current 25-year warranty on all products and materials. All contractors must be Corning EWP certified and Belden CSV certified, please refer to the Installer / Contractor Requirements Section. Requirements Copper to the Desktop All communication outlets will be equipped with but not limited to two (2) category 6, twisted pair copper station wiring, both terminating in a RJ45 modular jack. Unless otherwise specified in the design phase, all cables will terminate to a category 6 patch panel within the wiring closet. A category 6 patch panel will be installed to connect with the telephone company demarcation point. All connections between the active data equipment and/or the voice patch panels to the category 6 station wiring patch panel will be accomplished through category 6 RJ45 jumpers.

2 Wireless Network All new and retro-fitted facilities are required to have wireless communications. Refer to the Wireless Network Documentation General All station wiring will be continuous wire from the MDF/IDF to the communication outlet, All MDF/IDF terminations shall be of 100% cross connected as per the ANSI/TIA/EIA-568-B and its addenda specifications. To facilitate future cable installations, a new pull string shall be installed in conduits simultaneously with the pull-in of cable. All MDF/IDF shall be provided with one or more grounded 19" by 84" EIA standard wiring rack(s) and category 6 patch panels / Rack mount fiber termination cabinets or splice housings in quantities necessary to terminate the required cables. Appropriate wire management hardware will be provided to support routing of patch cables in a neat and organized manner. The electrical work shall include requirements for installation of a conduit (1" minimum diameter) from each communication outlet and "stubbed" up above ceiling level. A pull string and appropriate junction or "pull" boxes shall also be provided in each conduit run to facilitate future installation of cable(s). Cable trays shall be installed to route the station cable to the MDF/IDF. All IDF, MDF and connecting blocks must be properly identified according to specifications provided by the Information Resource Manager. All cable pairs in copper riser cables or the copper entrance cable must be terminated on Category 6, 110 style to RJ45 patch panels and identified according to ANSI/TIA/EIA 606-A specifications. Fiber runs between MDF and IDF shall consist of a 12 fiber 62.5/125 micron multimode cable and a 12 fiber single-mode cable terminated in SC connectors and placed in appropriate fiber patch panels. All communication outlets not in use, either wired or empty, must have a blank plate covering the outlet. All modular jack assemblies must be labeled and identified according to ANSI/TIA/EIA 606-A specifications.

3 All wiring inside of rooms should be protected by conduit or other means such as wire mold. Cable may be run exposed above ceilings, provided this cabling is supported independent of other utilities, such as conduits, pipes, ceiling support systems, cable trays, and not laid directly on the ceiling panels. Cable to be plenum rated. All patch cables both copper and fiber are to be provided by the contractor at the time of completion. All copper patch cables are to be category 6 compliant and 7 in length. All MDF/IDF patch cords should be 3 meters sc-sc type. Installer / Contractor Requirements General condition Approved Vendor General The Contractor must be a Belden-authorized Certified System Vendor (hereinafter referred to as Belden CSV) of the Belden IBDN Gigabit System The Vendor must have successfully completed all Belden IBDN design and installation training provided by Belden. Contractor must also be a member of the 2007 Corning Extended Warranty Program and must adhere to the engineering, installation and testing procedures and utilize the authorized manufacturer components and distribution channels in provisioning the Project. The Contractor shall show proven expertise in the implementation of cabling projects. This expertise can be illustrated through the inclusion of details of at least three (3) projects involving the design and installation of a Category 6 unshielded twisted-pair (hereinafter referred to as UTP) cabling systems within the past two (2) year period. Names, addresses and telephone numbers of references for the three (3) projects should be included. Proof shall be required at the time of quote acceptance that the Firm or Company is an established organization, within (20) miles of the project, The successful bidder should hereinafter be referred to as the Vendor. The Vendor should accept complete responsibility for the design, installation, acceptance testing and certification of the Belden IBDN Gigabit System The Vendor should provide proof of current Belden CSV status and should deliver the Belden certification of the installed Belden IBDN Gigabit System 2400 to the Purchaser.

4 General condition Approved Installer General The vendor must be a Belden-authorized Certified System Vendor (hereinafter referred to as Belden CSV) of the Belden IBDN Gigabit System The Vendor must have successfully completed all Belden IBDN design and installation training provided by Belden. The vendor shall be a licensed and registered with the State of Florida Department of Business Professional Regulation and who is, and who has been, regularly engaged in providing and installing non-residential, communication and technology systems of this type and size for at least the immediate past five (5) years and one (1) RCDD on staff as permanent employees. The Contractor's Project Manager, Foreman, and Technicians shall possess current 2007 Belden s IBDN-700R certificate of completion for the system being provided. The installation of the Belden IBDN Gigabit System 2400 should be performed by employees of the Vendor and shall be required to provide proof of Belden authorization to install a Belden IBDN Gigabit System Installers: Due to the time restriction and the accelerated project schedule the Systems Contractor shall directly employ a minimum of ten (10) skilled systems installers with current 2007 IBDN-700R course certificate of completion and whose normal work is systems installation, who shall provide all systems equipment and who shall make the wire and cable connections thereto. All work should be performed and supervised by technicians and managers qualified to install and test the Belden IBDN Gigabit System 2400 in accordance with Belden requirements. The supervisor should have a minimum of 5 years experience and successfully completed Belden IBDN installation training provided by Belden. General condition Approved products Approved products Here is a list of approved products. Approved 4-pair UTP Cable: Belden IBDN Gigaflex 2400 Cable series (Cat. 6)

5 Approved RG 6 Cable: Belden 1189AP Coax Approved high pair count UTP Cable manufacturer: Belden Approved UTP connector product manufacturer: Belden Approved Rack and Cabinet manufacturer: Belden Approved IDC cross-connect system manufacturer: Belden Approved Patch Panel manufacturer: Belden Approved UTP Patch Cord manufacturer: Belden Approved Fiber Optic Cable: Corning Cable Systems Equivalent products Due to the nature and type of communications all products, including but not limited to faceplates, jacks, patch panels, racks, IDC blocks, copper cable products and patch cords, for the purpose of this document, should be manufactured by Belden. There will be no substitutions allowed. Building Communication Facilities General Guidelines concerning the number of communications outlets by room type are outlined below. Specific requirements for each room and each project shall be coordinated with the using agency at the onset of design for the project, the architect/engineer is cautioned that the Building Program also includes requirements, but may not be all inclusive regarding communication facilities. Therefore, the project architect/engineer must work very closely with appropriate Using Agency and Voice/Data/Communications personnel during initial planning to assure total coordination and minimize the need for revisions or changes at the second or design development document submittal stage. Sections 4 and 5 also contain data of concern to the project architect/engineer. Terminations Faculty/Administrative 0ffices - Each office shall have one communication outlet per 80 square feet. ((2) CAT6 per outlet)

6 Clerical/Staff Offices - One communication outlet per designated occupant plus one spare cabled outlet for every two (2) occupants or fraction thereof or one communication outlet per 80 square feet whichever is greater. ((2) CAT6 per outlet) Secretary/Administrative Assistant Offices - One communication outlet per designated occupant plus two outlets per office area or 2 extra outlets per five people or one communication outlet per 80 square feet whichever is greater. ((2)CAT6 per outlet) This extra facility allows for future growth and/or high density office/business machines used concurrently with other staff activities (perhaps facsimile transmission while using a word processor). Lab Conference Rooms - One communication outlet per 80 square feet with two CAT6 per outlet with a minimum of (1) Wireless Access Point Dormitories - One data communication outlet and one F type coaxial outlet for each planned occupant per dormitory room. (1) RJ45 (CAT6) per pillow. If the unit is single room, multiple occupancy units, the above specifications will apply to the room. All dormitory building facilities will also be provided with direct fiber optic connection to the campus backbone. This connection will consist of (12) 62.5/125 micron multimode fibers and (12) single mode fibers. Each dormitory facility will also include a Main Data Closet to house the active (SWITCH) equipment and the terminated fibers to the campus backbone. Two 48port POE switches per building & 6-10 access points per floor (transmission & security scanning) for the Wireless Network. Facilities Trunk and Access Facilities Copper (Twisted Pair / Coaxial) cables from the communication outlets described in the previous section should be connected to an accessible MDF/IDF close to the center of the terminations on each floor rather than at the single (or major) communications room for the building. The fiber cables from the communication outlets described in the previous section should be routed through an accessible MDF/IDF close to the center of the terminations on each floor and either home run or fusion splice onto high count riser cables that lead to the MDF where all data communications electronics will be located. Spaces, for a communications trunk to support future instructional needs, must interconnect laboratory, classroom, office pad areas, and the building communications equipment room. Cable tray (preferred and greater than 6 inch cross section) or a 4" conduit is an appropriate facility (raceway) if the actual needs are not known,

7 ROOM TEMPERATURE AND HUMIDITY - The ambient temperature shall be maintained between 60 and 68 degrees Fahrenheit and the relative humidity shall be maintained between 20 and 50 percent, unless otherwise specified. Temperature, and humidity requirements are on a 24-hour, 7 day-a-week basis regardless of the heat generated by normally operating communication equipment. Communications Equipment Room Space for connection of the building circuits to the outside plant should be provided as a separate room and not shared with other utility services, particularly the electrical service. When possible, it will not be adjacent to the electrical distribution room. Minimum room size is 100 square feet for MDF and 60 square feet for each IDF, A size may or may not be included in the Project Building Program. The project Architect/Engineer must, during the initial (Schematic-Preliminary) Planning stage, engage coordinated efforts of the Information Resource Manager s Office, Facilities Management and the Using Agency to assure appropriate size and arrangement of the communications equipment room(s). TELEPHONE - At least 1 Telephone per MDF / IDF. LIGHTING - All communications equipment rooms (MDF & IDF) shall have a light intensity of foot candles at 30 inches above the floor. DUST ELIMINATION - The walls, floors, and ceiling of all communications equipment rooms (MDF & IDF) shall be painted or otherwise treated to eliminate dust. If the walls are painted, a light colored, latex type paint should be used. BACKBOARD - All MDF & IDF shall have fire retardant plywood backboards 8'x4'x3/4" mounted on the back and side walls. The plywood backboard shall be affixed in such a manner that it will adequately support the weight of the cable, terminals, and other equipment that will be attached to it. The plywood backboard shall be treated with a fire retardant material. VERTICAL RISERS - Communications equipment rooms (IDF & MDF) contain the vertical cable riser space. The communications equipment rooms shall then provide vertical riser sleeves and bushings through the floor and/or ceiling to other vertically stacked communication equipment rooms. All sleeves shall be a minimum of 4 inches in diameter or sized to support the actual cabling requirements whichever is greater. Every communications equipment room should be equipped with a minimum of 5 riser sleeves; 2 for voice, 2 for data and 1 for video or any additional sleeves as required by actual cable needs. The communication equipment rooms shall be centrally located to optimize the length of the cable run to the telephone outlets. The length of a cable run shall not exceed 290 feet. In multi-level buildings, the communications equipment rooms should be located over the vertical cable riser space,

8 Special ventilation may be required for a battery back-up system in some buildings. Electrical Facility Relationships Building earth ground must be provided for all communications equipment rooms such that the DC resistance from the rooms to the building earth ground on the longest run does not exceed 0.5 ohms. In the MDF, at least six 12OV, 20 amp dedicated circuits with duplex outlets whose feeds are isolated from any motors, air conditioning or lighting circuits must be provided irrespective of room size. A separate small sub-panel with integrated surge suppression would provide the proper isolation in the MDF. At least three 12OV, 20 amp circuits with duplex outlets must be provided in the IDF. Although the electrical load is minimal (most terminals draw less than 1 amp), every component requires electrical 'service: modems, terminals, printers, etc. Each communication outlet (equipped or wired for) must be provided with a 12OV, 20 amp circuits with duplex outlet whose feed is isolated from any motors, air conditioning or lighting circuits. Electrical Electrical requirements Requirements for for all all MDF MDF / /IDF IDF are: are: (2) Quads with 110 (2) L620-UPS / switch (2)L630-UPS / switch Lock Access to all rooms or closets containing voice or data equipment will be through one uniform master key system. The standard key for all communications closets shall be a unique key under the Best lock grand master key system. No key will be issued by the Key Bank without the signed approval of the Director of Information Resource Manager Campus-wide Network Services. Security All MDF and IDF must have Proxy access. All users must be approved by the Director of Network Infrastructure and C.I.O. Outside Plant All new building construction planning must include a connection into existing tunnels or manholes and should connect via five (5) 4" conduits. These conduits would be for the data, voice and video facilities only. Whenever possible, all abandoned cable should be removed from tunnels, manholes, and conduit. If it is not feasible to remove said cable, it should be clearly tagged as abandoned and should be reported to the Information Resource Manager.

9 No cable should be installed in any facilities (raceways) other than those intended for that use. Gas pipe and water pipes must not be used for conduit under any circumstances. All buildings shall be wired with a 75 OHMS RG6 U coaxial cable. All buildings video topology shall be star-wired to a closed-circuit television (CCTV) stainless steel communications wall plate with F81 barrel splice termination. The signal strength at the F81 wall plate outlet shall be measured at no more than l0db. All connectors shall be one-piece crimp-on. All connections between the CCTV backbone network and the building communications closet shall be made with jacketed 1/2" coaxial cable or Single-mode fiber. All new building construction planning must include a connection to the campus fiber optic backbone which terminates in the Perry-Paige building. This backbone connection must consist of a 48 strand composite fiber optic cable (24 Single-mode and 24 Multimode. Outside Plant Fiber Optic Cable Specifications The 48 strand composite cable shall consist of 24 Multi Mode fibers and 24 Single Mode fibers with 2 sub groupings distributed as follows: 1 Multi Mode sub groupings containing 24 multi-mode fibers each and 1 single mode sub grouping containing 24 single-mode fibers. The Multi mode sub grouping will be individually color coded. The Single mode sub grouping will be individually color coded and imprinted with a black stripe or hash mark imprinted on the buffer tube. Multimode Fibers: All multi-mode fibers will be 62.5/125micron fiber. All cables will be of loose tube construction with the following fiber specifications: 100 KPSI proof tested; Core diameter 62.5um +/- 3um; Cladding diameter 125um +/- 2um; Core Non-Circularity less than or equal to 6%; Cladding Non -Circularity less than or equal to 2%; Numerical Aperture of / ; Coating Concentricity Greater than or equal to 0.7; Primary coating shall be 250 +/- 15 micron dual layered UV cured acrylate applied by the fiber manufacturer which may be mechanically or chemically stripped without damaging the fiber; Multi Mode attenuation less than or equal to nm and nm; minimum bandwidth of nm and nm (this specification shall be a maximum attenuation for each fiber over the entire operating temperature range of the cable). Single-mode Fibers:

10 All Single Mode fibers will be 8.3/125 micron fibers. All cables will be of loose tube construction with the following fiber specifications: 100 KPSI proof tested; Core diameter 8.3um; Numerical Aperture of 0.13; Cladding diameter 125um +/- 2um; Core to cladding offset of less than or equal to 0.8um; Cladding Non-Circularity of less than or equal to 1.0%; Coating Concentricity Greater than or equal to 0.7; Primary coating shall be 250 micron dual layered UV cured acrylate applied by the fiber manufacturer which may be mechanically or chemically stripped without damaging the fiber; The cabled fiber cutoff wavelength shall be less than or equal to 1250nm; Attenuation Uniformity - no point of discontinuity greater than 0.1db at either 1310nm or 1550nm; Single Mode attenuation less than or equal to nm and nm (this specification shall be a maximum attenuation for each fiber over the entire operating temperature range of the cable). General Cable Specifications: Optical fibers shall be placed inside a loose buffer tube containing up to 18 fibers. The fibers shall not adhere to the inside of the buffer tube. All optical fibers and buffer tubes shall be color coded per ANSI/EIA/TIA-568-B.3. In buffer tubes containing multiple fibers, the colors shall be stable during temperature cycling and not subject to fading or smearing onto each other or into the gel filling material. Colors shall not cause fibers to stick together. Fillers may be included in the cable core to lend symmetry to the cable cross-section where needed. The cable shall contain a central strength member composed of an all dielectric epoxy/glass composite. Each buffer tube and the cable core interstices shall be filled with a non-hygroscopic, non-nutritive to fungus, electrically non-conductive, homogenous gel. The gel shall be free from dirt and foreign matter. The gel shall be readily removable with conventional non-toxic solvents. Binders shall be applied with sufficient tension to secure the buffer tubes to the central member without crushing the buffer tubes. The binders shall be non-hygroscopic, non-wicking (or rendered so by the flooding compound), and dielectric with low shrinkage. Tensile strength shall be provided by high tensile strength aramid yarns and/or fiberglass. The high tensile strength aramid yarns/fiberglass shall be helically stranded evenly around the cable core. All dielectric cables (with no armoring) shall be sheathed with medium density polyethylene. The minimum nominal jacket thickness shall be 1.0 mm. Jacketing material shall be applied directly over the tensile strength members and flooding compound All fibers must be useable and meet minimum specifications, no spare fibers shall be included. The fiber optic cable shall withstand water penetration when tested with a one meter static head or equivalent continuous pressure applied at one end of a one meter length of filled cable for one hour. No water shall leak through the open cable end. Testing shall be done in accordance with FOTP-82, "Fluid Penetration Test for Filled Fiber Optic Cable.". The cable shall exhibit no flow (drip or leak) at 80 degrees C. The weight of any compound that drips from the sample shall be less than 0.05 grams (0.002 ounce). A representative sample of cable shall be tested in accordance with FOTP-81, "Compound Flow (Drip) Test for Filled Fiber Optic Cable.". The test sample shall be prepared in accordance with method A. All optical fibers shall be 100% attenuation tested. Outside Plant Fiber Optic Cable Specifications (Continued)

11 The attenuation of each fiber shall be provided with each cable reel. Cables shall have crush resistance of 220 N/cm, Flex resistance of 25 cycles, and impact resistance of 25 impacts. All cables will have tensile strength of greater than or equal to 2700N short term and 600N long term. Minimum bend radius for all cables will be less than or equal to 20 times the outside diameter under installation tensile load and 10 times the outside diameter under long term tensile load. All fibers in the cable must be useable fibers and meet required specifications. The cable provided will be new, unused, and of current design and manufacture. Outer jacket shall be fungus resistant, UV inhibited, Water resistant, and shall have a non wicking rip cord for easy removal. The outer jacket or sheath shall be free of holes splits or blisters. Outer cable jacket will be marked with "(Manufacturer s Name) Optical Cable", Sequential foot or meter markings, and year of manufacture. The height of the markings shall be approximately 2.5mm. The cable jacket shall contain no metal elements and shall be of a consistent thickness. The outer jacket color shall be black. NETWORK DESIGN Each building or physically connected building complex will support user connections at 10/100/1000 full duplex switch Ethernet speed. The main switch for the building shall be equipped with an Gigabit switch capable of performing LES/BUS/LANE functions should it s connection from the campus backbone become inoperative and should connect to the campus backbone via redundant load sharing Gigabit Single mode or Multimode links. NETWORK SWITCHING EQUIPMENT Each network switch will have as a minimum the following functions. Backplane support for switched GBPS speeds Ethernet. Backplane support for Gigabit switching Uplink capability forms the switched Ethernets to the Gigabit switch fabric. Each switch shall include redundant load balancing power supplies capable of N+1 redundancy. Full SNMP Management of all chassis/bridging functions. Support the LANE, PNNI, and MPOA standards that are current at the time of acquisition. Support upgrades to Layer 3 switching as the standards become established. Full RMON support for all RMON groups standardized at the time of acquisition.

12 Per port RMON / RMON II support for all switched Ethernet ports as well as port replication. Support for out of band / side band network management via isolated 100 or 1000 MB Ethernet. Wiring Closet Power Supplies Each wiring closet will be provided with one or more rack mounted uninterruptable power supplies of sufficient capacity to power all active data equipment within the closet Each UPS will be fully SMNP manageable or shall be capable of being managed through the switching equipment. Testing and Certification COPPER TWISTED PAIR CABLE Each station cable will be tested for continuity from the closet to the workstation. This test shall verify continuity, determine the proper polarity and verify proper location of each pair of the 4 pair cable. In addition to a continuity test each station will be tested with a 100 or 1000Mb tester to verify each station location to be category 6 compliant. The tester shall provide a hard copy printout of each cable tested. Each pair will be checked for noise level and signal loss. The total loss for a cable shall not exceed -5db. This test shall be performed on the four common bands (1-4). Band 1 Low 10Khz-150Khz; Band 2 ALL 10Khz-100Mhz; Band 3 High 10Mhz-100Mhz; Band 4 Impulse noise. Each cable will be scanned for length bi-directionally with an automated test unit, If the distance readings are different the cable must be tested for faulty punch downs. Each cable tested is to be recorded in a log with the cable number, date, and the initials of the technician who tested the cable. A printout of the test results for each cable shall be placed in the log. Any cables failing the above tests shall be replaced. A copy of the logs, a termination sequence chart, and all test results shall be provided to the Information Resource Manager prior to acceptance of the job as satisfactory and complete. FIBER OPTIC CABLE Testing and certification will be performed by the installing contractor to verify the correctness of termination and overall transmission loss using an approved fiber optic transmission loss test instrument.

13 A certification report shall be provided listing the calculated and measured loss at both 850 and 1300 nanometers for multimode fibers and 1310 nanometers for single mode fibers. The certification report shall also include the installed lengths for all fibers within the cables that have been provided. All cabling will be tested bi-directionally with an optical power meter with printouts of the results for each fiber provided as part of the certification documents. All fibers will also be tested bi-directionally with an OTDR and printouts of the traces for each fiber will be provided as part of the certification documents. The University desires to achieve the following minimum results. All Multi Mode cables not to exceed 1 db plus.0013 db per foot end to end attenuation at 850nm All Single Mode cables not to exceed 1 db plus.0008 db per foot end to end attenuation at 1310nm Approval of the test results will be made by the Information Resource Manager before the project is accepted by the University as satisfactory and completed. CABLE TV (Campus Cable Television System) CCTS Cable TV outlets should consist of (1) RG-6 per TV location. All Cable TV request should be entered into the EIT TMS Service Request system and approvals are made by the Director of Network Infrastructure. FACILITY INFORMATION RESOURCE REQUIREMENTS This facility includes areas to be used as laboratory and classroom space as well as staff and support offices. The nature of these offices requires the need for communication and computing. Additionally these areas will have the need for video transmission that originates within the facilities. Computing hardware for Laboratory, classroom, and office workstations will be acquired in various platforms IE: PC compatible, Macintosh, UNIX, etc. For each of these platforms current minimum standards are: PC/Compatible: Pentium 4.xGhz Pentium IV, 4GB RAM, 120GB Fixed disk, 64x CDRW, 16bit sound card and speakers (MPC2 Compatible), and network card appropriate to the facility that the equipment will be located in. Macintosh: G4, 4GB RAM, 300GB Fixed disk, 64x CDROM, and network card appropriate to the facility that the equipment will be located in. UNIX: 32bit 1GHz RISC processor, 1GB RAM, 80GB Fixed disk, 48x CDROM, and network card appropriate to the facility that the equipment will be located in.

14 The specifications for these platforms will be upgraded to meet the standards at the time of acquisition. To enable printing within the facility a variety of printing devices will be acquired, including 1 or more high volume (greater than 15PPM) laser printers and smaller individual printers as required. The information resource needs for classrooms and laboratories will depend upon the specific design and use of those classroom and laboratory facilities. As part of this equipment, included are large screen video projection units capable of reproduction of computerized video and other types of media. Large projection screens, VCRs, LaserDisc / CD players, document cameras, and specialized sound systems will also be included. Video conferencing equipment capable of facilitating distances learning activities and functional with the campus wide information technology system design and interactive video conferencing delivery systems will be installed in appropriate areas.

home site map help ECMS Project: 70197 Standard / Federal Oversight Advertised

home site map help ECMS Project: 70197 Standard / Federal Oversight Advertised Page 1 of 6 S PECIAL PROVISION home site map help ECMS BP ADMIN Project: 70197 Standard / Federal Oversight Advertised Short Description: US 422 Schuylkill River Bridge - D/B: Retaining Wall; ITS Devices;

More information

DIVISION 27 COMMUNICATIONS. A. System design shall be completed by a Registered Communications Distribution Designer (RCDD).

DIVISION 27 COMMUNICATIONS. A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). DIVISION 27 COMMUNICATIONS 27 00 00 COMMUNICATIONS A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). B. Comply with American National Standards Institute

More information

Presenters Brett Weiss, Gabe Martinez, Brian Kroeger.

Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. 1 Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. Topics to be covered: Cable identification Purpose of the various cable types Installation techniques Building Infrastructure Overview of networking

More information

Network Design. Yiannos Mylonas

Network Design. Yiannos Mylonas Network Design Yiannos Mylonas Physical Topologies There are two parts to the topology definition: the physical topology, which is the actual layout of the wire (media), and the logical topology, which

More information

1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications.

1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications. Issued 2005/06/01 Section 16743 Data System Page 1 of 7 PART 1 GENERAL 1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications..2 Data system equipment

More information

1. Furnish and install faceplate and modular jacks at each single gang outlet as described below:

1. Furnish and install faceplate and modular jacks at each single gang outlet as described below: Washington University in St. Louis Building: Communication Specification: Research Voice/Network/Typical 1. Furnish and install faceplate and modular jacks at each single gang outlet as described below:

More information

Fiber Optic Specifications

Fiber Optic Specifications Fiber Optic Specifications All Fiber Optic shall be Corning Altos Single Mode OS1 Outdoor Loose Tube Gel Free Cable Corning Fiber Products only will be accepted and no substitutions or alternates will

More information

ATTACHMENT F 050R6800016 - CABLE AND WIRING SERVICES FUNCTIONAL AREA I PRICE PROPOSAL FORM Amendment 6

ATTACHMENT F 050R6800016 - CABLE AND WIRING SERVICES FUNCTIONAL AREA I PRICE PROPOSAL FORM Amendment 6 050R6800016 CABLE AND WIRING SERVICES (Column A) (Column B) (Column C) (Column D) (Column E) (Column F) (Column G) (B+C+D+E)*F= G Item Description PER 100' RUN PER 150' RUN PER 200' RUN PER 300' RUN QUANTITY

More information

SECTION 680 FIBER OPTIC CABLE DESCRIPTION

SECTION 680 FIBER OPTIC CABLE DESCRIPTION 680 SECTION 680 FIBER OPTIC CABLE DESCRIPTION 680.01.01 GENERAL A. The work under this section shall consist of furnishing, installing, and testing all underground and outdoor fiber optic cables. B. All

More information

Specifying an IT Cabling System

Specifying an IT Cabling System Specifying an IT Cabling System This guide will help you produce a specification for an IT cabling system that meets your organisation s needs and gives you value for money. You will be able to give your

More information

DEPARTMENTAL REGULATION

DEPARTMENTAL REGULATION U.S. DEPARTMENT OF AGRICULTURE WASHINGTON, D.C. 20250 DEPARTMENTAL REGULATION SUBJECT: Service Center Technology Modernization Project (SCTMP) Wiring/Cabling Specifications for Service Center Agencies

More information

CORNING CABLE SYSTEMS GENERIC SPECIFICATION FOR TIGHT BUFFER OPTICAL FIBER CABLES FOR INTER- AND INTRABUILDING APPLICATIONS.

CORNING CABLE SYSTEMS GENERIC SPECIFICATION FOR TIGHT BUFFER OPTICAL FIBER CABLES FOR INTER- AND INTRABUILDING APPLICATIONS. CORNING CABLE SYSTEMS GENERIC SPECIFICATION FOR TIGHT BUFFER OPTICAL FIBER CABLES FOR INTER- AND INTRABUILDING APPLICATIONS September 2006 Revision 7 Corning Cable Systems reserves the right to update

More information

ANSI/TIA/EIA - 568-A, Commercial Building Telecommunications Cabling Standard.

ANSI/TIA/EIA - 568-A, Commercial Building Telecommunications Cabling Standard. WIRING STANDARD INTRODUCTION This standard defines a telecommunications wiring system for North Dakota State Agencies, offices or buildings that will support a multi-product environment. The purpose of

More information

SECTION 16121 FIBER OPTIC CABLE AND ACCESSORIES

SECTION 16121 FIBER OPTIC CABLE AND ACCESSORIES SECTION 16121 FIBER OPTIC CABLE AND ACCESSORIES PART 1 GENERAL 1.1 Summary A. This section includes the components and fiber optic cable necessary to provide a network Connection as indicated. The components

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-27 05 14.00 10 (April 2006) -------------------------------- Preparing Activity: USACE Superseding UFGS-27 05 14.00 10 (April 2004) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

Cable Installation Project

Cable Installation Project Cable Installation Project 1. Intent. It is the intent of the U.S. Court of Appeals to install Category 6 (CAT6) data cabling in the Robert F. Peckham Federal Building and United States Courthouse, 280

More information

UT Southwestern Medical Center Information Resources Cable Installation Standard

UT Southwestern Medical Center Information Resources Cable Installation Standard UT Southwestern Medical Center Information Resources Cable Installation Standard PART 1- GENERAL 1.01 SUMMARY A. Furnish and install wire, cable, devices, equipment, and accessories for a complete system

More information

SECTION 25110 TELECOMMUNICATION ROOMS

SECTION 25110 TELECOMMUNICATION ROOMS PART 1 - GENERAL 1.1 SUMMARY A. SCOPE SECTION 25110 TELECOMMUNICATION ROOMS 1. This section includes the minimum installation requirements for equipment and cabling infrastructure in Telecommunication

More information

TCTC Cabling Specifications

TCTC Cabling Specifications TCTC Cabling Specifications Purpose: To provide a standard specification that will be used for all Tri County Technical College (TCTC) facilities requiring structured cabling installation. Product specifications,

More information

Structured Wiring Specifications ERAU Daytona Beach Campus (Dec 14 2011)

Structured Wiring Specifications ERAU Daytona Beach Campus (Dec 14 2011) Structured Wiring Specifications ERAU Daytona Beach Campus (Dec 14 2011) A. Objectives The Information Technology (IT) Department of Embry-Riddle Aeronautical University (ERAU) seeks to establish a standards-based

More information

Cabling Services (price per pull) Zone 1 Zone 2 Zone 3 Zone 4 Zone 5

Cabling Services (price per pull) Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 BryComm, LLC -SDD-1901 Cabling Services (per pull) - Labor Only STANDARD TIME The price per cable pull represents all labor to include fishing walls, running cable through modular furniture, terminating,

More information

SECTION 27 13 24 COMMUNICATIONS OPTICAL FIBER OSP CABLING

SECTION 27 13 24 COMMUNICATIONS OPTICAL FIBER OSP CABLING SECTION 27 13 24 COMMUNICATIONS OPTICAL FIBER OSP CABLING PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete

More information

University of Houston. Telecommunication Cabling Standards

University of Houston. Telecommunication Cabling Standards University of Houston Information Technology Telecommunication Cabling Standards As prepared by IT Network Operations University of Houston, Telecommunication Cabling Standard - Page 1 Table of Contents

More information

SECTION 16750. TELECOMMUNICATIONS SYSTEM (Cat 6)

SECTION 16750. TELECOMMUNICATIONS SYSTEM (Cat 6) SECTION 16750 TELECOMMUNICATIONS SYSTEM (Cat 6) PART 1 - GENERAL 1.01 REQUIREMENTS A. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements, apply

More information

STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENTAL SPECIFICATION 804 FIBER OPTIC CABLE FOR TRAFFIC SIGNAL INTERCONNECT JANUARY 19, 2007

STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENTAL SPECIFICATION 804 FIBER OPTIC CABLE FOR TRAFFIC SIGNAL INTERCONNECT JANUARY 19, 2007 804.01 Description 804.02 General 804.03 Materials 804.04 Fan-Out Kit 804.05 Drop Cable 804.06 Fiber Optic Patch Cord 804.07 Termination Panel 804.08 Fusion Splice 804.09 Fiber Optic Connector 804.10 Splice

More information

Request for Proposal (RFP) IP Cameras/Door Access Control

Request for Proposal (RFP) IP Cameras/Door Access Control WAHPETON PUBLIC SCHOOLS Information Technology Department Request for Proposal (RFP) IP Cameras/Door Access Control Inquiries and requests regarding this RFP should be directed to: Jason Pfahl, Director

More information

BLACK BOX. Secure network ports from unauthorized access and accidental disconnects.

BLACK BOX. Secure network ports from unauthorized access and accidental disconnects. FC black process black LockPORT Security Patch Cables CAT5e, CAT6 and Fibre 5th black Secure network ports from unauthorized access and accidental disconnects. BLACK BOX» LockPORT cables stay locked in

More information

Structured and Point to Point Network Cabling for Industrial Automation

Structured and Point to Point Network Cabling for Industrial Automation Structured and Point to Point Network Cabling for Industrial Automation Introduction Industrial automation systems are undergoing dramatic transformations that require businesses to adopt new strategies

More information

The following terms are defined within the context of the fiber optic industry

The following terms are defined within the context of the fiber optic industry The following terms are defined within the context of the fiber optic industry Adapter A mechanical media termination device designed to align and join fiber optic connectors. Often referred to as coupling,

More information

March 2007. 27 08 00 Commissioning of Communications. See Appendix E3. 27 08 00-1

March 2007. 27 08 00 Commissioning of Communications. See Appendix E3. 27 08 00-1 March 2007 27 08 00 Commissioning of Communications See Appendix E3. 27 08 00-1 27 11 00 Communications Equipment Room Fittings 1.0 General TELEPHONE RISERS: A. All copper telephone riser cables must be

More information

21 st Century Campus Network Responsibility Matrix 5/26/10

21 st Century Campus Network Responsibility Matrix 5/26/10 Definitions: DoIT Standards This column details the minimal configuration, which DoIT has defined in order to provide a campus-wide standard level of service. Departments may request services, which exceeds

More information

The Optical Fiber Ribbon Solution for the 10G to 40/100G Migration

The Optical Fiber Ribbon Solution for the 10G to 40/100G Migration The Optical Fiber Ribbon Solution for the 10G to 40/100G Migration Bill Charuk, SR Product Manager, Data Center Solutions Introduction With the advent of data centers in communication infrastructure, various

More information

SECTION 16715 TELECOMMUNICATIONS ACCEPTANCE TESTING

SECTION 16715 TELECOMMUNICATIONS ACCEPTANCE TESTING PART 1 - GENERAL 1.1 SECTION INCLUDES A. Testing Publications and Standards B. Inspection and testing procedures for copper and fiber optic cable, RF CATV / MATV systems, and the antenna systems. C. Documentation

More information

Cabling and Building Infrastructure for Technology

Cabling and Building Infrastructure for Technology Cabling and Building Infrastructure for Technology by: Ernest J. Schirmer, Director Information Technology Infrastructure Design CUH2A Architecture Engineering Planning 211 Carnegie Center Princeton, NJ

More information

DIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION

DIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION DIVISION 26 - ELECTRICAL PART 1 - GENERAL 1.01 SUMMARY A. Section Includes 1. Instrumentation Cables 1.02 SUBMITTALS A. Submit in accordance with requirements of Section 01 33 00. B. Product Data: Submit

More information

FIBER OPTIC CABLE PLANT DOCUMENTATION

FIBER OPTIC CABLE PLANT DOCUMENTATION C H A P T E R 13 FIBER OPTIC CABLE PLANT DOCUMENTATION JIM HAYES Documenting the fiber optic cable plant is a necessary part of the design and installation process for the fiber optic network. Documenting

More information

REQUEST FOR BID AS-NEEDED CABLING SERVICES FOR COUNTY FACILITIES

REQUEST FOR BID AS-NEEDED CABLING SERVICES FOR COUNTY FACILITIES REQUEST FOR BID AS-NEEDED CABLING SERVICES FOR COUNTY FACILITIES SECTION 1 REQUIREMENTS AND GUIDELINES INTRODUCTION The County of El Paso ( County ) is issuing this Request for Bid ( Solicitation ) to

More information

Table of Contents. Fiber Trunking 2. Copper Trunking 5. H-Series Enclosures 6. H-Series Mods/Adapter Panels 7. RSD Enclosures 8

Table of Contents. Fiber Trunking 2. Copper Trunking 5. H-Series Enclosures 6. H-Series Mods/Adapter Panels 7. RSD Enclosures 8 Data Center Guide 1 Our Philosophy As a leader in the enterprise cable industry since our inception over three decades ago, we can help you implement the solution that will work best for your cabling infrastructure,

More information

The color scheme for the fibers in the cable complies with the Telcordia (formerly Bellcore) specification.

The color scheme for the fibers in the cable complies with the Telcordia (formerly Bellcore) specification. 10 Cables The cables referred to below are provided with standard single- and multimode fibers. Other commercially available fibers can be provided on request. The bare fibers are colored in all cases

More information

Implementing Fast Ethernet

Implementing Fast Ethernet Implementing Fast Ethernet R The Next Generation of Ethernet Fast Ethernet (also known as IEEE 802.3u or 100BASE-T) is quickly becoming the successor to Ethernet as the network topology of choice. Fast

More information

Wired and Wireless Network Request for Proposal New Washington County High School Facility

Wired and Wireless Network Request for Proposal New Washington County High School Facility Washington County Board Of Education P.O. Box 716 501 Industrial Drive Sandersville, GA 31082 (478) 552-3981 FAX (478) 552-3128 Description Wired and Wireless Network Request for Proposal New Washington

More information

SECTION 271525 OPTICAL FIBER CABLES AND ACCESSORIES. A. Interior Raceways, Fittings, and Accessories: Section 260532.

SECTION 271525 OPTICAL FIBER CABLES AND ACCESSORIES. A. Interior Raceways, Fittings, and Accessories: Section 260532. SECTION 271525 OPTICAL FIBER CABLES AND ACCESSORIES PART 1 GENERAL 1.01 RELATED WORK SPECIFIED ELSEWHERE A. Interior Raceways, Fittings, and Accessories: Section 260532. B. Wiring, General - 600 Volts

More information

HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE: 10.17.12

HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE: 10.17.12 SECTION 27 05 26 - GROUNDING AND BONDING FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes grounding and bonding products, design requirements and installation for communications

More information

NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION 27 10 00 STRUCTURE CABLING TESTING

NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION 27 10 00 STRUCTURE CABLING TESTING RELATED SECTIONS: NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT Section 27 00 00 General Requirements Section 27 02 00 General Communication Requirements Section 27 05 26 Grounding and Bonding for Communications

More information

Network Telecommunications Design Standards Last Updated June 2013. Youngstown State University

Network Telecommunications Design Standards Last Updated June 2013. Youngstown State University 1 Network Telecommunications & Security Youngstown State University One University Plaza Youngstown, OH 44555 Network Telecommunications Design Standards Last Updated June 2013 Youngstown State University

More information

Minimum Standards for Data/Voice Infrastructure in New Building Construction

Minimum Standards for Data/Voice Infrastructure in New Building Construction UNIVERSITY OF WATERLOO Minimum Standards for Data/Voice Infrastructure in New Building Construction 12/17/2012 Offices 1. Two Work Area Outlets (WAO) on opposite walls, each with 2 jacks 2. Each WAO shall

More information

Accelerating Light. Copper Cabling Solutions. Category 6A

Accelerating Light. Copper Cabling Solutions. Category 6A Accelerating Light Copper Cabling Solutions Category 6A Category 6A Copper Cabling Solutions Fibernet designs and manufactures premium, high performance copper communication infrastructure and connectivity

More information

Discontinued. Volition. Fiber Optic Cable. 3Innovation

Discontinued. Volition. Fiber Optic Cable. 3Innovation Volition Fiber Optic Cable Tough enough to take it. Easy to handle. The Volition Network Solution from 3M includes horizontal and backbone cable with 62.5/125 µm and 50/125 µm multimode fiber, and 9/125

More information

Reliable, Consistent, Quality

Reliable, Consistent, Quality Reliable, Consistent, Quality 1-877-320-3143 www.fibertronics.com Reliable, Consistent, Quality Welcome To Fibertronics Inc. Reliability, consistency, and quality is what we put behind every Fiber optic

More information

CommScope Intelligent Building Infrastructure Solutions (IBIS)

CommScope Intelligent Building Infrastructure Solutions (IBIS) SYSTIMAX Solutions CommScope Intelligent Building Infrastructure Solutions (IBIS) Questions & Answers Q. What is an Intelligent Building? A. An intelligent building can be defined as one which provides

More information

RF Video Distribution System. Why Z-Band is The Right Choice for Quality Video

RF Video Distribution System. Why Z-Band is The Right Choice for Quality Video RF Video Distribution System Why Z-Band is The Right Choice for Quality Video Requirements for Quality RF Video Correct Signal & Noise Levels from Source/s Correct Signal & Noise Levels from Backbone Cabling

More information

Structured Cabling Network Services & Equipment Inside/Outside Plant Design Trenching

Structured Cabling Network Services & Equipment Inside/Outside Plant Design Trenching Structured Cabling Network Services & Equipment Inside/Outside Plant Design Trenching 502 Buffalo Rd., Ft. Pierre, SD 57532 (605) 224-1111 or (800) 747-6427 www.windcircle.net sales@windcircle.net Computers

More information

SECTION 16750 VOICE AND DATA COMMUNICATION CABLING

SECTION 16750 VOICE AND DATA COMMUNICATION CABLING SECTION 16750 VOICE AND DATA COMMUNICATION CABLING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Store drawing set and general provisions of the Contract, including General and Supplementary Conditions and

More information

TIA 569 Standards Update Pathways & Spaces. Ignacio Diaz, RCDD April 25, 2012

TIA 569 Standards Update Pathways & Spaces. Ignacio Diaz, RCDD April 25, 2012 TIA 569 Standards Update Pathways & Spaces Ignacio Diaz, RCDD April 25, 2012 The purpose of this Standard is to standardize specific pathway and space design and construction practices in support of telecommunications

More information

FTE Cabling Best Practices Author: Todd Bill, RCDD/NTS

FTE Cabling Best Practices Author: Todd Bill, RCDD/NTS FTE Cabling Best Practices Author: Todd Bill, RCDD/NTS Document ID: WP-07-01-ENG Original Issue Date: May 2007 Version: 1.0 FTE Cabling Best Practices 1 Table of Contents Introduction and Applicable Standards...3

More information

1 Campus Cabling Systems Introduction

1 Campus Cabling Systems Introduction 1 Campus Cabling Systems Introduction This document represents the campus cable and infrastructure standards adopted and supported by the XXXX. All new construction and renovation should conform to these

More information

Special Specification 6033 Computerized Transportation Management System

Special Specification 6033 Computerized Transportation Management System 6033 Special Specification 6033 Computerized Transportation Management System 1. DESCRIPTION Relocate computerized transportation management system (CTMS) equipment as shown on the plans and as described

More information

SEAGATE SOFTWARE. About Seagate Software. IBDN Success Stories Technology. Currently, Seagate Software has customers in more than 75 countries

SEAGATE SOFTWARE. About Seagate Software. IBDN Success Stories Technology. Currently, Seagate Software has customers in more than 75 countries About Seagate Software Seagate Software is an international software corporation headquartered in Scotts Valley, California. Established in 1984 as Crystal Services Inc., Seagate Software was purchased

More information

SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM

SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION INTELLIGENT REPORTING FIRE DETECTION SYSTEM PART 1 GENERAL 1.1 DESCRIPTION A. This specification includes the furnishing,

More information

Chapter 4 Connecting to the Internet through an ISP

Chapter 4 Connecting to the Internet through an ISP Chapter 4 Connecting to the Internet through an ISP 1. According to Cisco what two things are essential to gaining access to the internet? a. ISPs are essential to gaining access to the Internet. b. No

More information

Request for Quote E-Rate Eligible Services Scope of Work - Internal Connections: Network Infrastructure Equipment and Cabling

Request for Quote E-Rate Eligible Services Scope of Work - Internal Connections: Network Infrastructure Equipment and Cabling Request for Quote E-Rate Eligible Services Scope of Work - Internal Connections: Network Infrastructure Equipment and Cabling Due Date: Allowable Contract Date from Posted 470 The Saddle Mountain Unified

More information

a. Design or design review of Voice, Data, and Wireless systems b. Copper cable manufacturer selection for new buildings and large scale renovations.

a. Design or design review of Voice, Data, and Wireless systems b. Copper cable manufacturer selection for new buildings and large scale renovations. 5.18 Voice and Data Distribution 5.18.1 General Introduction 1. This standards document is to be used for any projects on the University of Calgary campus that involves the voice and data distribution

More information

Innovation. Volition Network Solutions. Leading the way in Network Migration through Innovative Connectivity Solutions. 3M Telecommunications

Innovation. Volition Network Solutions. Leading the way in Network Migration through Innovative Connectivity Solutions. 3M Telecommunications 3M Telecommunications Solutions for Networks Volition Network Solutions Leading the way in Network Migration through Innovative Connectivity Solutions Innovation The Broadband Migration Path 3M TM Volition

More information

Business Customer Demarcation Information

Business Customer Demarcation Information Building Industry Consulting Service (BICS) Business Customer Demarcation Information The intent of this document is to clearly define Communications terminology and deployment with reference to business

More information

Quick Installation Guide 24-port PoE switch with 2 copper Gigabit ports and 2 Gigabit SFP ports (af Version 15.4W)

Quick Installation Guide 24-port PoE switch with 2 copper Gigabit ports and 2 Gigabit SFP ports (af Version 15.4W) Quick Installation Guide 24-port PoE switch with 2 copper Gigabit ports and 2 Gigabit SFP ports (af Version 15.4W) Table of Contents Introduction.. Power Over Ethernet (PoE) & Features.... Unpacking and

More information

NUIG Campus Network - Structured Cabling System Standards Information s Solutions & Services (ISS)

NUIG Campus Network - Structured Cabling System Standards Information s Solutions & Services (ISS) NUIG Campus Network - Structured Cabling System Standards Information s Solutions & Services (ISS) Revision date 28 th January 2014 The purpose of this document is to assist Building Refurbishment and

More information

RoHS DATA, COAXIAL AND ELECTRONIC M.R. D A TA, C O A X I A L, ECOLGICAL Telecom Cables A N D EL E CTRON I C. Cables

RoHS DATA, COAXIAL AND ELECTRONIC M.R. D A TA, C O A X I A L, ECOLGICAL Telecom Cables A N D EL E CTRON I C. Cables RoHS DATA, COAXIAL AND ELECTRONIC D A TA, C O A X I A L, A N D EL E CTRON I C Cables Index SOLID MULTI-CONDUCTOR CABLES STRANDED MULTI-CONDUCTOR CABLES SPEAKER/ZIP WIRE THERMOSTAT CABLE FIRE ALARM CABLE

More information

Networks. The two main network types are: Peer networks

Networks. The two main network types are: Peer networks Networks Networking is all about sharing information and resources. Computers connected to a network can avail of many facilities not available to standalone computers: Share a printer or a plotter among

More information

HIGHSPEED ETHERNET THE NEED FOR SPEED. Jim Duran, Product Manager - Americas WHITE PAPER. Molex Premise Networks

HIGHSPEED ETHERNET THE NEED FOR SPEED. Jim Duran, Product Manager - Americas WHITE PAPER. Molex Premise Networks HIGHSPEED ETHERNET THE NEED FOR SPEED Jim Duran, Product Manager - Americas WHITE PAPER Molex Premise Networks EXECUTIVE SUMMARY Over the years structured cabling systems have evolved significantly. This

More information

Specifications for Communication Cabling Distribution Systems

Specifications for Communication Cabling Distribution Systems Washington University in St. Louis Specifications for Communication Cabling Distribution Systems General Overview Listed below are the separate sub-systems of Washington University s structured cabling

More information

Information and Communication Technology Network Cabling Infrastructure Standard

Information and Communication Technology Network Cabling Infrastructure Standard Approved on Dec-2005 by Eugene Formato Manager, Communications Services Last Amended Aug-2009 by Jarren Beveridge Network Engineer, Communications Services Scheduled for Review Jan-2010 Information and

More information

Structured Cabling, Earthing & Equipotential Bonding

Structured Cabling, Earthing & Equipotential Bonding White Paper Information and Communication Technology Structured Cabling, Earthing & Equipotential Bonding English Rev. 1.0.1 / 2012-06-01 1 Abstract All Dallmeier network products (PoE cameras, recorders,

More information

TELECOMMUNICATIONS NETWORK STANDARDS AND GUIDELINES FOR THE NEW ADMINISTRATION BULDING

TELECOMMUNICATIONS NETWORK STANDARDS AND GUIDELINES FOR THE NEW ADMINISTRATION BULDING TELECOMMUNICATIONS NETWORK STANDARDS AND GUIDELINES FOR THE NEW ADMINISTRATION BULDING October 1998 Table of Contents SECTION I: New Construction Programming 1.0 New Construction 1.1 Design Elements..................................

More information

How To Set Up A Minipatch System For A Small Office Or Home Use

How To Set Up A Minipatch System For A Small Office Or Home Use Issue : 4 Wood Communications Networking Products Catalogue Small Office & Home Solution Small Office / Home Solution Min LAN Comms Cabinets - Multimedia Panel - Soho Ethernet Switches - Multiroom Audio/Video,

More information

Cabling Requirements for the District of Columbia on behalf of the Criminal Justice Coordinating Council

Cabling Requirements for the District of Columbia on behalf of the Criminal Justice Coordinating Council Cabling Requirements for the District of Columbia on behalf of the Criminal Justice Coordinating Council Date: 6/19/2013 Version: 1.0 Prepared by: Gregory Cotten Department of General Services District

More information

B. PART 1 - GENERAL of SECTION 271300 BACKBONE COMMUNICATIONS CABLING shall also apply to this section.

B. PART 1 - GENERAL of SECTION 271300 BACKBONE COMMUNICATIONS CABLING shall also apply to this section. SECTION 271500 - HORIZONTAL UTP CABLING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Terminating 25-Pair Cable and 4-Pair Cross Connects

Terminating 25-Pair Cable and 4-Pair Cross Connects Terminating 25-Pair Cable and 4-Pair Cross Connects Estimated Time: 90 minutes Number of Teams: 2 Number of Team Members: one to four This Lab has four major parts that will be addressed separately. 1.

More information

Cat7/Class F New Installation Concept New infrastructure. Handbook

Cat7/Class F New Installation Concept New infrastructure. Handbook Cat7/Class F New Installation Concept New infrastructure Handbook contents 1 Introduction 3 2 What is the Cat7/Class F installation concept 3 3 Distribution centre 3 3.1 Patch Modules 3 4 How to handle

More information

SECTION 28 05 00 COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND SECURITY

SECTION 28 05 00 COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND SECURITY SECTION 28 05 00 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specifications Sections, apply

More information

Standards. www.nordx.com 5 ANSI/TIA/EIA-569-A (CSA T530)

Standards. www.nordx.com 5 ANSI/TIA/EIA-569-A (CSA T530) The primary focus of this standard is to provide design specifications and guidance for all building facilities relating to telecommunications cabling systems and components. This standard identifies and

More information

Division 27 Master Specification for

Division 27 Master Specification for Division 27 Master Specification for Information Transport Systems and Spaces May 1, 2014 1 Table of Contents 1 Section 27 10 01 Structured Cabling General Requirements 1.1 Scope 1.2 Approved Contractor

More information

STRUCTURED CABLE SPECIFICATION INFORMATION SYSTEMS AND SERVICES ISSUE 1 NOVEMBER 2011

STRUCTURED CABLE SPECIFICATION INFORMATION SYSTEMS AND SERVICES ISSUE 1 NOVEMBER 2011 STRUCTURED CABLE SPECIFICATION INFORMATION SYSTEMS AND SERVICES ISSUE 1 NOVEMBER 2011 Project Ref. Project Name Project Manager Date issued... Consultant/Contractor... 1 CONTENTS 1000 GENERAL OVERVIEW

More information

SECTION 27 08 23 TESTING OF FIBER OPTIC CABLES

SECTION 27 08 23 TESTING OF FIBER OPTIC CABLES SECTION 27 08 23 TESTING OF FIBER OPTIC CABLES PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction,

More information

DOUBLE STAINLESS STEEL TUBE DTS FIBER OPTIC CABLE FTSF-FSUTS(DTS)

DOUBLE STAINLESS STEEL TUBE DTS FIBER OPTIC CABLE FTSF-FSUTS(DTS) DOUBLE STAINLESS STEEL TUBE DTS FIBER OPTIC CABLE FTSF-FSUTS(DTS) Double Jelly Filled Stainless Steel Tube General Description This document specifies non armour sensing fiber cable with double stainless

More information

AMP NETCONNECT CABLING SYSTEMS FOR DATA CENTERS & STORAGE AREA NETWORKS (SANS) High-density, High Speed Optical Fiber and Copper Solutions

AMP NETCONNECT CABLING SYSTEMS FOR DATA CENTERS & STORAGE AREA NETWORKS (SANS) High-density, High Speed Optical Fiber and Copper Solutions AMP NETCONNECT CABLING SYSTEMS FOR DATA CENTERS & STORAGE AREA NETWORKS (SANS) High-density, High Speed Optical Fiber and Copper Solutions TABLE OF CONTENTS TABLE OF CONTENTS... 2 INTRODUCTION... 3 CABLING

More information

B. Cross-Connect: A facility enabling the termination of cable elements and their interconnection or cross-connection.

B. Cross-Connect: A facility enabling the termination of cable elements and their interconnection or cross-connection. DIVISION 16 ELECTRICAL Section 16740 Telephone System PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

UTSC CABLE SYSTEMS SPECIFICATION SITE DESIGN CRITERIA DESIGN REQUIREMENTS INSTALLATION PRODUCTS

UTSC CABLE SYSTEMS SPECIFICATION SITE DESIGN CRITERIA DESIGN REQUIREMENTS INSTALLATION PRODUCTS UTSC CABLE SYSTEMS SPECIFICATION SITE DESIGN CRITERIA DESIGN REQUIREMENTS INSTALLATION PRODUCTS University of Toronto Scarborough Cable Systems Specification 1/23 Network Administrators Glenn Attwood Manager,

More information

DESIGN GUIDELINES. Local Area Network

DESIGN GUIDELINES. Local Area Network DESIGN GUIDELINES Local Area Network The total oversight and management responsibilities for information assurance (IA) and protection of DoDEA s critical infrastructure fall under the purview of the DoDEA

More information

TELECOMMUNICATIONS STRUCTURED CABLING GUIDELINES AND SPECIFICATIONS. University of Chicago IT Services Infrastructure Services October 2011

TELECOMMUNICATIONS STRUCTURED CABLING GUIDELINES AND SPECIFICATIONS. University of Chicago IT Services Infrastructure Services October 2011 TELECOMMUNICATIONS STRUCTURED CABLING GUIDELINES AND SPECIFICATIONS IT Services Infrastructure Services October 2011 Table of Contents 1 Introduction... 4 1.1 Planning and Design... 4 1.2.1 Roles and Responsibilities...

More information

A Remodeler's Guide to: Communications Wiring for Today's New Homes

A Remodeler's Guide to: Communications Wiring for Today's New Homes A Remodeler's Guide to: Communications Wiring for Today's New Homes Page 1 of Copper for Telecommunications Electrical Energy Efficiency A Remodeler's Guide to: COMMUNICATIONS WIRING FOR TODAY'S HOMES

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION 17650 SECURITY SYSTEMS

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION 17650 SECURITY SYSTEMS PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Inspections and observations by the Owner do not relieve the A/E of contract responsibilities. B. Chain of command 1. The DPS Project Manager is

More information

SECTION 27 20 00 - DATA COMMUNICATIONS. A. Complete vertical and horizontal Communication/Data Network System as indicated.

SECTION 27 20 00 - DATA COMMUNICATIONS. A. Complete vertical and horizontal Communication/Data Network System as indicated. SECTION 27 20 00 - PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this

More information

Data and Voice Network Infrastructure

Data and Voice Network Infrastructure Data and Voice Network Infrastructure Denis Levesque Mike Milne Sponsored By Data and Voice Network Infrastructure Page 1 Copyright APPA 2015 Published by APPA: APPA is the association of choice serving

More information

Types of Optic Cable andApplications

Types of Optic Cable andApplications STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENTAL SPECIFICATION 904 FIBER OPTIC CABLE AND COMPONENTS April 18, 2014 904.01 Fiber Optic Cable. Furnish loose-tube, single-mode, step-index dielectric

More information

FITNESS FACILITY WIRING SPECIFICATIONS. NETPULSE Inc. 2331 3rd Street San Francisco, CA 94107 Phone: 415.643.0223

FITNESS FACILITY WIRING SPECIFICATIONS. NETPULSE Inc. 2331 3rd Street San Francisco, CA 94107 Phone: 415.643.0223 FITNESS FACILITY WIRING SPECIFICATIONS NETPULSE Inc. 2331 3rd Street San Francisco, CA 94107 Phone: 415.643.0223 CONTENTS: - Scope of work Summary - Equipment list - Technical specifications - Map of data

More information

Optical Fibers Fiber Optic Cables Indoor/Outdoor

Optical Fibers Fiber Optic Cables Indoor/Outdoor presents Optical Fibers Fiber Optic Cables Indoor/Outdoor Content Optical fiber function, types optical effects applications production of optical fibre Cable - general types Indoor Indoor / outdoor Outdoor

More information

Designing A Communications Cabling System for the Colocation Data Center Larry Smith President, ABR Consulting Group, Inc.

Designing A Communications Cabling System for the Colocation Data Center Larry Smith President, ABR Consulting Group, Inc. Designing A Communications Cabling System for the Colocation Data Center Larry Smith President, ABR Consulting Group, Inc. It is often said that the communications cabling system is the conduit over which

More information

VIDEO SURVEILLANCE OVER UTP WHITE PAPER INTRODUCING VIPER VIDEO SURVEILLANCE

VIDEO SURVEILLANCE OVER UTP WHITE PAPER INTRODUCING VIPER VIDEO SURVEILLANCE VIDEO SURVEILLANCE OVER UTP WHITE PAPER INTRODUCING VIPER VIDEO SURVEILLANCE 1 C O N T E N T S Security Systems can be integrated into any IT Network The Network Manager s New Responsibility The Problem

More information

Polymer Coated Fiber Cable (PCF)

Polymer Coated Fiber Cable (PCF) Polymer Coated Fiber Cable (PCF) Panduit has introduced a Polymer Coated Fiber (PCF) to their fiber cable offering available in 50µm and 62.5µm core diameters. Along with this cable having a stronger durability

More information

Gigabit Ethernet on Copper Cabling Infrastructures

Gigabit Ethernet on Copper Cabling Infrastructures Gigabit Ethernet on Copper Cabling Infrastructures Overview of Gigabit Ethernet (1000Base-T) Ethernet was developed by the Xerox Corporation in the early 1970 s and has emerged as the dominant networking

More information