A. The requirements of Section govern the work specified in this section.

Size: px
Start display at page:

Download "A. The requirements of Section 27 01 00 govern the work specified in this section."

Transcription

1 SECTION COMMUNICATIONS CABLING PART 1 GENERAL 1.1 RELATED DOCUMENTS A. The requirements of Section govern the work specified in this section. B. Refer to the following sections for related work: PART 2 PRODUCTS Grounding and Bonding for Electrical Systems Telecommunication Wiring Cable Trays 2.1 APPROVED PRODUCTS AND MANUFACTURERS A. UTP 4-pair Plenum-rated Cable for voice data and wireless: Category 6 Cable, Teal colored jacket for voice and data and yellow colored jacket for wireless. Cable must meet or exceed ANSI/TIA/EIA 568B.2-1 standards. 1. All cable shall conform to the requirements for communications circuits defined by the National Electrical Code (Article 800). Cable listed to NEC Article (a) will be used for Plenum installations. a. CommScope Ultra Media #7504 b. Panduit PUP6004TL-U/N c. Hubbell Premise Wiring - #C6RPT (teal), #C6RPY (yellow) B. UTP 4-pair Outside Plant Cable: Category 6, must meet or exceed ANSI/TIA/EIA 568B.2-1 standards. 1. All cable shall conform to the requirements for communications circuits defined by the National Electrical Code (Article 800). a. CommScope Outdoor, #6NF4, or equal C. High pair count UTP Plenum-rated Cable: Category 3, must meet or exceed ANSI/TIA/EIA 568A standards. 1. General Cable 25 pair, # , or equal 2. General Cable 50 pair, # , or equal D. High pair count UTP OSP Cable: Category 3, must meet or exceed ANSI/TIA/EIA 568 A standards 1. General Cable 25 pair, # , or equal 2. General Cable 50 pair, # , or equal E. Optical Fiber Cable for distances up to 300 meters: Must meet or exceed ANSI/TIA/EIA- 568-B Plenum-rated Tight-Buffered Cable, 12-strand, Multi-Mode, 10G, 50/125 um, Aqua, jacket constructed with aluminum interlocking armor, NEC/CEC compliant (OFCP listed). TELECOMMUNICATIONS COMMUNICATIONS CABLING

2 a. CommScope #P-012-DZ-5L-FSUAQ, or equal b. Corning - #012S A3 2. Optical Indoor/Outdoor Plenum-rated Tight-Buffered Cable, 12-strand, 10G, 50/125 um, Aqua, NEC/CEC compliant. a. CommScope #P-012-LZ-5L-F12BK with interlocking armor and P-012-LN-5L- F12BK without interlocking armor (inner duct will be used in lieu), or equal b. Corning - #012S8P A3 with interlocking armor. 3. Optical Outdoor Fiber Cable, 12-strand, 10G, 50/125 um, Loose Tube-GEL FILLED, NEC/CEC compliant. a. CommScope #D-012-LN-5L-F12NS with interlocking armor, or equal b. Corning - #012SSF-T4180DA1 with interlocking armor. F. Optical Fiber connectors 1. Corning X, or equal 2. CommScope Uniprise SFC-STQ-09 G. UTP CAT 6 jacks all products must be rated CAT 6 with T568-B pin out. 1. Panduit a. Data jacks blue - #CJ688TPBU b. Voice jacks green - #CJ688TPGR c. Power fail red - #CJ688TPRD d. Wireless - yellow-#cj688tpyl 2. CommScope Uniprise a. Data jacks blue - #UNJ600-BL b. Voice jack green - #UNJ600-GR c. Power fail red - #UNJ600-RD d. Wireless yellow - #UNJ600-YL 3. Hubbell a. Data jacks blue #HXJ6B25, #HXJ6B b. Voice jacks green - #HXJ6GN25, #HXJ6GN c. Power fail red - #HXJ6R d. Wireless yellow #HXJ6Y25, #HXJ6Y H. Consolidation Point Enclosures CAT 6 1. Panduit #WMCPESGBL, or equal. I. Fiber Optic Enclosures: Telecommunications Contractor is responsible for providing and installing all necessary coupling panels, couplings, connectors, and all other devices needed per manufacturers recommendations Inch Rack Mounted Enclosure & Closet Splice Housing a. Panduit TELECOMMUNICATIONS COMMUNICATIONS CABLING

3 1) Enclosure a) 24 port FMD1 Drawer b) 72 port FRME4 Enclosure 2) ST Connector 6-Pack - #FAP6WST 3) 6-Pack Blank - #FAPB b. Commscope Uniprise 1) 24 port Enclosure- RFE-SLG-EMT/1U Drawer (includes 3 blanks) a) ST Connector 6-Pack MFA-ST06-AQ b) 6-Pack Blank RFE-PNL-Blank-BK/4U 2) 72 port Enclosure RFE-FXD-EMT-BK-4U c. Hubbell a) ST Connector 6-Pack RFE-PNL-006-MFA-ST01-BK/4U\ b) 6-Pack Blank RFE-PNL-Blank-BK/4U 1) Enclosure a) 36 port - #FCR350SP36R (holds 6 adapter panels) b) 72 port - #FCR525SPR (holds 12 adapter panels) c) 90 port - #FCR700SP (holds 15 adapter panels) 2) ST Connector 6-pack - #FSPST6 3) 6-Pack Blank - #FSPB d. Corning 1) Enclosure a) 24 port - #PCH-01U b) port - #PCH-04U 2. Wall Splice Enclosures & Splice Trays a. Panduit 1) Enclosure - #FWME8 a) ST Connector 6-Pack #FAP6WST b) 6-Pack blank #FAPB b. Commscope Uniprise 1) Enclosure WFE-EMT-BK-4P: c. Hubbell a) ST Connector 6-Pack #WFE-PNL-006-MFA-ST06-ZZ-BG b) 6-Pack blank #WFE-PNL-Blank-ZZ TELECOMMUNICATIONS COMMUNICATIONS CABLING

4 1) Enclosure - #FTU4SP (holds 2 splice trays) d. Corning a) ST Connector 6-pack - #FSPST6 b) 6-Pack Blank - #FSPB 1) Enclosure - #WSH-16SPT J. Surface Mount Raceway Products 1. Wiremold, or equivalent in ivory, or a color to match the existing raceway. 2. The raceway system shall consist of raceway, appropriate fittings and accessories to complete installation. All raceways shall be comprised of metallic materials. All surface raceways will be secured to walls by using anchors spaced 18 to 24 inches apart. 3. All hardware to be installed in plenum environment must be rated acceptable for plenum rated environments. 4. A full complement of fittings must be available and installed per the manufacturers recommendations. The Telecommunications Contractor (TC) shall provide all necessary fittings to include, but are not limited to flat, internal and external elbows, divided tees and entrance fittings, grommets, couplers, and end caps. The fittings shall provide a means for connecting to the raceway and shall be capable of maintaining a 1 inch minimum cable bend radius. Applicable fittings shall be of base and cover design in order to maintain complete enclosure, maintain separation of power and data channels, and to eliminate mitering. They shall overlap the raceway to hide uneven cuts. 5. Divided junction boxes and angled faceplates shall be available for mounting standard devices. The junction boxes shall be available in standard versions. The junction boxes must have a divider wall to maintain separation of power and data cables and allow for termination of both services in one junction box. The deep boxes shall have a divider wall to be used similar to the shallow box. In addition, an insert to allow for the perpendicular routing through of cables to additional boxes shall be available. The angled faceplates shall allow for terminating of standard electrical devices, both duplex and rectangular styles, and accept jacks designated for this project as inserts for data terminations. The angled faceplates shall accommodate up to 4 jacks and shall be modular in design to accept UTP, Coax, ST, SC, FC and Fiber Jack type of connectors. 6. Angled faceplates shall be available in ivory, or a color to match the existing raceway. 7. Multi-Channel Surface Raceway: All multi-channel surface raceway will be installed by a licensed electrician. a. The raceway shall maintain separation of the power and data channels utilizing an integral barrier. The raceway shall be ivory and have a smooth texture. Where existing surface mounted raceway is present, provide new surface mounted raceway in a color and texture to match the existing. 8. Single Channel Surface Raceway a. The Single Channel Surface Raceway shall be a one-piece design. Raceway shall be comparable to Wiremold 700 or Wiremold b. The raceway and all system components must be UL Listed and exhibit nonflammable. c. Wiremold 700 shall contain no more than 1 CATEGORY 6 cable, or 1 Series 6 TELECOMMUNICATIONS COMMUNICATIONS CABLING

5 coax cable. WM 2000 shall be installed when cable count exceeds the above specified requirements. 9. Vertical Power Pole: Wiremold 25DTP-4 or equivalent a. The Power and Communications Pole channel shall be aluminum. b. Provide all necessary fittings for the Power and Communications Pole including, but not limited to, entrance end fitting, which protects cable bend radius, for the top of the pole, ceiling trim plate, pole mounting bracket, Velcro carpet gripper pad, grommets, and adhesive pad as well as communication covers, angled connector faceplates, inserts and specialty mounting bezels. c. The power and communications pole must be UL listed for field modifications, changes and additions of receptacles, devices, and circuits. d. Surface mounted outlet boxes installed on power poles shall be avoided. Provide necessary adapter plates to ensure a quality installation. K. Approved Rack and Cabinet 1. 7 foot Aluminum Floor Mounted Racks; #12-24 tapped holes, Black a. Panduit-Aluminum Alloy, Flat Black; #12-24 mounting screws; #CMR19X84 b. Saunders/Cooper B-Line-Aluminum Alloy, Flat Black; #12-24 mounting screws; #SB XU c. Great Lakes-Aluminum, Flat Black; #12-24 mounting screws; #GLRR1984BA 2. Wall Mounted Racks a. Homaco Heavy Duty Swing-EZ Wall Racks, or equal 1) H - #19-21-T25DHYDTB 2) H - #19-35-T25DHYDTB b. Superior Modular 19 W, 25 D Swing Racks 1) 24 H-SR225 2) 36 H-SR325 3) 48 H-SR Wall Enclosures a. Saunders/Cooper B-Line, or equal 1) 2 H E2-WM R or L-PD-B 2) 3 H E2-WM R or L-PD-B 3) 4 H E2-WM R or L-PD-B 4) 5 H E2-WM R or L-PD-B b. Great Lakes 1) 2 H GL24WM 2) 3 H GL36WM 3) 4 H GL48WM TELECOMMUNICATIONS COMMUNICATIONS CABLING

6 L. Wire Management 1. 7 foot Vertical a. Panduit, or equal 6 inches w x 6 inches w X 83 inches h, front & rear duct # WMPVHC45E 2. Horizontal 1) Center mount Bracket Kit #WMPVCB a. Panduit, or equal 3 x 3 inches front duct, 2 x 5 inches rear duct #NCMH2 M. Patch Panel All products must be rated CAT 6 with T568-B pin out. 1. Data/Voice Horizontal a. 48 Port 1) Panduit #DP48688TG 2) Commscope Uniprise - #UNP ) Hubbell - #P6E48U b. 24 Port 2. Wireless 1) Panduit #DP24688TG 2) Commscope Uniprise - #UNP ) Hubbell - #P6E24U a. 24 Port N. 110 Wiring Blocks 1. Panduit 1) Panduit #CP24BL 2) Commscope Uniprise - #UNP-MOD-24P 3) Hubbell - #UDX24E a. 100 pair base with legs-#p110bw100-x b. 4-Pair Connecting Blocks - #P110CB4-XY c. Label Holder #P110LH 2. Commscope Uniprise a. 100 pair base with legs - #UN-110-WB-100PR b. 4-Pair Connecting Blocks - #UN-110-CB-4P-10C c. Label Holder - #UN-110-LH 3. Hubbell a. 100 pair base with legs - #110BLK100BWL b. 4-Pair Connecting Blocks - #110CB4PR10 c. Label Holder - #XPH11010 TELECOMMUNICATIONS COMMUNICATIONS CABLING

7 O. Tie-Wraps 1. Thomas and Betts-#TY-25M-9, or equal 2. Panduit a. 4 #PLT1M-C702 b #PLT2S-C702 c #PLT3S-C702 P. Building Entrance Terminals/Protectors-Voice Applications-Solid State-CAT 3 1. Circa Protectors a. Terminals 1) 12 pair, #2612QC/QC 2) 25 pair, #1890ECT1/NSC-25 3) 50 pair, #1890ECT1/NSC-50 4) 100 pair, #1890ECT1/NSC-100 b. Modules Solid State, 5 pin 1) Data - #3B3S-30 2) Voice - #3B1FS Porta Systems Protectors a. Terminals 1) 10 pair, # M66 2) 25 pair, # M66 3) 50 pair, # M66 4) 100 pair, # M66 b. Modules Solid State, 5 pin 1) Data - #MLVP27E 2) Voice - #115SCNHDS-230 Q. Building Entrance Terminals/Protectors-Data Applications-CAT pair UTP a. ITWLINX - #CAT 6-LAN or equal b. Porta Systems-#CAT 6-Series 606 R. Power Strips, must be UL listed, 19 rack mounted, 20 amps, 8 rear outlets, 15 feet service tail 1. Geist-#VSSL R20, or equal S. Faceplates for recessed applications 1. Panduit TELECOMMUNICATIONS COMMUNICATIONS CABLING

8 a. 2 Port-#CFPE2IW b. 4 Port-#CFPE4IW c. 6 Port-#CFPE6IW 2. Commscope Uniprise a. 2 Port #UNF-D-2P-CM b. 3 Port #UNF-D-3P-CM c. 4 Port - #UNF-D-4P-CM d. 6 Port - #UNF-D-6P-CM 3. Hubbell a. 2 Port #IFP12OW b. 3 Port #IFP13OW c. 4 Port #IFP14OW d. 6 Port #IFP16OW T. Faceplates for Wiremold 700 and Wiremold 2000 applications 1. Panduit - #CFPSE4IW, or equal 2. Hubbell Premise Wiring - #DFIAL, #DFA2KAL (2) U. Faceplates for 4000 Wiremold applications, angled raceway adapter 1. Wiremold - #CM-ARA, or equal 2. Hubbell Premise Wiring Module Bezel KPIMBZAL & DFA2KAL V. External Ringer: Operates from 24 VDC, connects into standard telephone wall jack, equipped with three position volume switch and 103 db maximum modulated tone output. 1. After School Bell a. Dees Communications, or equal 1) Stinger Ringer - # Café Manager s Office/Kitchen W. 106 Frames a. Valcom, or equal 1. Panduit 1) Loud Horn - #V-9945A a. 2-Port - #CF1062IWY, or equal b. 4-Port - #CF1064IWY, or equal 2. Hubbell a. 2-Port - #BR106C b. 4-Port - #Q106O TELECOMMUNICATIONS COMMUNICATIONS CABLING

9 PART 3 - EXECUTION 3.1 HORIZONTAL DISTRIBUTION CABLING A. Horizontal cabling is installed in a star topology. B. Bridged taps and splices are not permitted as part of the copper horizontal cabling. C. All connectivity products such as patch panels, faceplates and data jacks shall be of the same manufacturer (see approved products list). D. All cables shall be plenum rated, unless otherwise noted. E. Contractor shall install all cabling according to latest industry standards, manufacturer s recommendations and best practices. Cabling shall be installed in an orderly and neat manner. Cables shall be installed parallel and perpendicular to building lines. F. Horizontal cables shall terminate to the closest Telecommunications Room (TR) on the same floor. G. Horizontal cable links shall not exceed 90 meters. H. UTP cable shall be installed so that there are no bends smaller than 4 times the cable s outside diameter at any point in the cabling run and the termination area. If cables are kinked or the cable jacket is damaged during the installation, the cable will be removed and replaced with new cables at no additional cost to the Owner. I. Pulling tension on 4-pair UTP cables shall not exceed 25-lbf for a four-pair UTP cable. J. A pull cord (nylon; 1/8 inch minimum) shall be co-installed with all cable installed in any homerun conduit and conduits exceeding 2 in diameter. K. Cable raceways shall not be filled greater than the TIA/EIA-569-A maximum fill for the particular raceway type or 40%. L. Where transition points or consolidation points are required, they shall be located in accessible locations and housed in an enclosure intended and suitable for the purpose. M. Slack required 1. Data room a. 10 feet minimum for UTP b. 20 feet minimum for Fiber, not including the 15 feet of workable fiber wound inside fiber cabinet 2. Work area outlets 12 inch minimum for UTP 3. Access point locations 20 feet minimum for UTP N. The ceiling cable support throughout most of the facility will be accomplished by utilizing open areas above ceilings and cable trays when available. If cable trays or sleeves are available, the TC must use the cable trays and sleeves as their pathway, unless the TC has received formal approval from the Designer. All penetrations through fire-rated walls or floors must be sleeved. In areas where support structure is not available, cables will be supported with metallic J-brackets at regular 4-5 foot intervals. Cables may only be TELECOMMUNICATIONS COMMUNICATIONS CABLING

10 supported by building structure when the cable spans do not exceed 5 foot intervals. Cables SHALL NOT be supported on top of walls or I-beams or in areas where the cable is susceptible to damage or EMI. Cables shall not be attached to ceiling grid or lighting fixture wires. At no point shall cable(s) rest on acoustic ceiling grids or panels. O. When utilizing J-hooks, the TC shall neatly groom the cables with tie-wraps. P. No more than 12 inches of cable sag shall be allowed between supports. Q. There shall be a minimum of three inches of clearance between the cable support system and the ceiling tile support grid. R. No cables shall run exposed. In areas of no accessible ceiling and where a pathway is not being provided by others, the Contractor shall provide the pathway. The pathway shall be EMT conduit in commons areas, or wiremold metallic raceway in classroom/office areas. TC shall provide all necessary sleeving of walls and floors where sleeves or openings are not being provided by others. S. All equipment and materials installed in plenum environment shall be UL rated acceptable for plenum environments. T. Horizontal distribution cables shall be bundled in groups of no more than 40 cables. Cable bundle quantities in excess of 40 cables may cause deformation of the bottom cables within the bundle and degrade cable performance. This includes cable bundles supported in J-Hooks. U. Cable shall be installed above fire-sprinkler systems and shall not be attached to the system or any ancillary equipment or hardware. The cable system and support hardware shall be installed so that it does not obscure any valves, fire alarm conduit, boxes, or other control devices. V. TC must ensure that TIA/EIA recommended minimum separation distances are maintained between the newly installed cabling and high-energy sources that may interfere with data transmission. Cables shall never come into contact with any ceiling grids or lighting sources or any devices that emit EMI. W. Cables routing under slab or outside shall be rated outside plant and provide water blockage. Upon entering the building and exiting the conduit, the outdoor cable shall be transitioned to a plenum rated cable. This will be accomplished by placing transition points within 50 of the cable s entry into the building. X. Provide over voltage protection on both ends of cabling exposed to lightning or accidental contact with power conductors. Y. Abandoned cables shall be removed port to port. 3.2 TELECOMMUNICATION ROOM (TR) A. Data Racks 1. Data racks shall be installed where shown on the drawings. Racks shall not be located under any equipment, pipes or ductwork that may cause condensation or possibly leakage. Consult with Designer on rack lay-out if these conflicts are present. 2. Racks shall be heavy duty EIA complaint nineteen (19) inch wide, seven (7) foot tall equipment racks, unless otherwise noted. Racks shall have a black finish. Side TELECOMMUNICATIONS COMMUNICATIONS CABLING

11 channels shall be drilled and tapped on both sides. 3. Racks shall be securely anchored to the floor slab using 3/8 expansion anchors. The rack shall tie to the wall via a 12 ladder cable runway for routing cables. 4. Racks shall be placed with a 36 minimum clearance from the room walls on all sides of the rack. When mounting racks in a row, maintain a minimum of 36 clearance from the walls behind and in front and from the wall at each end of the row. 5. Unused rack equipment mounting screws shall be bagged and attached to the racks upon completion of the project. 6. All racks shall be grounded to the telecommunications ground bus bar provided in each TR. B. UTP Cable Termination Hardware 1. Each horizontal or backbone cabling run will be terminated using appropriate connectors or connecting blocks depending upon the cable type. Matching patch cords, provided by the Owner, unless otherwise noted, will be used to perform cross-connect activities or to connect into the networking/voice hardware. 2. Cables shall be dressed and terminated in accordance with the recommendations made in the TIA/EIA-568-B standard, manufacturer's recommendations and best industry practices. 3. Pair untwist at the termination shall not exceed Bend radius shall not exceed 4 times the outside diameter of the cable. 5. Splitting the pairs prior to termination is not acceptable. 6. Cables shall be neatly bundled and dressed into their respective panels or blocks. Each panel or block shall be fed by an individual bundle separated and dressed back to the point of cable entrance into the rack or frame. 7. The cable jacket shall be maintained as close as possible to the termination point. 8. Each cable will be clearly labeled on the cable jacket behind the patch panel. Labels shall be machine printed and clearly visible within the bundle. 9. Wall mounted termination block field s enclosures and racks shall be mounted on plywood backboards located in TR and installed per manufacturer s recommendations. a. Backbone and horizontal voice cables shall be terminated on 110 blocks mounted on the fire-rated plywood behind the data racks. Use metallic D-Rings as necessary for cable management. Size D-rings to fit the application. b. Wall mounted termination block fields shall be installed with the lowest edge of the mounting frame 48 inches from the finished floor. c. 110 type IDC connecting clips shall be installed for every installed cable pair. 10. Four-pair Category 6 UTP cabling shall be terminated onto a four-pair Category 6 module. All modules shall be terminated using the T568B (B) wiring scheme. The eight position module shall exceed the connector requirements of the proposed TIA/EIA Category 6 standard. 11. Patch Panels shall be of the manufacturer and part number as listed in these specifications. The patch panels shall be T568B wiring configurations. Rack mountable patch panels shall mount to standard EIA 19"W floor mounted data racks. Cables shall be neatly groomed with Velcro Integral cable ties. Port and panels shall be easy to identify with write-on areas. Patch panels shall be completely populated. 12. Cables routing from the wireless access points shall be terminated in a separate 24 port modular patch panel. The patch panels shall be clearly labeled Wireless. C. Fiber Termination Hardware TELECOMMUNICATIONS COMMUNICATIONS CABLING

12 1. All fiber optic terminations shall be accomplished by fusion or no epoxy/no-polish field terminations. 2. The terminated strands shall be secured within fiber optic enclosures. Fiber slack shall be neatly coiled within the fiber splice tray or enclosure. 3. Telecommunications Contractor will supply the appropriate number of fiber coupler panel blanks for each fiber enclosure where fiber optic terminations are not made. 4. The cables strength member shall be securely attached to the cable strain relief bracket in the enclosure. 5. When terminated the fiber via splicing, each fiber bundle shall be stripped upon entering the splice tray and then route the individual fibers in the splice tray. 6. When terminated with field installable connectors, no epoxy/no-polish ST connectors shall be used. The connector installation shall not require the use of epoxies, adhesives or ovens. The connectors shall be compliant with industry standard ANSI/TIA/EIA-568-B-3. D. Plywood Backboards 1. TC to provide ¾ inch fire-rated plywood in 4 x 8 foot sheets and void free. The plywood shall be painted with two coats of white fire-retardant paint leaving the manufacturer s printed labels unpainted and clearly visible. 2. In Telecommunications Rooms, plywood shall be mounted horizontally starting at 24 inches AFF and to approximately 6 inches below ceiling. One wall shall be covered, see Construction Documents for locations. 3. In the Main Telecommunications Room-MC (Equipment Room) plywood shall be mounted horizontally starting at 24 inches AFF to 6 inches below ceiling. All walls shall be covered, see Construction Documents for details. E. Cable Management 1. Horizontal and Vertical Wire Management shall be provided and utilized by the TC. The system provided shall be comprised of equipment to manage cables on both the front and rear of the rack. The Wire Management shall protect network performance by controlling bend radius and providing cable strain relief. 2. All cable management channels shall have covers. 3. Horizontal Wire Managers shall be placed above and below each patch panel and shall intersect with the Vertical Wire Managers seamlessly. 4. D-rings shall be metallic and used in areas where cables are not supported by cable runway or cable tray. The D-Rings shall be a minimum size of 4 inches. The TC shall be responsible for determining quantity and the placement of D-Rings at strategic points throughout the Telecommunications Room. F. Grounding and Bonding 1. Grounding shall be installed per NEC and ANSI/TIA/EIA 607 and manufacturer s grounding requirements as minimum. 2. Bond and ground equipment racks, housings, messenger cables, ladder racks, metallic raceways, and armored fiber with a #6 AWG stranded green insulated conductor. #12 AWG stranded insulated green conductor shall be used to bond surface mounted metallic raceways. However, in plenum areas, the grounding conductor shall be a bare, solid conductor for all grounding applications. Coordinate with electrical contractor. Electrical contractor (EC) to bond or ground all pathways provided by electrical contractor. 3. TMGB (Telecommunications Main Grounding Busbar) and TGB Telecommunications Grounding Busbar) shall be provided by the EC unless otherwise noted. EC shall bond the TMGB to the electrical service equipment ground and to building steel with a #6 AWG green conductor unless otherwise noted TELECOMMUNICATIONS COMMUNICATIONS CABLING

13 on the Electrical Construction Documents. building steel by the EC. The TGB shall also be bonded to G. Firestop 1. All penetrations through fire-rated building structures (walls and floors) shall be sealed with an appropriate firestop system. This requirement applies to through penetrations (complete penetration) and membrane penetrations (through one side of a hollow fire rated structure). Any penetrating item i.e., riser slots and sleeves, cables, conduit, cable tray, and raceways that are specifically designated for the data/video/voice infrastructure shall be properly firestopped. The contracting discipline installing the sleeve or slot, shall be responsible for sealing the area on the exterior of the sleeve or slot. The TC shall be responsible for firestopping the interior annular area. 2. Firestop systems utilized shall be dictated by this project s Professional Electrical Engineer s UL design. See Electrical Drawings and specifications for exact details. If a Professional Engineer s UL design is not available, the Contractor shall provide appropriate UL design for penetrations through rated walls and properly firestop penetrations. These documents shall be submitted to the Designer. 3.3 WORK AREA OUTLETS A. Cables shall be coiled in the in-wall or surface-mount boxes if adequate space is present to house the cable coil without exceeding the manufacturer s bend radius. Excess slack shall be loosely coiled and stored in the accessible ceiling above each drop location when there is not enough space present in the outlet box to store slack cable. B. Pair untwist at the termination shall not exceed.5. C. Bend radius of the cable in the termination area shall not be less than 4 times the outside diameter of the cable. D. The cable jacket shall be maintained to as close as possible to the termination point. E. Data/voice and wireless cables shall be terminated on a RJ45 jack. Jack colors shall be Blue for data, Green for voice within a modular faceplate. The faceplate at each work area shall be capable of holding up to a minimum of one (1) RJ45 jack more than what is indicated on the Construction Documents except when using Wiremold 700, or equivalent. A blank cover shall be installed on all unused positions within each faceplate. All RJ45 jacks shall meet or exceed the TIA/EIA-568-B.2-1 standard for Category 6. F. Data jacks, unless otherwise noted in drawings, shall be located in the bottom position(s) of each faceplate. Data jacks in horizontally oriented faceplates shall occupy the right-most position(s). G. Voice jacks shall occupy the top position(s) on the faceplate. Voice jacks in horizontally oriented faceplates shall occupy the left-most position(s). H. 106 Frames, if required, shall be a 2 or 4 port frame that mounts onto U.S. NEMA standard junction boxes and wall board adapters with screw-to-screw dimensions of 3.28" (83.3mm) and behind NEMA standard 106 duplex electrical faceplates. Frame shall accept individual modules that can be individually inserted and removed as required. I. For surface mounted raceway equivalent to Wiremold 4000 and power poles, provide TELECOMMUNICATIONS COMMUNICATIONS CABLING

14 angled connector faceplates. The TC to provide all necessary fittings and additional materials to adhere to manufacturer s installation guidelines. J. Stainless steel blank cover plates for all unused Telecommunications Outlets shall be provided by others unless otherwise specified on the Construction Drawings. K. Contractor provided surface mounted metallic raceway shall be bonded to building steel utilizing a #12 AWG green conductor. 3.4 BACKBONE CABLE INSTALLATION A. All cables shall be plenum rated, unless otherwise noted. B. A pull cord (nylon; 1/8 inch minimum) shall be co-installed with all cable installed in any conduit. C. Where backbone cables and distribution cables are installed in a cable tray or wireway, backbone cables shall be bundled separately from the horizontal distribution cables. D. All backbone cables shall be securely fastened to the sidewall of the Telecommunications Rooms on each floor with metallic D-Rings on the fire-rated plywood behind the data racks. E. Backbone cables spanning more than three floors shall be securely attached at the top of the cable run with a wire mesh grip and on alternating floors or as required by local codes. F. Vertical runs of cable shall be supported to messenger strand, cable ladder, or other method to provide proper support for the weight of the cable. G. Large bundles of cables and/or heavy cables shall be attached using metal clamps and/or metal banding to support the cables. H. Provide over voltage protection on both ends of cabling exposed to lightning or accidental contact with power conductors. I. Refer to PART 3.1 Horizontal Distribution Cabling of this section for additional cabling requirements. 3.5 IDENTIFICATION AND LABELING A. All cables, faceplates, patch patch panels, ports, grounding conductors and junction boxes shall be labeled with self-adhesive printed labels. Cables shall be labeled on each end. Refer to ANSI/TIA/EIA 606 and Owner requirements to coordinate labeling schemes. 1. Label each data rack/enclosure room designations, ie. TR-1-1, TR-1-2, etc. 2. Label the face of data/voice patch panels with patch panel designations, ie. Data A, Data B, Wireless A, Wireless B. 3. The label on data/voice horizontal cables and faceplates shall read TR1-A-12 where TR or MC determines the Telecommunications Room; the A designates the patch panel and the 12 designates the port on the patch panel. 4. The label on wireless access point cables shall read TR1-AP-1 where TR or MC determines the Telecommunications Room; the AP designates that it is a wireless access point cable, and the 1 shall designate the number of the access point. The access points shall be numbered sequentially according to telecommunications TELECOMMUNICATIONS COMMUNICATIONS CABLING

15 3.6 TESTING rooms. If there is more than one 24 port patch panel needed for wireless access points, the labeling shall be TR1-AP-A-1, where the A following the AP designates the wireless patch panel in the rack. If the access point is in the ceiling, then the Contractor shall label the ceiling grid below the access point as well as the access point and cable for the access point. 5. On backbone copper cables, the label shall read MC-TR1 where MC determines the Telecommunications Room where the cable originates and the TR determines the final destination of the backbone cable. 6. The label shall read on fiber cables MC-TR1 where MC determines the Telecommunications Room where the cable originates and the TR determines the final destination for the fiber. These cables shall be labeled after exiting the junction box outside of the MC and before entering the fiber enclosure at the opposite end. 7. For Telecommunications Bonding Conductors, label cables on each end and at each point of connection. The Telecommunications Bonding Conductor the label shall read TBC-TR2 where the 2 designates the Telecommunications Room that the conductor originates. Labels shall be visible during installation and after project completion. A. The Owner reserves the right to test all delivered goods, and to use a portion of any goods before the results of the tests are delivered, without prejudice to any final adjustments, rejecting the unused portion of the delivery, and making payment on an adjusted basis for the used portion. The cost of inspections and test of any item, which fails to meet the advertised specifications, shall be borne by the TC. B. All cables and termination hardware shall be 100% tested for defects to verify cabling system performance under installed conditions according to the requirements of ANSI/TIA/EIA-568-B and A. The field test equipment shall meet the requirements of ANSI/TIA/EIA-568-B. Testing shall be accomplished using level III field testers for copper, and a power meter and light source tester for fiber. C. Test each pair and shield of each cable for opens, shorts, grounds, and pair reversal. Correct grounded and reversed pairs. Examine open and shorted pairs to determine if problem is caused by improper termination. D. Testing equipment shall be factory calibrated within in 12 months prior to testing. E. Test results shall be submitted within ten (10) days of the completion of each testing phase. F. When repairs and re-tests are performed, the problem found and corrective action taken shall be noted, and both the failed and passed test data shall be documented and included in the final close out documents submittal. G. Copper Permanent Link Testing 1. Perform testing of copper cables with tester meeting ANSI/TIA/EIA-568-B.1 and B.2 requirements. 2. If horizontal cables contain bad conductors or shield, remove and replace cable. 3. Continuity - Each pair of each installed cable shall be tested using a test unit that shows opens, shorts, polarity and pair-reversals, crossed pairs and split pairs. Shielded/screened cables shall be tested with a device that verifies shield continuity in addition to the above stated tests. The test shall be recorded as pass/fail as indicated by the test unit in accordance with the manufacturers recommended procedures, and referenced to the appropriate cable identification number and circuit TELECOMMUNICATIONS COMMUNICATIONS CABLING

16 or pair number. Any faults in the wiring shall be corrected and the cable re-tested prior to final acceptance. 4. Length - Each installed cable link shall be tested for installed length using a TDR type device. The cables shall be tested from patch panel to patch panel, block to block, patch panel to outlet or block to outlet as appropriate. The cable length shall conform to the maximum distances set forth in the ANSI/TIA/EIA-568-B standard. Cable lengths shall be recorded, referencing the cable identification number and circuit or pair number. This documentation shall be in a sequential format. For multipair cables, the shortest pair length shall be recorded as the length for the cable. 5. Category 6 Performance a. Follow the Standards requirements established in ANSI/TIA/EIA-568-B. b. A level III test unit is required to verify category 6 performances. c. Required tests 1) Wire Map 2) Insertion Loss 3) Length 4) NEXT loss, pair-to-pair, measured from local end 5) NEXT loss, pair-to-pair, measured from far-end 6) NEXT loss, power sum, measured from local end 7) NEXT loss, power sum, measured from far-end 8) Return Loss, measured from local end 9) Return Loss, measured from far-end 10) ELFEXT, pair-to-pair 11) ELFEXT, power sum 12) Propagation Delay 13) Delay skew 14) ACR 15) Power Sum (PSACR) 6. Category 3 Performance a. Follow the Standards requirements established in ANSI/TIA/EIA-568-A. b. Required tests H. Fiber Testing 1) Polarity 2) Length 3) Reversal of pairs 4) Wire transpositions 5) Continuity 6) Opens 7) Shorts 1. All backbone and horizontal cabling, which is terminated by the TC, shall be tested to applicable EIA/TIA Standards. 2. The insertion loss for each mated fiber optic connector pair shall be 0.75 db. Reflectance for single-mode single fiber UPC cable assemblies shall be -55dB. Mated connector pair loss testing shall be based on one unidirectional OTDR inspection in accordance with the OTDR operating manual for systems greater than 100 meters. 3. In addition to connector insertion loss for each mated pair, the TC shall perform endto-end insertion loss testing for each multimode fiber at 850 nm and 1300 nm from one direction for each terminated fiber span in accordance with EIA/TIA A TELECOMMUNICATIONS COMMUNICATIONS CABLING

17 (OFSTP 14) and single-mode fibers at 1310 nm and 1550 nm from one direction for each terminated fiber span in accordance with TIA/EIA (OFSTP 7). For spans greater than 90 meters, each tested span must test to a value less than or equal to the value determined by calculating a link loss budget. For horizontal spans less than or equal to 90 meters, each tested span must be 2.0 db. 4. Inspect each terminated multimode fiber span for continuity and anomalies with an OTDR at 1300 nm from one direction in accordance with the OTDR operating manual for systems greater than 100 meters. Inspect each terminated single-mode fiber span for continuity and anomalies with an OTDR at 1550 nm from one direction in accordance with OTDR operating manual for systems greater than 100 meters. 3.7 SYSTEM DOCUMENTATION AND OWNER ACCEPTANCE A. The final inspection by the Designer and/or Owner shall be the closure of all previously listed punch list items. B. The Completion Date of Project is defined as the date that all documentation obligations have been met under the Construction Documents and these specifications. C. The final inspection by Building Standards shall be the closure of required Electrical Permits. D. Upon completion of the installation, the TC shall provide two (2) full documentation sets to the Owner for approval. E. Close-Out Documents Submittal 1. CD disk containing test results. The disk shall be clearly marked on the outside front cover with the words Project Test Documentation, the project name, the company name and the Project Completion Date. The CD shall also contain the software needed to view results. a. The results shall include a record of test frequencies, cable type, conductor pair and identified in the same format required in the Identification and Labeling section of these specifications, measurement direction, reference setup, and crew member name(s). Results shall have all cables sequentially listed. The test documents shall detail the test method used and the specific settings of the equipment during the test as well as the software version being used in the field test equipment. 1) Copper Test Results (Permanent Link) 2) Copper Test Summary (Single Line) for each cable print out. (Hard copy and electronic file). 3) Copper Test Detail for each cable (Electronic file only). 4) Fiber Test Results (Basic Link) 5) OTDR results 6) Fiber Test Summary (Single Line) print out for each fiber. (Hard copy and electronic file). 7) Patch panel logs in editable electronic format b. As-built electronic files in AutoCAD format, bind all external references. 2. Draft (marked up) as-built drawings submitted within 30 days of the Completion Date of Project. TELECOMMUNICATIONS COMMUNICATIONS CABLING

18 3. Calibration Sheets a. Include test equipment name, manufacturer, model number, serial number, software version and last calibration date. Submit sheets for each tester being used for the project. 4. Patch Panel Log a. Labeling shall be consistent with the Identification and Labeling section of these specifications listed above. 5. Electrical Permit Inspection Detail 6. Final As-Built Drawings a. Submitted drawings shall be neat and clear and professionally produced. Do not place text over objects where the label indicator cannot be deciphered. Use care to keep the text size consistent throughout the drawings. Do not use colored ink to distinguish between symbols, or lines. Provide another symbol or line type designation to represent different components. Any final as-built drawing will be subject to rejection if the Designer and/or Owner find the information on the plotted drawings unclear. b. Final drawings shall indicate all backbone and horizontal cable routes. Also indicate final outlet locations labeled according to the Identification and Labeling section of these specifications listed above. Indicate final pathway locations and final locations of all equipment. Use a different Line-type for each type of cable installed. c. Include a legend on the first sheet indicating Line-type of each cable, and any additional symbols the Contractor has added. d. Plot drawings in black and white, where the Line type scale is easily discernable. 1) Plotted drawings sizes a) (2) Two E1 size (30 x42 ) b) (1) B size (12 x18 ) 7. Provide facility assignment records which include, patch panel logs and as-built C size (11 x22 ) in a protective cover (laminated) at each Telecommunications Room location that is specific to the facilities terminated therein. 8. The Designer and/or Owner may conduct and or request that a 10% random field retest be conducted on the cable system, at no additional cost, to verify documented findings. The Owner and or Designer can require this test to be performed by an outside agency. Tests shall be a repeat of those defined above. If findings contradict the documentation submitted by the TC, additional testing can be requested to the extent determined necessary by the Designer and/or Owner, including a 100% re-test by an outside agency. This re-test shall be at no additional cost to the Owner. 3.8 SITE CLEAN UP A. All classrooms, offices, labs or anywhere work is conducted shall be cleaned up on a daily basis. 3.9 TELECOMMUNICATIONS ROOM/CABINET CLEAN UP A. All room locations must be broom or vacuum swept. This includes the space between the racks and the trough between the base footprint of the rack. TELECOMMUNICATIONS COMMUNICATIONS CABLING

19 B. All data racks and enclosures shall be wiped clean. C. All cabinet locations must be broom or vacuum swept. This includes the bottom space of the cabinet. END OF SECTION TELECOMMUNICATIONS COMMUNICATIONS CABLING

DIVISION 27 COMMUNICATIONS. A. System design shall be completed by a Registered Communications Distribution Designer (RCDD).

DIVISION 27 COMMUNICATIONS. A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). DIVISION 27 COMMUNICATIONS 27 00 00 COMMUNICATIONS A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). B. Comply with American National Standards Institute

More information

SECTION 25110 TELECOMMUNICATION ROOMS

SECTION 25110 TELECOMMUNICATION ROOMS PART 1 - GENERAL 1.1 SUMMARY A. SCOPE SECTION 25110 TELECOMMUNICATION ROOMS 1. This section includes the minimum installation requirements for equipment and cabling infrastructure in Telecommunication

More information

1. Furnish and install faceplate and modular jacks at each single gang outlet as described below:

1. Furnish and install faceplate and modular jacks at each single gang outlet as described below: Washington University in St. Louis Building: Communication Specification: Research Voice/Network/Typical 1. Furnish and install faceplate and modular jacks at each single gang outlet as described below:

More information

DIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION

DIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION DIVISION 26 - ELECTRICAL PART 1 - GENERAL 1.01 SUMMARY A. Section Includes 1. Instrumentation Cables 1.02 SUBMITTALS A. Submit in accordance with requirements of Section 01 33 00. B. Product Data: Submit

More information

TCTC Cabling Specifications

TCTC Cabling Specifications TCTC Cabling Specifications Purpose: To provide a standard specification that will be used for all Tri County Technical College (TCTC) facilities requiring structured cabling installation. Product specifications,

More information

Presenters Brett Weiss, Gabe Martinez, Brian Kroeger.

Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. 1 Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. Topics to be covered: Cable identification Purpose of the various cable types Installation techniques Building Infrastructure Overview of networking

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-27 05 14.00 10 (April 2006) -------------------------------- Preparing Activity: USACE Superseding UFGS-27 05 14.00 10 (April 2004) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

ANSI/TIA/EIA - 568-A, Commercial Building Telecommunications Cabling Standard.

ANSI/TIA/EIA - 568-A, Commercial Building Telecommunications Cabling Standard. WIRING STANDARD INTRODUCTION This standard defines a telecommunications wiring system for North Dakota State Agencies, offices or buildings that will support a multi-product environment. The purpose of

More information

NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION 27 10 00 STRUCTURE CABLING TESTING

NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION 27 10 00 STRUCTURE CABLING TESTING RELATED SECTIONS: NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT Section 27 00 00 General Requirements Section 27 02 00 General Communication Requirements Section 27 05 26 Grounding and Bonding for Communications

More information

Minimum Standards for Data/Voice Infrastructure in New Building Construction

Minimum Standards for Data/Voice Infrastructure in New Building Construction UNIVERSITY OF WATERLOO Minimum Standards for Data/Voice Infrastructure in New Building Construction 12/17/2012 Offices 1. Two Work Area Outlets (WAO) on opposite walls, each with 2 jacks 2. Each WAO shall

More information

B. Cross-Connect: A facility enabling the termination of cable elements and their interconnection or cross-connection.

B. Cross-Connect: A facility enabling the termination of cable elements and their interconnection or cross-connection. DIVISION 16 ELECTRICAL Section 16740 Telephone System PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

UT Southwestern Medical Center Information Resources Cable Installation Standard

UT Southwestern Medical Center Information Resources Cable Installation Standard UT Southwestern Medical Center Information Resources Cable Installation Standard PART 1- GENERAL 1.01 SUMMARY A. Furnish and install wire, cable, devices, equipment, and accessories for a complete system

More information

Specifications for Communication Cabling Distribution Systems

Specifications for Communication Cabling Distribution Systems Washington University in St. Louis Specifications for Communication Cabling Distribution Systems General Overview Listed below are the separate sub-systems of Washington University s structured cabling

More information

SYSTIMAX SCS PowerSum and GigaSPEED XL Cabling Installation Guidelines

SYSTIMAX SCS PowerSum and GigaSPEED XL Cabling Installation Guidelines SYSTIMAX SCS PowerSum and GigaSPEED XL Cabling Installation Guidelines This document contains critical information regarding the installation of a certified SYSTIMAX SCS that meets or exceeds performance

More information

SECTION 28 05 00 COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND SECURITY

SECTION 28 05 00 COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND SECURITY SECTION 28 05 00 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specifications Sections, apply

More information

Category 6 Solutions. 4. Category 6 Solutions. 09/08 400836IN TrueNet Structured Cabling. Introduction... 4.2. Cable... 4.3. Patch Panels... 4.

Category 6 Solutions. 4. Category 6 Solutions. 09/08 400836IN TrueNet Structured Cabling. Introduction... 4.2. Cable... 4.3. Patch Panels... 4. Category 6 Solutions Introduction... 4.2 Cable... 4.3 Patch Panels... 4.4 Modules... 4.6 Patch Cords... 4.12 Outlets... 4.16 Faceplates...4.18 4. 1 Search Category 6 Solutions Introduction ADC KRONE s

More information

ATTACHMENT F 050R6800016 - CABLE AND WIRING SERVICES FUNCTIONAL AREA I PRICE PROPOSAL FORM Amendment 6

ATTACHMENT F 050R6800016 - CABLE AND WIRING SERVICES FUNCTIONAL AREA I PRICE PROPOSAL FORM Amendment 6 050R6800016 CABLE AND WIRING SERVICES (Column A) (Column B) (Column C) (Column D) (Column E) (Column F) (Column G) (B+C+D+E)*F= G Item Description PER 100' RUN PER 150' RUN PER 200' RUN PER 300' RUN QUANTITY

More information

1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications.

1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications. Issued 2005/06/01 Section 16743 Data System Page 1 of 7 PART 1 GENERAL 1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications..2 Data system equipment

More information

Colorado Army National Guard Grand Junction Readiness Center NGB PN 080204 Coover-Clark & Associates CCA Job No. 0726

Colorado Army National Guard Grand Junction Readiness Center NGB PN 080204 Coover-Clark & Associates CCA Job No. 0726 SECTION 260523 - CONTROL-VOLTAGE ELECTRICAL POWER CABLES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. UTP cabling. 2. RS-232 cabling. 3. RS-485 cabling. 4. Low-voltage control cabling. 5. Control-circuit

More information

TELECOMMUNICATIONS STRUCTURED CABLING GUIDELINES AND SPECIFICATIONS. University of Chicago IT Services Infrastructure Services October 2011

TELECOMMUNICATIONS STRUCTURED CABLING GUIDELINES AND SPECIFICATIONS. University of Chicago IT Services Infrastructure Services October 2011 TELECOMMUNICATIONS STRUCTURED CABLING GUIDELINES AND SPECIFICATIONS IT Services Infrastructure Services October 2011 Table of Contents 1 Introduction... 4 1.1 Planning and Design... 4 1.2.1 Roles and Responsibilities...

More information

HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE: 10.17.12

HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE: 10.17.12 SECTION 27 05 26 - GROUNDING AND BONDING FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes grounding and bonding products, design requirements and installation for communications

More information

Terminating 25-Pair Cable and 4-Pair Cross Connects

Terminating 25-Pair Cable and 4-Pair Cross Connects Terminating 25-Pair Cable and 4-Pair Cross Connects Estimated Time: 90 minutes Number of Teams: 2 Number of Team Members: one to four This Lab has four major parts that will be addressed separately. 1.

More information

Division 27 Master Specification for

Division 27 Master Specification for Division 27 Master Specification for Information Transport Systems and Spaces May 1, 2014 1 Table of Contents 1 Section 27 10 01 Structured Cabling General Requirements 1.1 Scope 1.2 Approved Contractor

More information

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations. DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,

More information

Intelligent Cable Management Systems

Intelligent Cable Management Systems Intelligent Cable Management Systems Bringing Practical Application Karen Pearson - Leviton Why Cable Management Matters Performance Cooling and air-handling Maintenance ANSI/TIA 569* Telecommunication

More information

SECTION 27 13 24 COMMUNICATIONS OPTICAL FIBER OSP CABLING

SECTION 27 13 24 COMMUNICATIONS OPTICAL FIBER OSP CABLING SECTION 27 13 24 COMMUNICATIONS OPTICAL FIBER OSP CABLING PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete

More information

Cable Installation Project

Cable Installation Project Cable Installation Project 1. Intent. It is the intent of the U.S. Court of Appeals to install Category 6 (CAT6) data cabling in the Robert F. Peckham Federal Building and United States Courthouse, 280

More information

B. PART 1 - GENERAL of SECTION 271300 BACKBONE COMMUNICATIONS CABLING shall also apply to this section.

B. PART 1 - GENERAL of SECTION 271300 BACKBONE COMMUNICATIONS CABLING shall also apply to this section. SECTION 271500 - HORIZONTAL UTP CABLING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

800 Communications Circuits

800 Communications Circuits ARTICLE 800 Communications Circuits INTRODUCTION TO ARTICLE 800 COMMUNICATIONS CIRCUITS This article has its roots in telephone technology. Consequently, it addresses telephone and related systems that

More information

March 2007. 27 08 00 Commissioning of Communications. See Appendix E3. 27 08 00-1

March 2007. 27 08 00 Commissioning of Communications. See Appendix E3. 27 08 00-1 March 2007 27 08 00 Commissioning of Communications See Appendix E3. 27 08 00-1 27 11 00 Communications Equipment Room Fittings 1.0 General TELEPHONE RISERS: A. All copper telephone riser cables must be

More information

Standards and Guidelines for Telecommunications Wiring Design and Installation Montana State University-Bozeman

Standards and Guidelines for Telecommunications Wiring Design and Installation Montana State University-Bozeman Standards and Guidelines for Telecommunications Wiring Design and Installation Montana State University-Bozeman This document defines the standards used for voice and data wiring in buildings used by MSU

More information

Cabling Services (price per pull) Zone 1 Zone 2 Zone 3 Zone 4 Zone 5

Cabling Services (price per pull) Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 BryComm, LLC -SDD-1901 Cabling Services (per pull) - Labor Only STANDARD TIME The price per cable pull represents all labor to include fishing walls, running cable through modular furniture, terminating,

More information

SECTION 16750 VOICE AND DATA COMMUNICATION CABLING

SECTION 16750 VOICE AND DATA COMMUNICATION CABLING SECTION 16750 VOICE AND DATA COMMUNICATION CABLING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Store drawing set and general provisions of the Contract, including General and Supplementary Conditions and

More information

NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION 27 05 26 GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS

NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION 27 05 26 GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS SECTION GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS RELATED SECTIONS: Section 27 00 00 General Requirements Section 27 02 00 Communication General Requirements Section 27 05 28 Pathways for Communications

More information

Telecommunications Systems Narrative Page 1 The Engineering Enterprise

Telecommunications Systems Narrative Page 1 The Engineering Enterprise I. TELECOMMUNICATIONS GENERAL REQUIREMENTS A. The project consists of a renovation to the historic Clinical Sciences building, originally built in 1933. The existing building has a total area of 105,000

More information

Building Telecommunications Infrastructure Requirements

Building Telecommunications Infrastructure Requirements Building Telecommunications Infrastructure Requirements This page identifies specific requirements for the design of telecommunications infrastructure for buildings at Clemson University. (Revised October,

More information

ADC Structured Cabling Solutions

ADC Structured Cabling Solutions ADC Structured Cabling Solutions The highest performing cross-connect system in the world HighBand Wall Mount Patching Solution Reliable, secure and cost effective ADC s HighBand cross connect solution

More information

University of Houston. Telecommunication Cabling Standards

University of Houston. Telecommunication Cabling Standards University of Houston Information Technology Telecommunication Cabling Standards As prepared by IT Network Operations University of Houston, Telecommunication Cabling Standard - Page 1 Table of Contents

More information

Generic Category 5e Cabling Specification

Generic Category 5e Cabling Specification Telecommunications Cabling System Technical Specification Category 5e Tyco Electronics Corporation provides this information as a courtesy to its customers and potential customers. Customer should review

More information

Reliable, Consistent, Quality

Reliable, Consistent, Quality Reliable, Consistent, Quality 1-877-320-3143 www.fibertronics.com Reliable, Consistent, Quality Welcome To Fibertronics Inc. Reliability, consistency, and quality is what we put behind every Fiber optic

More information

1 Campus Cabling Systems Introduction

1 Campus Cabling Systems Introduction 1 Campus Cabling Systems Introduction This document represents the campus cable and infrastructure standards adopted and supported by the XXXX. All new construction and renovation should conform to these

More information

BIX Cross-Connect System Distribution Connectors, Multiplying Connectors and Modular Jack Connectors

BIX Cross-Connect System Distribution Connectors, Multiplying Connectors and Modular Jack Connectors C O M M E R C I A L N E T W O R K I N G C O P P E R 15.13 Distribution Connectors, Multiplying Connectors and Modular Jack Connectors A0393146 QCBIX1A4 Connector BIX Distribution Connector The BIX Distribution

More information

Pretium Connector Housings

Pretium Connector Housings Pretium Connector Housings A LANscape Pretium Solutions Product Applications Main cross connect, intermediate cross connects and telecommunications rooms Rack or equipment cabinet installations Data center

More information

Cabinets 101: Configuring A Network Or Server Cabinet

Cabinets 101: Configuring A Network Or Server Cabinet Cabinets 101: Configuring A Network Or Server Cabinet North, South and Central America White Paper May 2012 www.commscope.com Contents Background Information 3 What is a network or server cabinet? 3 What

More information

Network Telecommunications Design Standards Last Updated June 2013. Youngstown State University

Network Telecommunications Design Standards Last Updated June 2013. Youngstown State University 1 Network Telecommunications & Security Youngstown State University One University Plaza Youngstown, OH 44555 Network Telecommunications Design Standards Last Updated June 2013 Youngstown State University

More information

ANSI/TIA/EIA-606. Administration Standard for the Telecommunications Infrastructure of Commercial Buildings

ANSI/TIA/EIA-606. Administration Standard for the Telecommunications Infrastructure of Commercial Buildings ANSI/TIA/EIA-606 Administration Standard for the Telecommunications Infrastructure of Commercial Buildings Distributed by NDS INFORMATION- TELECOM SYSTEM --------------------------------------------- Head

More information

SECTION 16750. TELECOMMUNICATIONS SYSTEM (Cat 6)

SECTION 16750. TELECOMMUNICATIONS SYSTEM (Cat 6) SECTION 16750 TELECOMMUNICATIONS SYSTEM (Cat 6) PART 1 - GENERAL 1.01 REQUIREMENTS A. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements, apply

More information

Structured Cabling Statement of Work

Structured Cabling Statement of Work Structured Cabling Statement of Work Multiple Locations June 15, 2010 Page 1 A. GENERAL a. San Joaquin County (referred to as Owner ) is requesting proposals for a new structured cabling infrastructure

More information

Structured Wiring Specifications ERAU Daytona Beach Campus (Dec 14 2011)

Structured Wiring Specifications ERAU Daytona Beach Campus (Dec 14 2011) Structured Wiring Specifications ERAU Daytona Beach Campus (Dec 14 2011) A. Objectives The Information Technology (IT) Department of Embry-Riddle Aeronautical University (ERAU) seeks to establish a standards-based

More information

DEPARTMENTAL REGULATION

DEPARTMENTAL REGULATION U.S. DEPARTMENT OF AGRICULTURE WASHINGTON, D.C. 20250 DEPARTMENTAL REGULATION SUBJECT: Service Center Technology Modernization Project (SCTMP) Wiring/Cabling Specifications for Service Center Agencies

More information

The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables

The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables The National Armored Cable Manufacturers Association Presents Installation Standard for Types AC and MC Cables An ANSI Standard Original document jointly produced by NECA and NACMA as Standard for Installing

More information

270526-TC Grounding and Bonding for Telecommunications Systems

270526-TC Grounding and Bonding for Telecommunications Systems 270526-TC Grounding and Bonding for Telecommunications Systems Part 1 - General Related Documents The following related sections of the OT standards shall also be applicable to this section. OT Engineer

More information

Specifying an IT Cabling System

Specifying an IT Cabling System Specifying an IT Cabling System This guide will help you produce a specification for an IT cabling system that meets your organisation s needs and gives you value for money. You will be able to give your

More information

REQUEST FOR BID AS-NEEDED CABLING SERVICES FOR COUNTY FACILITIES

REQUEST FOR BID AS-NEEDED CABLING SERVICES FOR COUNTY FACILITIES REQUEST FOR BID AS-NEEDED CABLING SERVICES FOR COUNTY FACILITIES SECTION 1 REQUIREMENTS AND GUIDELINES INTRODUCTION The County of El Paso ( County ) is issuing this Request for Bid ( Solicitation ) to

More information

TIA 569 Standards Update Pathways & Spaces. Ignacio Diaz, RCDD April 25, 2012

TIA 569 Standards Update Pathways & Spaces. Ignacio Diaz, RCDD April 25, 2012 TIA 569 Standards Update Pathways & Spaces Ignacio Diaz, RCDD April 25, 2012 The purpose of this Standard is to standardize specific pathway and space design and construction practices in support of telecommunications

More information

DESIGN GUIDELINES. Local Area Network

DESIGN GUIDELINES. Local Area Network DESIGN GUIDELINES Local Area Network The total oversight and management responsibilities for information assurance (IA) and protection of DoDEA s critical infrastructure fall under the purview of the DoDEA

More information

SECTION 271525 OPTICAL FIBER CABLES AND ACCESSORIES. A. Interior Raceways, Fittings, and Accessories: Section 260532.

SECTION 271525 OPTICAL FIBER CABLES AND ACCESSORIES. A. Interior Raceways, Fittings, and Accessories: Section 260532. SECTION 271525 OPTICAL FIBER CABLES AND ACCESSORIES PART 1 GENERAL 1.01 RELATED WORK SPECIFIED ELSEWHERE A. Interior Raceways, Fittings, and Accessories: Section 260532. B. Wiring, General - 600 Volts

More information

Standards. www.nordx.com 5 ANSI/TIA/EIA-569-A (CSA T530)

Standards. www.nordx.com 5 ANSI/TIA/EIA-569-A (CSA T530) The primary focus of this standard is to provide design specifications and guidance for all building facilities relating to telecommunications cabling systems and components. This standard identifies and

More information

STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENTAL SPECIFICATION 804 FIBER OPTIC CABLE FOR TRAFFIC SIGNAL INTERCONNECT JANUARY 19, 2007

STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENTAL SPECIFICATION 804 FIBER OPTIC CABLE FOR TRAFFIC SIGNAL INTERCONNECT JANUARY 19, 2007 804.01 Description 804.02 General 804.03 Materials 804.04 Fan-Out Kit 804.05 Drop Cable 804.06 Fiber Optic Patch Cord 804.07 Termination Panel 804.08 Fusion Splice 804.09 Fiber Optic Connector 804.10 Splice

More information

SECTION 27 05 36 CABLE TRAYS FOR COMMUNICATIONS SYSTEMS

SECTION 27 05 36 CABLE TRAYS FOR COMMUNICATIONS SYSTEMS SECTION 27 05 36 CABLE TRAYS FOR COMMUNICATIONS SYSTEMS PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such

More information

Code Compliance for Spring Steel Fasteners Based on the 2005 NEC

Code Compliance for Spring Steel Fasteners Based on the 2005 NEC Code Compliance for Spring Steel Fasteners Based on the 2005 NEC B-Line has recognized the need for a reference source, detailing the National Electrical Code requirements for Spring Steel Fasteners. The

More information

Network Design. Yiannos Mylonas

Network Design. Yiannos Mylonas Network Design Yiannos Mylonas Physical Topologies There are two parts to the topology definition: the physical topology, which is the actual layout of the wire (media), and the logical topology, which

More information

ELECTRIC METERING COMMERCIAL & INDUSTRIAL

ELECTRIC METERING COMMERCIAL & INDUSTRIAL ELECTRIC METERING COMMERCIAL & 1.0 INDEX 1.0 INDEX 2.0 SCOPE 3.0 GENERAL REQUIREMENTS 4.0 METER LOCATIONS 5.0 UNDERGROUND TERMINATIONS 6.0 METERING TRANSFORMER ENCLOSURES 7.0 SINGLE CUSTOMER METER INSTALLATIONS

More information

SECTION 17400 ACCESS CONTROL SYSTEM. CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section.

SECTION 17400 ACCESS CONTROL SYSTEM. CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section. SECTION 17400 ACCESS CONTROL SYSTEM CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section. PART 1 - GENERAL 1.1 RELATED WORK A. 16060 Grounding and Bonding B. 16070 Electrical

More information

The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects

The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects White Paper /7/0 Executive Summary Now that the TIA/EIA-568-B.- Category 6 Copper Cabling

More information

LIEBERT VNSA Installation Sheet

LIEBERT VNSA Installation Sheet LIEBERT VNSA Installation Sheet Description The Liebert vnsa network switch is designed for connecting multiple Ethernet-ready devices and comes in various models. The unit may have: A Liebert icom display

More information

CDGRD-10. Grounding. Solutions For Comm/Data Applications

CDGRD-10. Grounding. Solutions For Comm/Data Applications CDGRD-10 Grounding Solutions For Comm/Data Applications Overview & Table of Contents Cooper B-Line s Grounding products for rack & runway provide a complete solution for grounding metal supports. The offering

More information

FTE Cabling Best Practices Author: Todd Bill, RCDD/NTS

FTE Cabling Best Practices Author: Todd Bill, RCDD/NTS FTE Cabling Best Practices Author: Todd Bill, RCDD/NTS Document ID: WP-07-01-ENG Original Issue Date: May 2007 Version: 1.0 FTE Cabling Best Practices 1 Table of Contents Introduction and Applicable Standards...3

More information

Victor Elementary School District. Technology Infrastructure Standards 02-26-03. Victor Elementary School District

Victor Elementary School District. Technology Infrastructure Standards 02-26-03. Victor Elementary School District 15579 Eighth Street Victorville, CA 92392 Phone 760. 245-1691 Fax 760.245-6245 www.vesd.net 02-26-03 TABLE OF CONTENTS Introduction 3 Overview of Standards 3 Equipment Specifications 4 Material Specifications

More information

Installing a Physical Network. Chapter 8

Installing a Physical Network. Chapter 8 Installing a Physical Network Chapter 8 Contents Recognize and describe the function of basic components in a structured cabling system Explain the process of installing structured cable Install a network

More information

CORNING CABLE SYSTEMS GENERIC SPECIFICATION FOR TIGHT BUFFER OPTICAL FIBER CABLES FOR INTER- AND INTRABUILDING APPLICATIONS.

CORNING CABLE SYSTEMS GENERIC SPECIFICATION FOR TIGHT BUFFER OPTICAL FIBER CABLES FOR INTER- AND INTRABUILDING APPLICATIONS. CORNING CABLE SYSTEMS GENERIC SPECIFICATION FOR TIGHT BUFFER OPTICAL FIBER CABLES FOR INTER- AND INTRABUILDING APPLICATIONS September 2006 Revision 7 Corning Cable Systems reserves the right to update

More information

B. Related Sections: 1. Section 26 05 33 - Raceway and Boxes for Electrical Systems.

B. Related Sections: 1. Section 26 05 33 - Raceway and Boxes for Electrical Systems. SECTION 262726 - WIRING DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section includes wall switches; wall dimmers; receptacles; multioutlet assembly; and device plates and decorative box covers. B. Related

More information

Request for Proposal (RFP) IP Cameras/Door Access Control

Request for Proposal (RFP) IP Cameras/Door Access Control WAHPETON PUBLIC SCHOOLS Information Technology Department Request for Proposal (RFP) IP Cameras/Door Access Control Inquiries and requests regarding this RFP should be directed to: Jason Pfahl, Director

More information

Solar Panel Installations

Solar Panel Installations Solar Panel Installations Page 1 of 6 SINGLE-FAMILY RESIDENTIAL CHECKLIST City of Hayward Development Services Department Revised: 7-09-15 PERMIT REQUIREMENTS Permits are required for all solar panel installations.

More information

LSA-PLUS Series 2 Connection and Disconnection Modules and Accessories

LSA-PLUS Series 2 Connection and Disconnection Modules and Accessories LSA-PLUS Series 2 Connection and Disconnection Modules and Accessories 2015 PRODUCT CATALOG 2ND EDITION LSA-PLUS Series 2 Connection and Disconnection Modules and Accessories A technically and commercially

More information

InstaPATCH Cu Cabling Solutions for Data Centers

InstaPATCH Cu Cabling Solutions for Data Centers SYSTIMAX Solutions InstaPATCH Cu Cabling Solutions for Data Centers Design Guidelines August 2008 www.commscope.com Contents Overview 1 Instapatch Cu Solution Specification 2 Harness Assembly Design 3

More information

Coordinate size and location of telecommunications rooms with the architect to be in compliance with this document and NEC Article 800.

Coordinate size and location of telecommunications rooms with the architect to be in compliance with this document and NEC Article 800. Section 16700- TELECOMMUNICATIONS Part 1 - General The scope of this project includes providing all material and labor to install a complete telecommunication system. The systems shall include riser cables,

More information

STRUCTURED CABLE SPECIFICATION INFORMATION SYSTEMS AND SERVICES ISSUE 1 NOVEMBER 2011

STRUCTURED CABLE SPECIFICATION INFORMATION SYSTEMS AND SERVICES ISSUE 1 NOVEMBER 2011 STRUCTURED CABLE SPECIFICATION INFORMATION SYSTEMS AND SERVICES ISSUE 1 NOVEMBER 2011 Project Ref. Project Name Project Manager Date issued... Consultant/Contractor... 1 CONTENTS 1000 GENERAL OVERVIEW

More information

Installation Manual For Support Call 01704 807114 or email info@hipentertainment.co.uk

Installation Manual For Support Call 01704 807114 or email info@hipentertainment.co.uk Installation Manual Hip Smart Hub (Standard BT and BT FTTP Sites) The Home Network Hub houses the Home Owner s Broadband Router and connects the hardwired network ports on that Router to three network

More information

HIGH SPEED COMMUNICATIONS PLENUM CABLE CATEGORY 5e CMP FEP JACKETED, PVC-FREE UNSHIELDED TWISTED PAIR (UTP)

HIGH SPEED COMMUNICATIONS PLENUM CABLE CATEGORY 5e CMP FEP JACKETED, PVC-FREE UNSHIELDED TWISTED PAIR (UTP) Cable Specification Category 5e CMP HIGH SPEED COMMUNICATIONS PLENUM CABLE CATEGORY 5e CMP FEP JACKETED, PVC-FREE UNSHIELDED TWISTED PAIR (UTP) This cable specification complies with the electrical transmission

More information

E Series. E Series. Category 6 and 5e. Features

E Series. E Series. Category 6 and 5e. Features E Series Category 6 and 5e CommScope, world leader in copper and fiber connectivity, offers the E Series product line as the ideal solution to all your infrastructure needs for safe and reliable data transmission.

More information

CHARTER TOWNSHIP OF SHELBY REQUEST FOR PROPOSAL. Fiber Optic and Data Cabling Project Shelby Township Police Building

CHARTER TOWNSHIP OF SHELBY REQUEST FOR PROPOSAL. Fiber Optic and Data Cabling Project Shelby Township Police Building CHARTER TOWNSHIP OF SHELBY REQUEST FOR PROPOSAL The Charter Township of Shelby is soliciting proposals to install fiber optic and data cabling to serve a new Police Building that is under construction

More information

SECTION 16715 TELECOMMUNICATIONS ACCEPTANCE TESTING

SECTION 16715 TELECOMMUNICATIONS ACCEPTANCE TESTING PART 1 - GENERAL 1.1 SECTION INCLUDES A. Testing Publications and Standards B. Inspection and testing procedures for copper and fiber optic cable, RF CATV / MATV systems, and the antenna systems. C. Documentation

More information

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage:

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage: Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016 * Garage construction requires permits (electrical, building) * Permits must be applied for at the time. * Dial

More information

This presentation to be used in conjunction with:

This presentation to be used in conjunction with: 1 This presentation to be used in conjunction with: Spec Sheets: SA-GRSP10, SA-GRSP09, SA-GRSP11 Samples in DC-GROUND-KIT 8/16/2012 2 Network Bonding and Grounding: TIA-607-B Generic Telecommunications

More information

Requirements for the Attachment of Communication Cable Facilities on PPL Poles

Requirements for the Attachment of Communication Cable Facilities on PPL Poles Page 99 of 137 Requirements for the Attachment of Communication Cable Facilities on Replaces: URS-3002 URS-3004 URS-101C-304 A-157649 Page 100 of 137 Reference Notes for Drawings: General 1. The term communication

More information

Rittal s Comprehensive Family Of... NETWORK RACK SOLUTIONS

Rittal s Comprehensive Family Of... NETWORK RACK SOLUTIONS Rittal s Comprehensive Family Of... NETWORK RACK SOLUTIONS STANDARD & ECONOMICAL BasicRack A complete low-cost, high-quality basic equipment management system. Design Six web channel holes per side allow

More information

Cable Assembly Solutions at the Speed of Light

Cable Assembly Solutions at the Speed of Light Cable Assembly Solutions at the Speed of Light Peggy Kovling ACI Founder Peggy Kovling credits her extensive knowledge of the cable business, along with her abilities in customer relationship management,

More information

Vertical Phone System Upgrades 2014. Scope of Work

Vertical Phone System Upgrades 2014. Scope of Work Vertical Phone System Upgrades 2014 Scope of Work Project Overview Install new Vertical phone system and phones on site. Complete testing with API helpdesk. Remove old phone system, phones and box up for

More information

Technical Writing - A Glossary of Telephone Utilities and UtilitiesTechnical Specifications

Technical Writing - A Glossary of Telephone Utilities and UtilitiesTechnical Specifications LSUHSC Computer Services 433 Bolivar Street New Orleans, LA 70112 Phone 504-568-6130 LSUHSC Enterprise Networking Cabling Infrastructure: Design & Installation Standards Last Revised: July 16, 2012 Contents

More information

GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables

GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables Engineering Department SEPTEMBER, 2007 GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables General Requirements This section applies to all public and private utilities,

More information

electrics P OW E R E N T RY B A S I C S P OW E R & C O M M U N I C AT I O N S B A S I C S P OW E R D I S T R I B U T I O N B A S I C S

electrics P OW E R E N T RY B A S I C S P OW E R & C O M M U N I C AT I O N S B A S I C S P OW E R D I S T R I B U T I O N B A S I C S P RO D U C T M A P / TA B L E O F C O N T E N T S..................6 8 6 E L E C T R I C S & C O M M U N I C AT I O N S O V E RV I E W.............6 8 9 P OW E R E N T RY B A S I C S PA N E L - M O U N

More information

Conduit Fittings & Accessories Directional Drilling Conduit Utility Duct Telephone Duct Residential Boxes

Conduit Fittings & Accessories Directional Drilling Conduit Utility Duct Telephone Duct Residential Boxes CANTEX INC. 301 Commerce Ste 2700 Fort Worth, Texas 76102 817-215-7000 Fax: 817-215-7001 Conduit Fittings & Accessories Directional Drilling Conduit Utility Duct Telephone Duct Residential Boxes YOUR FULL

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION 17650 SECURITY SYSTEMS

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION 17650 SECURITY SYSTEMS PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Inspections and observations by the Owner do not relieve the A/E of contract responsibilities. B. Chain of command 1. The DPS Project Manager is

More information

E-Rate Data Cabling RFP. Addendum 2 ISSUED BY: Alvord Unified School District Information Technology Department

E-Rate Data Cabling RFP. Addendum 2 ISSUED BY: Alvord Unified School District Information Technology Department ALVORD UNIFIED SCHOOL DISTRICT E-Rate Data Cabling RFP Addendum 2 ISSUED BY: Alvord Unified School District Information Technology Department The following are Addendums to the original RFP titled DataCablingRFP.pdf.

More information

SECTION 27 20 00 - DATA COMMUNICATIONS. A. Complete vertical and horizontal Communication/Data Network System as indicated.

SECTION 27 20 00 - DATA COMMUNICATIONS. A. Complete vertical and horizontal Communication/Data Network System as indicated. SECTION 27 20 00 - PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this

More information

Telecommunications Infrastructure Standard for Data Centers. 802.3 Tutorial

Telecommunications Infrastructure Standard for Data Centers. 802.3 Tutorial Telecommunications Infrastructure Standard for Data Centers 802.3 Tutorial Prepared by: Jonathan Jew - J&M Consultants and Chris DiMinico - MC Communications - Co-chairs TR42.1.1 TR42: Data Center Standard

More information

UTSC CABLE SYSTEMS SPECIFICATION SITE DESIGN CRITERIA DESIGN REQUIREMENTS INSTALLATION PRODUCTS

UTSC CABLE SYSTEMS SPECIFICATION SITE DESIGN CRITERIA DESIGN REQUIREMENTS INSTALLATION PRODUCTS UTSC CABLE SYSTEMS SPECIFICATION SITE DESIGN CRITERIA DESIGN REQUIREMENTS INSTALLATION PRODUCTS University of Toronto Scarborough Cable Systems Specification 1/23 Network Administrators Glenn Attwood Manager,

More information

HP UPS R1500 Generation 3

HP UPS R1500 Generation 3 HP UPS R1500 Generation 3 Installation Instructions Part Number 650952-001 NOTE: The rating label on the device provides the class (A or B) of the equipment. Class B devices have a Federal Communications

More information