Construction Drawings and Terminology for the Infection Prevention Professional. Objectives. Disclaimer
|
|
- Merry Beasley
- 8 years ago
- Views:
Transcription
1 Construction Drawings and Terminology for the Infection Prevention Professional APIC Greater St. Louis Chapter 073 October 2012 Objectives Define the terms and descriptions of airborne engineering controls Visualize what is occurring in each engineering control to better understand the applications Discuss proactive planning, design and construction of patient care environments with engineers, architects and contractors Review IP evaluation of construction projects, both large and small Disclaimer Drawings, figures, pictures and sketches and name usage are for illustrative and educational purposes only Use of these is should not be considered as endorsement, recommendation or support This program is for educational purposes only 1
2 Definitions Airborne Engineering Controls Negative Pressure Laminar Flow Positive Pressure HEPA CFM ACH Constant Volume VAV FCU Plenum HVAC AHU Other Good Terms to Know Chase RFI CCD MEPFP Riser Stack Ventilation Issues Airborne transmission of disease has been a problem since mankind has lived indoors. Sunlight (UV radiation) kills most microbes that cause disease in humans. Many respiratory pathogens have adapted to our comfortable indoor environments, escaping deadly sunlight. 2
3 The HVAC System Heating Ventilation and Air Conditioning Specialized field of engineering Healthcare facilities are environments of controlled hazards Ventilation, humidity, aerosolized pharmaceuticals, airborne contagions, chemical handling Airborne Engineering Controls Functions of the HVAC system Dilution ventilation Contaminant exhaust Directional airflow control Filtration Environmental temperature control Relative humidity control Airborne Engineering Controls Air pressure differential is a measurable quantity Airflow is measured in cubic feet per minute (CFM) CFM is a standard measure of airflow How many cubic feet pass a stationary point in one minute Higher CFM = more air 1 CFM approximately 2 liters per second 3
4 Negative Pressure Supply < exhaust Higher exhaust pulls air into room Air flow differential rate 100 CFM SUPPLY EXHAUST NEGATIVE PRESSURE (SUPPLY<EXHAUST) LOCAL EXHAUST SUPPLY EXHAUST NEGATIVE PRESSURE (SUPPLY<EXHAUST) LOCAL EXHAUST 4
5 Negative Pressure Room Identification 5
6 NEGATIVE PRESSURE Supply < exhaust Supply = 300 cfm Exhaust = 400 cfm Negative pressure Supply < Exhaust 300 CFM 400 CFM Laminar Air Flow Used in clean rooms Air makes single pass through room Air enters room through filter (HEPA) Exhausted through walls or floor Vertical Horizontal Requires higher airflow exchange rates than negative, positive or neutral pressure 6
7 Terminology HEPA High efficiency particulate air filter HEPA filters have minimum removal efficiencies of 99.97% or higher with particulates > 0.30 microns Filter bacteria, mold and viruses Viruses can be 0.01 microns usually attach to larger particles Average diameter, microns Kowalski et al. HPAC, July 1998, p 35. Vertical Laminar Air Flow Best control of clean working environment Supply through diffusers on ceiling Airborne contamination from personnel or procedure immediately exhausted out 7
8 SUPPLY HEPA FILTER EXHAUST EXHAUST Horizontal Laminar Air Flow Supply through wall on one side of room Exhaust through ceiling or wall on other side of room May have some downstream contamination in direction of air flow Equipment required (HEPA, ductwork, etc.) may result in cost savings SUPPLY HEPA FILTER EXHAUST 8
9 Positive Pressure Protective Environment Air flow goes from clean to dirty 95% Efficiency Filter Supply > exhaust Higher supply rate pushes air out Air flow differential rate 100 CFM SUPPLY WITH 95% FILTER EXHAUST POSITIVE PRESSURE (SUPPLY>EXHAUST) LOCAL EXHAUST Supply Air > exhaust Supply Air 500 CFM Exhaust 400 CFM Supply > exhaust by 100 CFM 9
10 Terminology ACH Air changes per hour Different rooms have different ACH requirements Operating rooms and delivery rooms require 25 ACH minimum Nurseries, ED triage and Airborne Infection Isolation rooms require 12 ACH minimum Patient rooms, physical therapy, laboratory require 6 ACH minimum (2003 ASHRAE HVAC Design Manual for Hospitals and Clinics; pp ) Terminology Air based HVAC (Heating, ventilation and airconditioning) have two basic categories, variable air volume (VAV) and constant volume Constant volume used when pressure differential required like in OR and lab VAV used when pressure differential doesn t need to be controlled like in hallways Terminology AHU / Air handling unit Part of the HVAC system Large metal box with blowers, heating and or cooling elements, filter racks etc Usually connects to ductwork to distribute air to building and return to AHU 10
11 Terminology FCU Fan coil unit Below window unit that moves room air Provides either heating or cooling May be located other than below window 11
12 Terminology Plenum space provided for air circulation for HVAC Typically above a suspended ceiling to structural deck above May also contain cables, pipes, etc Proper barriers are required in plenum to deck above 12
13 Terminology Chase - A vertical or horizontal shaft in a wall for mechanical, electrical, pipes, duct and conduit to pass through. Chases are usually fire rated Suitable barrier since penetrations are sealed Terminology RFI Request for information usually a clarification of something shown on the drawings ASI - Architect s supplemental instruction a response to the RFI CCD Construction change directive signed by the owner and architect, document becomes effective immediately MEPFP Mechanical, electrical, plumbing and fire protection 13
14 Terminology Stack vertical pipes for the plumbing waste system Three sections Soil stack carries waste from toilets Waste carries waste from all other fixtures Vent Provides air circulation throughout the waste system and allows release of sewer gas Risers pipes leading from the water supply to the fixtures PLUMBING STACKS Waste Stack Soil Stack Vent 14
15 15
16 Construction Drawings 16
17 17
18 18
19 Infection Prevention and Construction Planning Early involvement is key Recommended by American Institute of Architects (AIA), American Society of Heating, Refrigeration and Air-Conditioning (ASHRAE), APIC Input in initial planning Approval during design phase Walk through with contractor prior to work Infection Prevention and Construction Planning Patient risks Worker risks Intra-construction monitoring HEPAs Negative Pressure Walk off mats Debris removal Authority to close job down (check your policy) 19
20 Things To Look For 20
21 21
22 22
23 23
24 Revised 10/07 Start Date: Project Name: Step 5 - Sign and authorize risk End Date: Project Location: Step 3 - Find Precaution Level: assessment below Step 1 - Choose Step 2 - Choose Step 4 - Color level of project: Step 6 - Return to Infection work area: type of work: Control - Addresses below 1 - Work Area 1 - Work Area 2 - Type of Work 3 - Infection Control Precautions 3 - Infection Control Precautions 1 4 A GREEN ORANGE Non-Physician Offices Endo / DDCC Non-invasive, inspection, wallcovering, 1A, 2A, 3A, 5A, 6A, 6B, 6C, 6D 4A, 3B, 2C, 5C 2 CSPD electrical trim, minor plumbing *Ceiling tile sprayed with bleach to GREEN and In addition cafeterias Pharmacy NO sanding, wall cutting or dust prior to displacing, replaced YELLOW precautions; Kitchens, Main CAM fl.1,6,10,11,12** AND all satellites generation at all immediately after visual inspection. *Infection Control consulted 4400, 7200 B * Visitor and patient traffic routes * Dust minimized - partitions 6300, 6400 Dialysis Small scale, short duration, minimal should avoid work area. erected to deck above. 7300, 7400, 7500 ALL ORs dust generation. Including but not * Clean supplies transported and * Optimal: Chute for debris removal, 10100, Perfusion, limited to; cables or wires above ceilings, stored away from contaminated with HEPA filter or see Card Cath 11100, All ICUs and CCUs accessing chase spaces, wall cutting, materials. YELLOW elevator guidelines , Chemo Center ceiling penetrations where dust can * Water interruption scheduled * Barriers - dampers closed, assure 12100, All nurseries be controlled during times of low activity. adjacent air filters functioning, 13100, , 5400 C YELLOW airtight plastic or drywall barriers 14400, Work that generates moderate to high 1B, 1C, 2B, 5B from floor to ceiling, seams sealed 15300, 15400, Radiation Oncology levels of dust, removal or demolition of In addition to GREEN precautions; with duct tape or ECUs - NOTE Gamma Knife fixed building components or * Mist work surfaces when cutting barriers must be removed carefully CAM fl. 4,7,8** assemblies, including but not *Air vents or returns blocked and to minimize dust generation. Barriers 3 limited to; Center, 3200, 5900 sanding walls, removing floorcovering, sealed - Facilities Engineering to be disposed of with other debris. Wound CDL Admitting, ED 6900, 7900 ceiling tiles and casework, new wall to evaluate - If air handler supplies *Negative pressure in const. area Pulmonary Rehab 8100, 9400 construction, minor duct or electrical construction area only, it should be with HEPA filters Resp Care, Lab 89ICU & PICRU work above ceilings, major cabling or shut down *Increase air filter changing. PACU, Shukar, SDSA Bronch, MPC wiring activities, or anything that cannot (monitor filters during contruction * Vents cleaned prior to occupancy All Radiology and CT 5 be completed within a single work and change if necessary) * Water lines at site and adjacent Physical Therapy near shift. *1 room areas to have walls areas flushed prior to occupancy Outside from floor CAM fl. 2,3,5,13,14** air intakes <75ft to ceiling, door closed, frame and *Outside demolition >75 feet from D 2100, 6200, construction. door duct taped. air intakes. Major demolition or 7100, 71OU away Including but not limited to; activities *Debris removed Outside from in covered, sealed RED Nuclear Medicine air intakes > 75 ft which require consecutive work shifts, or taped containers, use service 4B, 3C, 4C, 1D, 2D, 3D, 4D, 5D 9100, 9200 heavy demolition or removal of elevators or non patient elevator. In addition to GREEN, YELLOW and 10100, 10200, complete cabling or wiring systems, * Walk-off mats at entrance ORANGE precautions; 4900, 5200 new construction. *Penetrations in walls not open for *Infection Control consulted Ultrasound NOTE: DAMAGED STEP 5 > 4 hours. Cover w/ plastic and *Patients relocated to remote area ASBESTOS FOUND Date tape if more. away from construction. WILL BE ABATED Contractor *Ceiling tiles ** Listings for areas replaced ASAP, if not specifically OR ENCAPSULATED I am aware open >4 hours, must be covered. of and will enforce STEP 6 covered in work PER Infection Control precautions required to Infection areas Please send Control ENVIRONMENTAL for this project. Elevator(s) approved for debris removal Fax HEALTH AND ler1631@bjc.org mailstop SAFETY POLICY BJH/WUSM Project Manager After Hours/weekend pager A Good Idea! 24
25 INFECTION PREVENTION NOTES THIS PROJECT WILL REQUIRE G.C. TO FILL OUT DAILY (ILSM) INTERIM LIFE SAFETY MANAGEMENT SHEETS. ALL WORK AREAS UNDER CONSTRUCTION MUST BE SEALED OFF FROM ADJACENT AREAS. NEGATIVE PRESSURE MUST BE MAINTAINED AT ALL TIMES IN CONSTRUCTION AREAS. ALL DEBRIS LEAVING CONSTRUCTION AREAS FOR DUMPSTER MUST BE COVERED W/ DAMP COVER & CART WIPED DOWN PRIOR TO LEAVING. CONTRACTOR TO MAINTAIN WET MAT, WALK-OFF MAT, BARRIER, & DRY MAT AT ALL CONSTRUCTION ENTRANCES. WALK-OFF MATS TO BE CHANGED HOURLY MIN. OR AS NEEDED. REFER TO TYP. ROOM LAYOUT DETAIL 10/A7. G.C. TO INSTALL OWNER FURNISHED CONSTRUCTION PATIENT ROOM ENTRY DOORS. Summary Have a basic understanding of construction drawings Speak the same language Maintain visibility In house as well as outside contractors Don t be afraid to ask questions Stay involved References 2003 ASHRAE HVAC Design Manual for Hospitals and Clinics AIA Guidelines for Design and Construction of Health Care Facilities Bartley JM. APIC State-of-the-Art Report: The role of infection control during construction in health care facilities. AJIC; April 2000 :
26 Loie Ruhl, RN, BS, CIC Barnes-Jewish Hospital 4901 Forest Park Avenue Mailstop St. Louis, Missouri Questions???? 26
Infection Control Risk Assessment Matrix of Precautions for Construction & Renovation
Infection Control Risk Assessment Matrix of Precautions for Construction & Renovation Step One: Using the following table, identify the Type of Construction Project Activity (Type A-D) TYPE A TYPE B TYPE
More informationInfection Control Risk Assessment Matrix of Precautions for Construction & Renovation
Infection Control Risk Assessment Matrix of Precautions for Construction & Renovation Step One: Using the following table, identify the Type of Construction Project Activity (Type A-D) TYPE A TYPE B TYPE
More informationSTATEMENT OF WORK (SOW) 2. Contract Title. HEPA Supply/Exhaust fans for Clean room USP 797 Compliance
1. Contracting Officer s Representative (COR). STATEMENT OF WORK (SOW) Name: Oscar Garcia Section: Engineering Address: 3350 La Jolla Village Dr. 92161 Phone Number: Fax Number: E-Mail Address: Oscar.garcia2@va.gov
More informationCSA Z317-13-12 Infection Control during Construction, Renovation and Maintenance of Health Care Facilities Overview and Case Studies
CSA Z317-13-12 Infection Control during Construction, Renovation and Maintenance of Health Care Facilities Overview and Case Studies Grant Rogers, BSc. Principal 1 North West Environmental Group Industrial
More informationDESERT RESEARCH INSTITUTE MOLD ASSESSMENT AND REMEDIATEION PROCEDURE
1.0 Introduction DESERT RESEARCH INSTITUTE This Desert Research Institute (DRI) Mold Assessment and Remediation Procedure was established to assure that consistent and uniform information is provided to
More informationInfection Control Risk Assessment : the Infection Preventionist s Role in Construction
Infection Control Risk Assessment : the Infection Preventionist s Role in Construction Key Concepts Use of ICRA is an important element in an infection prevention program Should be an integral part of
More informationWATER DAMAGE INVESTIGATION. Massachusetts Department of Public Utilities 1 South Station Boston, Massachusetts
WATER DAMAGE INVESTIGATION Massachusetts Department of Public Utilities 1 South Station Boston, Massachusetts Prepared by: Massachusetts Department of Public Health Bureau of Environmental Health Indoor
More informationNADCA GENERAL SPECIFICATIONS FOR THE CLEANING OF COMMERCIAL HEATING, VENTILATING AND AIR CONDITIONING SYSTEMS
NADCA GENERAL SPECIFICATIONS FOR THE CLEANING OF COMMERCIAL HEATING, VENTILATING AND AIR CONDITIONING SYSTEMS National Air Duct Cleaners Association 1518 K Street, N.W. Suite 503 Washington, DC 20005 (202)
More informationHow to Estimate the Cost of a. Laboratory Renovation. Candidate Number: 0714144
How to Estimate the Cost of a Laboratory Renovation Candidate Number: 0714144 December 15, 2014 1 Table of Contents Cover Page Page 1 Table of Contents Page 2 Introduction Page 3 Types & Methods of Measurements
More informationQuestions & Answers (Q & A) Regarding Asbestos Treatment with the Fire Suppression and Renovation Project
Questions & Answers (Q & A) Regarding Asbestos Treatment with the Fire Suppression and Renovation Project The Watergate Community is currently in the process with the fire suppression and interior renovations
More informationASBESTOS MANAGEMENT PROGRAM
ASBESTOS MANAGEMENT PROGRAM Prepared By: Triumvirate Environmental Program Approval Developed: August 2011 Updated: June 2015 Associate Vice President of Public Safety & Administrative Services Date Associate
More informationSECTION 23 01 30.51 HVAC AIR-DISTRIBUTION SYSTEM CLEANING
SECTION 23 01 30.51 HVAC AIR-DISTRIBUTION PART 1 - GENERAL 1.1 SUMMARY A. Section includes cleaning of interior surfaces of HVAC equipment. The HVAC equipment cleaning work includes the following: 1. Air
More informationGuidelines for Mold Remediation (Removal)
Guidelines for Mold Remediation (Removal) Indoor mold growth, water damage, or musty odors should be addressed quickly. Removing mold growth and correcting the underlying cause of water accumulation can
More informationDESIGN AND INSTALLATION OF RESIDENTIAL FLEXIBLE DUCTWORK SYSTEMS
DESIGN AND INSTALLATION OF RESIDENTIAL FLEXIBLE DUCTWORK SYSTEMS A. SCOPE 1. This information is intended to assist contractors, installers and code officials in the proper design and installation of flexible
More informationCONTROL METHODS. There are five ways to control the release of asbestos fibers:
Control Methods CONTROL METHODS When asbestos containing materials are found in a building, the owner must decide which method or methods will be used to deal with the asbestos. The decision will be based
More informationSection # Medical Advisory Committee Charlton Campus West 5th Campus King Campus
Hamilton Hospitals Infection Prevention & Control Effective at Hamilton Health Sciences, St. Joseph s Healthcare (This is a Hamilton Region Infection Control policy and procedure.) St. Joseph s Healthcare
More informationTerms of Reference Air Handling Unit (HVAC System) Cleaning
Terms of Reference Air Handling Unit (HVAC System) Cleaning Introduction General cleaning of the air handling units is currently undertaken by the Mechanical Division staff composing of 3 personnel. Cleaning
More informationRadford University. Indoor Air Quality Management Plan
Radford University Indoor Air Quality Management Plan Spring 2015 Introduction Concerns with Indoor Air Quality (IAQ) have increased since energy conservation measures were instituted in office buildings
More informationMold Response and Remediation Plan
1.0 Policy Statement The University of New Haven has developed a mold response and remediation plan in accordance with best practices set forth by the Environmental Protection Agency (EPA), Occupational
More informationSubpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,
4658.4500 PLUMBING SYSTEMS; NEW CONSTRUCTION. Subpart 1. Installation. All plumbing systems must be installed and tested according to this chapter and chapter 4715, the Minnesota Plumbing Code. Subp. 2.
More informationBasics of HVAC Cleaning
Basics of HVAC Cleaning Seminar Outline Residential 1. Types of systems used and why 2. Types of air distribution systems 3. System components 4. Determining the need for cleaning (ACR2002) 5. Project
More informationMOLD RESPONSE AND REMEDIATION PLAN
MOLD RESPONSE AND REMEDIATION PLAN Prepared By: Triumvirate Environmental Developed: April 2011 Last Revised: March 2015 Program Approval Associate Vice President of Public Safety & Administrative Services
More informationAsbestos in the Workplace: A Guide to Removal of Friable Asbestos Containing Material
Asbestos in the Workplace: A Guide to Removal of Friable Asbestos Containing Material Revised November 21, 2013 Application Code of Practice Where asbestos is present or believed to be present in a workplace
More informationHVAC Checklist - Long Form
HVAC Checklist - Long Form Page 1 of 14 Appendix B discusses HVAC system components in relation to indoor air quality. utside Air Intake Location pen during occupied hours? Unobstructed? Standing water,
More informationINDOOR AIR QUALITY ASSESSMENT MOLD INVESTIGATION. Department Of Children and Family 810 Memorial Drive Cambridge, Massachusetts
INDOOR AIR QUALITY ASSESSMENT MOLD INVESTIGATION Department Of Children and Family 810 Memorial Drive Cambridge, Massachusetts Prepared by: Massachusetts Department of Public Health Bureau of Environmental
More informationAsbestos Work Permit Procedures
These procedures are to be followed by all persons required to perform the following work: Handling, installation or removal of non-friable manufactured products known to contain asbestos provided no sanding,
More informationControlling Condensation On CWP Insulation BY ED LIGHT, MEMBER ASHRAE; JAMES BAILEY, P.E., MEMBER ASHRAE; AND ROGER GAY
This article was published in ASHRAE Journal, Decemeber 2014. Copyright 2014 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without
More informationASBESTOS SCIENCE TECHNOLOGIES, INC.
ASBESTOS SCIENCE TECHNOLOGIES, INC. P.O. Box 505 Bangor, CA 95914 Phone (530) 518-0934 Email - astinc17@yahoo.com Report for Lincoln Elementary School 1582 Lincoln Road Yuba City, Ca. 95993 Mold Report
More informationUAMS Representative: The person who is most directly responsible for aspects on location where renovation and construction will occur.
UAMS ADMINISTRATIVE GUIDE NUMBER: 11.2.08 DATE: 5/21/2002 REVISION: 10/03/2005, 09/18/2008, 10/05/2011, 07/10/2013 PAGE: 1 of 15 SECTION: CAMPUS OPERATIONS AREA: GENERAL SUBJECT: INTERIM LIFE SAFETY MEASURES
More informationIEQ Management Plan. Denver Museum of Nature and Science ECF Addition
IEQ Management Plan GH Phipps Construction Companies 5995 Greenwood Plaza Blvd., Suite 100 Greenwood Village, Colorado 80111-4710 303.571.5377 PHONE www.ghphipps.com Denver Museum of Nature and Science
More informationUNIVERSITY OF TOLEDO
UNIVERSITY OF TOLEDO SUBJECT: INTERIM LIFE SAFETY MEASURES AND INFECTION Procedure No: LS-08-008 CONTROL PROCEDURE STATEMENT Interim life safety and infection control measures will be implemented to protect
More informationPreparing the Work Area
Preparing the Work Area Work Area Preparation Objectives of Work Area Prep Sequence and Methods for Prep Engineering Controls: Negative Pressure Requirements, Equipment and Set-up Purpose of Area Prep
More informationBUILDING DYNAMICS, LLC
BUILDING DYNAMICS, LLC www.building-dynamics.com INDUSTRIAL HYGIENE 1216 Ashton Road Ashton, MD 20861 240.899.6926 (mobile) elight@building-dynamics.com HVAC ENGINEERING 703.963.0824 (mobile) jbailey@building-dynamics.com
More informationUNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01
GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per
More informationPresented by Harlan Nelson 952-237-4644 Harlan.nelson@comcast.net
Construction Risk Assessment Presented by Harlan Nelson 952-237-4644 Harlan.nelson@comcast.net Statistics to Consider Hospital acquired infections Over 100,000 deaths per year Majority are failure to comply
More informationGlossary of HVAC Terms
Glossary of HVAC Terms Heating, Ventilation and Air Conditioning (HVAC) is a major sub- discipline of mechanical engineering. The goal of HVAC design is to balance indoor environmental comfort with other
More informationHVAC Systems and Indoor Air Quality. Douglas K. Spratt, M.Sc., P.Eng.
HVAC Systems and Indoor Air Quality Douglas K. Spratt, M.Sc., P.Eng. The 5 Senses Architecture Electrical Structural Mechanical Hearing Seeing Smelling Feeling Tasting HVAC Systems are Dynamic Heat Gains
More informationBUILDING ASSESSMENT QUESTIONNAIRE. B. TENANTS Is there more than one tenant in the building? YES
Department of Health and Human Services, Division of Public Health Occupational and Environmental Epidemiology Branch 1912 Mail Service Center, Raleigh, North Carolina 27699-1912 BUILDING ASSESSMENT QUESTIONNAIRE
More informationHEPA-filtered Negative Air Machines and their Role in Creating Airborne Infection Isolation Rooms with the ECU AnteRoom. Frequently Asked Questions
HEPA-filtered Negative Air Machines and their Role in Creating Airborne Infection Isolation Rooms with the ECU AnteRoom Frequently Asked Questions What is a negative air machine and why do I need one?
More informationWater Incursion Standard Operating Procedure
Water Incursion Standard Operating Procedure Purpose: To provide a standardized procedure in the event of water incursion into any Penn State University facility. References: A Brief Guide to Mold, Moisture
More informationGramercy Place Condo Association, Inc.
Gramercy Place Condo Association, Inc. UNIT MODIFICATION REQUEST Date of Application: Name of Owner (s): Telephone: (Home) (Cell) E-Mail: Anticipated start date: Anticipated ending date: Permission is
More informationASTACEA4 Inspect complex/central air conditioning systems
Overview This Unit covers the competences required to inspect complex/central air conditioning systems as defined by the CIBSE TM 44 Figure 1.1: Summary of system types and their component parts. The air
More informationGlossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
More informationWater should be removed as soon as possible once the safety of the structure has been verified.
FACT SHEET Posted October 18 2005 Check List for Infection Control Concerns when Reopening Healthcare Facilities Closed due to Extensive Water and Wind Damage Prior to opening a healthcare facility that
More informationMarch 2007. Get The Mold Out: Mold Clean-Up Guidance for Residences. Introduction
March 2007 Connecticut Department of Public Health Environmental Health Section Environmental & Occupational Health Assessment Program 410 Capitol Avenue MS # 11EOH, PO Box 340308 Hartford, CT 06134-0308
More informationSECTION 00 0110 TABLE OF CONTENTS. H. 00 2115.01 - Proposed Material, Product or Equipment Substitution Request
SECTION 00 0110 PROCUREMENT AND CONTRACTING REQUIREMENTS 1.1 DIVISION 00 -- PROCUREMENT AND CONTRACTING REQUIREMENTS A. 00 0101 - Project Title Page B. 00 0105 - Certifications Page C. 00 0110 - Table
More informationPEOSH. Indoor Air Quality Training for Asthma-Friendly Schools Part I PEOSH Indoor Air Quality Standard Overview. Eric Weren, MSIH
PEOSH Indoor Air Quality Training for Asthma-Friendly Schools Part I PEOSH Indoor Air Quality Standard Overview Eric Weren, MSIH Public Employees Occupational Safety and Health Unit IAQ Asthma-Friendly
More informationKEY ELEMENTS IN PREVENTING AND MITIGATING MOLD CLAIMS
KEY ELEMENTS IN PREVENTING AND MITIGATING MOLD CLAIMS By Jerome E. Spear, CSP, CIH Effective January 1, 2005, consultants who prepare mold management plans for buildings located in Texas must be licensed
More informationHOSPITAL ISOLATION ROOM HVAC SYSTEM DESIGN
HOSPITAL ISOLATION ROOM HVAC SYSTEM DESIGN Presented to: ASHRAE YEA Illinois Chapter Specialty Environment Design Conference March 24, 2014 Jean O. Gibbons, PE, LEED AP Senior Vice President Grumman/Butkus
More informationGet The Mold Out: Mold Clean-Up Guidance for Residences. Introduction
Connec cut Department of Public Health Environmental & Occupa onal Health Assessment Program Environmental Health Sec on 410 Capitol Avenue, MS # 11EOH, PO Box 340308 Har ord, CT 06134-0308 Telephone:
More informationAll substantial design decisions and budget confirmation shall be resolved for the College to approve the Design Development Submittal.
2.02 DESIGN DEVELOPMENT PHASE GENERAL The Architect shall prepare the Design Development Documents from the approved Schematic Design. The Design Development Documents shall consist of drawings and other
More informationDUST AND DEBRIS MANAGEMENT PROCEDURES HPD HOUSING REHABILITATION PROGRAMS
DUST AND DEBRIS MANAGEMENT PROCEDURES HPD HOUSING REHABILITATION PROGRAMS Dust and Debris Management Procedures refers to preventive measures that shall be undertaken by the contractor to prevent exposure
More informationQuality Assurance Calendar Maintenance Responsible Party Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Generator fire up Generator 1 hour load test Generator 4 hour load test Fire extinguisher integrity checks Fire extinguisher certification Fire drills Fire door integrity Fire signage lighting Fire alarm
More informationENHANCED LABORATORY HVAC SYSTEM
ENHANCED LABORATORY HVAC SYSTEM INTRODUCTION Since the early 1980's the attention to more energy efficient laboratory designs has been on the rise due to the increase in energy cost and the emergence of
More informationOld Dominion University Mold Management Plan
OFFICE OF ENVIRONMENTAL HEALTH AND SAFETY 5255 Hampton Blvd. Spong Hall, suite 2501 Norfolk, Virginia 23529 Phone: (757) 683-4495 Fax: (757) 683-6025 Occupational Safety & Health Environmental Health Laboratory
More informationWalkthrough Inspection Checklist
Walkthrough Inspection Checklist This checklist is to aid during an IAQ Walkthrough of the school. The checklist includes considerations both inside and outside the school building: Instructions: 1. Read
More informationGuidelines for Cleaning Staff on Managing Mould Growth in State Buildings
Guidelines for Cleaning Staff on Managing Mould Growth in State Buildings Prepared by the State Claims Agency 2 Index 1. Background 2. What are moulds? 3. What are the possible health effects? 4. How do
More informationPROPERTY INSPECTION OR ASSESSMENT OF DAMAGES
PROPERTY INSPECTION OR ASSESSMENT OF DAMAGES ADDRESS: 123 MAIN ST MIAMI, FL CLIENT: BUYER ID No: 2014193 DATE: 5/13/2014 INSPECTION OR ASSESSMENT BY: GAIA CONSTRUCTION INC. CGC 1516136 FLORIDA HI-2792
More informationConstruction Indoor Air Quality Management Plans for LEED. Matt Gregg, PE, LEED AP
Construction Indoor Air Quality Management Plans for LEED Matt Gregg, PE, LEED AP Agenda What is a Construction IAQ Management Plan? What are the LEED Requirements? What is the Mechanical Contractor s
More informationSTANDARD OPERATING PROCEDURES FOR MOLD REMEDIATION
West Virginia University Environmental Health and Safety STANDARD OPERATING PROCEDURES FOR MOLD REMEDIATION Origination Date August 2013. Contents Purpose:... 2 Job Scope... 2 Definitions... 2 Roles/Responsibilities:...
More informationEnvironmental Monitoring
Chapter 10 Environmental Monitoring By the end of this chapter, you will be able to: l List the types of environmental testing l Name three types of checks that are carried out to ensure the isolator is
More informationThis permit does not include replacement or upgrading of the existing electrical panel or service (a separate electrical permit must be obtained).
CITY OF MILPITAS Building & Safety Department 455 E. Calaveras Blvd. Milpitas, CA 95035 408-586-3240 www.ci.milpitas.ca.gov RESIDENTIAL AIR CONDITIONING, REPLACEMENT 1. PERMIT INFORMATION: The replacement
More informationMechanical Systems Proposal revised
Mechanical Systems Proposal revised Prepared for: Dr. William Bahnfleth, Professor The Pennsylvania State University, Department of Architectural Engineering Prepared by: Chris Nicolais Mechanical Option
More information4 Installation Requirements
4 Installation Requirements 9 4.1 Code Reference The authority having jurisdiction should be referenced to determine what law, ordinance or code shall apply in the use of flexible duct. Ducts conforming
More informationMold and Mildew Mold and mildew can be detected by sight, smell and touch.
Mold and Mildew Mold and mildew can be detected by sight, smell and touch. Molds are usually black (not unlike the molds that grow in showers and between grout), green or tan in color, but can be in various
More informationThere are several types of air cleaning devices available, each designed to remove certain types of pollutants.
Please Note: EPA neither certifies nor recommends particular brands of home air cleaning devices. While some home air cleaning devices may be useful in some circumstances, EPA makes no broad endorsement
More informationHome Energy Evaluation Report for Fritz Kreiss and Catherine McQueen
Home Energy Evaluation Report for Fritz Kreiss and Catherine McQueen May 2008 Wisconsin Area PO BOX 115 Lake Geneva, WI 53147 CELL (414) 550-4765 Home Performance with ENERGY STAR Evaluation Report Customer
More informationIndoor Air Quality Issues for Hotels
Indoor Air Quality Issues for Hotels Chai chen Chao DEA 670 Spring, 2000 Thermal Control Relative Humidity Winter Temperature Summer Temperature 30% 68.5 F - 76.0 F 74.0 F - 80.0 F 40% 68.5 F - 75.5 F
More informationAsbestos Abatement Work Plan for the Carter Carburetor Superfund Site
for the Prepared for: ACF Industries LLC 101 Clark Street St. Charles, Missouri 63301 Prepared by: AMEC Environment & Infrastructure, Inc. 15933 Clayton Road, Suite 215 Ballwin, Missouri 63011 Project
More informationAttachment #23 Health Safety Table. Client Education Inform issue and document. How to clean & maintain gutters. How to adjust sprinklers
Exterior Visual Health & Safety Issue Allowable Action Site Drainage Exterior grade does not slope 2% within the first 10' Site drainage causing bulk moisture in crawl space or basement Repairs to existing
More information2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT
Presentation Synopsis Heating, Ventilating and Air Conditioning Building Condition Assessment Vancouver, B.C. Prepared for: EPIC Prepared by: Douglas Spratt, P.Eng Douglas Spratt & Associates Ltd. www.dspratt-associates.com
More informationDUCT CLEANLINESS FOR NEW CONSTRUCTION GUIDELINES
DUCT CLEANLINESS FOR NEW CONSTRUCTION GUIDELINES Sheet Metal and Air Conditioning Contractors National Association, Inc. 4201 Lafayette Center Drive Chantilly, VA 20151-1209 DUCT CLEANLINESS FOR NEW CONSTRUCTION
More informationEVERYONE'S RESPONSIBILITY
EVERYONE'S RESPONSIBILITY Guidelines for an Asbestos Operations and Maintenance Program February 2007 Guidelines for an Asbestos Operations and Maintenance Program Workplace Safety & Health Division 200
More informationIEQ-15 Air Distribution System
AIM OF CREDIT To encourage and recognise the design and maintenance of air distribution systems that minimise the risk of particulate and microbial contamination to the internal air supply. CREDIT CRITERIA
More informationHVAC INSTALLATION SUCCESS WITH 2012 IECC DELAWARE. for Builders & Trades. Recommended Practices for Optimized Energy Savings
SUCCESS WITH 2012 IECC DELAWARE Recommended Practices for Optimized Energy Savings for Builders & Trades COPYRIGHT 2015 ADVANCED ENERGY. ALL RIGHTS RESERVED VERSION 2015.1.0 CHECKLIST: JOB READY 1. 2.
More informationUBC Plant Operations Asbestos Work Procedures April 2004
UBC Plant Operations Asbestos Work Procedures April 2004 These Procedures are for use by UBC Plant Operations, Utilities, Housing & Conferences, and IT Services only and are not intended for use by other
More informationNDSU TABLE OF CONTENTS
NDSU TABLE OF CONTENTS 1.0 INTRODUCTION 2.0 DEFINITIONS AND DESCRIPTIONS 3.0 OPERATIONS AND MAINTENANCE PROCEDURES FOR ACM 4.0 FIBER RELEASE EPISODES 5.0 DEMOLITION INFORMATION 6.0 REMARKS 1.0 INTRODUCTION
More informationRisk Bulletin. Mold Prevention and Control for Mechanical and HVAC Contractors. XL Group Insurance
XL Group Insurance Risk Bulletin Mold Prevention and Control for Mechanical and HVAC Contractors Mechanical contractors have an inherent risk of mold claims arising out of the heating, ventilation, and
More informationHVAC INSTALLATION. Success with 2015 IECC Northeast & Mid-Atlantic. Checklist for Builders & Trades
Success with 2015 IECC Northeast & Mid-Atlantic Checklist for Builders & Trades COPYRIGHT 2015 ADVANCED ENERGY. ALL RIGHTS RESERVED TEMPLATE 2015.1.0 PAGE 1 CHECKLIST: JOB READY 1. 2. 3. 4. 5. 6. 7. 8.
More informationWATER DAMAGE/MOLD INVESTIGATION. Massachusetts Department of Developmental Services 68 North Main Street Carver, Massachusetts
WATER DAMAGE/MOLD INVESTIGATION Massachusetts Department of Developmental Services 68 North Main Street Carver, Massachusetts Prepared by: Massachusetts Department of Public Health Bureau of Environmental
More informationFlexibility, Efficiency In San Antonio Arena
2005, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Reprinted by permission from ASHRAE Journal, (Vol. 47, No. 9, September 2005). This article may not
More informationEssam E. Khalil khalile1@asme.org
AIR-CONDITIONING SYSTEMS DEVELOPMENTS IN HOSPITALS: COMFORT, AIR QUALITY, AND ENERGY UTILIZATION Essam E. Khalil khalile1@asme.org PROFESSOR OF MECHANICAL ENGINEERING, CAIRO UNIVERSITY, EGYPT Abstract
More information2012 Operating Room Design Manual
CHAPTER 9 ROOM VENTILATION SYSTEMS Lead Author: Kamal Maheshwari, MD, Staff Anesthesiologist, Cleveland Clinic Foundation Checklist 1. Does the ventilation system in your operating room (OR) meet the standards
More informationSummary of Georgia s Lead-Based Paint (LBP) Renovation, Repair and Painting (RRP) Rules For Contractors, Property Managers, and Maintenance Personnel
Second Edition Revised January 2014 Summary of Georgia s Lead-Based Paint (LBP) Renovation, Repair and Painting (RRP) Rules For Contractors, Property Managers, and Maintenance Personnel Summary of Requirements
More informationPresentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks
Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same
More informationDATA CENTERS. Protect Your Best in Class Technology With Ours CLEAN AIR SOLUTIONS
DATA CENTERS Protect Your Best in Class Technology With Ours CLEAN AIR SOLUTIONS COSTLY FAN ENERGY REDUCED BY CAMFIL PREMIUM PRODUCTS = COST SAVINGS Power Usage Effectiveness (PUE) is an important metric
More informationIndoor Environmental Quality Checklist Including Background Information in Comment Section
Department of Employee Relations Indoor Environmental Quality Checklist Including Background Information in Comment Section Building Description Original construction date Renovation dates Number of floors
More informationNational Academy of Forensic Engineers FE ANALYSIS OF LATENT WATER DAMAGE TO BUILDINGS
National Academy of Forensic Engineers FE ANALYSIS OF LATENT WATER DAMAGE TO BUILDINGS July 10, 2005 CHICAGO RENAISSANCE HOTEL How Could Anything So Small Cause So Much Damage? PRESENTED BY PAUL J. HALYARD,
More informationWhy is my air conditioner dripping on my customers?
De-Mystifying HVAC Why is my air conditioner dripping on my customers? By Ron Prager One of the most frequent emergency service requests is a call for an air conditioner leaking water into the store. These
More informationSPECIAL APPLICATIONS
Page 1 SPECIAL APPLICATIONS The protection of microelectronics clean rooms using aspirating smoke detection systems requires special consideration. The physical configuration of the room(s) and the direction
More informationUniversity of Nevada, Reno Facilities Services Department STANDARD OPERATING PROCEDURE. Facilities Maintenance Services
University of Nevada, Reno Facilities Services Department STANDARD OPERATING PROCEDURE Facilities Maintenance Services Indoor Flood Cleanup and Mold Prevention DATE: 6/24/15 REVISED: PURPOSE This University
More informationPlanning For Future Emergencies. Presented by: Rudi Suminski Director of Consulting Services
Planning For Future Emergencies Presented by: Rudi Suminski Director of Consulting Services Goals Supplement your knowledge for when disaster strikes Exchange Information with the group Save you money
More informationMOLD REMEDIATION KEY STEPS
MOLD REMEDIATION KEY STEPS The EPA has developed the following guidelines for mold remediation managers. These guidelines are generally helpful, but we believe an expert in the industry should be consulted
More informationSECTION 23 05 12 GENERAL PROVISIONS FOR HVAC WORK
SECTION 23 05 12 GENERAL PROVISIONS FOR HVAC WORK 1 GENERAL 1.1 GENERAL REQUIREMENTS A. This Section is coordinated with and complementary to the General Conditions and Supplementary General Conditions
More informationVentilation Standard For Health Care Facilities
The following article was published in ASHRAE Journal, October 2008. Copyright 2008 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes
More informationMechanical Heating Ventilation and Air Conditioning Ductwork and Duct Accessories
Basis of Design This section applies to the design and installation of ductwork, air terminal boxes, air outlets and inlets, volume dampers, pressure relief dampers, smoke/fire dampers, and smoke/fire
More informationST. MONICA FOOD PANTRY HOUSTON, TEXAS
PROJECT MANUAL FOR ST. MONICA FOOD PANTRY HOUSTON, TEXAS OWNER: ST. MONICA CATHOLIC CHURCH 8421 W. MONTGOMERY ROAD HOUSTON, TEXAS 77088 ARCHITECT: C SIX ARCHITECTURE, LLC 4606 F.M. 1960 WEST, STE 400 HOUSTON,
More informationAPPENDIX B. EPA s Investigating, Evaluating, and Remediating Moisture and Mold Problems (see EPA website for complete details)
APPENDIX B. EPA s Investigating, Evaluating, and Remediating Moisture and Mold Problems (see EPA website for complete details) Table 1: Water Damage - Cleanup and Mold Prevention Table 1 presents strategies
More informationCHAPTER 4 VENTILATION
CHAPTER 4 VENTILATION SECTION 401 GENERAL 401.1 Scope. This chapter, in conjunction with the building code, shall govern the ventilation of spaces within a building intended to be occupied. Mechanical
More informationHVAC Air Duct Leakage. Eli P. Howard, III Group Director Technical Resources SMACNA
HVAC Air Duct Leakage Eli P. Howard, III Group Director Technical Resources SMACNA Key Variables that Affect the Amount of Leakage Static Pressure Amount of Duct Openings in the Duct Surface Seams, Joints,
More information