Iso Floor Raised Floor System

Size: px
Start display at page:

Download "Iso Floor Raised Floor System"

Transcription

1 Iso Floor Raised Floor System Optimal modularity for Data Centers, Network Operation Centers, etc. in all seismic zones. The bridge shown is the Öresund Bridge between Sweden and Denmark 1

2 Bergvik company facts Bergvik was founded in 1970 Iso Floor raised floors are used by customers such as Cingular, IBM,T- Mobile, Bell South, Digicel, MTN, Telmex, Vivo, American Movil, Vodafone, Vodacom, Celtel, Areeva etc in more than 100 countries around the world Since 1993, Bergvik has been the sole global supplier of raised floors and seismic bracing to Ericsson, the world leading Telecom Network provider Subsidiary in the USA since 2000, customers like AT&T, Bell South, Internap, Hoganas, Rettenmeier etc have seen the advantages. The fully automated 65,000 SF factory in Bergvik, Sweden 2

3 Secure raised floor solutions for your Data Center The right floor should be strong and modular Bergvik, a world-renowned raised floor supplier, offers a series of raised flooring systems engineered for use in all seismic zones. Adapted to accommodate all types of equipment and designed with room to expand, the Bergvik Iso Floor is a flexible, secure and cost competitive solution for your Data Center flooring needs. Proven mechanical strength Bergvik has developed and adapted a series of three different raised floor designs to accommodate all seismic zones. To further verify all structural calculations, we submit the floor and bracing structures to dynamic fullscale laboratory tests in accordance with NEBS GR-63 and NEBS GR

4 Cost saving features using Iso Floor IT Perspective: Only 2 grounding lug points diagonally per room are needed to provide a high potential to the main ground bar. 4

5 Cost saving features using Iso Floor IT Perspective: No additional steel substructures needed for heavy equipment like CRAC air conditioner units, UPS and Rectifiers since floor offers modular loading capabilities, making it easy to add pedestals and steel beams. 5

6 Cost saving features using Iso Floor IT Perspective: Directional air grille panel option forcing more of the cold air directly onto the face of the equipment. 6

7 Cost saving features using Iso Floor Infrastructure Perspective: All floor panels can be removed without effecting the structural-integrity and the stability of the floor. 7

8 Cost saving features using Iso Floor Infrastructure Perspective: Open bottom access for the racks and cabinets can be provided using 1½ inch (38x38mm) square tubing bolted on top of the framework. 8

9 Cost saving features using Iso Floor Infrastructure Perspective: More useable space between pedestals compared to conventional raised floors with 24 spacing

10 Cost saving features using Iso Floor Infrastructure Perspective: As an option we can provide the floor with stepless cable ladder brackets to reduce installation time. 10

11 Cost saving features using Iso Floor Infrastructure Perspective: Optimization of Data Center floor space is possible due to the different panel size option. Up to 25% more equipment on the same room footprint

12 Infrastructure Perspective: Using conventional raised floors, threaded rod tip protection is needed to secure heavy equipment. 12

13 Cost saving features using Iso Floor Infrastructure Perspective: No threaded rod tip protection going down to sub floor is needed 13

14 Infrastructure Perspective: Using conventional raised floors, bridging is needed due to the set 24 spacing between pedestals. 14

15 Cost saving features using Iso Floor Infrastructure Perspective: No bridging needed due to flexible spacing between pedestals. Even heavy transformers or UPS can be transported and mounted by decreasing the space between pedestals. 15

16 Maximum cooling of Blade Servers can be achived by using optional Bergvik solutions 16

17 Iso Floor design for seismic zone 1-2 Reinforced for added strength Bergvik s floor design for NEBS Zone 1 2 offers the same stable construction as our base model but with additional reinforcements to accommodate a higher risk of seismic activity. Strengthened with a 60 x 60 mm pedestal anchored to the sub-floor with steel plate connections between primary and secondary steel sections, the Iso Floor model fulfills the requirements for seismic reliability according to NEBS. This floor has passed both calculated stress as well as dynamic full-scale tests in accordance with NEBS GR-63 and NEBS GR

18 Iso Floor design for seismic zone 3-4 Maximum stability The Bergvik raised floor designed for NEBS Zone 3-4 is the most secure product on the market today. The addition of solid bracing frames anchored to the concrete sub-floor provides the strength and stability to withstand severe seismic activity. This Bergvik raised floor system fulfills all the requirements for seismic reliability according to NEBS. The frames have passed both calculated stress as well as dynamic full-scale tests in accordance with NEBS GR-63 and NEBS GR Floor Heights available in inch (350 to 910 mm). Seismic bracing frames integrated with the raised floor have pre-torqued cross bracing rods, therefore no tightening is needed following an earthquake. 18

19 Iso Floor accessories Panel lifter Pre-cut panels for cable intake Steps, ramps, border fascia, guard rail Ventilated panels Cable ladders and stepless brackets 19

20 High loads on standard panel with minimum permanent deflection due to high e-module Concentrated Load in aisle: P = 1500 lbs (680 kg) gives 0.18 (4.7 mm) temporary deflection P = 2000 lbs (908 kg) gives 0.24 (6.1 mm) temporary deflection Permanent deflection after 5000 times = inch (0.1 mm). Rolling Load, CISCA Test: P = 600 lbs (272 kg) using a 6 diam x 1.5 wide Alathane wheel. Permanent deflection after passes = inch (0.2 mm). 20

21 Standard panel construction and panel options Suitable for most applications, the standard panel consists of a 1½" (38 mm) high density HD particleboard, moistureresistant quality V313. The bottom side is laminated with aluminum. Standard panels weigh only 22 lbs. Flame spread is 20 (class 1) in accordance with ASTM E84 / NFPA 266 / UL 723. As an option we offer a high density, all non-combustible calcium sulphate panel if there are limitations on the amount of combustible materials to be used in accordance with e.g. local building codes. 21

22 Bergvik Laminate finish Extremely wear resistant Easy to clean even the most difficult stains Decor: M335 Granite Direct-laminated without glue, which could work loose. Surface to ground resistivity: < 2x10 11 Ohms at min 40% RH. Other surface finishes such as vinyl, linoleum or carpet tiles are available upon request. Decor: A287 Oak Decor: H817 Alder 22

23 Tapered panel edges Attractive, functional and safe When floor panels are removed and other surrounding panels shift (which will happen), the unique tapered panel edge design of the Iso Floor allows the removed panels to self adjust and go back flush to prevent tripping. The thin edge trim gives the floor an aesthetically pleasing appearance by making the panel edges virtually disappear into the flooring surface, while fully protecting the surface finish edge. 23

24 Features and Benefits: Iso Floor provide high lateral stability, meaning all panels can be removed without the risk of the floor shifting. The free-standing, high stability floor substructure doesn t need walls for support, allowing you to only plan for the space needed today, with room to expand. 25% more room for equipment in your Network Center will save money on the real estate investment. This can be achieved by using Bergvik custom size panels in aisles. Up to 70% less pedestal supports than conventional raised floors will provide lots of space for wiring, cable ladders etc. Removal of all floor panels in equipment aisles are now possible since Bergvik produce custom size panels to your specification. Open bottom access and/or perforated aisle panels allows for maximum cooling of Server racks. Airflow grilles with built-in fans directly in front of server racks can also be provided as an option. Floor panel meets NFPA 75 chapter for fire resistance. Flame spread is 20 (class 1). Test report can be provided upon request. The all-bolted floor structure is sufficiently grounded by only two (2) grounding wires attached in opposite corners of the floor mechanics. A 5 year warranty is what you can expect. 24

25 Iso Floor Technical Data The floor system in general Gross weight: approx. 45 kg/m2 (9.3 lbs/sf) Uniform distributed load, UDL: 5-50 kn/m2 ( lbf/sf) where 7.4 kn/m2 (150 lbf/sf) is used as a standard value Finished floor height, FFH: mm (14 75 inch). Higher than 900 mm, zone 0-2 only. Laminate floor panel specification Material: 38 mm high density particle board, V313 moist resistant quality is standard Panel sizes: 600x600, 600x800, 600x400 mm (23.6 square, 23.6 x31.5, 23.6 x15.8 ) as standard. Custom sizes available. Surface finish: Bergvik direct laminate as standard. Optional surfaces available. 36x24 inch Perforated aisle panel: open area 0.78 sf (0.072 m2). Electrical resistance: >500 kohms and <2 x Ohms at RH min 40%. Color pattern: M335 Granite laminate as standard. H817 Alder is optional. Wear resistance: 4,000-6,000 cycles according to EN 438-2: Color fastness: >6 according to EN 438-2: Weight: 10 kg (22 lbs) for floor panel 600 x 600 mm (23.6 square). Flame spread: 20 In accordance with ASTM E84 or NFPA 266 Cleaning: With vacuum cleaner or dry mop. For difficult stains use citrus cleaner on a buffing pad. Bergvik is an innovative knowledge company specializing in raised floor systems and seismic bracing solutions tailored to our customer's applications. For an Iso Floor Master Specification, please contact us or visit our website. NA Hoganas, PA, USA SAS Flight Academy, Sweden Bergvik Flooring AB Box 46 Vannsätter SE Bergvik, Sweden Tel: info@bergvik.com Web: Bergvik North America, Inc 212 West Main Street, Suite 202-B Salisbury, MD USA Tel: dawn.brandstrom@bergvik.com Web: Cingular Wireless, WA, USA 25 Bergvik Flooring AB Subject to change without notice

Iso Floor. the only dynamic raised floor on the market

Iso Floor. the only dynamic raised floor on the market Iso Floor The dynamic raised floor offering full flexibility, stability and optimization of Racks in Data Centers, Network Operation Centers and Electrical Switchgear Rooms. Iso Floor the only dynamic

More information

Modular Access Floor for Data Center. From Rack to Row to Room to Building

Modular Access Floor for Data Center. From Rack to Row to Room to Building Modular Access Floor for Data Center From Rack to Row to Room to Building Why using Scneider Electric modular access floor in Data Centers The evolution of modern Data Centers emphasizes specific exigencies

More information

MERO Access Floor / Floor systems for data centers * *Ready for Cloud-Computing

MERO Access Floor / Floor systems for data centers * *Ready for Cloud-Computing MERO Access Floor / Floor systems for data centers * *Ready for Cloud-Computing Innovative Komplettlösungen aus einer Hand Innovative solutions from one source Development Access floor Consulting Hollow

More information

Data Center The New Standard in Data Center Design... ASM H-D System

Data Center The New Standard in Data Center Design... ASM H-D System Data Center The New Standard in Data Center Design... ASM H-D System U.S.A. Engineered Products U.S.A. Quality & Testing Global Vision ASM s Enviro Panel: Most widely used panel design in the world ASM

More information

TecCrete. Data Center Flooring

TecCrete. Data Center Flooring TecCrete Data Center Flooring The TecCrete Data Center product is based on Haworth s proven TecCrete access flooring platform. For the last 30 years, it has been the leading choice for architects and developers

More information

More than shelving & racking. All for your storage demands.

More than shelving & racking. All for your storage demands. More than shelving & racking. All for your storage demands. CONTENTS SELECTIVE PALLET RACKING A cost effective storage system providing direct access to all pallet. SLOTTED ANGLE SHELVING Simple, cost-effective

More information

DIGITUS Network & Server Cabinets. UNIQUE Series

DIGITUS Network & Server Cabinets. UNIQUE Series DIGITUS Network & Server Cabinets UNIQUE Series Benefits - Server Rack 4-Point locking system front door 3-point locking system rear door Swing handle lock with profile zylinder in front and rear door

More information

MERO Floor Systems - CleanRoom

MERO Floor Systems - CleanRoom MERO Floor Systems - CleanRoom Innovative solutions out of one hand Development Access floor Consulting Hollow floor Planning Floor covering and Manufacturing Installation Installation Services Floor systems

More information

Doc Ref: 2015.06.01.002. 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC

Doc Ref: 2015.06.01.002. 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC TM 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC TM D400E Data Module (60Hz) The EDGE D400E is designed to meet high power density requirements for both the HPC and Web Scale environments while

More information

A few inches will give your business room to grow...

A few inches will give your business room to grow... A few inches will give your business room to grow... Unitile s Unitile's Wood core product range are made from chipboard particles which are extracted from well managed forests, controlled sources or recycled

More information

LOADING DOCK EQUIPMENT. A. Section 03100 - Concrete Forms and Accessories: Placement of anchors into concrete.

LOADING DOCK EQUIPMENT. A. Section 03100 - Concrete Forms and Accessories: Placement of anchors into concrete. LOADING DOCK EQUIPMENT PART 1 GENERAL 1.1 SECTION INCLUDES A. Loading dock equipment of the following types: 1. Dock lifts. 2. Control stations. 1.2 RELATED SECTIONS A. Section 03100 - Concrete Forms and

More information

Key Considerations for Selecting Server Cabinets for Seismic Areas

Key Considerations for Selecting Server Cabinets for Seismic Areas Key Considerations for Selecting Server Cabinets for Seismic Areas Protect Up to 1500 of Critical Network Equipment without Sacrificing Flexibility Planning a data center in a seismically active area requires

More information

How To Build A T7 Rack For Information Technology

How To Build A T7 Rack For Information Technology THE NEXT GENERATION RACK FOR INFORMATION TECHNOLOGY THE RACK CABINET FOR INFORMATION TECHNOLOGY T7, THE HI-TECH HEART OF THE BLADESHELTER SYSTEM The real answer to the requirements of: Safety Versatility

More information

BLADE S-MAX Cabinet for Blade Server

BLADE S-MAX Cabinet for Blade Server Cabinet for Blade Server 1 2 Overview Material specification Corner verticals: 1.5 mm steel End frames: 1.5 mm steel Panel mounts: 2.0 mm steel Panel mount supports: 1.5 mm steel Side panels, door and

More information

Rittal s Comprehensive Family Of... NETWORK RACK SOLUTIONS

Rittal s Comprehensive Family Of... NETWORK RACK SOLUTIONS Rittal s Comprehensive Family Of... NETWORK RACK SOLUTIONS STANDARD & ECONOMICAL BasicRack A complete low-cost, high-quality basic equipment management system. Design Six web channel holes per side allow

More information

www.access-floors-ltd.co.uk email sales@access-floors-ltd.co.uk Authorized Dealers Access Floors Limited The Studio 15 Huntsmead Northampton NN3 5HT

www.access-floors-ltd.co.uk email sales@access-floors-ltd.co.uk Authorized Dealers Access Floors Limited The Studio 15 Huntsmead Northampton NN3 5HT Authorized Dealers Access Floors Limited The Studio 15 Huntsmead Northampton NN3 5HT Tel No: 01604 409922 www.access-floors-ltd.co.uk email sales@access-floors-ltd.co.uk Uniflair modular access floor -

More information

Cannon T4 Modular Data Centres. For Outside Deployment & Challenging Environments

Cannon T4 Modular Data Centres. For Outside Deployment & Challenging Environments Cannon T4 Modular Data Centres For Outside Deployment & Challenging Environments A high performance, full specification Data Centre, up to Tier 4* resilience, instantly deployable A highly secure Data

More information

SECTION 26 05 49 VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

SECTION 26 05 49 VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS SECTION 26 05 49 VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes seismic restraints and other earthquake-damage-reduction measures for electrical

More information

Knürr DCM. Knürr DCM. 19 Server Rack System 19 Heavy Duty Rack 1.2 to 1.9 1.1

Knürr DCM. Knürr DCM. 19 Server Rack System 19 Heavy Duty Rack 1.2 to 1.9 1.1 Knürr DCM 19 Server Rack System 19 Heavy Duty Rack 1.2 to 1.9 1.1 Knürr DCM conquers the world Standardization in the data center begins with the Knürr DCM! The Knürr DCM is the modular building block

More information

glass & Glazing Products

glass & Glazing Products glass & Glazing Products WallMaker Create an unlimited variety of bright, beautiful and secure interior environments with the easy-to-install Stylmark WallMaker glass wall system. This versatile system

More information

first look at GigaCrete s revolutionary new New Construction GigaHouse GigaHouse Utilizing GigaPanel

first look at GigaCrete s revolutionary new New Construction GigaHouse GigaHouse Utilizing GigaPanel first look at GigaCrete s revolutionary new New Construction GigaHouse GigaHouse Utilizing GigaPanel What is GigaCrete GigaCrete is a family of products based on low carbon footprint Green ceramic binders

More information

Cooling a hot issue? MINKELS COLD CORRIDOR TM SOLUTION

Cooling a hot issue? MINKELS COLD CORRIDOR TM SOLUTION Cooling a hot issue? MINKELS COLD CORRIDOR TM SOLUTION The heat load in data centers is increasing rapidly, the adaptation of a cooling strategy is often necessary. Many data centers and server rooms use

More information

SOHOline and SOHO Slimline The SOHOline and SOHO Slimline offer a modular, sturdy and compact design

SOHOline and SOHO Slimline The SOHOline and SOHO Slimline offer a modular, sturdy and compact design SOHOline and SOHO Slimline The SOHOline and SOHO Slimline offer a modular, sturdy and compact design Ideal installation for; Offices Branch Offices Schools Computer Aided Classes Government Offices Hotels

More information

Cabinets 101: Configuring A Network Or Server Cabinet

Cabinets 101: Configuring A Network Or Server Cabinet Cabinets 101: Configuring A Network Or Server Cabinet North, South and Central America White Paper May 2012 www.commscope.com Contents Background Information 3 What is a network or server cabinet? 3 What

More information

UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS

UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS: Carefully read these instructions before installing your new air-conditioner. AUSTRALIAN AUTOMOTIVE AIR AL00500054E 1 Table

More information

screens U N D E R S TA N D I N G S C R E E N S...9 0 PA N E L WA L L A D D - O N S C R E E N B A S I C S...9 3

screens U N D E R S TA N D I N G S C R E E N S...9 0 PA N E L WA L L A D D - O N S C R E E N B A S I C S...9 3 U N D E R S TA N D I N G S C R E E N S...........................9 0 PA N E L WA L L A D D - O N S C R E E N B A S I C S...................9 3 P L A N N I N G W I T H A D D - O N S C R E E N S.....................9

More information

Product Information. Tel: 905.696.9900 x2426 or x2443 Fax: 905.696.9300 Email: sales@alusion.com

Product Information. Tel: 905.696.9900 x2426 or x2443 Fax: 905.696.9300 Email: sales@alusion.com Tel: 905.696.9900 x2426 or x2443 Fax: 905.696.9300 Email: sales@alusion.com Product Information 6320-2 Danville Rd. Mississauga, Ontario Canada L5T 2L7 TABLE OF CONTENTS Sheet Product Alusion Sheet Products.......................................................

More information

Cardok Sàrl CP37 CH-1295 Tannay Switzerland Phone: 0041 22 77 66 051 info@cardok.com

Cardok Sàrl CP37 CH-1295 Tannay Switzerland Phone: 0041 22 77 66 051 info@cardok.com CARDOK CARLIFT Fast access to underground garages Fast, Silent, Discreet, Design, High-Tech Installation to replace an access ramp on private property Dimensions: (Built to measure, all dimensions can

More information

SECTION 14 20 10 - FREIGHT & PARKING GARAGE ELEVATORS PART I - GENERAL

SECTION 14 20 10 - FREIGHT & PARKING GARAGE ELEVATORS PART I - GENERAL SECTION 14 20 10 - FREIGHT & PARKING GARAGE PART I - GENERAL 1.1 SECTION INCLUDES [NOTE to AE: The following lists requirements that are specific to freight elevators. These requirements are in addition

More information

Cabinet V800 V800 CABINETS

Cabinet V800 V800 CABINETS V800 Cabinet Siemon s V800 cabinets provide a robust, cost-effective enclosure solution that provides valuable Zero-U space on each side of the equipment rails for cable management, PDU mounting or connectivity

More information

The space-saving storage solution.

The space-saving storage solution. The space-saving storage solution. Save space. Make space. Whether your operation is large or small, the demand for increased filing and storage capacity will eventually impact your operations by either

More information

19 DYNAmax Free Standing Server C A B I N E T s

19 DYNAmax Free Standing Server C A B I N E T s 9 DYNAmax Free Standing Server C A B I N E T s 9 DYNAmax Free Standing Server Cabinets FAMILY W=mm and W=800mm DYNAmax Series Free Standing Server Cabinets DYNAmax series Servering Enclosures, provide

More information

CHALKBOARDS, MARKERBOARDS, TACKBOARDS, DISPLAY CASES, AND BULLETIN BOARD CABINETS

CHALKBOARDS, MARKERBOARDS, TACKBOARDS, DISPLAY CASES, AND BULLETIN BOARD CABINETS SECTION 10100 CHALKBOARDS, MARKERBOARDS, TACKBOARDS, DISPLAY CASES, AND BULLETIN BOARD CABINETS PART 1 GENERAL 1.01 SUBMITTALS A. Product Data: Submit copies of manufacturer's technical data and installation

More information

19" Data Racks. Adjustable feet To compensate for uneven floors and assure great stability all feet can be up to 20 mm adjusted.

19 Data Racks. Adjustable feet To compensate for uneven floors and assure great stability all feet can be up to 20 mm adjusted. 19" Data Racks Attractive design and high quality are characteristic. Basic framework is welded from multiple bent metal plate, which assures great rigidity suitable for heavier equipment. All profile

More information

How To Fit A Dll 2420 And 4220 Rack Enclosure

How To Fit A Dll 2420 And 4220 Rack Enclosure DELL BEST PRACTICES GUIDE FOR RACK ENCLOSURES A Dell Technical White Paper PE2420 & PE4220 By Danny Alvarado Dell Data Center Infrastructure THIS WHITE PAPER IS FOR INFORMATIONAL PURPOSES ONLY, AND MAY

More information

8' W x 8' H or 10' H Peak Style Shelter Assembly Instructions

8' W x 8' H or 10' H Peak Style Shelter Assembly Instructions ' W x ' H or ' H Peak Style Shelter Assembly Instructions Description ' x ' x ' Peak Style Shelter - Gray ' x ' x ' Peak Style Shelter - Gray Recommended Tools Please read instructions COMPLETELY before

More information

19 DYNAmax Free Standing Server C A B I N E T s

19 DYNAmax Free Standing Server C A B I N E T s 9 DYNAmax Free Standing Server C A B I N E T s 9 DYNAmax Free Standing Server Cabinets FAMILY W=600mm and W=800mm DYNAmax Series Free Standing Server Cabinets DYNAmax series Servering Enclosures, provide

More information

PRE-ASSEMBLED INSTALLATION INSTRUCTIONS FOR PACB SERIES COAL FIRED OVENS

PRE-ASSEMBLED INSTALLATION INSTRUCTIONS FOR PACB SERIES COAL FIRED OVENS PRE-ASSEMBLED INSTALLATION INSTRUCTIONS FOR PACB SERIES COAL FIRED OVENS OVENS MANUFACTURED BY: EARTHSTONE OVENS-6717 SAN FERNANDO RD GLENDALE CA 91201 TELEPHONE: 800-840-4915 818-553-1134 FAX: 818-553-1133

More information

Open Up Your Space, Add Light Series 2050 and Series 2050i Garden Windows

Open Up Your Space, Add Light Series 2050 and Series 2050i Garden Windows Open Up Your Space, Add Light Series 2050 and Series 2050i Garden Windows Series 2050 Garden Window The Series 2050 standard garden window has an outstanding reputation for its distinctive design and excellent

More information

Dimensions (HxDxW) Total Cabinet Area 89.96x 39.69 x 24 in/ 2,285 x 1,008.17 x 612.77 mm 95.47x 48 x 32 in/ 2,425 x 1,219.2 x 812.

Dimensions (HxDxW) Total Cabinet Area 89.96x 39.69 x 24 in/ 2,285 x 1,008.17 x 612.77 mm 95.47x 48 x 32 in/ 2,425 x 1,219.2 x 812. 1 Compaq 10000 Series Racks The 10000 series racks are a family of 1000mm deep racks which are available in 22U, 36U, 42U and 47U 600mm widths. Compaq 10000 Series Racks provides a common, integrated platform

More information

Unbeatable energy efficient glass curtain wall system

Unbeatable energy efficient glass curtain wall system Unbeatable energy efficient glass curtain wall system CONTENT Introduction 1 System 2 World Class Engineering 4 Unit Selection 5 Energy Efficiency & Comfort 10 Maximised Installation Efficiency 12 Aesthetics

More information

Data Center Rack Systems Key to Business-Critical Continuity. A White Paper from the Experts in Business-Critical Continuity TM

Data Center Rack Systems Key to Business-Critical Continuity. A White Paper from the Experts in Business-Critical Continuity TM Data Center Rack Systems Key to Business-Critical Continuity A White Paper from the Experts in Business-Critical Continuity TM Executive Summary At one time, data center rack enclosures and related equipment

More information

Managing Data Centre Heat Issues

Managing Data Centre Heat Issues Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design

More information

RELAZZO DECKING THE TERRACE. INSTALLATION GUIDE. Construction Automotive Industry. REHAU R20680 EN 05.2015 www.rehau.com/relazzo

RELAZZO DECKING THE TERRACE. INSTALLATION GUIDE. Construction Automotive Industry. REHAU R20680 EN 05.2015 www.rehau.com/relazzo Construction Automotive Industry RELAZZO DECKING THE TERRACE. INSTALLATION GUIDE REHAU R20680 EN 05.2015 www.rehau.com/relazzo Scan the QR code and learn more: RELAZZO DECKING THE TERRACE. Installation

More information

Storage Solutions. Maximize Storage & Optimize Space

Storage Solutions. Maximize Storage & Optimize Space Storage Solutions Maximize Storage & Optimize Space Your Files Are Important With the cost and availability of office space at a premium, space utilization is key. An end-tab color-coded filing system

More information

TopSky DLG Installation Manual

TopSky DLG Installation Manual TopSky DLG Installation Manual Attention: Because after the compound materials solidify, there will be ammonia iris on the surface, which affect the bonding strength afterwards. Please polish with sandpaper

More information

HORIZONTAL INSTALLATION

HORIZONTAL INSTALLATION THERMO/SOLAR Žiar s.r.o. MANUAL FOR INSTALLATION PV SUPPORTING FRAMES HORIZONTAL INSTALLATION Technical alternation reserved A1410 1 12/2014 CONTENT ORD.NO. PAGE Mounting information 3 Mounting, flat roof

More information

CLEAR-DIVISIONS CENTERFOLD

CLEAR-DIVISIONS CENTERFOLD CLEAR-DIVISIONS CENTERFOLD Introduction: The following three (3) part specification offers the Standard and Optional features for the CLEAR-DIVISIONS CENTERFOLD moveable The yellow highlighted areas in

More information

INSTRUCTIONS: LocknCharge Laptop Carts

INSTRUCTIONS: LocknCharge Laptop Carts INSTRUCTIONS: LocknCharge Laptop Carts www.lockncharge.com Extra Tools required: Hammer, Philips head screwdriver, medium adjustable spanner. (Allen key supplied) (Panel colours for illustration purposes

More information

What is Seismic Retrofitting?

What is Seismic Retrofitting? What is Seismic Retrofitting? SEISMIC RETROFITTING A Seismic Retrofit provides existing structures with more resistance to seismic activity due to earthquakes. In buildings, this process typically includes

More information

SECTION 08332 COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)

SECTION 08332 COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here) SECTION 08332 COILING COUNTER DOORS Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Coiling Metal Counter Doors. B. Coiling Counter Fire Doors. 1.2

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer

More information

COLORADO MODEL. 35 x 65 SPECIFICATIONS

COLORADO MODEL. 35 x 65 SPECIFICATIONS COLORADO MODEL 35 x 65 SPECIFICATIONS Dimensions: Roof Dimensions 35-0 x 65-0 Column Dimensions (center to center) 31-0 x 30-6 Minimum Clearance 14-0 Roof Height @ Peak ±18-8 Curved Roof ±42-6 radius Square

More information

HIGHLY EFFICIENT COOLING FOR YOUR DATA CENTRE

HIGHLY EFFICIENT COOLING FOR YOUR DATA CENTRE HIGHLY EFFICIENT COOLING FOR YOUR DATA CENTRE Best practices for airflow management and cooling optimisation AIRFLOW MANAGEMENT COLD AND HOT AISLE CONTAINMENT DC ASSESSMENT SERVICES Achieving true 24/7/365

More information

Data Centre and Server Room Technical Cleaning

Data Centre and Server Room Technical Cleaning Data Centre and Server Room Technical Cleaning Mill Studio Business Centre Crane Mead Ware, Herts SG12 9PY T 01920 444 053 E sales@dataroomsolutions.co.uk www.dataroomsupplies.co.uk Data Room Solutions

More information

SINGLE-FAMILY EARTHQUAKE (SEISMIC) RETROFITS

SINGLE-FAMILY EARTHQUAKE (SEISMIC) RETROFITS CITY OF BEAVERTON Community Development Department Building Division 12725 SW Millikan Way / PO Box 4755, Beaverton, OR 97076 Phone: (503) 526-2493 Fax: (503) 526-2550 General Information (503) 526-2222

More information

WHI 90-Minute Rated Veneered Door Frame Installation Instructions

WHI 90-Minute Rated Veneered Door Frame Installation Instructions No. 940-03-10 INSTALLATION INSTRUCTIONS 90 MINUTE RATED VENEERED DOOR FRAME DOOR REQUIREMENTS: Consult the door manufacturer to make sure that the doors are qualified for the hardware to be installed,

More information

Connection Solutions

Connection Solutions Connection Solutions DESIGN BUILD SYSTEM Connection Solutions for Cold formed Steel Construction Complies with; AS/NZS 4600:2005 AISI S100:2007 AS/NZ 1397 ASTM A653 DESIGN & BUILD SYSTEM FRAMECAD Construction

More information

March 14, 2007. Installation of Bay, Bow and Garden Windows

March 14, 2007. Installation of Bay, Bow and Garden Windows March 14, 2007 Re: Installation of Bay, Bow and Garden Windows Attached are the Atrium Companies, Inc recommendation for the installation of bay, bow and garden windows. These instructions were developed

More information

DENVER MODEL 30 X 30 SPECIFICATIONS

DENVER MODEL 30 X 30 SPECIFICATIONS DENVER MODEL 30 X 30 SPECIFICATIONS Dimensions: Roof Dimensions 30-0 x 30-0 (4) Columns (Center to Center) 25-6½ x 25-6½ Minimum Clearance 8-0 Roof Height @ Peak Dependent on Col. Ht. Hip Roof 4:12 pitch

More information

CLEAR-DIVISIONS APERTO

CLEAR-DIVISIONS APERTO CLEAR-DIVISIONS Introduction: The following three (3) part specification offers the Standard and Optional features for the CLEAR-DIVISIONS moveable glass wall system. The yellow highlighted areas in the

More information

Light-Weight Panels. High quality panels. www.stenca.com

Light-Weight Panels. High quality panels. www.stenca.com Light-Weight Panels High quality panels WELCOME TO STENCA TRADING - Global focus with local service Stenca Trading offers optimal solutions for the offshore, marine, refineries and cogeneration industry.

More information

MIDMARK DENTAL CABINETRY vs LOCAL CABINET MAKERS

MIDMARK DENTAL CABINETRY vs LOCAL CABINET MAKERS MIDMARK DENTAL CABINETRY vs LOCAL CABINET MAKERS Because dental practices are specialized treatment facilities, they have needs that are profession and practice specific. Integra Dental Casework and Artizan

More information

ECM-D70T / ECM-D70T1.5

ECM-D70T / ECM-D70T1.5 Elliptical Ceiling Dual Mount for 37 to 50 Flat Panels INSTALLATION INSTRUCTIONS CREATING POSITIVE CUSTOMER EXPERIENCES 9531-041-001-01 Contents ECM-D70T / ECM-D70T1.5 Installation Tools... 3 Parts List...

More information

Specifications, Product Testing and Terminology

Specifications, Product Testing and Terminology Specifications, Product Testing and Terminology The following synopsis provides a review of various material and final product testing, which is performed on our products, as well as, many of our competitors.

More information

Slips, Trips and Falls

Slips, Trips and Falls Slips, Trips and Falls Introduction o Slips, trips and falls cause: The majority of general industry accidents 15 percent of all accidental deaths (~12,000/yr) More fatalities than all other causes but

More information

Solar Mounting System

Solar Mounting System Xiamen Antai New Energy Tech.Co., Ltd Installation Manual Antai Rail Solar Mounting System (Flat Roof Solution) Version 1.1 Office Add: 508#, North Tower, Guangxia Building Huli Torch Hi-tech Zone, Xiamen,

More information

MEZZANINE SPECIFICATIONS PART 1 GENERAL 1.1 SCOPE 1.2 APPROVED MANUFACTURER 1.3 REGULATORY ORGANIZATIONS AND GROUPS 1.4 QUALITY ASSURANCE

MEZZANINE SPECIFICATIONS PART 1 GENERAL 1.1 SCOPE 1.2 APPROVED MANUFACTURER 1.3 REGULATORY ORGANIZATIONS AND GROUPS 1.4 QUALITY ASSURANCE MEZZANINE SPECIFICATIONS PART 1 GENERAL 1.1 SCOPE This specification is intended to describe the general requirements applicable to a proper structural mezzanine design. In addition, it is to serve as

More information

Secure your IT equipment with confidence... secure with NetClosure

Secure your IT equipment with confidence... secure with NetClosure Secure your IT equipment with confidence... secure with NetClosure SERVER CABINETS NetClosure s REM Series Server Cabinet is the ultimate solution designed and engineered for demanding data center environments.

More information

MONDOATHENS BASKETBALL SET (Reference PK110)

MONDOATHENS BASKETBALL SET (Reference PK110) MONDOATHENS BASKETBALL SET (Reference PK110) DESCRIPTION The MONDOATHENS backstop unit is mainly designed for multi-sports pavilions and installations where the highest-level basketball competitions are

More information

Walking and Working Surface Checklist:

Walking and Working Surface Checklist: Walking and Working Surfaces Purpose: This information is presented to improve the level of safety in our operations, and to inform you that we will comply with the OSHA Standard 29 CFR 1910.23. Responsibility:

More information

AMS 120. EFT Guest Card Terminal & Refund unit

AMS 120. EFT Guest Card Terminal & Refund unit AMS 120 EFT Guest Card Terminal & Refund unit ACCOUNT MANAGEMENT STATIONS Wall mounted kiosk offering Visitor card purchase and refund Card deposit EFT purchase, refund and loading Full statement facilities

More information

Spetec. Laminar Flow Box. Portable Clean Room Technology

Spetec. Laminar Flow Box. Portable Clean Room Technology Spetec Laminar Flow Box Portable Clean Room Technology 1 Fundamentals Portable Clean Room Technology Laminar Flow The basis for the development of the clean room technology was first established in the

More information

DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 41 13 METAL ROOF PANELS REPORT HOLDER: FIRESTONE BUILDING PRODUCTS COMPANY, LLC

DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 41 13 METAL ROOF PANELS REPORT HOLDER: FIRESTONE BUILDING PRODUCTS COMPANY, LLC 0 ICC ES Report ICC ES (800) 423 687 (62) 699 043 www.icc es.org 000 Most Widely Accepted and Trusted ESR 3422 Reissued 09/201 This report is subject to renewal 09/2016. DIVISION: 07 00 00 THERMAL AND

More information

CT8 Fitness Training System

CT8 Fitness Training System CT8 Fitness Training System The TuffSTuff Fitness CT8 Fitness Training System ignites a revolution in Functional Fitness! Made in the USA from materials only seen in the highest quality commercial strength

More information

Installation Instructions

Installation Instructions READ BEFORE INSTALLING UNIT For Through-the-Wall Air Conditioners To avoid risk of personal injury, property damage, or product damage due to the weight of this device and sharp edges that may be exposed:

More information

SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS

SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word

More information

IN00419 (rev A) Aqua 6 Glide Quadrant and Off-set Quadrant Enclosure

IN00419 (rev A) Aqua 6 Glide Quadrant and Off-set Quadrant Enclosure IN00419 (rev A) Aqua 6 Glide Quadrant and Off-set Quadrant Enclosure Instruction suitable for both Quadrant & Off-set Quadrant variations. Instruction suitable for both Right and Left Hand fixing variations

More information

TFL CUSTOM FIREPLACES WITH MASONRY BRICK LININGS. standard INSTALLATION SPECIFICATION INTO TIMBER FRAMING

TFL CUSTOM FIREPLACES WITH MASONRY BRICK LININGS. standard INSTALLATION SPECIFICATION INTO TIMBER FRAMING 6.CW.1A TFL CUSTOM FIREPLACES WITH MASONRY BRICK LININGS wood or gas standard INSTALLATION SPECIFICATION INTO TIMBER FRAMING The Fireplace Ltd is able to design and fabricate custom brick open masonry

More information

Built to Last. Built for Beauty. Good. Solid. Logix. TM

Built to Last. Built for Beauty. Good. Solid. Logix. TM Built to Last. Built for Beauty. Good. Solid. Logix. TM Quality, Value and Service Introducing LOGIX Insulated Concrete Forms. Based on the simple concept of interlocking blocks, LOGIX ICF gives you a

More information

Data Centre Testing and Commissioning

Data Centre Testing and Commissioning Data Centre Testing and Commissioning What is Testing and Commissioning? Commissioning provides a systematic and rigorous set of tests tailored to suit the specific design. It is a process designed to

More information

InstaPATCH ZERO Solution Guide

InstaPATCH ZERO Solution Guide SYSTIMAX Solutions InstaPATCH ZERO Solution Guide Rapid Server Deployment and Change Management North, South and Central Americas 1 As data centers face ever-increasing IT demands, growth demands and evolving

More information

1. When we deform a material and it recovers its original shape, we say that it is a) Rigid

1. When we deform a material and it recovers its original shape, we say that it is a) Rigid UNIT 05 TEST TECHNOLOGY 1º ESO GROUP: A DATE: / / 1. When we deform a material and it recovers its original shape, we say that it is 2. When we try to deform a material and it doesn t change its shape,

More information

sound reduction systems for commercial, educational and industrial environments

sound reduction systems for commercial, educational and industrial environments sound reduction systems for commercial, educational and industrial environments Tel: +44 ()14 3874 Fax: +44 ()14 38957 E-mail: info@soundreduction.co.uk Web: www.soundreduction.co.uk soundblocker Acoustic

More information

INSTALLATION OF A BAY WINDOW

INSTALLATION OF A BAY WINDOW INSTALLATION OF A BAY WINDOW Installation of a Bay Window These instructions relate to the replacement of an existing bay window or replacement of a straight window with a new bay window, in an opening

More information

WTW SWANTM. Linear slot air diffusers of wall-to-wall design for ceilings

WTW SWANTM. Linear slot air diffusers of wall-to-wall design for ceilings SWANTM WTW Linear slot air diffusers of wall-to-wall design for ceilings Quick facts Wall-to-wall installation Diffuser face of light aluminium design 2, 3 or slots Horizontal/vertical air distribution

More information

CLEAR-DIVISIONS VARIOFOLD

CLEAR-DIVISIONS VARIOFOLD CLEAR-DIVISIONS VARIOFOLD Introduction: The following three (3) part specification offers the Standard and Optional features for the CLEAR-DIVISIONS VARIOFOLD moveable The yellow highlighted areas in the

More information

Chapter 3 Pre-Installation, Foundations and Piers

Chapter 3 Pre-Installation, Foundations and Piers Chapter 3 Pre-Installation, Foundations and Piers 3-1 Pre-Installation Establishes the minimum requirements for the siting, design, materials, access, and installation of manufactured dwellings, accessory

More information

Profiles. Exclusively Manufactured By

Profiles. Exclusively Manufactured By Profiles and TRANSITIONS Exclusively Manufactured By PrORound Introducing a new choice in high quality Profiles and Transitions. Enhance the beauty of tile and natural stone surfaces in your projects with

More information

DCF Optimized Rack System

DCF Optimized Rack System Integrated Cabinet Solutions For Business-Critical Continuity DCF Optimized Rack System User Manual IMPORTANT SAFETY GUIDELINES SAVE THESE INSTRUCTIONS This manual contains important instructions that

More information

The load carrier system designed for professionals

The load carrier system designed for professionals The load carrier system designed for professionals THULE PROFESSIONAL The rugged time-saving system Thule Professional is a load carrier system from the world leader in utility transportation. Every aspect

More information

DIRECTIONS FOR ASSEMBLING BASE & WALL CABINETS

DIRECTIONS FOR ASSEMBLING BASE & WALL CABINETS DIRECTIONS FOR ASSEMBLING BASE & WALL CABINETS TheRTAStore.com STEP 1: CLEAR A WORK SPACE Place your RTA cabinet panels on a smooth, scratch resistant surface in a large, open area. (Some people like to

More information

Cable ladder installation at S.C.M. Chemicals Limited s titanium dioxide Plant in Western Australia

Cable ladder installation at S.C.M. Chemicals Limited s titanium dioxide Plant in Western Australia Exel Composites Cable Support Systems offer engineers a structural product for solving many design and plant engineering problems, enabling long term reliable support of expensive and often critical cables.

More information

Material test chamber with mechanical convection

Material test chamber with mechanical convection FP series 400 Material test chambers Material test chamber with mechanical convection A BINDER material test chamber with mechanical convection of the FP series provides reliably short drying times and

More information

WOLFFKRAN. 1 Schedule drawing. 1.1 Schedule drawing, WOLFF 6023.6clear. max. hook height above ground. Data WOLFF 6023.6clear

WOLFFKRAN. 1 Schedule drawing. 1.1 Schedule drawing, WOLFF 6023.6clear. max. hook height above ground. Data WOLFF 6023.6clear 1 Schedule drawing 1.1 Schedule drawing, WOLFF 6023.6clear [X] max. hook height above ground Data WOLFF 6023.6clear Item Crane type Design Type of setup Basis of calculation Payload torque Hoist winch

More information

FF+E Package 1: Casegoods Specifications UCSD NORTH CAMPUS HOUSING, PHASE 1

FF+E Package 1: Casegoods Specifications UCSD NORTH CAMPUS HOUSING, PHASE 1 FF+E Package 1: Casegoods Specifications UCSD NORTH CAMPUS HOUSING, PHASE 1 Issue Date: 3/3/2009 Each furniture item scheduled in this specification manual is assigned a "key" code; each key code is crossreferenced

More information

Vanishing Lid Trays Construction Methods with Tile or Masonry

Vanishing Lid Trays Construction Methods with Tile or Masonry 1-800-447-2838 Installation Instructions Vanishing Lid Trays Construction Methods with Tile or Masonry Table of Contents 1. Tools and Equipment...1 2. Vanishing Lid Trays...3 2.1 Materials for Finished

More information

In-Floor Cooling Solutions. In-Floor Cooling Solutions. Airfl ow Management Solutions for Raised Floor Data Centers

In-Floor Cooling Solutions. In-Floor Cooling Solutions. Airfl ow Management Solutions for Raised Floor Data Centers In-Floor Cooling Solutions In-Floor Cooling Solutions Airfl ow Management Solutions for Raised Floor Data Centers Virtual Aisle Containment In-floor Cooling Airflow Panels and Controls Virtual containment

More information

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings

More information

- White Paper - Data Centre Cooling. Best Practice

- White Paper - Data Centre Cooling. Best Practice - White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH

More information