1 Introduction to Data Centre Design Barry Elliott BSc RCDD MBA CEng Earthing, grounding and bonding November 09

2 Earthing what s the point Safety from electrical hazards Reliable signal reference within the entire information technology installation Satisfactory electromagnetic performance of the entire information technology installation

3 UK Applicable Standards BS 6701 Telecommunication cabling and equipment installations BS 7671 Requirements for electrical installations: IEE wiring regulations 16 th Edition Europe EN Application of equipotential bonding and earthing in buildings with information technology equipment EN Information technology Cabling installation Part 2 installation and planning practices inside buildings

4 Applicable Standards World IEC Electrical installations of buildings, various sections including; Part 5-548: Earthing arrangements and equipotential bonding for information technology equipment ISO 11801:2002 Information technology cabling for customer premises USA ANSI/TIA/EIA-J-STD-607 Commercial building grounding and bonding requirements for telecommunications IEEE STD Powering and Grounding Sensitive Electronic Equipment

5 Applicable Standards and. ETS Equipment engineering earthing and bonding of telecommunications equipment in telecommunication centres ITU-T K.27 Bonding configurations and earthing inside a telecommunications building ITU-T K.31 Bonding configurations and earthing of telecommunications installations inside a subscriber s building

6 Terminology Earthing The connection of the exposed conductive parts of an installation to the main earthing terminal of that installation (BS 7671) Equipotential bonding The electrical connection putting various exposed conductive parts and extraneous conductive parts at a substantially equal potential (EN ) Grounding (American) A conducting connection, whether intentional or accidental, between an electrical circuit and the earth. (TIA/EIA-607)

7 Bolting it all together the equipotential bonding system In an installation, main equipotential bonding conductors shall connect to the main earthing terminal extraneous conductive parts of that installation including the following: Water service pipes Gas service pipes Other service pipes and ducting Central heating and air conditioning systems Exposed metallic structural parts of the building The lightning protective system The metallic sheath of any telecommunications cable

8 Supplementary equipotential bonding conductors (where required) Exposed conductive parts Extraneous conductive part Circuit protective conductors Main equipotential bonding conductors Main earthing terminal Earthing conductor Main metallic water pipe

9 EN Application of equipotential bonding and earthing in buildings with information technology equipment

10 The frame ground grid shall be installed with a maximum cell size of 2 metres in each horizontal direction. The minimum cross-sectional area of the conductors that create the frame ground grid shall be 10 mm² min. The frame ground grid shall be connected to the earthing network at multiple points, where available. If the raised floor is installed with a surface that is intended to provide protection against electrostatic discharge, the DC resistance between the raised floor surface and the earthing grid shall be in the range 1 MΩ to 10 MΩ EN 50310

11 TIA 607

12 6.3 mm thick 101 mm high

13 Examples of Clean Earth Bar

14 Earth everything!

15 Earth everything!

16 Additionally, every sixth metallic raised floor pedestal needs to be bonded (to the SRG). This helps to bleed off static charges built up from the raised floor system. *EN suggest every 2 or 3 pedestals earthed with a 10 sq mm wire

17 Earthing system for computer room and entrance room

18 Underfloor TGB serving a row of racks

19

20 TGB in Entrance Room

21 Signal Reference Grid - Purpose

22 Signal reference grid G TIA 942 Data center grounding infrastructure. IEEE Standard 1100 provides recommendations for the electrical design of bonding and grounding. Consideration should be given to installing a common bonding network (CBN) such as a signal reference structure as described in IEEE Standard 1100 for the bonding of telecommunications and computer equipment. If the system is on raised flooring, use a 2- foot x 2-foot (61-cm x 61-cm) grounding grid. (HP) Site preparation guide

23 SRG - Do we need one? Access (raised) flooring systems that utilize bolted stringer construction can be used to provide a simple SRG. Floor systems that have either no stringer or snap-in stringers do not provide for an effective SRG, and other methods for installing an SRG should be used. (IBM) system reference potential plane (SRPP) conductive solid plane, as an ideal goal in potential equalising, is approached in practice by horizontal or vertical meshes. The mesh width thereof is adapted to the frequency range to be considered. Horizontal and vertical meshes may be interconnected to form a grid structure approximating to a Faraday cage, EN 50310

24 The high operating frequencies of modern computer equipment require that computer room products be supported both by a good equipment-grounding system and an effective signal reference grid. Compaq/HP A signal reference grid should be designed for the computer room. This provides an equal potential plane of reference over a broad band of frequencies through the use of a network of low-impedance conductors installed throughout the facility. SUN

25 ETSI EN Signal reference Reliable signal reference shall be provided by a SRPP dedicated at least to a functional unit or a system block. To avoid undue functional distortion or risk of component failure, the SRPP shall provide sufficiently low impedance up to the highest frequency to be regarded by using a metal plane or a meshed configuration having adequate mesh dimensions, e.g. a bonding mat. The frequency band to be covered shall include the spectral components of transients caused by switching, short circuits and atmospheric discharges.

26 Critical equipment should be located and bonded to the SRG at more than 6 feet away from the building steel or other potential lightning paths. All interconnecting communications, data and power cables should lay on or very close to the SRG Bond the signal reference grid to each piece of electronic equipment and to any other electrical or mechanical equipment located on the signal reference grid. Bonding connections to the signal reference grid should be as short as practical with no sharp folds or bends. Flexible straps are preferred to the use of round conductors.

27

28

29 IEEE 1100

Earthing (Grounding) and Bonding Guidelines For Uniprise Solutions F/UTP Cabling System

Earthing (Grounding) and Bonding Guidelines For Uniprise Solutions F/UTP Cabling System Uniprise Solutions Earthing (Grounding) and Bonding Guidelines For Uniprise Solutions F/UTP Cabling System January 2012 www.commscope.com Contents Contents 1.0 Introduction 3 2.0 Earthing and Bonding 3

More information

Screened cable and data cable segregation

Screened cable and data cable segregation December 2007 Screened cable and data cable segregation Can an armoured power cable be considered a screened cable and how does this relate to power and data cable segregation? The short answer is yes;

More information

Earthing and Bonding Recommendations

Earthing and Bonding Recommendations APPENDIX C Earthing and Bonding Recommendations Note This appendix applies to the Cisco MGX switches and gateways described in this guide: MGX 8850 (PXM45/PXM1E), MGX 8850/B, MGX 8950, MGX 8830 and MGX

More information

270526-TC Grounding and Bonding for Telecommunications Systems

270526-TC Grounding and Bonding for Telecommunications Systems 270526-TC Grounding and Bonding for Telecommunications Systems Part 1 - General 1.1 Work Included 1.2 Scope of Work A. Provide all labor, materials, tools and equipment required for the complete installation

More information

270526-TC Grounding and Bonding for Telecommunications Systems

270526-TC Grounding and Bonding for Telecommunications Systems 270526-TC Grounding and Bonding for Telecommunications Systems Part 1 - General Related Documents The following related sections of the OT standards shall also be applicable to this section. OT Engineer

More information

EMC Engineering Guidelines For Automation Systems PS 4 PS 416 04/97 AWB 27-1287-GB

EMC Engineering Guidelines For Automation Systems PS 4 PS 416 04/97 AWB 27-1287-GB EMC Engineering Guidelines For Automation Systems PS 4 PS 416 1st edition 04/97 Moeller GmbH, Bonn Author: Werner Albrecht Editors: Klaus Krüger, Thomas Kracht Translator: Chris Baker, Terence Osborn Contents

More information

NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION 27 05 26 GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS

NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION 27 05 26 GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS SECTION GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS RELATED SECTIONS: Section 27 00 00 General Requirements Section 27 02 00 Communication General Requirements Section 27 05 28 Pathways for Communications

More information

Use of the Signal Reference Grid in Data Centers

Use of the Signal Reference Grid in Data Centers Use of the Signal Reference Grid in Data Centers By Neil Rasmussen White Paper #87 Executive Summary Signal reference grids are automatically specified and installed in data centers despite the fact that

More information

Earthing (grounding) system

Earthing (grounding) system Earthing (grounding) system according to IEC, BS-EN and IEEE standards Legal regulations being applied when designing earthing (grounding) systems 1. Good earthing (grounding) system according to IEC/BS

More information

GroundRod AC Substation Earthing Tutorial

GroundRod AC Substation Earthing Tutorial 1 GroundRod AC Substation Earthing Tutorial 1. Functions of an earthing system The two primary functions of a safe earthing system are: To ensure that a person who is in the vicinity of earthed facilities

More information

Coaxial Cable Entry Panels, Coax and Grounding Connectors. Technical Note

Coaxial Cable Entry Panels, Coax and Grounding Connectors. Technical Note Coaxial Cable Entry Panels, Coax and Grounding Connectors Technical Note Coaxial Cable Entry Panels, Coax and Grounding Connectors Surge Protection Solutions for PTC 2 Coaxial Cable Entry Panels, Coax

More information

SPECIFICATION STANDARD GROUNDING AND BONDING

SPECIFICATION STANDARD GROUNDING AND BONDING PART 1: GENERAL 1.01 SCOPE OF WORK SPECIFICATION STANDARD A. The grounding and bonding system refers to all electrodes required by NEC, as well as including made, supplementary, information technology

More information

This presentation to be used in conjunction with:

This presentation to be used in conjunction with: 1 This presentation to be used in conjunction with: Spec Sheets: SA-GRSP10, SA-GRSP09, SA-GRSP11 Samples in DC-GROUND-KIT 8/16/2012 2 Network Bonding and Grounding: TIA-607-B Generic Telecommunications

More information

PROTECTIVE MULTIPLE EARTHING AND THE RADIO AMATEUR

PROTECTIVE MULTIPLE EARTHING AND THE RADIO AMATEUR PROTECTIVE MULTIPLE EARTHING AND THE RADIO AMATEUR RSGB EMC Committee Leaflet EMC 07 Iss 2 1 Disclaimer This leaflet is intended for members of the RSGB who have passed the Radio Amateur s Examination

More information

HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE: 10.17.12

HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE: 10.17.12 SECTION 27 05 26 - GROUNDING AND BONDING FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes grounding and bonding products, design requirements and installation for communications

More information

Technical Data. General specifications Switching element function Rated operating distance s n 15 mm

Technical Data. General specifications Switching element function Rated operating distance s n 15 mm 0102 Model Number Features Comfort series 15 mm flush Accessories MHW 01 Modular mounting bracket MH 04-2057B Mounting aid for VariKont and +U1+ Technical Data General specifications Switching element

More information

Consultants Handbook

Consultants Handbook Consultants Handbook CONSULTANTS HANDBOOK Welcome to our Wallis Designers Lightning Protection Handbook. This handbook offers a guide for any designers of the structural Lightning protection system to

More information

Mirage over door heater. Features: Electric and LPHW versions. Compact and Versatile. Suitable for mounting up to 3.0m high from finished floor level.

Mirage over door heater. Features: Electric and LPHW versions. Compact and Versatile. Suitable for mounting up to 3.0m high from finished floor level. Features: Electric and LPHW versions. Compact and Versatile Suitable for mounting up to 3.0m high from finished floor level. Recessed or surface mounted. Energy saving controls option available. Available

More information

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management. AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled

More information

Session 14 Cable Support Systems

Session 14 Cable Support Systems Session 14 Cable Support Systems Cable Support Systems in the IEC World A new IEC Standard, IEC61537 2001 has been developed If full details of the cabling layout are available then the likely cable load

More information

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management. AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled

More information

Structured Cabling, Earthing & Equipotential Bonding

Structured Cabling, Earthing & Equipotential Bonding White Paper Information and Communication Technology Structured Cabling, Earthing & Equipotential Bonding English Rev. 1.0.1 / 2012-06-01 1 Abstract All Dallmeier network products (PoE cameras, recorders,

More information

PROTECTION AGAINST ELECTRIC SHOCK by John Ware

PROTECTION AGAINST ELECTRIC SHOCK by John Ware 16 become live under fault conditions. The potential of the metal enclosure is higher than that of the main earthing terminal of the installation (and that of Earth) because of a potential difference created

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 62305-3 Edition 2.0 2010-12 colour inside Protection against lightning Part 3: Physical damage to structures and life hazard INTERNATIONAL ELECTROTECHNICAL COMMISSION PRICE CODE

More information

Trade of Electrician. Earthing and Bonding

Trade of Electrician. Earthing and Bonding Trade of Electrician Standards Based Apprenticeship Earthing and Bonding Phase 2 Module No. 2.2 Unit No. 2.2.6. COURSE NOTES Created by Eugene Trindles Cork TC Revision 1 April 2000 by Eugene Trindles

More information

Foreword. Page 2 EN 50174-2:2000

Foreword. Page 2 EN 50174-2:2000 Page 2 Foreword This European Standard has been prepared by Technical Committee CENELEC TC 215 "Electrotechnical aspects of telecommunication equipment" under the framework of the Mandates M/212 on Telecommunication

More information

Power Separation Guidelines for SYSTIMAX Installations

Power Separation Guidelines for SYSTIMAX Installations SYSTIMAX Solutions Power Separation Guidelines for SYSTIMAX Installations Design and installation guidelines August 2011 www.commscope.com 1.0 General These guidelines are based on extensive testing and

More information

Soares Book on Grounding and Bonding 2014 NEC Connecting to Earth - The Grounding Electrode System

Soares Book on Grounding and Bonding 2014 NEC Connecting to Earth - The Grounding Electrode System Soares Book on Grounding and Bonding 2014 NEC Connecting to Earth - The Grounding Electrode System Presentation by: International Association of Electrical Inspectors Instructor: L. Keith Lofland IAEI

More information

There are three possible installation kits for the MIS5022 switch. Make sure that you have the installation kit that you ordered.

There are three possible installation kits for the MIS5022 switch. Make sure that you have the installation kit that you ordered. Installation Guide Installing the Switch in the Rack There are three possible installation kits for the MIS5022 switch. Make sure that you have the installation kit that you ordered. Table 1 - Installation

More information

Separation of power and information technology cabling

Separation of power and information technology cabling Technical bulletin Separation of power and information technology cabling Date: 08/2006 This technical bulletin provides you with information on specific technical subjects. It is based on the current

More information

CUSTOMER REQUIREMENTS AT POWER SUBSTATIONS

CUSTOMER REQUIREMENTS AT POWER SUBSTATIONS CUSTOMER REQUIREMENTS AT POWER SUBSTATIONS Customer Handout Date Aug 2, 2010 Version 1.0 File Name Customer Requirements At Power Substations Document Id Outside Plant Engineering 1 Table Of Contents 1.0

More information

Standards. www.nordx.com 5 ANSI/TIA/EIA-569-A (CSA T530)

Standards. www.nordx.com 5 ANSI/TIA/EIA-569-A (CSA T530) The primary focus of this standard is to provide design specifications and guidance for all building facilities relating to telecommunications cabling systems and components. This standard identifies and

More information

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4 CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,

More information

Chapter 9. Bonding and Grounding

Chapter 9. Bonding and Grounding Chapter 9 Bonding and Grounding Objectives Describe why the cable should be bonded Describe bonding and grounding procedures Define Bonding and Grounding Explain Safety Benefits and intent of bonding and

More information

9.5 Lightning and surge protection for cable networks and antennas for TV, sound signals and interactive services

9.5 Lightning and surge protection for cable networks and antennas for TV, sound signals and interactive services 9.5 Lightning and surge protection for cable networks and antennas for TV, sound signals and interactive services IEC 6078-: 005 complies with the state of the art and offers easy, standardised and effective

More information

Technical Data. Dimensions

Technical Data. Dimensions 0102 Model Number Features 15 mm quasi flush Usable up to SIL2 acc. to IEC 61508 Accessories BF 30 Mounting flange, 30 mm V1-G-N-2M-PUR Female cordset, M12, 2-pin, NAMUR, PUR cable V1-W-N-2M-PUR Female

More information

1. Franklin Rod Performance 2. LEC/DAS Performance

1. Franklin Rod Performance 2. LEC/DAS Performance THREE ESSENTIALS OF LIGHTNING PROTECTION: BONDING, GROUNDING AND SURGE PROTECTION by Richard Kithil, President and Orlando Alzamora, Vice-President National Lightning Safety Institute (NLSI) 1.0 Summary.

More information

Cabinets 101: Configuring A Network Or Server Cabinet

Cabinets 101: Configuring A Network Or Server Cabinet Cabinets 101: Configuring A Network Or Server Cabinet North, South and Central America White Paper May 2012 www.commscope.com Contents Background Information 3 What is a network or server cabinet? 3 What

More information

Manual. IS1 - Remote I/O System. > Earthing and shielding

Manual. IS1 - Remote I/O System. > Earthing and shielding Manual > Contents 1 Contents 1 Contents...2 2 General Information...2 2.1 Manufacturer...2 2.2 Symbols used...3 3 General Safety Instructions...3 3.1 Safety instructions for the engineering personnel...3

More information

EARTHING SYSTEM CALCULATION

EARTHING SYSTEM CALCULATION BAZIAN STEAL FACTORY S/S 132/11kV, 1x30/40MVA EARTHING SYSTEM CALCULATION Kurdistan Region Sulaimani May 2011 Bazian Steal Factory S/S 132/11kV, 1x30/40 MVA Contents: 1. Introduction... 3 2. List of references

More information

Technical Data. Dimensions

Technical Data. Dimensions 0102 Model Number Features Comfort series 5 mm flush Usable up to SIL 2 acc. to IEC 61508 Accessories BF 18 Mounting flange, 18 mm EXG-18 Quick mounting bracket with dead stop Technical Data specifications

More information

Interfacing electrification and system reliability. Earthing of AC and DC railways 4,10,13

Interfacing electrification and system reliability. Earthing of AC and DC railways 4,10,13 Interfacing electrification and system reliability Roger White Professional Head of Electrification and Plant Rail Abstract Integration is the term given to ensuring that the different elements of an electrified

More information

EARTHING: YOUR QUESTIONS ANSWERED

EARTHING: YOUR QUESTIONS ANSWERED 18 EARTHING: YOUR QUESTIONS ANSWERED By Geoff Cronshaw What are earthed and unearthed systems? What are the requirements of BS 7671? What are the advantages and disadvantages of the various types of earthing

More information

C&G Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations. Continuity of Protective Conductors

C&G Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations. Continuity of Protective Conductors C&G 2395-01 Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations Continuity of Protective Conductors 1 Outcomes of this Session State the requirements which need

More information

Presenters Brett Weiss, Gabe Martinez, Brian Kroeger.

Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. 1 Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. Topics to be covered: Cable identification Purpose of the various cable types Installation techniques Building Infrastructure Overview of networking

More information

Grounding and Bonding

Grounding and Bonding ARTICLE 250 Grounding and Bonding INTRODUCTION TO ARTICLE 250 GROUNDING AND BONDING No other article can match Article 250 for misapplication, violation, and misinterpretation. Terminology used in this

More information

Grounding Demystified

Grounding Demystified Grounding Demystified 3-1 Importance Of Grounding Techniques 45 40 35 30 25 20 15 10 5 0 Grounding 42% Case 22% Cable 18% Percent Used Filter 12% PCB 6% Grounding 42% Case Shield 22% Cable Shielding 18%

More information

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting 12 SOLAR PHOTOVOLTAIC POWER by John Ware IT IS PLANNED for BS 7671:2008 to include a new Section 712 providing additional requirements for safety applicable to solar photovoltaic (pv) power supply systems.

More information

HEAVY DUTY STORAGE GAS

HEAVY DUTY STORAGE GAS Multi-Fin flue technology Flue damper saves energy Electronic controls HEAVY DUTY STORAGE GAS Dependability The Rheem heavy duty gas range is the work horse of the industry having proved itself over many

More information

NZECP 35:1993 ISSN 0114-0663 COVER PAGE

NZECP 35:1993 ISSN 0114-0663 COVER PAGE NZECP 35:1993 ISSN 0114-0663 COVER PAGE NZECP:35 1993 NEW ZEALAND ELECTRICAL CODE OF PRACTICE for POWER SYSTEMS EARTHING Issued by the Office of The Chief Electrical Inspector, Energy and Resources Division,

More information

TIA 569 Standards Update Pathways & Spaces. Ignacio Diaz, RCDD April 25, 2012

TIA 569 Standards Update Pathways & Spaces. Ignacio Diaz, RCDD April 25, 2012 TIA 569 Standards Update Pathways & Spaces Ignacio Diaz, RCDD April 25, 2012 The purpose of this Standard is to standardize specific pathway and space design and construction practices in support of telecommunications

More information

Calculating Creepage and Clearance Early Avoids Design Problems Later Homi Ahmadi

Calculating Creepage and Clearance Early Avoids Design Problems Later Homi Ahmadi Calculating Creepage and Clearance Early Avoids Design Problems Later Homi Ahmadi One of the most common errors uncovered by product safety engineers stems from manufacturers and designers failing to fully

More information

Verizon NEBS TM Compliance: HVAC Systems NEBS Requirements Verizon Technical Purchasing Requirements VZ.TPR.9808 Issue 1, April 2014

Verizon NEBS TM Compliance: HVAC Systems NEBS Requirements Verizon Technical Purchasing Requirements VZ.TPR.9808 Issue 1, April 2014 Verizon NEBS TM Compliance: HVAC Systems NEBS Requirements Verizon Technical Purchasing Requirements VZ.TPR.9808 Issue 1, April 2014 CHANGE CONTROL RECORD: Version Date Action* Reason for Revision 1 4/14/2014

More information

ELECTRICAL INSTALLATION CERTIFICATE Issued in accordance with British Standard BS 7671 Requirements for Electrical Installations

ELECTRICAL INSTALLATION CERTIFICATE Issued in accordance with British Standard BS 7671 Requirements for Electrical Installations ELECTRICAL INSTALLATION CERTIFICATE Issued in accordance with British Standard BS 7671 Requirements for Electrical Installations Certificate Reference 0039291 1. DETAILS OF THE CLIENT Client 2. DETAILS

More information

EN 50174-1 and EN 50174-2: 2008 Integrated standards for telecommunications cabling installation

EN 50174-1 and EN 50174-2: 2008 Integrated standards for telecommunications cabling installation EN 50173-1 EN 50173-2 EN 50173-3 EN 50173-4 EN 50173-5 EN 50346 EN 50174-1 EN 50174-2 EN 50174-3 DESIGN INSPECTION TESTING PLANNING INSTALLATION National Standards National Regulations EN 50174-1 and EN

More information

No. 8940. EUROPEAN AGREEMENT CONCERNING THE INTERNATIONAL CAR RIAGE OF DANGEROUS GOODS BY ROAD (ADR). DONE AT GENEVA ON 30 SEPTEMBER 1957'

No. 8940. EUROPEAN AGREEMENT CONCERNING THE INTERNATIONAL CAR RIAGE OF DANGEROUS GOODS BY ROAD (ADR). DONE AT GENEVA ON 30 SEPTEMBER 1957' 1975 United Nations Treaty Series Nations Unies Recueil des Traités 435 [TRANSLATIN TRADUCTIN] No. 8940. EURPEAN AGREEMENT CNCERNING THE INTERNATINAL CAR RIAGE F DANGERUS GDS BY RAD (ADR). DNE AT GENEVA

More information

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage:

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage: Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016 * Garage construction requires permits (electrical, building) * Permits must be applied for at the time. * Dial

More information

www.klmtechgroup.com TABLE OF CONTENT

www.klmtechgroup.com TABLE OF CONTENT Page : 1 of 13 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia ELECTIRAL GROUNDING TABLE OF CONTENT

More information

Network Design. Yiannos Mylonas

Network Design. Yiannos Mylonas Network Design Yiannos Mylonas Physical Topologies There are two parts to the topology definition: the physical topology, which is the actual layout of the wire (media), and the logical topology, which

More information

BLADE S-MAX Cabinet for Blade Server

BLADE S-MAX Cabinet for Blade Server Cabinet for Blade Server 1 2 Overview Material specification Corner verticals: 1.5 mm steel End frames: 1.5 mm steel Panel mounts: 2.0 mm steel Panel mount supports: 1.5 mm steel Side panels, door and

More information

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION Page 1 of 11 ****This Standard Supercedes BECo CS2.13-2.3 & ComElectric OH Construction Manual, System Grounding Section, drawings CGND, GRDSUM, and C2**** 1.0 Bill of Materials GROUNDING AND BONDING POLE-MOUNTED

More information

Excerpts from the Canadian National Building Code (NBC)

Excerpts from the Canadian National Building Code (NBC) Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more

More information

Technical specifications. Containerized data centre NTR CDC 40f+

Technical specifications. Containerized data centre NTR CDC 40f+ Technical specifications Containerized data centre NTR CDC 40f+ CONTENT 1 THE PURPOSE OF CDC... 3 2 BASIC PROPERTIES... 4 2.1 EXTERNAL DIMENSIONS... 4 2.2 INSTALLATION REQIREMENTS... 4 2.3 ELECTRICAL CONNECTION

More information

Comparative study for cables and busbars

Comparative study for cables and busbars Comparative study for cables and busbars Preliminary considerations To compare the prices of two categories of product as different as traditional cables and busbars, it is necessary to make some preliminary

More information

PERMIT APPLICATION REQUIREMENTS FOR RESIDENTIAL ROOF MOUNTED PHOTOVOLTAIC SYSTEMS

PERMIT APPLICATION REQUIREMENTS FOR RESIDENTIAL ROOF MOUNTED PHOTOVOLTAIC SYSTEMS Butte County Department of Development Services PERMIT CENTER 7 County Center Drive, Oroville, CA 95965 Main Phone (530)538-7601 Permit Center Phone (530)538-6861 Fax (530)538-7785 FORM NO DBP-71 PERMIT

More information

Protection and Safety

Protection and Safety MECH3005 Building Services http://www.hku.hk/bse/mech3005/ Electrical Supply Protection and Safety Dr. Sam C M Hui Department of Mechanical Engineering The University of Hong Kong E-mail: cmhui@hku.hk

More information

Earthing Requirements for IMS Equipment

Earthing Requirements for IMS Equipment IMS-SYSTEM-EARTHING-201204-GGv1 - Page 1 of 8 - Earthing Requirements for IMS Equipment Document Number IMS-SYSTEM-EARTHING-201204-GGv1 IMS-SYSTEM-EARTHING-201204-GGv1 - Page 2 of 8 - Contents IMS-SYSTEM-EARTHING-201204-GGv1

More information

EARTHING AND BONDING AT SECONDARY SUBSTATIONS

EARTHING AND BONDING AT SECONDARY SUBSTATIONS DISTRIBUTION CONSTRUCTION MANUAL SECTION 4 - SUBSTATIONS ISSUE B SEPT 1996 4.4.4 EARTHING AND BONDING AT SECONDARY SUBSTATIONS 1 SCOPE This section of the Distribution Construction Manual lays down the

More information

SOHOline and SOHO Slimline The SOHOline and SOHO Slimline offer a modular, sturdy and compact design

SOHOline and SOHO Slimline The SOHOline and SOHO Slimline offer a modular, sturdy and compact design SOHOline and SOHO Slimline The SOHOline and SOHO Slimline offer a modular, sturdy and compact design Ideal installation for; Offices Branch Offices Schools Computer Aided Classes Government Offices Hotels

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

PXL-250: Network Wiring

PXL-250: Network Wiring This document provides the network wiring requirements for a PXL-250 access control network. Network Requirements The PXL-250 uses a half-duplex, RS-485 communication bus. Per the RS-485 specification,

More information

Minimum Standards for Data/Voice Infrastructure in New Building Construction

Minimum Standards for Data/Voice Infrastructure in New Building Construction UNIVERSITY OF WATERLOO Minimum Standards for Data/Voice Infrastructure in New Building Construction 12/17/2012 Offices 1. Two Work Area Outlets (WAO) on opposite walls, each with 2 jacks 2. Each WAO shall

More information

INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1

INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 City of Cotati Building Division 201 W. Sierra Ave. Cotati, CA 94931 707 665-3637 Fax 792-4604 INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 Any PV system on a new structures should be included

More information

Linkeo 19" freestanding cabinets

Linkeo 19 freestanding cabinets 87045 LIMOGES Cedex France Telephone: (+33) 05 55 06 87 87 - Fax: (+33) 05 55 06 88 88 Linkeo 19" freestanding cabinets Page 1. General characteristics....1 2. Range....2 3. Technical characteristics...3

More information

NCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003)

NCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003) NCMA TEK National Concrete Masonry Association an information series from the national authority on concrete masonry technology CONCRETE MASONRY FOUNDATION WALL DETAILS TEK 5-3A Details (2003) Keywords:

More information

Power Quality for Information Technology System

Power Quality for Information Technology System Power Quality for Information Technology System ITS OBVIOUS THE TOLERANCE IS DIFFRENT But What isn t Tobvious? HOW MANY OF YOU HAVE : A COMPUTER AT HOME? = Computers are not screens and Keyboards COMPUTERS

More information

FEBRUARY 2006. Data centre design. 1.0 Purpose. 2.0 Disclaimer. 3.0 Introduction. 4.0 Physical location of the data centre

FEBRUARY 2006. Data centre design. 1.0 Purpose. 2.0 Disclaimer. 3.0 Introduction. 4.0 Physical location of the data centre Consultant Programme WHITE PAPER FEBRUARY 2006 Data centre design Contents 1.0 Purpose By Barry Elliott BSc, MBA, RCDD, C.Eng, MIEE barry.elliott@ engineeringeducation.co.uk Engineering Education Ltd 2006

More information

Technical Data. General specifications Switching element function Rated operating distance s n 5 mm

Technical Data. General specifications Switching element function Rated operating distance s n 5 mm 0102 Model Number Features 5 mm flush Usable up to SIL 2 acc. to IEC 61508 Accessories EXG-18 Quick mounting bracket with dead stop BF 18 Mounting flange, 18 mm Technical Data specifications Switching

More information

No Phone Line System. Quick Start Guide NPL II. 1.0 Installation

No Phone Line System. Quick Start Guide NPL II. 1.0 Installation Used in conjunction with EntraGuard Gold Telephone Entry Systems, the provides No Phone Line communication and door or gate control through existing building telephone lines without the need purchase phone

More information

Regulatory & IEC 950. Nick Stapleton 3Com

Regulatory & IEC 950. Nick Stapleton 3Com Regulatory 802.3 & IEC 950 Nick Stapleton 3Com Review of IEEE 802.3 Isolation Requirements 10BASE-T 1000BASE-T Multi-Port Devices Repeaters Switches 10BASE-T Isolation 14.3.1.1 Isolation requirement The

More information

AFUMEX LSX LOW SMOKE ZERO HALOGEN SCREENED WIRING CABLES BS8436 PRODUCT DATASHEET & APPLICATIONS GUIDE KEY BENEFITS:

AFUMEX LSX LOW SMOKE ZERO HALOGEN SCREENED WIRING CABLES BS8436 PRODUCT DATASHEET & APPLICATIONS GUIDE KEY BENEFITS: PRODUCT DATASHEET & APPLICATIONS GUIDE LOW SMOKE ZERO HALOGEN SCREENED WIRING CABLES BS8436 KEY BENEFITS: BASEC approved for the full size range of BS8436 (1.0mm 2 to 2.5mm 2 ) Additionally approved for

More information

DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)

DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) DETAILS OF THE CLEINT Client and address ADDRESS OF THE INSTALLATION Installation

More information

VOLUME AND SURFACE AREAS OF SOLIDS

VOLUME AND SURFACE AREAS OF SOLIDS VOLUME AND SURFACE AREAS OF SOLIDS Q.1. Find the total surface area and volume of a rectangular solid (cuboid) measuring 1 m by 50 cm by 0.5 m. 50 1 Ans. Length of cuboid l = 1 m, Breadth of cuboid, b

More information

WHY and HOW to GROUND ELECTRICAL SYSTEMS

WHY and HOW to GROUND ELECTRICAL SYSTEMS WHY and HOW to GROUND ELECTRICAL SYSTEMS Dr. Tom Van Doren Van Doren Company Rolla, MO, USA 1-573-578-4193 vandoren@mst.edu emc-education.com emclab.mst.edu Grounding is a very controversial and misunderstood

More information

PS 29M DUAL CHANNEL BELTPACK IN METAL CASE

PS 29M DUAL CHANNEL BELTPACK IN METAL CASE PS 29M DUAL CHANNEL BELTPACK IN METAL CASE USER MANUAL October 2013 This product is designed and manufactured by: ASL Intercom BV Zonnebaan 42 3542 EG Utrecht The Netherlands Phone: +31 (0)30 2411901 Fax:

More information

Lightning Arresters P30027 18 KVA P30038 10 KVA. Description & Installation

Lightning Arresters P30027 18 KVA P30038 10 KVA. Description & Installation Lightning Arresters P30027 18 KVA P30038 10 KVA Description & Installation Printed in USA 09/11 TO330 Rev. B Table of Contents Page 1.0 SCOPE 2 2.0 PRODUCT OVERVIEW 2 2.1 Intended Uses 2 2.2 Lightning

More information

EMC Immunity Test Electrostatic discharge. By Dr. Brian Chan Consultant EMC Centre Hong Kong Productivity Council

EMC Immunity Test Electrostatic discharge. By Dr. Brian Chan Consultant EMC Centre Hong Kong Productivity Council EMC Immunity Test Electrostatic discharge By Dr. Brian Chan Consultant EMC Centre Hong Kong Productivity Council 1 Agenda Background of ESD ESD Immunity Test - EN61000-4-2 Standard Scope Test level Test

More information

White Paper. General instructions on lightning safety for shelters. Contents

White Paper. General instructions on lightning safety for shelters.  Contents White Paper General instructions on lightning safety for shelters Contents Lightning protection Prevention of touch voltages Prevention of step voltages Installation of a lightning rod on shelters with

More information

Grounding Practice at Data and Communications Centers. David Brender, P.E., CPQ National Program Manager Copper Development Association Inc.

Grounding Practice at Data and Communications Centers. David Brender, P.E., CPQ National Program Manager Copper Development Association Inc. Grounding Practice at Data and Communications Centers David Brender, P.E., CPQ National Program Manager Copper Development Association Inc. Overview of This Presentation Elements of building wiring and

More information

RF data receiver super-reactive ASK modulation, low cost and low consumption ideal for Microchip HCS KEELOQ decoder/encoder family. 0.

RF data receiver super-reactive ASK modulation, low cost and low consumption ideal for Microchip HCS KEELOQ decoder/encoder family. 0. Receiver AC-RX2/CS RF data receiver super-reactive ASK modulation, low cost and low consumption ideal for Microchip HCS KEELOQ decoder/encoder family. Pin-out 38.1 3 Component Side 1 2 3 7 11 13 14 15

More information

SECTION 260536 - CABLE TRAYS. A. Continuous, rigid, welded steel or stainless steel wire mesh cable management system.

SECTION 260536 - CABLE TRAYS. A. Continuous, rigid, welded steel or stainless steel wire mesh cable management system. SECTION 260536 - CABLE TRAYS PART 1 - GENERAL SECTION INCLUDES: A. Continuous, rigid, welded steel or stainless steel wire mesh cable management system. B. Cable tray systems are defined to include, but

More information

EMC OF INSTALLATIONS AND RECOMMENDED CABLE SEPARATIONS

EMC OF INSTALLATIONS AND RECOMMENDED CABLE SEPARATIONS EMC Technical Information EMC OF INSTLLTIONS ND RECOMMENDED CBLE SEPRTIONS Technology Installation Services Providing a fully integrated installation service for the Computer/Telecommunications Industry

More information

Video Camera Installation Guide

Video Camera Installation Guide Video Camera Installation Guide The intent of this guide is to provide the information needed to complete or modify a video camera installation to avoid lightning and induced power surge damage. This guide

More information

No Phone Line II-48 System

No Phone Line II-48 System Used in conjunction with an EntraGuard Telephone Entry System, the -48 provides No Phone Line communication and door or gate control through existing building telephone lines without the need to purchase

More information

Cable Discharge Event

Cable Discharge Event Cable Discharge Event 1.0 Introduction The widespread use of electronic equipment in various environments exposes semiconductor devices to potentially destructive Electro Static Discharge (ESD). Semiconductor

More information

Specification SFTP CAT6 Network Cable 23AWG CU

Specification SFTP CAT6 Network Cable 23AWG CU Specification SFTP CAT6 Network Cable 23AWG CU S/FTP CAT6 Shielded S/FTP PVC Cable 23AWG 4pair Solid, Wooden drum 1000 Grey CAT6 600MHZ CM Shielded (S/FTP) Solid Cable: Our CAT6 600MHZ Shielded (S/FTP)

More information

Rittal s Comprehensive Family Of... NETWORK RACK SOLUTIONS

Rittal s Comprehensive Family Of... NETWORK RACK SOLUTIONS Rittal s Comprehensive Family Of... NETWORK RACK SOLUTIONS STANDARD & ECONOMICAL BasicRack A complete low-cost, high-quality basic equipment management system. Design Six web channel holes per side allow

More information

T A B L E T 1 T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A

T A B L E T 1 T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A T A B L E T 1 1 of 7 Tests & Inspection Cable PCUT & PCUT-A (Table T1) T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A No. Test Scale MOC Requirements G 20:10:001:01 Defined Test

More information

PERFORMANCE GROUNDING AND WIRING FOR SENSITIVE EQUIPMENT

PERFORMANCE GROUNDING AND WIRING FOR SENSITIVE EQUIPMENT Pacific Gas and Electric Company PERFORMANCE GROUNDING AND WIRING FOR SENSITIVE EQUIPMENT Introduction Many power quality variations that occur within customer facilities are related to wiring and grounding

More information

FIRE RESISTANT CABLE CONSTRUCTION OF CABLES

FIRE RESISTANT CABLE CONSTRUCTION OF CABLES FIRE RESISTANT CABLE In all fire disasters, fire smoke, heat and toxic fumes are the main obstacles to safe evacuation of a building or area. A major contribution towards overcoming these hazards is the

More information