1 5.18 Voice and Data Distribution General Introduction 1. This standards document is to be used for any projects on the University of Calgary campus that involves the voice and data distribution system or the facilities that house them. It is designed not only to provide the standard implementation system to be used on campus but also provides guidance regarding engagement of Network Services for projects. 2. This section of the standards document provides information on University of Calgary cabling practices, standards, and components. All cabling projects are required to follow these standards and practices to insure that the University structured cabling system can support new applications that require higher speeds and increased reliability. History has shown that the building structured cabling systems often require replacement at considerable cost before the effective life span of the building or project area. This fact significantly increases the carbon footprint and long term costs of campus projects. With this fact in mind the University of Calgary has now standardized on Cat 6A cabling for all new buildings as well as for capital and major projects that can form the basis for a building cable system renewal. Client requirements will be examined and Network Services in consultation with Campus Infrastructure will determine the best solution for each project. 3. Standards outlined here follow the EIA, TIA, and CSA standards for commercial buildings and BiCSi best practice recommendations. Relevant national electrical codes are always to be followed Network Services Project Involvement 1. Network Services project involvement. While University standards will be followed in all cases, the unique nature of every project requires Network Services input on all projects that involve voice, data, or wireless. Network Services is to be consulted for the following: a. Design or design review of Voice, Data, and Wireless systems b. Copper cable manufacturer selection for new buildings and large scale renovations. c. Demolition d. Construction e. Commissioning Project Management 1. Project Managers will engage Network Services at appropriate points in the project as indicated below. a. Initial project design and preliminary budgeting. b. Participate in site meetings. c. Network Services will examine how individual projects interact with existing and future infrastructure & equipment requirements to help specify the best campus solution. Last Updated: Jun 2010 Page 1 of Voice & Data Distribution

2 d. All Network Services costs are to be included in the project budget. Design Standards e. Project Managers need to provide as-built drawings for risers and cabling systems. f. If project designs are more than a year old they should be re-evaluated by Network Services to insure they meet current standards and components. 2. Project sign off by Network Services will occur at the following project stages. a. Specifications b. 80% design drawings c. Change orders d. Completion Cabling Systems 1. Copper Cabling. The U of C follows the TIA/EIA-568-B cabling standards with T568B pin pair assignments. Each project has to be evaluated to determine the copper station cabling to be used. Standard practice is shown below. a. Once a building has a manufacturer presence the whole building will remain with that manufacturer for that generation of cabling system. b. New buildings will be open for quotes using all approved copper cable manufacturers and our approved Cat 6A copper cabling solutions. Approved copper cable manufacturers include Belden, Panduit, and Commscope. c. Projects in older buildings will have to be evaluated by Network Services individually to see if cable plant renewal is required. Belden is the only manufacturer of Cat 6 cabling to be used if the cable plant is not upgraded to Cat 6A. d. Acceptable Belden Cat 6 cabling and components are specified in section e. Acceptable Cat 6A cabling and components are specified in section Acceptable manufacturers are Belden, Commscope, or Panduit. A given project will only use cable components from one manufacturer. f. 10 ft. patch cables for station connectivity and communication room equipment are to be included in the project scope and left on site in the communications room for deployment. 2. Building Fiber Cabling. The University of Calgary has standardized on Corning fiber solutions for all in building fiber and campus backbone fiber panel products. Cabling will be specified for each project depending on requirements. a. Should provide redundant routes for fiber. b. Typically only Single Mode fiber will be required. 3. Copper phone cables, connectors, and enclosures Last Updated: Jun 2010 Page 2 of Voice & Data Distribution

3 a. Backbone and riser cables are to be NORDX/CDT twenty-four (24) AWG ARMM/ATMM multi-conductor that conforms to CSA Standard T529-M91, Section Or a compatible product approved by Network Services. b. Communications Technology PIC Aerial Closure kits. c. 3M Telecom Systems MS2 Termination modules. d. Typical 200 pair required to building entrance AirUC Wireless 1. The AirUC wireless system must be installed in all new buildings and renovations. AirUC wireless costs will be included in project budgets. a. Network Services will produce required wireless designs for all projects and will consult with the project teams to determine AP locations. 2. Generally for a/b/g/n, one AP is installed for every 1200 square feet. Usage density, floor plans, and obstructions all influence AP placement so Network Services will provide placement recommendations based on blue prints and site surveys if required. 3. Certain types of research or other activities may produce radio interference with a/b/g/n wireless devices. Any anticipated radio interference sources shall be discussed with Network Services before project completion Contractor Requirements 1. Contractors. All contractors working on site must go through the EH&S CASP training as well as a Network Services orientation session. 2. Contractors are required to be manufacturer certified in the cabling solution being installed for a given project Facility Requirements 1. Main Riser a. The primary communications room of the building should be located close to the building service entrance. b. A minimum of three (3) 100 mm ducts or a 300 mm x 100 mm tray is required from the service entrance of the building to the communications room. The duct/tray shall originate to the existing low voltage tray in the service tunnel and terminate at the backboard. Sweep 90 degree bends are to be installed to facilitate pulling of PIC-S backbone cable, home run data cables, and fiber-optic cable. c. The building communications room shall be planned exclusively for telecommunications support. Avoid any building power or water distribution equipment for facilities in the same room. Last Updated: Jun 2010 Page 3 of Voice & Data Distribution

4 d. The floor of the communications rooms shall, at minimum, be sealed to reduce dust. Door seals or sweeps are preferred to reduce the collection of dust and debris in the communications room. e. While sizing will have to be adjusted to suit individual requirements, we recommend that the main communications room be a minimum of 3 m x 6 m unobstructed by door swing. See the next section for typical room layout and sizing information. f. Communications riser rooms shall be vertically aligned with the primary communications room, riser facilities. In some cases more than one riser stack might be required, cabletray shall be provided from the communications rooms to each remote riser system. g. All cable-trays shall be brought to the vicinity of one of the 6m walls without a door. Risers and all other cable-trays shall be located in the vicinity of the same wall. h. Three (3) 1,200 mm x 2,400 mm sheets of 20 mm G1S plywood shall be mounted, with their longest edge vertical, on the 3m wall noted above. The sheets shall be mounted directly to the wall and painted with fire retardant paint to match the surrounding area. i. A minimum of four (4) dedicated 120 VAC single-phase (15) ampere circuits shall be placed evenly in the cabinets with quad-outlet boxes. Emergency power and UPS shall be included for these and any communications riser room circuits on the system. Other outlets may be required depending on the actual equipment to be located in the room. j. Adequate light to allow technicians to work on communications support equipment shall be provided. k. There shall be a minimum of 2,400 mm of clearance between the working floor and the lowest ceiling-mounted fixtures (lights, cable-trays, etc.). l. The equipment located in the room will be generating heat. While precise environmental control requirements, if any cannot be generalized without specific knowledge of equipment requirements, air circulation through the room is required at minimum. The target room temperature shall be 18 C to 24 C (64 F to 75 F). Designers shall keep in mind the fact that many building air handling systems deliver heat during the cold months, and special treatment of the communications room may be required. m. Communications room doors must, at least, be provided with locks that are keyed to Maintenance and Operations Standards. Depending on the importance of the communications facilities to the occupants, security alarms should be seriously considered. n. Fire extinguishing water sprinklers may be provided in the ceiling of the communications room, but high temperature (100 C) fusible links shall be used and the system will be a dry pipe system. In some circumstances, a complete fire suppression system may be required. In any case, a fire extinguisher shall be located inside the door of the room. o. Smoke detectors and heat detectors shall be installed in the communications room and wired to the building fire alarm system. p. The communications room must have its own earth ground brought to the backboard noted. This ground must not be in common with building electrical grounds and shall join Last Updated: Jun 2010 Page 4 of Voice & Data Distribution

5 all communications riser grounds only at the building ground point. The ground is used for sensitive equipment, not for bonding conduit and tray systems. A minimum of #6 copper wire shall be used unless codes call for larger wire. The ground is to terminate on a solid copper ground bar (50 mm x 260 mm x 5.6 mm bent to have a 20 mm standoff. q. All communication racks to be grounded to the main grounding bar individually. r. Typical 24 Single Mode fiber to each floor. s. Panduit four post racks with 15 cable managers for station cables and 6 for fiber. t. Bonding - In all cases where pairs enter or leave the cable sheath, the cable shield must be bonded to the ground bus bar using #6 AWG copper wire. u. Any plywood mounted with in the room shall be painted with fire retardant paint Communications Riser Rooms And Riser Systems 1. Design considerations for communications riser rooms and riser systems are the same as those noted above for main riser room. a. The room size is dictated by the number of cabinets required in the room and the unobstructed clearance required around the cabinets and back wall. Room size requirements shall be based on the square footage of the area being serviced so that future growth can be accommodated without substantial redesign. The table and diagrams below can be used to determine required sizes. Risers servicing multiple floors may need to be larger. b. Under normal circumstances, three (3) 100 mm conduit sleeves per riser room shall be provided for passage between floors. In general, one sleeve will be used primarily for voice cabling, one sleeve will be used primarily for data cabling, and the third sleeve will allow for quick and inexpensive growth and change. Note that the recommendation is for short sleeves between floors and not for continuous conduit and that these sleeves must be equipped with removable fire stops. In general, we have found sleeves to be much easier to work with than slots or other facilities. All sleeves must be bonded to the building ground system. All sleeves shall have conduit extending 5cm above the floor slab to prevent water damage in the event of a flood. c. For buildings with certain types of communications requirements, the rule of three (3) conduit sleeves per riser room per floor would possibly change. d. For buildings with more than one (1) riser system, facilities shall be provided to support cable runs between the riser rooms on each floor, as will be detailed in the section on horizontal distribution systems below. e. These facilities must be separate from the horizontal distribution systems specified for the voice/data outlet wiring; i.e., riser cables must be kept separate from all other cables. f. The size of the communication riser room will vary depending on the floor space being covered. The following tables and diagrams indicate the required space requirements for various sized installations. It should be noted that typical requirements will be based Last Updated: Jun 2010 Page 5 of Voice & Data Distribution

6 on floor space and not initial space utilization due to the very high costs of adding additional capacity at a later date. g. Any plywood mounted with in the room shall be painted with fire retardant paint. h. All communication racks to be grounded to the main grounding bar individually. Table: Square feet to cabinet requirements for 24 port patch panels m * 3m m * 4m m * 5m m * 6m m *7m Last Updated: Jun 2010 Page 6 of Voice & Data Distribution

7 Diagram: One cabinet telecommunications room Diagram: Two cabinet telecommunications room Last Updated: Jun 2010 Page 7 of Voice & Data Distribution

8 Diagram: Three cabinet telecommunications room Diagram: Four cabinet telecommunication room Last Updated: Jun 2010 Page 8 of Voice & Data Distribution

9 Station Cable Distribution 1. Above Floor a. Centralized tray system. b. Consolidation point every 1200 square feet 2. Manufacture approved J hooks a. Conduits stubbed at location at least 5 cm above partition walls 3. Raised Floor a. Centralized tray system. b. Consolidation point every 1200 square feet c. Consolidation point locations shall be labeled d. If movable walls ties into furniture 4. Typically 2 cables per workstation location a. If conduit is to be installed each outlet requires its own run of conduit (no daisy-chaining) either to the main cabling pathway, or directly back to the main Comm. room 5. Terminated on 24 port patch panels 6. End to end solution provided through the project including all required patch cables. 7. Labeling (as per EIA/TIA 606A standards). Labeling processes are reviewed in the Network Services orientation for contractors but include the following. a. Building /Floor/Riser/Patch Panel/Port Jack location. b. Patch Panel to identify panel id/port/room 8. Some areas on campus that deal with medical information have additional security requirements that impact distribution systems. These requirements are in place to allow compliance with medical record information security standards. Network Services will provide advice on these standards as required Testing 1. Copper cable plant: a. Backbone and riser cable: Perform the following tests on the backbone and riser cables: b. Continuity and polarity test for each pair c. db loss of white blue pair of each binder group d. Length of white blue pair of each binder group Last Updated: Jun 2010 Page 9 of Voice & Data Distribution

10 e. Test results to be stored in Microsoft Excel or Microsoft Access format and soft copy (disk) to be presented to The University of Calgary Network Services Department. 2. Station wiring: a. Each drop shall be channel tested to meet the transmission performance specifications for the category of cable system being installed. b. Test results to be stored in Microsoft Excel or Microsoft Access format and soft copy (disk) to be presented to The University of Calgary Network Services Department. 3. Data tie cables: a. Testing is to meet the transmission performance specifications for the category of cable being installed. b. Test results to be stored in Microsoft Excel or Microsoft Access format and soft copy (disk) to be presented to The University of Calgary Network Services Department. 4. Testing procedures for fiber optic cables: a. After cable delivery (still on reel), for a fiber installation, the contractor or manufacturer shall test each fiber for attenuation at 1300 nm for Multi-Mode fiber and 1550 nm for Single-Mode fiber using an Optical Time domain Reflectometer (O.T.D.R.). The contractor shall provide a written report (with soft copy) of the test results to The University of Calgary. The University of Calgary must approve format of soft copy. The report must identify which fiber corresponds with the respective test measurement data supplied, so The University of Calgary; Network Services technical personnel can verify the results before installation begins. b. During and upon completion of a fiber cable installation, The University of Calgary, Network Services technical personnel reserves the right to inspect and test the cables at any time to ensure proper installation and testing procedures are being adhered to. c. O.T.D.R. tests are to be conducted upon completion of a fiber installation and are to be conducted from both directions. d. Attenuation is to be measured end to end. Nominal operating wavelengths of 850 nm and 1300 nm for Multi-mode fibers and 1550 nm for Single-Mode fibers are to be verified and specified in decibels (db) on acceptance documents approved by The University of Calgary, Network Services Department. e. Visual hard copy records (print of O.T.D.R. Data trace, signed off) of fiber, splice, and/or connectors are required. These records are also to be provided in soft format approved by The University of Calgary, Network Services Department f. Distances to localized attenuation, splices, connectors and fiber ends are to be measured on the O.T.D.R. documented on acceptance documents providing information for system maintenance and trouble shooting. Last Updated: Jun 2010 Page 10 of Voice & Data Distribution

11 g. O.T.D.R. graphs are to be submitted to The University of Calgary, Network Services Department. One signed off set of these graphs is required. Records are also to be submitted electronically, on USB drive, or on CD. The file format shall be in TIFF format. h. The cable shall meet or exceed the requirements of the specifications for fiber dimensions, attenuation, band width, numerical aperture, fire proof test, cable bending, tensile load, impact resistance, crush resistance, and attenuation versus temperature Services 1. Voice Services. All new projects will use VoIP and must carry the cost of upgrading building network hardware to support voice traffic requirements if required. Emergency and help phones will be specified on a project by project basis depending on project floor space and user requirements. a. VoIP and supporting network infrastructure will be deployed for all major renovation and new projects b. Dual power required for VoIP Head End equipment (refer to Data Network Standards section 5.4.1) c. Emergency TDM phones mounted in designated locations 2. For Classroom phones a. Mounted in the front of the room adjacent to the white (black) boards, on the side nearest the door. In cases of fixed commedia installations mount the phone on the side nearest the commedia installation. b. The Standard mounting height for the classroom phones shall be +1170mm (46") AFF to center of the box (single gang plaster ring). c. There shall be at least 200mm (8 ) clearance on each side from vertical center, at least 600mm (24 ) from a chalk board, and at least 600mm (24 ) clearance from horizontal center above and below. d. Install a single Cat 6A cable, leaving 3m from the edge of the backboard in the communications room and 0.3m at the jack. e. Label each end as, class phone and with room number. f. Install an RJ12 modular female insert at the end of the cable, leave loose in outlet box. Wire out the wh/blu, blu/wh only. 3. For wall phones a. The Standard mounting height for Wall phones shall be +1400mm (55") AFF to center of box (single gang plaster ring), with a minimum of 350 mm (14 ) radius of clear wall space. b. Install a single Cat 6A cable, leaving 3m from the edge of the backboard in the communications room and.3m at the jack. Last Updated: Jun 2010 Page 11 of Voice & Data Distribution

12 c. Label each end as the next jack in the room-labeling scheme. d. Install a single gang walljack, (with protruding wall-mounting studs). 4. Help phones inside locations a. Supply and install Guardian HDE-11 (flush mounted) b. The Standard mounting height for the Emergency Phones shall be +1170mm (46 ) AFF to center of mounting box (8.3 x10 x2.45 ). (This refers to the Guardian HDE-11 units with the stainless fronts). Note only original manufacturers back boxes are to be used. A cut out of 8.75 x10 is required for this box and it must be mounted in the centre of the hole. c. Blue light shall be mounted as high as practical but need not exceed + 3m (10 ) to the bottom of the light. d. Install a single Cat 6A cable, leaving 3m from the edge of the backboard and 0.3m at the jack. e. For outdoor installations (required at all building main entrances): Install a weather proof surface mount emergency phone yellow Guardian HDE-12. All conduit entries for help phones and blue lights shall be into the bottom of back boxes. Special assembly help phones subject to approval. 5. Help phones Mounted in dedicated use unisex accessible washrooms a. Supply and install Guardian HDE-11 back box for future use with Allen Bradley remote push button box. (refer to Appendix A) b. The Standard mounting height for the Emergency Phones shall be +1370mm (54 ) AFF to center of mounting box (8.3 x10 x2.45 ). (This refers to the Guardian HDE-11 recessed units with the stainless fronts). Note only original manufacturers back boxes are to be used. A cut out of 8.75 x10 is required for this box and it must be mounted in the centre of the hole. c. Mount a remote Push Button (below the Help Phone back box) at mm (18 ) AFF, in a 4 x 4 x 2 1/8 deep box c/w a 2 gang plaster ring. Install a ¾ EMT conduit between the remote PB and the Help Phone back box. Mount this box at 600 mm diagonally from the center of the W/C (seating position). Require a 4x4 stainless steel cover plate with knockout for the push button. d. Shall be mounted in a clear space to allow a fallen user to use any body part to activate the phone. Install a single cat 6a cable, leaving 3m from the edge of the backboard and 0.3m at the jack. e. Remote push button Allen Bradley. Contact Voice Services for part numbers. 6. Elevator telephones and equipment rooms a. Supply and install Adams Survivor Plus in each Car telephone with survivor panel or equivalent mounted in main elevator lobby. Last Updated: Jun 2010 Page 12 of Voice & Data Distribution

13 b. Provide three dedicated telephone lines (one for emergency service, one for elevator maintenance, and one for modem) terminated in a junction box in elevator machine room. c. Provide conduit with pull wire between nearest telephone closet and junction box in elevator machine room for elevator telephone. d. Provide conduit with cat6 wire from junction box in elevator machine room to elevator controllers for car telephone. e. Elevator car telephone phone specified: Adams Survivor Plus part # A930P3-01 Model 2400 or approved equivalent. f. The phone is to be mounted in COP (Car Operating Panel) behind a speaker vent. g. Install an ADA (American Disability Approved) illuminated pushbutton in Car Operating Panel to activate the above phone. h. Provide one additional in car telephone per car as part of spare parts list for elevator maintenance i. Wall outlet for elevator maintenance (Safety Phone) j. Provide dedicated wall telephone lines to main fire annunciator panel location Network Services Equipment 1. Every project deployment will use the University of Calgary s current standards for network equipment and device configuration. Project budgets carry the burden for the services they will use. This will insure proper system operation and quality support. Budgetary figures for the required equipment will be provided by Network Services during the project cycle. This equipment is documented in the document Data Network Standards: In Buildings. 2. Based on budgetary figures provided to the project Network Services will purchase, deploy, and configure all active components that are specifically required for voice and data services Other UCIT Services 1. When possible all server requirements should be housed in a UCIT data center. This will reduce the significant overhead costs associated with small data center construction and operation and reduce the environmental footprint of these systems. Due to the scale and level of support available through UCIT system reliability is usually higher in this scenario as well. UCIT can provide further information as required. 2. Panduit cabinets and parts are the standardized network racks and modular solution for the data centers. Last Updated: Jun 2010 Page 13 of Voice & Data Distribution

14 Parts and Components 1. Network Services uses a standard list of parts and components to decrease deployment time and improve long term serviceability of the systems. Occasional specialized applications may require components that are not listed below but in any case Network Services will approve the components that are to be used on specific projects. Part Number Color Systimax 10GX Cable AWH R1000 White MDVO MGS White Face Plates Dual M12LE-262 White Face Plates Quad M14LE-262 White Furniture Plates M14CE-262 White 7ft Patch Cords CPC F007 white 10ft Patch Cord CPC F010 White 15ft Patch Cord CPC F015 White 25ft Patch Cord CPC F025 White 24 port Patch Panel 1100GS5-24 Belden 10GX Cable White MDVO AX White Face Plates Dual AX White Face Plates Quad AX White Furniture Plates AX White 7ft Patch Cord AX White 10ft Patch Cord AX White 15ft Patch Cord AX White 25ft Patch Cord AX White 24 port Patch Panel AX Panduit 10GX Cable PUP6X04WH-UG White MDVO CJ6X88TGIW White Face Plates Dual CFPL2WHY White Face Plates Quad CFPL4WHY White Furniture Plates CFFP4WH White 7ft Patch Cord UTP6X7WHY White 10ft Patch Cord UTP6X10WHY White 15ft Patch Cord UTP6X15WHY White 25ft Patch Cord UTP6X25WHY White 24 port Patch Panel DP246X88TGY Belden Cat6 Cable (cat6) NOR MDVO PS5e (Blue) AX Blue MDVO USOC(Almond) AX Almond 106 Housing (Almond) AX Almond 10ft Patch Cord AX Yellow Last Updated: Jun 2010 Page 14 of Voice & Data Distribution

15 Part Number Color 15ft Patch Cord AX Yellow 25ft Patch Cord AX Yellow GigaBIX Mount AX GigaBIX connector AX GigaBIX Wire Guard AX GigaBIX Desi strip AX GigaBIX Management Ring AX Corning Fiber Components Rack Mount Enclosure PCH-04U Splice Tray Bracket PC4-SPLC-12SR 12 Fiber Splice Tray M RH 6 Port LC Panel CCH-CP-12-A9 12 Port ST MM Panel CCH-CP-12-15T Racks Panduit 4 Post Rack Panduit 6" Wire Manager Panduit 12" Wire Manager Panduit 15 Wire Manager VoIP and TDM Telephone Components Adams Survivor Plus Model 2400 Guardian HDE-11 Guardian HDE-12 Allen Bradley Remote Push Button Allen Bradley Contact Block Allen Bradley Latch Blue Lights CMR4P84 PRVF6 PRVF12 PRVF15 A930P FP-MM64 800FX10 800FALM Carmanah Signs 2. Data Center parts & Components: Parts Cabinets Copper Patch Cables Components Panduit CN1 Net-Access cabinet 45U (32 W X 41 D x 84 H with top, doors, sides Panduit CN2 Net-Access cabinet 45U (32 W X 41 D x 84 H with top and doors Panduit QAPP48HDBL Quicknet Patch Panel empty UTP 48- Port Angled for Preterm cassette Panduit QPP24BL Quicknet Patch Panel empty UTP 24- Port Angled for Preterm cassette Panduit QARWCHCHXX??N Quicknet UTP Cat 6A White riser cassette/cassette jacks?? Feet Panduit UTP6X_??? Cat6A patch cord??? colour _feet need to be supplied by Network services Last Updated: Jun 2010 Page 15 of Voice & Data Distribution

16 Appendix A Help phones Mounted in dedicated use unisex accessible washrooms drawing Last Updated: Jun 2010 Page 16 of Voice & Data Distribution

DIVISION 27 COMMUNICATIONS. A. System design shall be completed by a Registered Communications Distribution Designer (RCDD).

DIVISION 27 COMMUNICATIONS. A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). DIVISION 27 COMMUNICATIONS 27 00 00 COMMUNICATIONS A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). B. Comply with American National Standards Institute

More information

Minimum Standards for Data/Voice Infrastructure in New Building Construction

Minimum Standards for Data/Voice Infrastructure in New Building Construction UNIVERSITY OF WATERLOO Minimum Standards for Data/Voice Infrastructure in New Building Construction 12/17/2012 Offices 1. Two Work Area Outlets (WAO) on opposite walls, each with 2 jacks 2. Each WAO shall

More information

UT Southwestern Medical Center Information Resources Cable Installation Standard

UT Southwestern Medical Center Information Resources Cable Installation Standard UT Southwestern Medical Center Information Resources Cable Installation Standard PART 1- GENERAL 1.01 SUMMARY A. Furnish and install wire, cable, devices, equipment, and accessories for a complete system

More information

SECTION 25110 TELECOMMUNICATION ROOMS

SECTION 25110 TELECOMMUNICATION ROOMS PART 1 - GENERAL 1.1 SUMMARY A. SCOPE SECTION 25110 TELECOMMUNICATION ROOMS 1. This section includes the minimum installation requirements for equipment and cabling infrastructure in Telecommunication

More information

Presenters Brett Weiss, Gabe Martinez, Brian Kroeger.

Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. 1 Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. Topics to be covered: Cable identification Purpose of the various cable types Installation techniques Building Infrastructure Overview of networking

More information

TCTC Cabling Specifications

TCTC Cabling Specifications TCTC Cabling Specifications Purpose: To provide a standard specification that will be used for all Tri County Technical College (TCTC) facilities requiring structured cabling installation. Product specifications,

More information

1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications.

1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications. Issued 2005/06/01 Section 16743 Data System Page 1 of 7 PART 1 GENERAL 1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications..2 Data system equipment

More information

Building Telecommunications Infrastructure Requirements

Building Telecommunications Infrastructure Requirements Building Telecommunications Infrastructure Requirements This page identifies specific requirements for the design of telecommunications infrastructure for buildings at Clemson University. (Revised October,

More information

Specifying an IT Cabling System

Specifying an IT Cabling System Specifying an IT Cabling System This guide will help you produce a specification for an IT cabling system that meets your organisation s needs and gives you value for money. You will be able to give your

More information

1. Furnish and install faceplate and modular jacks at each single gang outlet as described below:

1. Furnish and install faceplate and modular jacks at each single gang outlet as described below: Washington University in St. Louis Building: Communication Specification: Research Voice/Network/Typical 1. Furnish and install faceplate and modular jacks at each single gang outlet as described below:

More information

SECTION 16715 TELECOMMUNICATIONS ACCEPTANCE TESTING

SECTION 16715 TELECOMMUNICATIONS ACCEPTANCE TESTING PART 1 - GENERAL 1.1 SECTION INCLUDES A. Testing Publications and Standards B. Inspection and testing procedures for copper and fiber optic cable, RF CATV / MATV systems, and the antenna systems. C. Documentation

More information

IT&T Infrastructure Standards

IT&T Infrastructure Standards Technology Services IT&T Infrastructure Standards Version 1.5 17 th April 2015 Page 1 Table of contents 1 CHANGE HISTORY... 3 1.1 DOCUMENT HISTORY... 3 1.2 REVIEWERS... 3 1.3 APPROVALS... 3 2 INTRODUCTION...

More information

TELECOMMUNICATIONS STRUCTURED CABLING GUIDELINES AND SPECIFICATIONS. University of Chicago IT Services Infrastructure Services October 2011

TELECOMMUNICATIONS STRUCTURED CABLING GUIDELINES AND SPECIFICATIONS. University of Chicago IT Services Infrastructure Services October 2011 TELECOMMUNICATIONS STRUCTURED CABLING GUIDELINES AND SPECIFICATIONS IT Services Infrastructure Services October 2011 Table of Contents 1 Introduction... 4 1.1 Planning and Design... 4 1.2.1 Roles and Responsibilities...

More information

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems

More information

BIX Cross-Connect System Distribution Connectors, Multiplying Connectors and Modular Jack Connectors

BIX Cross-Connect System Distribution Connectors, Multiplying Connectors and Modular Jack Connectors C O M M E R C I A L N E T W O R K I N G C O P P E R 15.13 Distribution Connectors, Multiplying Connectors and Modular Jack Connectors A0393146 QCBIX1A4 Connector BIX Distribution Connector The BIX Distribution

More information

University of North Carolina at Charlotte Design and Construction Manual Section 3, Annex K, 49er Card Systems ANNEX K 49ER CARD SYSTEMS

University of North Carolina at Charlotte Design and Construction Manual Section 3, Annex K, 49er Card Systems ANNEX K 49ER CARD SYSTEMS ANNEX K 49ER CARD SYSTEMS UNC CHARLOTTE 49ER CARD SYSTEM INSTALLATION AND CONTRACTOR REQUIREMENT SCOPE OF WORK: The following information pertains to the installation and contractor requirements to install

More information

TrueAlarm Fire Alarm Systems

TrueAlarm Fire Alarm Systems TrueAlarm Systems UL, ULC, CSFM Listed; FM Approved* Network Annunciators; es Features Provides a dedicated local area network (LAN) for connection of a TrueSite workstation server to remote clients: es

More information

ATTACHMENT F 050R6800016 - CABLE AND WIRING SERVICES FUNCTIONAL AREA I PRICE PROPOSAL FORM Amendment 6

ATTACHMENT F 050R6800016 - CABLE AND WIRING SERVICES FUNCTIONAL AREA I PRICE PROPOSAL FORM Amendment 6 050R6800016 CABLE AND WIRING SERVICES (Column A) (Column B) (Column C) (Column D) (Column E) (Column F) (Column G) (B+C+D+E)*F= G Item Description PER 100' RUN PER 150' RUN PER 200' RUN PER 300' RUN QUANTITY

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-27 05 14.00 10 (April 2006) -------------------------------- Preparing Activity: USACE Superseding UFGS-27 05 14.00 10 (April 2004) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

Information and Communication Technology Network Cabling Infrastructure Standard

Information and Communication Technology Network Cabling Infrastructure Standard Approved on Dec-2005 by Eugene Formato Manager, Communications Services Last Amended Aug-2009 by Jarren Beveridge Network Engineer, Communications Services Scheduled for Review Jan-2010 Information and

More information

NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION 27 10 00 STRUCTURE CABLING TESTING

NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION 27 10 00 STRUCTURE CABLING TESTING RELATED SECTIONS: NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT Section 27 00 00 General Requirements Section 27 02 00 General Communication Requirements Section 27 05 26 Grounding and Bonding for Communications

More information

InstaPATCH Cu Cabling Solutions for Data Centers

InstaPATCH Cu Cabling Solutions for Data Centers SYSTIMAX Solutions InstaPATCH Cu Cabling Solutions for Data Centers Design Guidelines August 2008 www.commscope.com Contents Overview 1 Instapatch Cu Solution Specification 2 Harness Assembly Design 3

More information

Data Center. Pre-terminated. Patch Panel System. Cabling Systems Simplified. Patch Panels. 10G + Gigabit. Patch Cords. Plug & Play Installation

Data Center. Pre-terminated. Patch Panel System. Cabling Systems Simplified. Patch Panels. 10G + Gigabit. Patch Cords. Plug & Play Installation Data Center Pre-terminated Patch Panel System Patch Panels Plug & Play Installation 10G + Gigabit Patch Cords Bundled + Labeled Cabling Systems Simplified Our Mission At Cablesys, our mission is to simplify

More information

1 Campus Cabling Systems Introduction

1 Campus Cabling Systems Introduction 1 Campus Cabling Systems Introduction This document represents the campus cable and infrastructure standards adopted and supported by the XXXX. All new construction and renovation should conform to these

More information

ADC Structured Cabling Solutions

ADC Structured Cabling Solutions ADC Structured Cabling Solutions The highest performing cross-connect system in the world HighBand Wall Mount Patching Solution Reliable, secure and cost effective ADC s HighBand cross connect solution

More information

DESIGN GUIDELINES. Local Area Network

DESIGN GUIDELINES. Local Area Network DESIGN GUIDELINES Local Area Network The total oversight and management responsibilities for information assurance (IA) and protection of DoDEA s critical infrastructure fall under the purview of the DoDEA

More information

LIEBERT VNSA Installation Sheet

LIEBERT VNSA Installation Sheet LIEBERT VNSA Installation Sheet Description The Liebert vnsa network switch is designed for connecting multiple Ethernet-ready devices and comes in various models. The unit may have: A Liebert icom display

More information

ANSI/TIA/EIA - 568-A, Commercial Building Telecommunications Cabling Standard.

ANSI/TIA/EIA - 568-A, Commercial Building Telecommunications Cabling Standard. WIRING STANDARD INTRODUCTION This standard defines a telecommunications wiring system for North Dakota State Agencies, offices or buildings that will support a multi-product environment. The purpose of

More information

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval. Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's

More information

Structured Wiring Specifications ERAU Daytona Beach Campus (Dec 14 2011)

Structured Wiring Specifications ERAU Daytona Beach Campus (Dec 14 2011) Structured Wiring Specifications ERAU Daytona Beach Campus (Dec 14 2011) A. Objectives The Information Technology (IT) Department of Embry-Riddle Aeronautical University (ERAU) seeks to establish a standards-based

More information

Network Design. Yiannos Mylonas

Network Design. Yiannos Mylonas Network Design Yiannos Mylonas Physical Topologies There are two parts to the topology definition: the physical topology, which is the actual layout of the wire (media), and the logical topology, which

More information

E Series. E Series. Category 6 and 5e. Features

E Series. E Series. Category 6 and 5e. Features E Series Category 6 and 5e CommScope, world leader in copper and fiber connectivity, offers the E Series product line as the ideal solution to all your infrastructure needs for safe and reliable data transmission.

More information

Data Center Cabling Design Trends

Data Center Cabling Design Trends Data Center Cabling Design Trends BICSI Regional Meeting Maurice Zetena Fiber Connect Infrastructure Trends Infrastructure Trends Any to All Trunk Cabling Trends: Data Center Infrastructure Media Choice:

More information

Specifications for Communication Cabling Distribution Systems

Specifications for Communication Cabling Distribution Systems Washington University in St. Louis Specifications for Communication Cabling Distribution Systems General Overview Listed below are the separate sub-systems of Washington University s structured cabling

More information

SECTION 27 13 24 COMMUNICATIONS OPTICAL FIBER OSP CABLING

SECTION 27 13 24 COMMUNICATIONS OPTICAL FIBER OSP CABLING SECTION 27 13 24 COMMUNICATIONS OPTICAL FIBER OSP CABLING PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete

More information

SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM

SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION INTELLIGENT REPORTING FIRE DETECTION SYSTEM PART 1 GENERAL 1.1 DESCRIPTION A. This specification includes the furnishing,

More information

AT&T Specifications Trenching Conduit Boxes and M anholes Aerial Entrance Masts Service Cabinets Bonding and Grounding

AT&T Specifications Trenching Conduit Boxes and M anholes Aerial Entrance Masts Service Cabinets Bonding and Grounding AT&T Specifications Trenching Conduit Boxes and M anholes Aerial Entrance Masts Service Cabinets Bonding and Grounding A Guide for California Developers of Com m ercial Property This guide consists of

More information

March 2007. 27 08 00 Commissioning of Communications. See Appendix E3. 27 08 00-1

March 2007. 27 08 00 Commissioning of Communications. See Appendix E3. 27 08 00-1 March 2007 27 08 00 Commissioning of Communications See Appendix E3. 27 08 00-1 27 11 00 Communications Equipment Room Fittings 1.0 General TELEPHONE RISERS: A. All copper telephone riser cables must be

More information

No Phone Line II-48 System

No Phone Line II-48 System Used in conjunction with an EntraGuard Telephone Entry System, the -48 provides No Phone Line communication and door or gate control through existing building telephone lines without the need to purchase

More information

Cabling Services (price per pull) Zone 1 Zone 2 Zone 3 Zone 4 Zone 5

Cabling Services (price per pull) Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 BryComm, LLC -SDD-1901 Cabling Services (per pull) - Labor Only STANDARD TIME The price per cable pull represents all labor to include fishing walls, running cable through modular furniture, terminating,

More information

SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS

SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS The equipment requirements of this section apply to the IUB Campus. The IUPUI Campus has a preferred vendor agreement for fire alarm systems. Contact Pat

More information

Design Guide. Universal Connectivity Grid. SYSTIMAX Solutions from CommScope

Design Guide. Universal Connectivity Grid. SYSTIMAX Solutions from CommScope Design Guide Universal Connectivity Grid SYSTIMAX Solutions from CommScope CONTENTS Introduction 3 Commercial building network overview 4 Zone cabling 5 Universal Connectivity Grid 6 UCG cell size 7 Integrating

More information

DEPARTMENTAL REGULATION

DEPARTMENTAL REGULATION U.S. DEPARTMENT OF AGRICULTURE WASHINGTON, D.C. 20250 DEPARTMENTAL REGULATION SUBJECT: Service Center Technology Modernization Project (SCTMP) Wiring/Cabling Specifications for Service Center Agencies

More information

SYSTIMAX SCS PowerSum and GigaSPEED XL Cabling Installation Guidelines

SYSTIMAX SCS PowerSum and GigaSPEED XL Cabling Installation Guidelines SYSTIMAX SCS PowerSum and GigaSPEED XL Cabling Installation Guidelines This document contains critical information regarding the installation of a certified SYSTIMAX SCS that meets or exceeds performance

More information

Cat7/Class F New Installation Concept New infrastructure. Handbook

Cat7/Class F New Installation Concept New infrastructure. Handbook Cat7/Class F New Installation Concept New infrastructure Handbook contents 1 Introduction 3 2 What is the Cat7/Class F installation concept 3 3 Distribution centre 3 3.1 Patch Modules 3 4 How to handle

More information

Telecommunications Systems Narrative Page 1 The Engineering Enterprise

Telecommunications Systems Narrative Page 1 The Engineering Enterprise I. TELECOMMUNICATIONS GENERAL REQUIREMENTS A. The project consists of a renovation to the historic Clinical Sciences building, originally built in 1933. The existing building has a total area of 105,000

More information

Network Telecommunications Design Standards Last Updated June 2013. Youngstown State University

Network Telecommunications Design Standards Last Updated June 2013. Youngstown State University 1 Network Telecommunications & Security Youngstown State University One University Plaza Youngstown, OH 44555 Network Telecommunications Design Standards Last Updated June 2013 Youngstown State University

More information

ADC-APC Integrated Cisco Data Center Solutions

ADC-APC Integrated Cisco Data Center Solutions Advanced Infrastructure Solution for Cisco Data Center 3.0 Ordering Guide ADC-APC Integrated Cisco Data Center Solutions The evolution of data centers is happening before our eyes. This is due to the

More information

800 Communications Circuits

800 Communications Circuits ARTICLE 800 Communications Circuits INTRODUCTION TO ARTICLE 800 COMMUNICATIONS CIRCUITS This article has its roots in telephone technology. Consequently, it addresses telephone and related systems that

More information

B. Cross-Connect: A facility enabling the termination of cable elements and their interconnection or cross-connection.

B. Cross-Connect: A facility enabling the termination of cable elements and their interconnection or cross-connection. DIVISION 16 ELECTRICAL Section 16740 Telephone System PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

DATA CENTER SOLUTIONS. MTP cables Patchcords Cat 6A PDU

DATA CENTER SOLUTIONS. MTP cables Patchcords Cat 6A PDU DATA CENTER SOLUTIONS MTP cables Patchcords Cat 6A PDU 1 DATA CENTER SOLUTIONS Table of contents ORBIS AS A DATA TRANSFER SUPPLIER 3 MECHANICS 4 Server and Network racks 4 PDU power bars 4 Coolers 5 Cold&Hot

More information

Table of Contents. Fiber Trunking 2. Copper Trunking 5. H-Series Enclosures 6. H-Series Mods/Adapter Panels 7. RSD Enclosures 8

Table of Contents. Fiber Trunking 2. Copper Trunking 5. H-Series Enclosures 6. H-Series Mods/Adapter Panels 7. RSD Enclosures 8 Data Center Guide 1 Our Philosophy As a leader in the enterprise cable industry since our inception over three decades ago, we can help you implement the solution that will work best for your cabling infrastructure,

More information

Fiber Plant Design Considerations for Active DAS Mike Brownson VP DAS Technical Solutions Hutton Communications

Fiber Plant Design Considerations for Active DAS Mike Brownson VP DAS Technical Solutions Hutton Communications Fiber Plant Design Considerations for Active DAS Mike Brownson VP DAS Technical Solutions Hutton Communications Topics! Understanding Fiber Types! Powering your Remotes via Composite Fiber! Fiber Design

More information

Northwestern University Information Technology Building Infrastructure Requirements for Communication Facilities ( January 2010)

Northwestern University Information Technology Building Infrastructure Requirements for Communication Facilities ( January 2010) Northwestern University Information Technology Building Infrastructure Requirements for Communication Facilities ( January 2010) I. Introduction This document presents the current Northwestern University

More information

TIA 569 Standards Update Pathways & Spaces. Ignacio Diaz, RCDD April 25, 2012

TIA 569 Standards Update Pathways & Spaces. Ignacio Diaz, RCDD April 25, 2012 TIA 569 Standards Update Pathways & Spaces Ignacio Diaz, RCDD April 25, 2012 The purpose of this Standard is to standardize specific pathway and space design and construction practices in support of telecommunications

More information

ANSI/TIA-942 Telecommunications Infrastructure Standards for Data Centers

ANSI/TIA-942 Telecommunications Infrastructure Standards for Data Centers ANSI/TIA-942 Telecommunications Infrastructure Standards for Data Centers Jonathan Jew jew@j-and and-m.com J&M Consultants, Inc Co-chair TIA TR-42.1.1 data center committee Co-chair BICSI data centers

More information

STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENTAL SPECIFICATION 804 FIBER OPTIC CABLE FOR TRAFFIC SIGNAL INTERCONNECT JANUARY 19, 2007

STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENTAL SPECIFICATION 804 FIBER OPTIC CABLE FOR TRAFFIC SIGNAL INTERCONNECT JANUARY 19, 2007 804.01 Description 804.02 General 804.03 Materials 804.04 Fan-Out Kit 804.05 Drop Cable 804.06 Fiber Optic Patch Cord 804.07 Termination Panel 804.08 Fusion Splice 804.09 Fiber Optic Connector 804.10 Splice

More information

Category 6 Solutions. 4. Category 6 Solutions. 09/08 400836IN TrueNet Structured Cabling. Introduction... 4.2. Cable... 4.3. Patch Panels... 4.

Category 6 Solutions. 4. Category 6 Solutions. 09/08 400836IN TrueNet Structured Cabling. Introduction... 4.2. Cable... 4.3. Patch Panels... 4. Category 6 Solutions Introduction... 4.2 Cable... 4.3 Patch Panels... 4.4 Modules... 4.6 Patch Cords... 4.12 Outlets... 4.16 Faceplates...4.18 4. 1 Search Category 6 Solutions Introduction ADC KRONE s

More information

DIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION

DIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION DIVISION 26 - ELECTRICAL PART 1 - GENERAL 1.01 SUMMARY A. Section Includes 1. Instrumentation Cables 1.02 SUBMITTALS A. Submit in accordance with requirements of Section 01 33 00. B. Product Data: Submit

More information

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT The purpose of these specifications is to insure that there are minimum

More information

B. PART 1 - GENERAL of SECTION 271300 BACKBONE COMMUNICATIONS CABLING shall also apply to this section.

B. PART 1 - GENERAL of SECTION 271300 BACKBONE COMMUNICATIONS CABLING shall also apply to this section. SECTION 271500 - HORIZONTAL UTP CABLING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

PUBLIC RESTROOMS, DESIGN INTENT

PUBLIC RESTROOMS, DESIGN INTENT PUBLIC RESTROOMS, DESIGN INTENT 1.01 STRUCTURAL A. Where feasible, metal stud partitions will be constructed on a 6 high concrete curb. 1.02 MECHANICAL A. Restrooms will have a minimum of 15 air changes

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION 17650 SECURITY SYSTEMS

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION 17650 SECURITY SYSTEMS PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Inspections and observations by the Owner do not relieve the A/E of contract responsibilities. B. Chain of command 1. The DPS Project Manager is

More information

FIBER OPTIC CABLE PLANT DOCUMENTATION

FIBER OPTIC CABLE PLANT DOCUMENTATION C H A P T E R 13 FIBER OPTIC CABLE PLANT DOCUMENTATION JIM HAYES Documenting the fiber optic cable plant is a necessary part of the design and installation process for the fiber optic network. Documenting

More information

Technical Specifications v5.6.14

Technical Specifications v5.6.14 Summer 14 Columbia University Information Technology [Author Name] Technical v5.6.14 [Type the abstract of the document here. The abstract is typically a short summary of the contents of the document.]

More information

InstaPATCH ZERO Solution Guide

InstaPATCH ZERO Solution Guide SYSTIMAX Solutions InstaPATCH ZERO Solution Guide Rapid Server Deployment and Change Management North, South and Central Americas 1 As data centers face ever-increasing IT demands, growth demands and evolving

More information

Organizing and Managing Equipment Rooms

Organizing and Managing Equipment Rooms Organizing and Managing Equipment Rooms How you organize and maintain your equipment room can be just as important as maintaining the operating systems on the boxes themselves. Although many companies

More information

The Telecommunications Closet and Building Services

The Telecommunications Closet and Building Services APPENDIX G Telecommunications Building & Network Standards 1. Expectations...2 2. Definitions...2 3. Contractor Requirements...2 4. Design Elements...3 4.1. Spaces...3 4.1.1. Building Service Entrance...3

More information

NUIG Campus Network - Structured Cabling System Standards Information s Solutions & Services (ISS)

NUIG Campus Network - Structured Cabling System Standards Information s Solutions & Services (ISS) NUIG Campus Network - Structured Cabling System Standards Information s Solutions & Services (ISS) Revision date 28 th January 2014 The purpose of this document is to assist Building Refurbishment and

More information

Intelligent Cable Management Systems

Intelligent Cable Management Systems Intelligent Cable Management Systems Bringing Practical Application Karen Pearson - Leviton Why Cable Management Matters Performance Cooling and air-handling Maintenance ANSI/TIA 569* Telecommunication

More information

21 st Century Campus Network Responsibility Matrix 5/26/10

21 st Century Campus Network Responsibility Matrix 5/26/10 Definitions: DoIT Standards This column details the minimal configuration, which DoIT has defined in order to provide a campus-wide standard level of service. Departments may request services, which exceeds

More information

CommScope Intelligent Building Infrastructure Solutions (IBIS)

CommScope Intelligent Building Infrastructure Solutions (IBIS) SYSTIMAX Solutions CommScope Intelligent Building Infrastructure Solutions (IBIS) Questions & Answers Q. What is an Intelligent Building? A. An intelligent building can be defined as one which provides

More information

Electrical. This section applies to the design and installation of building power distribution systems.

Electrical. This section applies to the design and installation of building power distribution systems. Basis of Design This section applies to the design and installation of building power distribution systems. Design Criteria This section contains the architectural, structural and mechanical provisions

More information

Beaver Dam Unified School District Request for Proposal Video Surveillance and Door Access Control Systems

Beaver Dam Unified School District Request for Proposal Video Surveillance and Door Access Control Systems Beaver Dam Unified School District Request for Proposal Video Surveillance and Door Access Control Systems The Beaver Dam Unified School District (BDUSD) is requesting proposals from qualified companies

More information

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 105.8a-6.1 TITLE: FIRE ALARM SYSTEM REQUIREMENTS SCOPE: This guideline

More information

LOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado 80027 303-666-8809

LOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado 80027 303-666-8809 LOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado 80027 303-666-8809 Contractor s Checklist and Installation Guide TABLE OF CONTENTS Fire Protection Narrative........... 3 Fire

More information

HP UPS R1500 Generation 3

HP UPS R1500 Generation 3 HP UPS R1500 Generation 3 Installation Instructions Part Number 650952-001 NOTE: The rating label on the device provides the class (A or B) of the equipment. Class B devices have a Federal Communications

More information

Installing a Physical Network. Chapter 8

Installing a Physical Network. Chapter 8 Installing a Physical Network Chapter 8 Contents Recognize and describe the function of basic components in a structured cabling system Explain the process of installing structured cable Install a network

More information

Panduit 28 AWG Patch Cords Installation Guideline

Panduit 28 AWG Patch Cords Installation Guideline Panduit 28 AWG Installation Guideline Introduction Panduit is a leading supplier of Structured Cabling Systems and Unified Physical Infrastructure. Panduit solutions enable the physical infrastructure

More information

UTSC CABLE SYSTEMS SPECIFICATION SITE DESIGN CRITERIA DESIGN REQUIREMENTS INSTALLATION PRODUCTS

UTSC CABLE SYSTEMS SPECIFICATION SITE DESIGN CRITERIA DESIGN REQUIREMENTS INSTALLATION PRODUCTS UTSC CABLE SYSTEMS SPECIFICATION SITE DESIGN CRITERIA DESIGN REQUIREMENTS INSTALLATION PRODUCTS University of Toronto Scarborough Cable Systems Specification 1/23 Network Administrators Glenn Attwood Manager,

More information

Fire Alarm System Plans Review Checklist Property location Date of Review

Fire Alarm System Plans Review Checklist Property location Date of Review Fire Alarm System Plans Review Checklist Property location Date of Review 1. Is application completed in entirety? 2. Are the plans review fee submitted with the application? 3. Does floor plan include

More information

DTW Works Master Specification Version 2006

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section 13852 Multiplex Fire Alarm System Page 1 of 10 PART 1 GENERAL 1.1 RELATED WORK.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Procedures..3 Section 01810 Commissioning..4

More information

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting

More information

1. STRUCTURED CABLING

1. STRUCTURED CABLING APPENDIX 3E CABLE INFRASTRUCTURE STANDARD 1. STRUCTURED CABLING 1.1. General Requirements 1.1.1. Comply with the following standards (latest versions) when designing and installing structured cabling:

More information

Standards. www.nordx.com 5 ANSI/TIA/EIA-569-A (CSA T530)

Standards. www.nordx.com 5 ANSI/TIA/EIA-569-A (CSA T530) The primary focus of this standard is to provide design specifications and guidance for all building facilities relating to telecommunications cabling systems and components. This standard identifies and

More information

Cable Installation Project

Cable Installation Project Cable Installation Project 1. Intent. It is the intent of the U.S. Court of Appeals to install Category 6 (CAT6) data cabling in the Robert F. Peckham Federal Building and United States Courthouse, 280

More information

AT&T. PARTNER Plus Door Phone. Installation and Operation Manual

AT&T. PARTNER Plus Door Phone. Installation and Operation Manual AT&T PARTNER Plus Door Phone Installation and Operation Manual Copyright 1990 AT&T All Rights Reserved Printed in U.S.A. CIC# 999-500-317 OII722050-051 Issue 1 October 1990 PARTNER Plus Door Phone is a

More information

in other campus buildings and at remote campus locations. This outage would include Internet access at the main campus.

in other campus buildings and at remote campus locations. This outage would include Internet access at the main campus. DATA CENTER The current Campus Data Center is located within historic Founders Hall which is in a less-than ideal location for a variety of reasons, but is typical of an existing campus IT infrastructure

More information

T1 Backhaul Connectivity Solution All Products :: Application Note

T1 Backhaul Connectivity Solution All Products :: Application Note Telect 1 RU Customer Interface Panel (CIP) Enables Demarcation, Remote Circuit Maintenance and Trouble Isolation at the Backhaul Node The Application: T1 Demarcation and Testing in Backhaul Environments

More information

TAB C-6 KEYLESS ACCESS AND SECURITY SYSTEM GUIDELINE

TAB C-6 KEYLESS ACCESS AND SECURITY SYSTEM GUIDELINE TAB C-6 KEYLESS ACCESS AND SECURITY SYSTEM GUIDELINE The University of Arizona has implemented a Keyless Access and Security System program to provide a cost effective, efficient, and maintainable means

More information

University Design Standard. Fire Alarm Systems

University Design Standard. Fire Alarm Systems University Design Standard Fire Alarm Systems 1.0 Overview This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit

More information

TELECOMMUNICATIONS NETWORK STANDARDS AND GUIDELINES FOR THE NEW ADMINISTRATION BULDING

TELECOMMUNICATIONS NETWORK STANDARDS AND GUIDELINES FOR THE NEW ADMINISTRATION BULDING TELECOMMUNICATIONS NETWORK STANDARDS AND GUIDELINES FOR THE NEW ADMINISTRATION BULDING October 1998 Table of Contents SECTION I: New Construction Programming 1.0 New Construction 1.1 Design Elements..................................

More information

Fibre Optic Wiring Guide for Multiple Dwelling Units (MDUs)

Fibre Optic Wiring Guide for Multiple Dwelling Units (MDUs) Fibre Optic Wiring Guide for Multiple Dwelling Units (MDUs) Greenfield/Brownfield Renovations Table of Contents Future-Proof your Building... 1 MTS Fibre Optics Installation Guidelines... 2 MTS Fibre Optics

More information

Installation Manual For Support Call 01704 807114 or email info@hipentertainment.co.uk

Installation Manual For Support Call 01704 807114 or email info@hipentertainment.co.uk Installation Manual Hip Smart Hub (Standard BT and BT FTTP Sites) The Home Network Hub houses the Home Owner s Broadband Router and connects the hardwired network ports on that Router to three network

More information

STRUCTURED CABLE SPECIFICATION INFORMATION SYSTEMS AND SERVICES ISSUE 1 NOVEMBER 2011

STRUCTURED CABLE SPECIFICATION INFORMATION SYSTEMS AND SERVICES ISSUE 1 NOVEMBER 2011 STRUCTURED CABLE SPECIFICATION INFORMATION SYSTEMS AND SERVICES ISSUE 1 NOVEMBER 2011 Project Ref. Project Name Project Manager Date issued... Consultant/Contractor... 1 CONTENTS 1000 GENERAL OVERVIEW

More information

Standard Comms Rooms Specification

Standard Comms Rooms Specification Standard Comms Rooms Specification Room Configuration Electrical General Distribution Boards Small Power Lighting Containment Fire Detection General To be defined in the project brief but should meet requirements

More information

SECTION 16750. TELECOMMUNICATIONS SYSTEM (Cat 6)

SECTION 16750. TELECOMMUNICATIONS SYSTEM (Cat 6) SECTION 16750 TELECOMMUNICATIONS SYSTEM (Cat 6) PART 1 - GENERAL 1.01 REQUIREMENTS A. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements, apply

More information

HARTING Ethernet Cabling 8-poles Overview

HARTING Ethernet Cabling 8-poles Overview Ethernet Cabling 8-poles Overview RJ45 Connectors [on page 8] System cables [on page 12] Distribution modules and Outlets [on page 17] Connectors [on page 20] System cables [on page 26] Panel feed-throughs

More information

C. Conform to requirements of Americans with Disabilities Act (ADA).

C. Conform to requirements of Americans with Disabilities Act (ADA). SECTION 28 31 00 - FIRE ALARM AND DETECTION SYSTEMS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire alarm and detection systems 1.2 REFERENCES A. NFPA 70 - National Electrical Code B. NFPA 72 - National

More information