1 ALVORD UNIFIED SCHOOL DISTRICT E-Rate Data Cabling RFP Addendum 2 ISSUED BY: Alvord Unified School District Information Technology Department

2 The following are Addendums to the original RFP titled DataCablingRFP.pdf. The modified documents are provided after the description of the modifications. 1. Scope of work a. When replacing data cabinets, bidders will utilize existing fiber and copper patch panels when possible and recertify connections when cabinet is replaced. If repair or replacement of connectors is required to achieve certification refer to AUSD Cabling specifications Document. Use of LC connectors for fiber has been rescinded. b. If contract is not able to be executed and completed over summer break work will need to be performed after school hours. Currently the latest schools are dismissed at 3PM. c. All wall cabinet replacements are exempt from the wire management requirements of section 2.18 of the AUSD Cabling Standards, except where feasible. d. All installed networking equipment in the data racks will be removed and reinstalled by the bidder. e. Old data cabinets will be disposed of by AUSD. 2. General. a. Submit bids with totals separated by site. Separate Data cabinet replacement and UPS installation costs from Data Drop installation costs. 3. IDF Data Cabinet Specifications. a. The following Data Cabinet Specifications are amended by site. School MDF/IDF# Location Original New Arizona MDF Main Office SWE U-E-W-CN SWE U-E-W-CN Arizona IDF 3 Rm 8 SWE U-E-W-CN SWE U-E-W-CN Arizona IDF 5 Prime Time SWE U-E-W-CN SWE U-E-W-CN Arizona IDF 9 Rm 8 SWE U-E-W-CN SWE U-E-W-CN Collett IDF 4 Next to Rm 10 SWE U-E-W-CN SWE U-E-W-CN Foothill IDF 5 LAB SWE U-E-W-CN SWE U-E-W-CN Foothill IDF 6 LIB SWE U-E-W-CN SWE U-E-W-CN Foothill IDF 7 Rm 34 SWE U-E-W-CN SWE U-E-W-CN Foothill IDF 8 Rm 29 SWE U-E-W-CN SWE U-E-W-CN La Granada IDF 11 Rm 18 SWE U-E-W-CN SWE U-E-W-CN Loma Vista IDF 12 Rm 97 SWE U-E-W-CN SWE U-E-W-CN Myra Lynn IDF 1 Rm 15 SWE U-E-W-CN SWE U-E-W-CN Myra Lynn IDF 2 Rm 10 SWE U-E-W-CN SWE U-E-W-CN Myra Lynn IDF 4 Rm 1 SWE U-E-W-CN SWE U-E-W-CN Myra Lynn IDF 5 K Ofc SWE U-E-W-CN SWE U-E-W-CN Orrenmaa IDF 3 K A SWE U-E-W-CN SWE U-E-W-CN Orrenmaa IDF 4 Rm 17 SWE U-E-W-CN SWE U-E-W-CN Terrace IDF 1 K1/K2 SWE U-E-W-CN SWE U-E-W-CN Terrace IDF 2 Rm 4 SWE U-E-W-CN SWE U-E-W-CN Villegas IDF 8a Snack Bar SWE U-E-W-CN SWE U-E-W-CN

3 4. The Following Amendments and/0r changes are made to the AUSD Cabling Standards Modifications. Item 2.24 Item 2.26 Item 2.28 APC smart 6000 UPS 208V 30 amp twist lock plug with battery pack and PDU in MDF (with APC 4 post enclosures) Or APC 2200 for Administration IDFs. (These are to be mounted in the bottom of the racks). Any wall mount IDF's require a rack mount APC V with standard 5-20 outlet. All racks with square holes will come with no less than the equivalent number of cage nuts and screws per rack to populate all slots plus 10%. Appendix C: MDF rack that can support the weight will have the APC SURT6KRMXL3U-TF5 (3-U) UPS with a 30 AMP twist lock receptor (L6-30) installed by the contractor. Wall mount MDF s that cannot support the weight or do not have the space will utilize an APC 2200 UPS. All IDFs will have the APC 2200 (2-U) UPS with a 5-20 receptacle installed by the contactor. All receptacles will be dedicated branch circuits with isolated grounds.

4 DATA CABINETS: Part #: Description Mfg. SWE E-W-CN 24HX23WX30D SOUTHWEST DATA SWE E-W-CN 36HX23WX30D SWDP SWE E-W-CN 48HX23WX30D SWDP SWE E-W-CN 72HX23WX30D SWDP SWE4000-CS CASTER KIT FOR SWE E-W-CN CH-415 Front & REAR LOCK KIT (key-415) SWDP UPS for CABINETS: Part #: Description Mfg. SURT6KRMXL3U-TF5 APC Smart-UPS RT 6KVA RM APC 208V w/ 208V to 120V 2U Step-Down Transformer208V input & 120/208V Output SURT192RMXLBP3U APC Smart-UPS RT 192V RM Battery Pack APC SURTA2200RMXL2U APC Smart-UPS RT 2200VA RM 120V APC SURTA48RMXLBP2U APC Smart-UPS RT 48V RM Battery Pack APC The complete updated Alvord USD Cabling Standards Document is attached. if you have any questions regarding these changes please

5 Alvord USD CABLING STANDARDS 1. AUSD - General. 1.1 The power meter test results shall be recorded and printed using the software provided with the test equipment. Provide a hard and soft copy of the fiber optics and copper test results to Alvord USD IT Department including a copy of the test equipment software. Hard copy test result must be provided in an 8-1/2 x 11 binder including a cover sheet. 1.2 A diagram of all network closets depicting the layout of equipment racks, fiber optic enclosures, patch panels, wire management and electronics hardware will be required in a Visio format. 1.3 All network closets (MDFs & IDFs) shall use the same key (key-415) to open the front door as well as the back locks. All MDFs and IDFs shall come with fans installed for ventilation and the cabinets shall have air vents in the side if the cabinets. 1.4 Use APC Data Products. All racks must be 4 posts with square holes and labeled U s on the front of the race posts. 1.5 Split A/C shall be installed in all IDF and MDF rooms. 2. Data Closet(s)-IDF & MDF: 2.1 Labeling shall be computer generated (P-Touch). 2.2 All workstation faceplates, data patch panels must be permanently labeled on both ends (P-Touch). 2.3 All fiber optic cables and cable pairs must be permanently labeled on both ends at the Fiber patch panel and all junction boxes with their IDF or MDF destination using (P- Touch) labeling. (i.e. To MDF) 2.4 All fiber optic and copper cables shall be installed with adequate slack and 10 service loops. 2.5 Fiber optic cabling shall consist of a minimum of (6) individual strands 50/125 multimode cables for each IDF home run to the MDF. 2.6 Fiber optic cables are to be installed in Contractor provided UL rated inner duct.

6 2.7 All fibers are to be terminated on both ends with SC connectors on the inside of the fiber patch panels and SC on the outside of the fiber patch panels and fiber shielding is to be secured to the stress relief in the fiber patch panel. 2.8 All fiber optic rack mount enclosures will be installed at the top of wall mount and freestanding equipment racks. 2.9 Pinning configuration for all data jacks shall be in accordance to the EIA/TIA 568B Standard All plywood must be fire resistant and coated with the appropriate type and quantity of fire resistive paint All distribution frames shall be built on shallow uni-strut that is attached to no less than three (3) studs on the wall by lag bolts. Lag bolts shall penetrate the studs by no less than 3 inches. IDF/MDF cabinet shall be attached to the mounted uni-struts with 3/8ths spring nuts and bolts. All distribution frames shall be permanently Grounded both the main unit as well as the door if plastic hinges are used Jumper wire management above and below the patch panels are provided and installed by the Contractor MDF to IDF, IDF to IDF Category 6A or better and able to meet 1 GB standards. Tie cables shall be terminated on contractor supplied (24) or (48) port patch panel frames with the appropriate number of RJ45 category 6A or better data inserts with a 10 foot service loop in IDF/MDF Contractor shall provide and install EMT conduit sleeves as required through any intervening walls/fire-walls to properly route the station cabling to the required locations. Additionally, any conduit sleeves provided by Contractor, or existing sleeves utilized by Contractor, to properly route station cabling from the station to the appropriate MDF, IDF, shall be properly fire-caulked by Contractor All exposed conduit ends and sleeves shall be properly protected with plastic bushings. Pull strings must be left in all conduits and sleeves exceeding four (4) feet in length Data Fiber Backbone Cables: Cable Type: (6) strand 50micron/125 multi-mode indoor/outdoor Outer Sheath Color: Different than existing station wiring (NOT RED) Outer Sheath NAPA Rating: CM or CMP

7 2.17 Data Station Cables: Cable Type: Stranded Category 6A or higher, four (4) pair, 24 awg copper UTP Outer Sheath Color: Blue Different than existing wiring and backbone (Not Red) Outer Sheath NAPA Rating: CM or CMP 2.18 Each equipment cabinet or rack shall be equipped with horizontal cable managers. (CM) as required if one patch panel+ 2 CM s; two patch panels +3 CM s, three-patch panel s +4 CM s, etc.). Horizontal cable managers shall be Panduit # WMPHF2 (or equal) for (48) port panel installations and Panduit # WMPFS (or equal) for (24) port panel installations. Where 19 x 7 free standing equipment racks are installed. Panduit # WMPvsf20 (or equal) should be supplied and installed for vertical cable management AUSD contractor will provide appropriate length and quantity, plus five percent (5%), Category 6A straight through serialized data patch cables (blue). (One (1) foot for racks (like AT161-BU Allentel) and ten (15) foot patch cables for wall jack to station (Like AT1615-BU Allentel) with snagless boots) All wire (copper, fiber, and ground) will enter and or exit equipment closets by passing through contractor provided and installed EMT conduit fastened where needed by unistrut A minimum of insulated #6 AWG copper conductor(s) wire will be provided and installed by the contractor and have an isolated ground in IDF or MDF and the electric circuit(s) for the IDF & MDF rooms shall be ONLY for those rooms Layout of the IDF or MDF Cabinet shall be installed as follows from the top of cabinet working down: Fiber patch panel, port patch panel(s) (2Us), Wire management (1U), 2U space left open for equipment i.e. switches, port patch panel(s) (2Us), Wire management (1U), 2U space left open for equipment i.e. switches, this pattern should be repeated to the bottom of the cabinet and into the second cabinet if needed. The bottom 8Us in each cabinet are to be left open for a rack mount UPS All Floor Mount racks will have a vertical 14 outlets Power Distribution Unit mounted internally in the back of the rack with surge protection. Not blocking any electronics that may be mounted in the rack using the back mounting posts. This Power Distribution Unit should plug into the ACP UPS unit APC smart 6000 UPS 208V 30 amp twist lock plug with battery pack and PDU in MDF (with APC 4 post enclosures) Or APC 2200 for Administration IDFs. (These are to be mounted in the bottom of the racks) Where Multiple Racks are installed in MDF/IDF they will be secured together with Baying Kits Any wall mount IDF's require a rack mount APC V with standard 5-20 outlet.

8 2.27 All floor mount Racks are to be installed with Seismic kits (Ladder racks and floor brackets bolted to the floor) All racks with square holes will come with no less than the equivalent number of cage nuts and screws per rack to populate all slots plus 10% All fiber mounted in the racks must have a 10 service loop All fiber service loops must be labeled All cables are to be dressed in the Data Racks using Velcro cable tie wraps. 3. Workstation Jacks: 3.1 Labeling shall be computer generated (P-Touch). 3.2 All workstation faceplates, data patch panels must be permanently labeled on both ends (P-Touch). (See Appendix A) 3.3 If flush mounting is not reasonably feasible, surface mounting with a back-box will be accepted. 3.4 Depending on the number of required outlets faceplates should be able to accommodate future cables. All un-jacked positions shall have a minimum of two blank inserts installed. 3.5 Faceplate: = almond/electric ivory Category 6A data jacks (RJ-45) = blue Blank Inserts = almond/electric ivory 3.6 Pinning configuration for all data jacks shall be in accordance to the EIA/TIA 568B Standard. 3.7 Data Station Jack Specification: Rating: Category 6A Jack Type: RJ-45 Pinning Config: EIA/TIA 568B Jack Color: Blue 3.8 Faceplate Specifications: Size: Single Gang USO Bezel Ports: Two (2) four (4) or six (6) Color: Almond/Electric Ivory Insert Color: Blue

9 3.9 All surface mounted raceway, back boxes, junction boxes, etc. (other than electrical conduit where called for) shall be from the Panduit Corporation or equal product line. Contractor will be required to provide all manufacturer specified devices for corners, turns, transitions, dead ends, etc. to provide a complete and workmanlike installation according to recommended methods and procedures. Mechanical fastening methods will be required in all cases (double sided tape or foam is not acceptable). 4. Walls & Ceiling: 4.1 Fiber optic cables are to be installed in Contractor provided UL rated inner duct. 4.2 Station cables are to be suspended on an independent hanger system supplied by the Contractor. The preferred suspension method will utilize an assembly of pencil rod or hanger wire, caddy clips and bridal rings. Any suspension system must meet all applicable standards for building and seismic requirements. Cable hanger shall be placed no more than four-foot (4 ) apart. (Use of ceiling grid system suspension wire is not acceptable). 4.3 Contractor shall provide and install EMT conduit sleeves as required through any intervening walls/fire-walls to properly route the station cabling to the required locations. Additionally, any conduit sleeves provided by Contractor, or existing sleeves utilized by Contractor, to properly route station cabling from the station to the appropriate MDF, IDF, shall be properly fire-caulked by Contractor. 4.4 All exposed conduit ends and sleeves shall be properly protected with plastic bushings. Pull strings must be left in all conduits and sleeves exceeding four (4) feet in length. 4.5 All conduits in the walls shall stub out in the open drop ceiling.

10 Appendix A: Labeling of all wall jacks are to use the following format: <MDF # or IDF #>.<JACK #> i.e. If the MDF or IDF was #7 and the patch panel number was 23 then the label on the wall jack would have the following label: (Letters for IDFs and/or MDFs are NOT admissible). If this is a new IDF please call the district s IT department (951) to get the new number for that IDF. This needs to happen for each school. If the patch panel is factory labeled with a set of redundant numbers i.e. 1-24, then the patch panel would have to be labeled to show the new set of numbers. For example IDF #7 already has a patch panel with the numbers 1-24 and a second patch panel is installed, it must be relabeled with the numbers The wall jack label would look like this There is a MDF / IDF topology map available from the IT department for each existing school site in the District. Call or to get a copy of these map(s). The Contractor is responsible for creating a Visio document of the school and the data Topology that includes all IDF and the MDF. This is to be submitted on DVD or CD to the IT Director, Steven Marx.

11 Appendix B: The following are codes and standards that apply to this installation: TIA/EIA-568B TIA/EIA-569 and spaces TIA/EIA-606 of commercial TIA/EIA-607 telecommunications TIA/EIA-67 cabling systems NEC ISO/IEC BICSI Commercial BLDG telecommunication wiring standard Commercial BDLG standards for telecommunications pathways Administration standard for the telecommunications infrastructure Buildings Commercial building grounding and bonding requirements for Transmission performance spec s for field testing of UTP National Electrical Code ANSI/IEEE series standards Telecommunications Distribution Methods Manual

12 Appendix C: These items are supplied and installed by the contractor. APC Netshelter for all 7 foot and above floor mount racks with seismic restraints bolted to the floor. Southwest Data Products for the IDF wall mount cabinets Levington for all Patch Panels, Fiber Panels, Work Station inserts and face plates. All MDF and IDF will have the appropriate sized APC UPS (rack mountable). MDF rack that can support the weight will have the APC SURT6KRMXL3U-TF5 (3-U) UPS with a 30 AMP twist lock receptor (L6-30) installed by the contractor. Wall mount MDF s that cannot support the weight or do not have the space will utilize an APC 2200 UPS. All IDFs will have the APC 2200 (2-U) UPS with a 5-20 receptacle installed by the contactor. All receptacles will be dedicated branch circuits with isolated grounds. DATA COMM: Part #: Description Mfg TP-00 CAT-6A DATA CABLE - PVC BERTEK 6110G-RL6 CAT-6A RJ-45 - BLUE LEVITON XXP FACE PLATE LEVITON U12 CAT-6A PATCH PANEL-12 PORT LEVITON U24 CAT-6A PATCH PANEL-24 PORT LEVITON U48 CAT-6A PATCH PANEL-48 PORT LEVITON WMPH2E 2-U WIRE MANAGEMENT PANEL PANDUIT FIBER MATERIAL: Part #: Description Mfg. DX06-055D-W3SB/OFNR 6 STRAND M/M IN/OUT FIBER CABLE OPTICAL CABLE S/C MULTIMODE ANAEROBIC CONN. SIECOR 5F100-3SC 3 PACK DUPLEX S/C INSERTS LEVITON 5R130-OON **IDF** 1-24 PORT RACK MOUNT PANEL LEVITON 5R460-OON **MDF** 1-72 PORT RACK MOUNT PANEL LEVITON

13 DATA CABINETS: Part #: Description Mfg. SWE E-W-CN 24HX23WX30D SOUTHWEST DATA SWE E-W-CN 36HX23WX30D SWDP SWE E-W-CN 48HX23WX30D SWDP SWE E-W-CN 72HX23WX30D SWDP SWE4000-CS CASTER KIT FOR SWE E-W-CN CH-415 Front & REAR LOCK KIT (key-415) SWDP UPS for CABINETS: Part #: Description Mfg. SURT6KRMXL3U-TF5 APC Smart-UPS RT 6KVA RM APC 208V w/ 208V to 120V 2U Step-Down Transformer208V input & 120/208V Output SURT192RMXLBP3U APC Smart-UPS RT 192V RM Battery Pack APC SURTA2200RMXL2U APC Smart-UPS RT 2200VA RM 120V APC SURTA48RMXLBP2U APC Smart-UPS RT 48V RM Battery Pack APC AR3307 APC NETSHELTER SX 48U APC AP outlet PDU surge Protector (1 for each rack) APC AR8112BLK Seismic Kit (1 for each rack) APC AR7600 Baying kit (to bond multiple racks 1 per 2 racks) APC

SECTION 25110 TELECOMMUNICATION ROOMS

SECTION 25110 TELECOMMUNICATION ROOMS PART 1 - GENERAL 1.1 SUMMARY A. SCOPE SECTION 25110 TELECOMMUNICATION ROOMS 1. This section includes the minimum installation requirements for equipment and cabling infrastructure in Telecommunication

More information

Presenters Brett Weiss, Gabe Martinez, Brian Kroeger.

Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. 1 Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. Topics to be covered: Cable identification Purpose of the various cable types Installation techniques Building Infrastructure Overview of networking

More information

1. Furnish and install faceplate and modular jacks at each single gang outlet as described below:

1. Furnish and install faceplate and modular jacks at each single gang outlet as described below: Washington University in St. Louis Building: Communication Specification: Research Voice/Network/Typical 1. Furnish and install faceplate and modular jacks at each single gang outlet as described below:

More information

1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications.

1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications. Issued 2005/06/01 Section 16743 Data System Page 1 of 7 PART 1 GENERAL 1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications..2 Data system equipment

More information

DIVISION 27 COMMUNICATIONS. A. System design shall be completed by a Registered Communications Distribution Designer (RCDD).

DIVISION 27 COMMUNICATIONS. A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). DIVISION 27 COMMUNICATIONS 27 00 00 COMMUNICATIONS A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). B. Comply with American National Standards Institute

More information

TCTC Cabling Specifications

TCTC Cabling Specifications TCTC Cabling Specifications Purpose: To provide a standard specification that will be used for all Tri County Technical College (TCTC) facilities requiring structured cabling installation. Product specifications,

More information

Minimum Standards for Data/Voice Infrastructure in New Building Construction

Minimum Standards for Data/Voice Infrastructure in New Building Construction UNIVERSITY OF WATERLOO Minimum Standards for Data/Voice Infrastructure in New Building Construction 12/17/2012 Offices 1. Two Work Area Outlets (WAO) on opposite walls, each with 2 jacks 2. Each WAO shall

More information

Cabinets 101: Configuring A Network Or Server Cabinet

Cabinets 101: Configuring A Network Or Server Cabinet Cabinets 101: Configuring A Network Or Server Cabinet North, South and Central America White Paper May 2012 www.commscope.com Contents Background Information 3 What is a network or server cabinet? 3 What

More information

SPECIFICATION STANDARD GROUNDING AND BONDING

SPECIFICATION STANDARD GROUNDING AND BONDING PART 1: GENERAL 1.01 SCOPE OF WORK SPECIFICATION STANDARD A. The grounding and bonding system refers to all electrodes required by NEC, as well as including made, supplementary, information technology

More information

UT Southwestern Medical Center Information Resources Cable Installation Standard

UT Southwestern Medical Center Information Resources Cable Installation Standard UT Southwestern Medical Center Information Resources Cable Installation Standard PART 1- GENERAL 1.01 SUMMARY A. Furnish and install wire, cable, devices, equipment, and accessories for a complete system

More information

Cable Installation Project

Cable Installation Project Cable Installation Project 1. Intent. It is the intent of the U.S. Court of Appeals to install Category 6 (CAT6) data cabling in the Robert F. Peckham Federal Building and United States Courthouse, 280

More information

Wired and Wireless Network Request for Proposal New Washington County High School Facility

Wired and Wireless Network Request for Proposal New Washington County High School Facility Washington County Board Of Education P.O. Box 716 501 Industrial Drive Sandersville, GA 31082 (478) 552-3981 FAX (478) 552-3128 Description Wired and Wireless Network Request for Proposal New Washington

More information

270526-TC Grounding and Bonding for Telecommunications Systems

270526-TC Grounding and Bonding for Telecommunications Systems 270526-TC Grounding and Bonding for Telecommunications Systems Part 1 - General Related Documents The following related sections of the OT standards shall also be applicable to this section. OT Engineer

More information

IC System TM Installation Guide

IC System TM Installation Guide IC System TM Installation Guide July 2009 IC System Installation...3 Wire Requirements...3 Installation...3 Wire Splices...4 Wire Splice Marking...4 Wire Handling and Outer Jacket Removal...5 Surge Protection...7

More information

Intelligent Cable Management Systems

Intelligent Cable Management Systems Intelligent Cable Management Systems Bringing Practical Application Karen Pearson - Leviton Why Cable Management Matters Performance Cooling and air-handling Maintenance ANSI/TIA 569* Telecommunication

More information

DEPARTMENTAL REGULATION

DEPARTMENTAL REGULATION U.S. DEPARTMENT OF AGRICULTURE WASHINGTON, D.C. 20250 DEPARTMENTAL REGULATION SUBJECT: Service Center Technology Modernization Project (SCTMP) Wiring/Cabling Specifications for Service Center Agencies

More information

270526-TC Grounding and Bonding for Telecommunications Systems

270526-TC Grounding and Bonding for Telecommunications Systems 270526-TC Grounding and Bonding for Telecommunications Systems Part 1 - General 1.1 Work Included 1.2 Scope of Work A. Provide all labor, materials, tools and equipment required for the complete installation

More information

ATTACHMENT F 050R6800016 - CABLE AND WIRING SERVICES FUNCTIONAL AREA I PRICE PROPOSAL FORM Amendment 6

ATTACHMENT F 050R6800016 - CABLE AND WIRING SERVICES FUNCTIONAL AREA I PRICE PROPOSAL FORM Amendment 6 050R6800016 CABLE AND WIRING SERVICES (Column A) (Column B) (Column C) (Column D) (Column E) (Column F) (Column G) (B+C+D+E)*F= G Item Description PER 100' RUN PER 150' RUN PER 200' RUN PER 300' RUN QUANTITY

More information

B. PART 1 - GENERAL of SECTION 271300 BACKBONE COMMUNICATIONS CABLING shall also apply to this section.

B. PART 1 - GENERAL of SECTION 271300 BACKBONE COMMUNICATIONS CABLING shall also apply to this section. SECTION 271500 - HORIZONTAL UTP CABLING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

HP UPS R1500 Generation 3

HP UPS R1500 Generation 3 HP UPS R1500 Generation 3 Installation Instructions Part Number 650952-001 NOTE: The rating label on the device provides the class (A or B) of the equipment. Class B devices have a Federal Communications

More information

Communications Infrastructure Standards Tenant Services Version 2.1

Communications Infrastructure Standards Tenant Services Version 2.1 Communications Infrastructure Standards Tenant Services Version 2.1 February 4, 2011 Table of Contents GENERAL: PURPOSE... 3 GENERAL: SCOPE... 3 GENERAL: STANDARD PRODUCTS AND TENANT CABLE INSTALLATION...

More information

TELECOMMUNICATIONS STRUCTURED CABLING GUIDELINES AND SPECIFICATIONS. University of Chicago IT Services Infrastructure Services October 2011

TELECOMMUNICATIONS STRUCTURED CABLING GUIDELINES AND SPECIFICATIONS. University of Chicago IT Services Infrastructure Services October 2011 TELECOMMUNICATIONS STRUCTURED CABLING GUIDELINES AND SPECIFICATIONS IT Services Infrastructure Services October 2011 Table of Contents 1 Introduction... 4 1.1 Planning and Design... 4 1.2.1 Roles and Responsibilities...

More information

Network Design. Yiannos Mylonas

Network Design. Yiannos Mylonas Network Design Yiannos Mylonas Physical Topologies There are two parts to the topology definition: the physical topology, which is the actual layout of the wire (media), and the logical topology, which

More information

HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE: 10.17.12

HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE: 10.17.12 SECTION 27 05 26 - GROUNDING AND BONDING FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes grounding and bonding products, design requirements and installation for communications

More information

Specifications for Communication Cabling Distribution Systems

Specifications for Communication Cabling Distribution Systems Washington University in St. Louis Specifications for Communication Cabling Distribution Systems General Overview Listed below are the separate sub-systems of Washington University s structured cabling

More information

Terminating 25-Pair Cable and 4-Pair Cross Connects

Terminating 25-Pair Cable and 4-Pair Cross Connects Terminating 25-Pair Cable and 4-Pair Cross Connects Estimated Time: 90 minutes Number of Teams: 2 Number of Team Members: one to four This Lab has four major parts that will be addressed separately. 1.

More information

Victor Elementary School District. Technology Infrastructure Standards 02-26-03. Victor Elementary School District

Victor Elementary School District. Technology Infrastructure Standards 02-26-03. Victor Elementary School District 15579 Eighth Street Victorville, CA 92392 Phone 760. 245-1691 Fax 760.245-6245 www.vesd.net 02-26-03 TABLE OF CONTENTS Introduction 3 Overview of Standards 3 Equipment Specifications 4 Material Specifications

More information

WIRING. Electrical cables and conductors must be as specified in the Contract Documents.

WIRING. Electrical cables and conductors must be as specified in the Contract Documents. The installation of all electrical cables and conductors must conform to the National Electrical Code (NEC). The Code represents the minimum required standard. MnDOT s requirements may exceed those of

More information

SECTION 16750. TELECOMMUNICATIONS SYSTEM (Cat 6)

SECTION 16750. TELECOMMUNICATIONS SYSTEM (Cat 6) SECTION 16750 TELECOMMUNICATIONS SYSTEM (Cat 6) PART 1 - GENERAL 1.01 REQUIREMENTS A. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements, apply

More information

Category 6 Solutions. 4. Category 6 Solutions. 09/08 400836IN TrueNet Structured Cabling. Introduction... 4.2. Cable... 4.3. Patch Panels... 4.

Category 6 Solutions. 4. Category 6 Solutions. 09/08 400836IN TrueNet Structured Cabling. Introduction... 4.2. Cable... 4.3. Patch Panels... 4. Category 6 Solutions Introduction... 4.2 Cable... 4.3 Patch Panels... 4.4 Modules... 4.6 Patch Cords... 4.12 Outlets... 4.16 Faceplates...4.18 4. 1 Search Category 6 Solutions Introduction ADC KRONE s

More information

DIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION

DIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION DIVISION 26 - ELECTRICAL PART 1 - GENERAL 1.01 SUMMARY A. Section Includes 1. Instrumentation Cables 1.02 SUBMITTALS A. Submit in accordance with requirements of Section 01 33 00. B. Product Data: Submit

More information

ADC-APC Integrated Cisco Data Center Solutions

ADC-APC Integrated Cisco Data Center Solutions Advanced Infrastructure Solution for Cisco Data Center 3.0 Ordering Guide ADC-APC Integrated Cisco Data Center Solutions The evolution of data centers is happening before our eyes. This is due to the

More information

800 Communications Circuits

800 Communications Circuits ARTICLE 800 Communications Circuits INTRODUCTION TO ARTICLE 800 COMMUNICATIONS CIRCUITS This article has its roots in telephone technology. Consequently, it addresses telephone and related systems that

More information

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage:

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage: Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016 * Garage construction requires permits (electrical, building) * Permits must be applied for at the time. * Dial

More information

SECTION 17400 ACCESS CONTROL SYSTEM. CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section.

SECTION 17400 ACCESS CONTROL SYSTEM. CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section. SECTION 17400 ACCESS CONTROL SYSTEM CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section. PART 1 - GENERAL 1.1 RELATED WORK A. 16060 Grounding and Bonding B. 16070 Electrical

More information

Bonding and Grounding AMP NETCONNECT Copper Cabling Systems

Bonding and Grounding AMP NETCONNECT Copper Cabling Systems White Paper Bonding and Grounding AMP NETCONNECT Copper Cabling Systems A complete review of bonding and grounding for copper twisted-pair cabling systems Taking the Guesswork out of Grounding & Bonding

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-27 05 14.00 10 (April 2006) -------------------------------- Preparing Activity: USACE Superseding UFGS-27 05 14.00 10 (April 2004) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

IT&T Infrastructure Standards

IT&T Infrastructure Standards Technology Services IT&T Infrastructure Standards Version 1.5 17 th April 2015 Page 1 Table of contents 1 CHANGE HISTORY... 3 1.1 DOCUMENT HISTORY... 3 1.2 REVIEWERS... 3 1.3 APPROVALS... 3 2 INTRODUCTION...

More information

Optical Cable Entry Facility (OCEF) Installation Instructions

Optical Cable Entry Facility (OCEF) Installation Instructions Instruction Sheet 860380690 Issue 4, February 2014 Uniprise Solutions Optical Cable Entry Facility (OCEF) Installation Instructions General The Optical Cable Entry Facility (OCEF) cabinet stores optical

More information

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations. DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION 17650 SECURITY SYSTEMS

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION 17650 SECURITY SYSTEMS PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Inspections and observations by the Owner do not relieve the A/E of contract responsibilities. B. Chain of command 1. The DPS Project Manager is

More information

SPECIFICATION STANDARD COMMUNICATIONS CABINETS, RACKS, FRAMES, and ENCLOSURES

SPECIFICATION STANDARD COMMUNICATIONS CABINETS, RACKS, FRAMES, and ENCLOSURES PART 1: GENERAL 1.01: SCOPE OF WORK A. The contractor, designated agent or employee is held responsible to be familiar with the provisions contained herein and with other Sections of this Specification

More information

STRUCTURED CABLE SPECIFICATION INFORMATION SYSTEMS AND SERVICES ISSUE 1 NOVEMBER 2011

STRUCTURED CABLE SPECIFICATION INFORMATION SYSTEMS AND SERVICES ISSUE 1 NOVEMBER 2011 STRUCTURED CABLE SPECIFICATION INFORMATION SYSTEMS AND SERVICES ISSUE 1 NOVEMBER 2011 Project Ref. Project Name Project Manager Date issued... Consultant/Contractor... 1 CONTENTS 1000 GENERAL OVERVIEW

More information

Installation Instructions

Installation Instructions Installation Instructions For Use with PXPV230, PXPV265, PXPD230, and PXPD265 models Attention! - Please read these instructions completely before attempting installation. Always unplug the power supply

More information

March 2007. 27 08 00 Commissioning of Communications. See Appendix E3. 27 08 00-1

March 2007. 27 08 00 Commissioning of Communications. See Appendix E3. 27 08 00-1 March 2007 27 08 00 Commissioning of Communications See Appendix E3. 27 08 00-1 27 11 00 Communications Equipment Room Fittings 1.0 General TELEPHONE RISERS: A. All copper telephone riser cables must be

More information

BIX Cross-Connect System Distribution Connectors, Multiplying Connectors and Modular Jack Connectors

BIX Cross-Connect System Distribution Connectors, Multiplying Connectors and Modular Jack Connectors C O M M E R C I A L N E T W O R K I N G C O P P E R 15.13 Distribution Connectors, Multiplying Connectors and Modular Jack Connectors A0393146 QCBIX1A4 Connector BIX Distribution Connector The BIX Distribution

More information

Structured Cabling Statement of Work

Structured Cabling Statement of Work Structured Cabling Statement of Work Multiple Locations June 15, 2010 Page 1 A. GENERAL a. San Joaquin County (referred to as Owner ) is requesting proposals for a new structured cabling infrastructure

More information

CopperTen 10 Gigabit UTP Solutions

CopperTen 10 Gigabit UTP Solutions CopperTen 10 Gigabit UTP Solutions Introduction...4.2 Cable...4.3 Patch Panels...4.5 19 Cable Management...4.6 Termination Modules...4.7 Wall Mount Cable Management...4.9 Patch Cords...4.10 Outlets...4.13

More information

NEWLINK FEATURED PRODUCTS - Q1-2016

NEWLINK FEATURED PRODUCTS - Q1-2016 CAT-6A STP SOLUTION 2791124 Rack mount Patch Panel Cat-6A STP 24-port RJ45 18803BL STP Patch Cord Cat-6A 50um Gold Blue 3 ft 18803GY STP Patch Cord Cat-6A 50um Gold Gray 3 ft 18807BL STP Patch Cord Cat-6A

More information

DCF Optimized Rack System

DCF Optimized Rack System Integrated Cabinet Solutions For Business-Critical Continuity DCF Optimized Rack System User Manual IMPORTANT SAFETY GUIDELINES SAVE THESE INSTRUCTIONS This manual contains important instructions that

More information

INSTALLATION MANUAL ELECTRIC RANGE. Please read these instructions thoroughly before installing and operating the range. LRE3025ST LRE3025SB LRE3025SW

INSTALLATION MANUAL ELECTRIC RANGE. Please read these instructions thoroughly before installing and operating the range. LRE3025ST LRE3025SB LRE3025SW ENGLISH ESPAÑOL INSTALLATION MANUAL ELECTRIC RANGE Please read these instructions thoroughly before installing and operating the range. LRE3025ST LRE3025SB LRE3025SW LRE3023ST LRE3023SB LRE3023SW Printed

More information

SECTION 271525 OPTICAL FIBER CABLES AND ACCESSORIES. A. Interior Raceways, Fittings, and Accessories: Section 260532.

SECTION 271525 OPTICAL FIBER CABLES AND ACCESSORIES. A. Interior Raceways, Fittings, and Accessories: Section 260532. SECTION 271525 OPTICAL FIBER CABLES AND ACCESSORIES PART 1 GENERAL 1.01 RELATED WORK SPECIFIED ELSEWHERE A. Interior Raceways, Fittings, and Accessories: Section 260532. B. Wiring, General - 600 Volts

More information

21 st Century Campus Network Responsibility Matrix 5/26/10

21 st Century Campus Network Responsibility Matrix 5/26/10 Definitions: DoIT Standards This column details the minimal configuration, which DoIT has defined in order to provide a campus-wide standard level of service. Departments may request services, which exceeds

More information

SYSTIMAX SCS PowerSum and GigaSPEED XL Cabling Installation Guidelines

SYSTIMAX SCS PowerSum and GigaSPEED XL Cabling Installation Guidelines SYSTIMAX SCS PowerSum and GigaSPEED XL Cabling Installation Guidelines This document contains critical information regarding the installation of a certified SYSTIMAX SCS that meets or exceeds performance

More information

SECTION 27 20 00 - DATA COMMUNICATIONS. A. Complete vertical and horizontal Communication/Data Network System as indicated.

SECTION 27 20 00 - DATA COMMUNICATIONS. A. Complete vertical and horizontal Communication/Data Network System as indicated. SECTION 27 20 00 - PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this

More information

SECTION 16750 VOICE AND DATA COMMUNICATION CABLING

SECTION 16750 VOICE AND DATA COMMUNICATION CABLING SECTION 16750 VOICE AND DATA COMMUNICATION CABLING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Store drawing set and general provisions of the Contract, including General and Supplementary Conditions and

More information

ARCHITECTURAL PARTNERS, P.C. 10 Ninth Street, Lynchburg, Va. 24504 434/846-8456 Fax 434/846-4534

ARCHITECTURAL PARTNERS, P.C. 10 Ninth Street, Lynchburg, Va. 24504 434/846-8456 Fax 434/846-4534 DATE: August 25, 2015 TO: All Plan Holders ARCHITECTURAL PARTNERS, P.C. 10 Ninth Street, Lynchburg, Va. 24504 434/846-8456 Fax 434/846-4534 FROM: Jim Vernon, Architectural Partners PROJECT NAME: Nelson

More information

No Phone Line II-48 System

No Phone Line II-48 System Used in conjunction with an EntraGuard Telephone Entry System, the -48 provides No Phone Line communication and door or gate control through existing building telephone lines without the need to purchase

More information

TAB C-6 KEYLESS ACCESS AND SECURITY SYSTEM GUIDELINE

TAB C-6 KEYLESS ACCESS AND SECURITY SYSTEM GUIDELINE TAB C-6 KEYLESS ACCESS AND SECURITY SYSTEM GUIDELINE The University of Arizona has implemented a Keyless Access and Security System program to provide a cost effective, efficient, and maintainable means

More information

FTE Cabling Best Practices Author: Todd Bill, RCDD/NTS

FTE Cabling Best Practices Author: Todd Bill, RCDD/NTS FTE Cabling Best Practices Author: Todd Bill, RCDD/NTS Document ID: WP-07-01-ENG Original Issue Date: May 2007 Version: 1.0 FTE Cabling Best Practices 1 Table of Contents Introduction and Applicable Standards...3

More information

ADC Structured Cabling Solutions

ADC Structured Cabling Solutions ADC Structured Cabling Solutions The highest performing cross-connect system in the world HighBand Wall Mount Patching Solution Reliable, secure and cost effective ADC s HighBand cross connect solution

More information

1 Campus Cabling Systems Introduction

1 Campus Cabling Systems Introduction 1 Campus Cabling Systems Introduction This document represents the campus cable and infrastructure standards adopted and supported by the XXXX. All new construction and renovation should conform to these

More information

Colorado Army National Guard Grand Junction Readiness Center NGB PN 080204 Coover-Clark & Associates CCA Job No. 0726

Colorado Army National Guard Grand Junction Readiness Center NGB PN 080204 Coover-Clark & Associates CCA Job No. 0726 SECTION 260523 - CONTROL-VOLTAGE ELECTRICAL POWER CABLES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. UTP cabling. 2. RS-232 cabling. 3. RS-485 cabling. 4. Low-voltage control cabling. 5. Control-circuit

More information

Accelerating Light. Copper Cabling Solutions. Category 6A

Accelerating Light. Copper Cabling Solutions. Category 6A Accelerating Light Copper Cabling Solutions Category 6A Category 6A Copper Cabling Solutions Fibernet designs and manufactures premium, high performance copper communication infrastructure and connectivity

More information

Code Compliance for Spring Steel Fasteners Based on the 2005 NEC

Code Compliance for Spring Steel Fasteners Based on the 2005 NEC Code Compliance for Spring Steel Fasteners Based on the 2005 NEC B-Line has recognized the need for a reference source, detailing the National Electrical Code requirements for Spring Steel Fasteners. The

More information

PREFACE - UT DATA/TELECOMMUNICATION SPECIFICATION DIRECTORY

PREFACE - UT DATA/TELECOMMUNICATION SPECIFICATION DIRECTORY PREFACE - UT DATA/TELECOMMUNICATION SPECIFICATION DIRECTORY GENERAL A. INTRODUCTION The Directory, contained here-in, is not provided as, nor intended as complete Table of Contents or as a Index of the

More information

This presentation to be used in conjunction with:

This presentation to be used in conjunction with: 1 This presentation to be used in conjunction with: Spec Sheets: SA-GRSP10, SA-GRSP09, SA-GRSP11 Samples in DC-GROUND-KIT 8/16/2012 2 Network Bonding and Grounding: TIA-607-B Generic Telecommunications

More information

Rittal s Comprehensive Family Of... NETWORK RACK SOLUTIONS

Rittal s Comprehensive Family Of... NETWORK RACK SOLUTIONS Rittal s Comprehensive Family Of... NETWORK RACK SOLUTIONS STANDARD & ECONOMICAL BasicRack A complete low-cost, high-quality basic equipment management system. Design Six web channel holes per side allow

More information

SaskTel pre-wiring guide and wire standards for Single Family Units (SFU)

SaskTel pre-wiring guide and wire standards for Single Family Units (SFU) SaskTel pre-wiring guide and wire standards for Single Family Units (SFU) Last revised: 23072012 Table of Contents General information... 3 Purpose of Guide... 3 Disclaimer... 3 Description of Pre-wiring...

More information

This Addendum forms a part of the Contract Documents and modifies the original Bidding Documents and Prior Addenda if any, as identified above.

This Addendum forms a part of the Contract Documents and modifies the original Bidding Documents and Prior Addenda if any, as identified above. To: All Vendors Bidding on The College of New Jersey Security Cameras Phase III From: Roselle Horodeski Finance and Business Services Date: April 10, 2015 ADDENDUM NO. 1 ISSUE DATE: April 10, 2015 REFERENCE:

More information

ANSI/TIA/EIA - 568-A, Commercial Building Telecommunications Cabling Standard.

ANSI/TIA/EIA - 568-A, Commercial Building Telecommunications Cabling Standard. WIRING STANDARD INTRODUCTION This standard defines a telecommunications wiring system for North Dakota State Agencies, offices or buildings that will support a multi-product environment. The purpose of

More information

Building Telecommunications Infrastructure Requirements

Building Telecommunications Infrastructure Requirements Building Telecommunications Infrastructure Requirements This page identifies specific requirements for the design of telecommunications infrastructure for buildings at Clemson University. (Revised October,

More information

DIIT Voice/Data Cable Infrastructure Specifications

DIIT Voice/Data Cable Infrastructure Specifications DIIT Voice/Data Cable Infrastructure Specifications Version 7.3.5 (8-22-13) Table of Contents About this Revision...3 Voice/Data Cable Infrastructure Specifications...5 1. Overview...5 2. Cabling Infrastructure

More information

InstaPATCH Cu Cabling Solutions for Data Centers

InstaPATCH Cu Cabling Solutions for Data Centers SYSTIMAX Solutions InstaPATCH Cu Cabling Solutions for Data Centers Design Guidelines August 2008 www.commscope.com Contents Overview 1 Instapatch Cu Solution Specification 2 Harness Assembly Design 3

More information

NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION 27 05 26 GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS

NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION 27 05 26 GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS SECTION GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS RELATED SECTIONS: Section 27 00 00 General Requirements Section 27 02 00 Communication General Requirements Section 27 05 28 Pathways for Communications

More information

READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY!

READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY! READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY! The main power to any existing system must be disconnected prior to the

More information

CDGRD-10. Grounding. Solutions For Comm/Data Applications

CDGRD-10. Grounding. Solutions For Comm/Data Applications CDGRD-10 Grounding Solutions For Comm/Data Applications Overview & Table of Contents Cooper B-Line s Grounding products for rack & runway provide a complete solution for grounding metal supports. The offering

More information

Cisco Unified IP Phone Wall Mount

Cisco Unified IP Phone Wall Mount Wall Mount Components for Cisco Unified IP Phone 690, page Wall Mount Components for Cisco Unified IP Phone 69, page 4 Adjust Handset Rest, page 0 Wall Mount Components for Cisco Unified IP Phone 690 The

More information

DESIGN GUIDELINES. Local Area Network

DESIGN GUIDELINES. Local Area Network DESIGN GUIDELINES Local Area Network The total oversight and management responsibilities for information assurance (IA) and protection of DoDEA s critical infrastructure fall under the purview of the DoDEA

More information

HARTING Ethernet Cabling 8-poles Overview

HARTING Ethernet Cabling 8-poles Overview Ethernet Cabling 8-poles Overview RJ45 Connectors [on page 8] System cables [on page 12] Distribution modules and Outlets [on page 17] Connectors [on page 20] System cables [on page 26] Panel feed-throughs

More information

B. Cross-Connect: A facility enabling the termination of cable elements and their interconnection or cross-connection.

B. Cross-Connect: A facility enabling the termination of cable elements and their interconnection or cross-connection. DIVISION 16 ELECTRICAL Section 16740 Telephone System PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

University of North Carolina at Charlotte Design and Construction Manual Section 3, Annex K, 49er Card Systems ANNEX K 49ER CARD SYSTEMS

University of North Carolina at Charlotte Design and Construction Manual Section 3, Annex K, 49er Card Systems ANNEX K 49ER CARD SYSTEMS ANNEX K 49ER CARD SYSTEMS UNC CHARLOTTE 49ER CARD SYSTEM INSTALLATION AND CONTRACTOR REQUIREMENT SCOPE OF WORK: The following information pertains to the installation and contractor requirements to install

More information

AMPINNERGY TM MODULAR POWER DISTRIBUTION SYSTEM. Consultant s / Specifier s Materials

AMPINNERGY TM MODULAR POWER DISTRIBUTION SYSTEM. Consultant s / Specifier s Materials AMPINNERGY TM MODULAR POWER DISTRIBUTION SYSTEM Consultant s / Specifier s Materials Overview AMPINNERGY In a Nutshell Power System Features Common Power System Configurations Supported Wiring Methods

More information

SECTION 27 13 24 COMMUNICATIONS OPTICAL FIBER OSP CABLING

SECTION 27 13 24 COMMUNICATIONS OPTICAL FIBER OSP CABLING SECTION 27 13 24 COMMUNICATIONS OPTICAL FIBER OSP CABLING PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete

More information

Data Center. Pre-terminated. Patch Panel System. Cabling Systems Simplified. Patch Panels. 10G + Gigabit. Patch Cords. Plug & Play Installation

Data Center. Pre-terminated. Patch Panel System. Cabling Systems Simplified. Patch Panels. 10G + Gigabit. Patch Cords. Plug & Play Installation Data Center Pre-terminated Patch Panel System Patch Panels Plug & Play Installation 10G + Gigabit Patch Cords Bundled + Labeled Cabling Systems Simplified Our Mission At Cablesys, our mission is to simplify

More information

Network Telecommunications Design Standards Last Updated June 2013. Youngstown State University

Network Telecommunications Design Standards Last Updated June 2013. Youngstown State University 1 Network Telecommunications & Security Youngstown State University One University Plaza Youngstown, OH 44555 Network Telecommunications Design Standards Last Updated June 2013 Youngstown State University

More information

SECTION 28 05 00 COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND SECURITY

SECTION 28 05 00 COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND SECURITY SECTION 28 05 00 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specifications Sections, apply

More information

2. GENERAL INSTALLATION REQUIREMENTS... Z General... Z INSTALLER SKILL LEVEL... Z General... Z-4

2. GENERAL INSTALLATION REQUIREMENTS... Z General... Z INSTALLER SKILL LEVEL... Z General... Z-4 SECTION Z INSTALLATION REQUIREMENTS FOR OUTSIDE PLANT (OSP) CONTENTS PAGE 1. INTRODUCTION... Z-3 1.1 General... Z-3 1.2 Scope... Z-3 1.3 General Requirements... Z-3 1.4 Definitions clarification on ATT-TP-76300

More information

CAT 6 UTP Network Drops

CAT 6 UTP Network Drops Data Wiring of Campuses (Network and Access Points Wiring) District Identifier: 319- ND & AP Wiring Posting Date: 12-16-2015 Background The Calcasieu Parish School Board (CPSB) is requesting proposals

More information

NUIG Campus Network - Structured Cabling System Standards Information s Solutions & Services (ISS)

NUIG Campus Network - Structured Cabling System Standards Information s Solutions & Services (ISS) NUIG Campus Network - Structured Cabling System Standards Information s Solutions & Services (ISS) Revision date 28 th January 2014 The purpose of this document is to assist Building Refurbishment and

More information

Vertical Phone System Upgrades 2014. Scope of Work

Vertical Phone System Upgrades 2014. Scope of Work Vertical Phone System Upgrades 2014 Scope of Work Project Overview Install new Vertical phone system and phones on site. Complete testing with API helpdesk. Remove old phone system, phones and box up for

More information

LIEBERT VNSA Installation Sheet

LIEBERT VNSA Installation Sheet LIEBERT VNSA Installation Sheet Description The Liebert vnsa network switch is designed for connecting multiple Ethernet-ready devices and comes in various models. The unit may have: A Liebert icom display

More information

ELECTRO-MECH SCOREBOARD CO.

ELECTRO-MECH SCOREBOARD CO. ELECTRO-MECH SCOREBOARD CO. MODEL 8350-4 HOCKEY SCOREBOARD OWNER S HANDBOOK Thank you for choosing an Electro-Mech Scoreboard for your athletic complex. We are confident that your new scoreboard will give

More information

EnerNOC Site Server - S2 Installation Guide - AUS, NZ

EnerNOC Site Server - S2 Installation Guide - AUS, NZ Installation Guide EnerNOC Site Server - S2 Installation Guide - AUS, NZ v 1.7 EnerNOC New Zealand Limited 2 Collina Terrace PO Box 12-202 Thorndon Wellington NZ 6144 +64 4 909 7546 1 Table of Contents

More information

Video Camera Installation Guide

Video Camera Installation Guide Video Camera Installation Guide The intent of this guide is to provide the information needed to complete or modify a video camera installation to avoid lightning and induced power surge damage. This guide

More information

FiberGuide Fiber Management Systems. 4th Edition

FiberGuide Fiber Management Systems. 4th Edition FiberGuide Fiber Management Systems 4th Edition Table of Contents Introduction Introduction...1 A Variety of Solutions...2 Innovative Products...3 Features and Benefits... 4 Applications Combining System

More information

Fiber Plant Design Considerations for Active DAS Mike Brownson VP DAS Technical Solutions Hutton Communications

Fiber Plant Design Considerations for Active DAS Mike Brownson VP DAS Technical Solutions Hutton Communications Fiber Plant Design Considerations for Active DAS Mike Brownson VP DAS Technical Solutions Hutton Communications Topics! Understanding Fiber Types! Powering your Remotes via Composite Fiber! Fiber Design

More information

TIA 569 Standards Update Pathways & Spaces. Ignacio Diaz, RCDD April 25, 2012

TIA 569 Standards Update Pathways & Spaces. Ignacio Diaz, RCDD April 25, 2012 TIA 569 Standards Update Pathways & Spaces Ignacio Diaz, RCDD April 25, 2012 The purpose of this Standard is to standardize specific pathway and space design and construction practices in support of telecommunications

More information

IMPORTANT INSTRUCTIONS READ & SAVE THESE INSTRUCTIONS. Electric Wall Panel. Owner s Manual & Installation Instructions L

IMPORTANT INSTRUCTIONS READ & SAVE THESE INSTRUCTIONS. Electric Wall Panel. Owner s Manual & Installation Instructions L Electric Wall Panel Owner s Manual & Installation Instructions 8 Element Wall Panel Front View 8 & 6 Element Wall Panel Side View 6 Element Wall Panel Back View Top 23 1 8 EWP 8 EWP 6 Bottom 17 1 4 2 3

More information