380VDC Data Center At Duke Energy

Size: px
Start display at page:

Download "380VDC Data Center At Duke Energy"

Transcription

1 380VDC Data Center At Duke Energy Dennis P. Symanski EPRI - Senior Project Manager Curtis Watkins Duke Energy - Senior Project Manager Emerging Technology (ET) Summit November 9, 2010 Sacramento, CA

2 From Dept of Energy Secretary Steven Chu As Energy Secretary Steven Chu has noted, America cannot build a 21st Century energy economy with a mid-20th Century electricity system. Transforming the current grid into a dynamic, resilient, and adaptable Smart Grid will be one of the biggest technological challenges of our times. The rewards, however, may be dramatic, enabling consumers to better control their electricity use, integrating the next generation of plug-in electric vehicles, increasing efficiency, and better harnessing renewable energy. Source: Department of Energy, Communications Requirement Of Smart Grid Technologies, October 5,

3 Smart Grid to Smart Buildings Source: EMerge Alliance Overview 3

4 DC Microgrids Throughout Buildings 24 VDC 380 VDC 380 VDC 24 & 380 VDC Source: EMerge Alliance Overview 4

5 Data Center Types, Sizes and Numbers Type Server Closet Server Room Localized Data Center Mid Aer Data Center Enterprise Class Data Center Scope Secondary computer loca0on, o2en outside of IT control, or may be a primary site for a small business Secondary computer loca0on, under IT control, or may be a primary site for a small business Primary or secondary computer loca0on, under IT control Primary compu0ng loca0on, under IT control Primary compu0ng loca0on, under IT control Power/cooling Standard room air condi0oning, no UPS Upgraded room air condi0oning, single UPS Maintained at 17 C; some power and cooling redundancy Maintained at 17 C; some power and cooling redundancy Maintained at 17 C; at least N+1 power & cooling redundancy Sq H <200sq 2 <500sq 2 <1,000sq 2 <5,000sq 2 >5,000 sq 2 US data centers (2009 est) Total Servers (2009 est) Average servers per loca0on 1,345,741 = 51.8% 1,170,399 = 45.1% 64,229 = 2.5% 9,758 = 0.4% 7,006 = 0.3% 2,135,538 = 17% 3,057,834 = 24% 2,107,592 = 16% 1,869,595 = 15% 3,604,678 = 28%

6 Data Center Type and Server Population 0.7% of data centers (Enterprise & Mid-tier) contain 43% of all servers (Amazon/Apple/Facebook/Google/Yahoo) They have staffs of internal electrical & mechanical engineers to design & construct efficient data centers % of data centers (more than 2.5 million of them) contain 57% of all servers (Hospitals/Hotels/Universities/Utilities/ Banks/City Halls/Supermarkets/Chain Stores) These data centers operators struggle with heat/space/power problems without much internal expertise 6

7 380VDC Data Center Activity Involved With Multiple 380VDC Demos Universities Electric Utilities Telecom Industry Harmonizing Multiple 380VDC Spec Efforts DC Power Partners Joining EMerge Alliance European Telecommunications Standards Institute International Electrotechnical Commission (SG4) Working With Many Manufacturers IT Equipment As Well As Facility Equipment 7

8 Worldwide ~380VDC Demos US Intel Corp. 400 VDC France Telecom 350 VDC Sweden UPN AB. 350 / 380VDC Japan NTT Group 380/400 VDC US UCSD 380 VDC Japan Other Demos VDC US DukeEnerg y 380 VDC New Zealand Telecom NZ 220 VDC Source: NTT FACILITIES, INC. 8

9 Duke Energy 380VDC Data Center Demo HP Servers IBM Servers EMC Storage Arrays Delta Rectifiers StarLine Busway Dranetz-BMI Metering 9

10 Duke Energy Data Center Set-Up 10

11 Why 380VDC? Sweet Spot IEC 900 BS (U.K.) High Long DC Voltage Ordinance (JPN) 600 NEC(U.S.) (192cell) 374 (168cell) 321 (144cell) [to 48] Validus 380 US DC Demo 300 NEDO PJ. (Sendai) Server PS Operating bulk - voltage 373(U.K.) 354(EU) 324V (US 311(JPN) Distribution efficiency Cable Distance Low Short 0 Law, Regulation, Code, and Stds. Distr. Gen. Telecom (Number of Cells) Demos (Reference) Rating voltage of parts and elements AC ICT input voltages ( Peak ) Benefit of HVDC system ETSI Std. (draft) Edited from source: NTT FACILITIES, INC. 11

12 380VDC vs ITI(CBEMA) VAC Operating Ranges Voltage Tolerance Envelope for traditional AC powered computers (left) New, DC version of curve, developed by EPRI with NTT and PSL (right) 12

13 380VDC Power Distribution NOTE: All loads are to be connected between L(+) and L(-). PE is not a power conductor. 13

14 Easier Integration Of Renewables 14

15 Benefits Summary Of 380VDC Higher Reliability Fewer Conversions/Fewer Points Of Failure Higher Efficiency Higher Efficiency Power Supplies & UPS No PDU Transformer Needed Smaller Size Better Power Quality Easier Integration Of Renewable Energy 15

16 Other DC Applications 380VDC Uses Telecom Central Offices (Operating Today At 48VDC) Variable Speed Drives (Washers/Dryers/Air Cond) Other Home Appliances (Stoves/Ovens) Rapid Charger For Plug-in Electric Vehicles 24VDC Uses Lighting Consumer Electronics (TVs, PCs, Projectors) EMerge Alliance Members Working On Both Voltages 16

17 DC Challenges Safety Agency Approval/Listing (e.g. UL) DC & AC Products Both Need These Approvals Paradigm Shift Back To Some Of Thomas Edison s DC Ideas We Are Used To The AC World Today Vendor Selection Many AC Vendors To Choose From Fewer DC Vendors Available --- At Least For Now 17

18 Utility Opportunities Possible new revenue opportunities Energy efficiency for new data center customers Reduce electrical costs anywhere from 10 30% DC O&M costs are on average 65% less than AC Conversion opportunities for existing data center customers Approximately 2.5 million small to medium data centers in the U.S. Component swap out, not a complete rip & replace 18

19 Utility Challenges Getting data center customers on board Faced it with our test (decided to test our own facility) Getting commitments Technology has to be proven, both in concept and financial feasibility Able to preliminarily show test results in the Duke Energy facility Conversions for brownfield sites key aspect of potential success 19

20 Potential Outcomes Based on preliminary results in the Duke Energy facility (which showed over 15% increase in efficiency) Average small to medium data center consumes approximately 0.5 to 5 MW Reduction possibilities of 10 to 30% Major impact for these data centers that are not enterprise sized Reinforces commitments to energy efficiency Provides new opportunities to interact with customers to provide wider range of products/services 20

21 Together Shaping the Future of Electricity 21

22 EPRI Data Center Energy Efficiency Research Dennis P. Symanski Senior Project Manager Power Delivery & Utilization Sector Emerging Technologies (ET) Summit November 9, 2010 Sacramento, CA

23 Why do electric utilities care about data centers?!? Great Customers Steady load (24 hours/day 7 days/week) Constant & predictable revenue stream High-tech exposure Challenging Customers Complaining about not getting enough power Complaining about too much heat Complaining about high cost of power 2

24 Data Center Types, Sizes and Numbers Type Server Closet Server Room Localized Data Center Mid tier Data Center Enterprise Class Data Center Scope Secondary computer location, often outside of IT control, or may be a primary site for a small business Secondary computer location, under IT control, or may be a primary site for a small business Primary or secondary computer location, under IT control Primary computing location, under IT control Primary computing location, under IT control Power/cooling Standard room air conditioning, no UPS Upgraded room air conditioning, single UPS Maintained at 17 C; some power and cooling redundancy Maintained at 17 C; some power and cooling redundancy Maintained at 17 C; at least N+1 power & cooling redundancy Sq ft <200sq ft <500sq ft <1,000sq ft <5,000sq ft >5,000 sq ft US data centers (2009 est) Total Servers (2009 est) Average servers per location 1,345,741 = 51.8% 1,170,399 = 45.1% 64,229 = 2.5% 9,758 = 0.4% 7,006 = 0.3% 2,135,538 = 17% 3,057,834 = 24% 2,107,592 = 16% 1,869,595 = 15% 3,604,678 = 28%

25 Data Center Type and Server Population 0.7% of data centers (Enterprise & Mid-tier) contain 43% of all servers (Amazon/Apple/Facebook/Google/Yahoo) They have staffs of internal electrical & mechanical engineers to design & construct efficient data centers % of data centers (more than 2.5 million of them) contain 57% of all servers (Hospitals/Hotels/Universities/Utilities/Banks /City Halls/Chain Stores) These data centers operators struggle with heat/space/power problems without much internal expertise 4

26 Telecom Central Offices Are Consuming More Than 1% Of Total Worldwide Electrical Energy Country Network Energy Consumption % of Country Total Energy Consumption USA Verizon TWh 0.24% Japan NTT Group TWh 1% Italy Telecom Italia TWh 1% France France Telecom- Orange TWh 0.4% Spain Telefonica TWh 0.6% Global electricity consumption of telecom industry estimated at 1%: 164 billion kwh More than the total electricity consumption of Iran, Turkey or Sweden Enough to power 1.6 million homes million tons of CO2 (equivalent to the annual emissions of 29 million cars!) 5

27 Data Centers versus Telecom Central Offices Similarities Both installing lots of computer equipment Both adding new services & capabilities (Central Offices looking more & more like Data Centers) Both are running out of power & cooling & space Data Centers VAC Commercial Grade Equip New/Modern Sites Differences Telecom Central Offices 48 VDC Telecom-certified Equip Old/Downtown Sites 6

28 Data Centers EPRI Energy Efficiency Research Just a few examples of EPRI energy efficiency research and field demonstrations are in the following areas: Airflow management Efficient Power Supplies Direct Current power distribution 7

29 Data Centers Air Flow Management This technology uses adaptive software to control heating, ventilation and air conditioning (HVAC) based on temperature. This avoids overcooling that is common in today s data centers Wireless temperature sensors make the installation fast and simple Franchise Tax Board, Sacramento, CA 8

30 Data Centers Air Flow Management Significant Savings Possible: Reduced fan energy 66% Lowered total energy 21.3% Saved 475,000 kwh/yr Eliminated > 400 tons CO2/yr Payback in 3.1 years Bottom-line: $42,722 per year saved Main breaker, kw 60 BEFORE DASH software started 50 manual control AFTER 0 1/31 2/5 2/10 2/15 date/time Balancing Heat and Fan Load 9

31 Data Centers Power Supply Retrofits The Cascade Effect - Power Supply Retrofits Provide the most Bang for the Buck 10

32 Data Centers Power Supply Retrofits Only EPRI tests efficient power supplies in support of the ECOS 80 PLUS program Field demonstrations are ongoing to verify savings EPA s Energy Star program adopted the same limits as 80 PLUS Not Compliant Compliant 11

33 Data Centers - Power Supply Swap Six Hot- Swappable Power Supplies will be replaced Power Supplies are tested and certified at our lab vendors are ready to ship 12

34 380VDC Data Centers?!? REALLY??? ~28% facility energy savings, incl. cooling compared to typical AC system ~7% facility energy savings, incl. cooling compared to best-in-class AC system ~33% space savings 200% to 1000% reliability improvement 15% electrical facility capital cost savings Overall heat load reduction reduces overall cooling requirement Using fewer of the earth s resources (15% component reduction) 13

35 Data Centers 380VDC Power Distribution EPRI participated in this 380VDC data center demonstration in 2006 showing: 7% efficiency improvement over state-of-the-art AC power distribution 28% efficiency improvement over typical AC power distribution 14

36 Standard 208VAC vs 380VDC Data Center 15

37 DC Voltage Why 380 VDC??? (Sweet Spot) IEC 900 BS (U.K.) 750 Ordinance (JPN) 600 NEC(U.S.) (192cell) 374 (168cell) 321 (144cell) 575 Validus 380 DC Demo (Sun) 300 NEDO PJ. (Sendai) Operating bulk - voltage 373(U.K.) 354(EU) 311(JPN) large Distribution efficiency Cable Distance 0 Law, Regulation, Code, and Stds. Distributed Telecom trends Gen. (Number of Cell) Demos (Reference) Rating voltage of parts and elements 186(U.S.) AC system voltages ( Peak ) small Benefit of HVDC system From NTT-Facilities Survey 16

38 380VDC vs ITI(CBEMA) VAC Operating Ranges Voltage Tolerance Envelope for traditional AC powered computers (left) New, DC version of curve, developed by EPRI with NTT and PSL (right) 17

39 Why Should EPRI Care About Data Centers??? Data Centers are: Getting bigger Getting more numerous Using more power Jaguar-World s fastest Supercomputer 8 MW Electrical Load 4 MW Cooling Load Causing more utility problems Causing more customer problems Increasing their Carbon Footprint 18

40 Together Shaping the Future of Electricity 19

Residential & Commercial Use Of DC Power

Residential & Commercial Use Of DC Power Residential & Commercial Use Of DC Power Dennis P. Symanski Senior Project Manager NEMA, UL & NFPA Low Voltage Direct Current Workshop 08APR2011 Arlington, VA From Dept of Energy Secretary Steven Chu As

More information

DC powered data centers in the world

DC powered data centers in the world DC powered data centers in the world Keiichi Hirose, Ph.D. Senior Research Engineer R&D Headquarters NTT Facilities, Inc. Tokyo Japan LVDC Workshop SMB Strategic Group 4 on LVDC distribution systems up

More information

Duke Energy - EPRI DC Powered Data Center Demonstration Executive Summary

Duke Energy - EPRI DC Powered Data Center Demonstration Executive Summary Duke Energy - EPRI DC Powered Data Center Demonstration Executive Summary What: Duke Energy and EPRI Sponsored DC Powered Data Center Demonstration Using 380V DC Power When: 2010-2011 Where: Duke Energy

More information

France Telecom Energy consumption, HVDC, cooling improvement

France Telecom Energy consumption, HVDC, cooling improvement France Telecom Energy consumption, HVDC, cooling improvement Didier Marquet (FT R&D and ETSI EE2 chairman), Marc Aubrée (FT R&D) Datacenter Code of Conduct meeting in IEA 2nd July 2007 A bit of history

More information

Edison s Data Center: 380Vdc brings Reliability and Efficiency to Sustainable Data Centers

Edison s Data Center: 380Vdc brings Reliability and Efficiency to Sustainable Data Centers Proposed article for IEEE Power & Energy Magazine November 2012 Issue: Edison s 380Vdc Data Center 1 Edison s Data Center: 380Vdc brings Reliability and Efficiency to Sustainable Data Centers Guy AlLee

More information

Agenda. Part I: Introduction to OptimumHVAC. Part II: Initial Energy Savings Analysis for MCO Main Terminal. Part III: Case Studies & Conclusion

Agenda. Part I: Introduction to OptimumHVAC. Part II: Initial Energy Savings Analysis for MCO Main Terminal. Part III: Case Studies & Conclusion OptimumHVAC Prepared for the: GOAA Energy Conservation & Environmental Initiatives Forum April 27, 2010 Jamie Wiecks Enterprise Account Manager Optimum Energy Mike Dillard Vice President, Business Development

More information

Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint

Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint Energy usage in the data center Electricity Transformer/ UPS Air 10% Movement 12% Cooling 25% Lighting, etc. 3% IT Equipment

More information

Electrical Systems. <Presenter>

Electrical Systems. <Presenter> Review Root Causes of Energy Inefficiency Roadmap to Maximize Energy Efficiency Best Practices Alternative Energy Sources Controls Take Aways Seek Professional Help. ENERGY INEFFICIENCY OF

More information

Edison Redux. 380 Vdc Brings Reliability and Efficiency to Sustainable Data Centers. By Guy AlLee and William Tschudi

Edison Redux. 380 Vdc Brings Reliability and Efficiency to Sustainable Data Centers. By Guy AlLee and William Tschudi Edison Redux By Guy AlLee and William Tschudi 380 Vdc Brings Reliability and Efficiency to Sustainable Data Centers Direct current (dc) technology has changed significantly over the last 120-plus years

More information

Applying ICT and IoT to Multifamily Buildings. U.S. Department of Energy Buildings Interoperability Vision Meeting March 12, 2015 Jeff Hendler, ETS

Applying ICT and IoT to Multifamily Buildings. U.S. Department of Energy Buildings Interoperability Vision Meeting March 12, 2015 Jeff Hendler, ETS Applying ICT and IoT to Multifamily Buildings U.S. Department of Energy Buildings Interoperability Vision Meeting March 12, 2015 Jeff Hendler, ETS ETS is an Energy Technology, Behavior Management, and

More information

Demand Response in Data Centers Feasibility and Proof of Concept Demonstration

Demand Response in Data Centers Feasibility and Proof of Concept Demonstration Demand Response in Data Centers Feasibility and Proof of Concept Demonstration Jay Madden, SCE; Mukesh Khattar, EPRI; Henry Wong, Intel; Chris Battista, Calit2 CalPlug Workshop Series #7 University of

More information

Data Center Facility Basics

Data Center Facility Basics Data Center Facility Basics Ofer Lior, Spring 2015 Challenges in Modern Data Centers Management, Spring 2015 1 Information provided in these slides is for educational purposes only Challenges in Modern

More information

AIA Provider: Colorado Green Building Guild Provider Number: 50111120. Speaker: Geoff Overland

AIA Provider: Colorado Green Building Guild Provider Number: 50111120. Speaker: Geoff Overland AIA Provider: Colorado Green Building Guild Provider Number: 50111120 Office Efficiency: Get Plugged In AIA Course Number: EW10.15.14 Speaker: Geoff Overland Credit(s) earned on completion of this course

More information

Ringing at the Door. Boiling an egg. Moving by car. Flows of solar energy. There is no energy crisis. How to boil an egg?

Ringing at the Door. Boiling an egg. Moving by car. Flows of solar energy. There is no energy crisis. How to boil an egg? Delft University of Technology There is no energy crisis How to boil an egg? Prof. Dr. Ad van Wijk 20-10-2011 Energy efficiency world wide is about 2% The sun gives us in one hour more energy than the

More information

De energievoorziening in 2040;

De energievoorziening in 2040; De energievoorziening in 2040; decentraal, duurzaam en intelligent! Prof. Dr. Ad van Wijk 25-6-2012 20-06-2012 Delft University of Technology Challenge the future There is no energy crisis Energy efficiency

More information

GREEN DATA CENTER DESIGN

GREEN DATA CENTER DESIGN Jeffrey Menig Global Facilities Facility Engineering The application of multiple available technologies resulting in improved energy optimization without significantly increasing capital investment. A

More information

Data Centers: Definitions, Concepts and Concerns

Data Centers: Definitions, Concepts and Concerns Data Centers: Definitions, Concepts and Concerns Arash Mousavi DCC September 2013 Agenda 1. Introduction 2. Issues in Modern Data Centers: Siemens Integrated Data Center Solutions 3. Issues in Modern Data

More information

Cisco Nexus 7000 Series Power Supply Modules

Cisco Nexus 7000 Series Power Supply Modules Cisco Nexus 7000 Series Power Supply Modules Product Overview The Cisco Nexus 7000 Series Power Supply Modules (Figures 1 and 2) deliver fault tolerance, high efficiency, load sharing, and hot-swappable

More information

VISIT 2010 Fujitsu Forum Europe 0

VISIT 2010 Fujitsu Forum Europe 0 VISIT 2010 Fujitsu Forum Europe 0 Virtualization & Automation Room 13a Shaping tomorrow with you. Green Data Center Services Martin Provoost Director, Data Centers and Networks, Fujitsu UK & Ireland 14:00

More information

How To Convert A Power Grid To A Direct Current (Dc) Power System

How To Convert A Power Grid To A Direct Current (Dc) Power System PHASING OUT ALTERNATING CURRENT DIRECTLY AN ENGINEERING REVIEW OF DC POWER FOR DATA CENTERS DAVID E. GEARY, P.E., SENIOR MEMBER, IEEE SUMMARY This is the first in a series of white papers defining and

More information

Next Generation Power Distribution for the High-Density Datacenter

Next Generation Power Distribution for the High-Density Datacenter Next Generation Power Distribution for the High-Density Datacenter George Wasielewski Eaton/Powerware Power Quality Products and Services Dallas Enhance (IT) July 10, 2008 2007 Eaton Corporation. All rights

More information

NEBS 2009 Optimization of Telecom Networks Through Energy Efficiency Eitan Amon Type Approval Team Leader Comverse Ltd.

NEBS 2009 Optimization of Telecom Networks Through Energy Efficiency Eitan Amon Type Approval Team Leader Comverse Ltd. NEBS 2009 Optimization of Telecom Networks Through Energy Efficiency Eitan Amon Type Approval Team Leader Comverse Ltd. Comverse Top Worldwide Customers* * Partial list only 2 Comverse Worldwide Operations

More information

DATA CENTERS BEST IN CLASS

DATA CENTERS BEST IN CLASS Data Energy Audit Chameleon Data Center DATA CENTERS BEST IN CLASS... By Wouter Kok, MSc, Strategic Advisor Global Data Center Practice Deerns leads the way in making data centers greener, by reducing

More information

Data Center Energy Efficient Cooling Control Demonstration PIR 10 052. (formerly Federspiel Controls)

Data Center Energy Efficient Cooling Control Demonstration PIR 10 052. (formerly Federspiel Controls) Data Center Energy Efficient Cooling Control Demonstration PIR 10 052 (formerly Federspiel Controls) Background 2009 PIER sponsored project resulted in the installation of intelligent supervisory control

More information

NetSure DC Power Solutions with esure High-Efficiency Technology

NetSure DC Power Solutions with esure High-Efficiency Technology NetSure DC Power Solutions with esure High-Efficiency Technology NetSure solutions with esure high-efficiency technology Our Efficiency Without Compromise promise Among the array of ever-changing challenges

More information

Building the Clean Energy Super Highway

Building the Clean Energy Super Highway Building the Clean Energy Super Highway The Development of the Global Smart Grid and the Next Innovation Infrastructure A presentation for the Fletcher School of Law & Diplomacy April 25, 2011 Drew Bennett,

More information

The Other Half of the Problem Server Closets and Small Server Rooms

The Other Half of the Problem Server Closets and Small Server Rooms The Other Half of the Problem Server Closets and Small Server Rooms Bill Tschudi Lawrence Berkeley National Laboratory October 24, 2012 wftschudi@lbl.gov SVLG Data Center Summit NEED TO CONVERT OT NON-STANFORD

More information

Energy Benchmarking Report for Lakeside Middle School. Millville, NJ

Energy Benchmarking Report for Lakeside Middle School. Millville, NJ Energy Benchmarking Report for Lakeside Middle School Millville, NJ (for the period: June 1, 2008 through May 31, 2009) Prepared by: Background & Findings: The New Jersey Clean Energy Program (NJCEP) developed

More information

415V DISTRIBUTION FOR GREEN DATA CENTERS

415V DISTRIBUTION FOR GREEN DATA CENTERS White Paper: HMRP-WP001-A1 October 1, 2010 415V DISTRIBUTION FOR GREEN DATA CENTERS Prepared by: Anthony (Tony) Hoevenaars, P. Eng President and CEO Mirus International Inc. Copyright 2005 Mirus International

More information

Control of Computer Room Air Handlers Using Wireless Sensors. Energy Efficient Data Center Demonstration Project

Control of Computer Room Air Handlers Using Wireless Sensors. Energy Efficient Data Center Demonstration Project Control of Computer Room Air Handlers Using Wireless Sensors Energy Efficient Data Center Demonstration Project About the Energy Efficient Data Center Demonstration Project The project s goal is to identify

More information

Qualitative Analysis of Power Distribution Configurations for Data Centers

Qualitative Analysis of Power Distribution Configurations for Data Centers Qualitative Analysis of Power Distribution Configurations for Data Centers White Paper #4 2007 The Green Grid. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted,

More information

Energy Efficiency and Green Data Centers. Overview of Recommendations ITU-T L.1300 and ITU-T L.1310

Energy Efficiency and Green Data Centers. Overview of Recommendations ITU-T L.1300 and ITU-T L.1310 Energy Efficiency and Green Data Centers Overview of Recommendations ITU-T L.1300 and ITU-T L.1310 Paolo Gemma Chairman of Working Party 3 of ITU-T Study Group 5 International Telecommunication Union Agenda

More information

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Lars Strong, P.E., Upsite Technologies, Inc. Kenneth G. Brill, Upsite Technologies, Inc. 505.798.0200

More information

Energy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie

Energy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie Energy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie Mukesh Khattar, Energy Director, Oracle National Energy Efficiency Technology Summit, Sep. 26, 2012, Portland, OR Agenda

More information

Solve your IT energy crisis WITH An energy SMArT SoluTIon FroM Dell

Solve your IT energy crisis WITH An energy SMArT SoluTIon FroM Dell Solve your IT energy crisis WITH AN ENERGY SMART SOLUTION FROM DELL overcome DATA center energy challenges IT managers share a common and pressing problem: how to reduce energy consumption and cost without

More information

Investor day. November 17, 2010. Power business Julio Rodriguez Executive Vice President

Investor day. November 17, 2010. Power business Julio Rodriguez Executive Vice President Investor day November 17, 2010 Power business Julio Rodriguez Executive Vice President Power: Business strategic domain Centralized generation Residential Residential Industries Non Residential Transmission

More information

FAQ' s. Frequently Asked Questions. A1 Control Units. Pge 1 of 7 PUMPKIN HOOK ROAD PO BOX OGD VAN HORNESVILLE NY 13475 USA 315-858-1002

FAQ' s. Frequently Asked Questions. A1 Control Units. Pge 1 of 7 PUMPKIN HOOK ROAD PO BOX OGD VAN HORNESVILLE NY 13475 USA 315-858-1002 Frequently Asked Questions FAQ' s A1 Control Units Pge 1 of 7 Table of Contents Q-1 Who are OGD and V-HVAC? 3 Q-2 Why do I need the A1 Control Unit and what are the benefits? 3 Q-3 How is the A1 Control

More information

Commercial Building Energy Initiative Tenant Business Case

Commercial Building Energy Initiative Tenant Business Case Commercial Building Energy Initiative Tenant Business Case April 2010 An initiative of the Greater Toronto CivicAction Alliance The business case for GTA tenants Why to invest in energy efficiency programs

More information

Public Overview of the EMerge Alliance Data/Telecom Center Standard Version 1.0

Public Overview of the EMerge Alliance Data/Telecom Center Standard Version 1.0 of the EMerge Alliance Data/Telecom Center Standard Version 1.0 A standard defining low voltage dc power distribution system requirements for use in data centers and telecom central offices Excerpted With

More information

Brian T. Patterson - Chairman. Governing Member, EMerge Alliance General Manager, Armstrong World Industries

Brian T. Patterson - Chairman. Governing Member, EMerge Alliance General Manager, Armstrong World Industries Brian T. Patterson - Chairman Governing Member, EMerge Alliance General Manager, Armstrong World Industries Vision Standards Eco-System Transformation The Current Reality PROBLEM: Mismatched AC and DC

More information

Green Data Centre Design

Green Data Centre Design Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS

More information

415V DISTRIBUTION FOR GREEN DATA CENTERS

415V DISTRIBUTION FOR GREEN DATA CENTERS White Paper: HMRP-WP001-A5 June 5, 2012 415V DISTRIBUTION FOR GREEN DATA CENTERS Prepared by: Anthony (Tony) Hoevenaars, P. Eng President and CEO Mirus International Inc. Copyright 2012 Mirus International

More information

ACTURA 4855. -48 V DC, 3-40 kw, 60-800 A. The Regional DC power system with Global Muscle

ACTURA 4855. -48 V DC, 3-40 kw, 60-800 A. The Regional DC power system with Global Muscle ACTURA 4855-48 V DC, 3-40 kw, 60-800 A The Regional DC power system with Global Muscle Reliability or Price Efficiency? Now you can have both! Customized power systems with high reliability at a competitive

More information

High-Efficiency AC Power Distribution for Data Centers

High-Efficiency AC Power Distribution for Data Centers High-Efficiency AC Power Distribution for Data Centers White Paper 128 Revision 2 by Neil Rasmussen > Executive summary The use of 240 volt power distribution for data centers saves floor space, simplifies

More information

Data Center Energy Efficiency Looking Beyond PUE

Data Center Energy Efficiency Looking Beyond PUE Data Center Energy Efficiency Looking Beyond PUE No Limits Software White Paper #4 By David Cole 2011 No Limits Software. All rights reserved. No part of this publication may be used, reproduced, photocopied,

More information

Better Cooling With Slower CRAC Fans

Better Cooling With Slower CRAC Fans Better Cooling With Slower CRAC Fans Dennis P. Symanski EPRI - Senior Project Manager SVLG Data Center Efficiency Summit 24OCT2012 AMD Sunnyvale, CA Thanks To The California Energy Commission!!! 2 EPRI

More information

Harmonizing Global Metrics for Data Center Energy Efficiency

Harmonizing Global Metrics for Data Center Energy Efficiency Harmonizing Global Metrics for Data Center Energy Efficiency Dan Azevedo, Symantec Chairman - Metrics & Measurements Work Group Industry Trends Energy Efficient IT The Climate Group: Smarter technology

More information

Improving Sustainability in Campus Data Centers Click To Edit Master Title Style

Improving Sustainability in Campus Data Centers Click To Edit Master Title Style Improving Sustainability in Campus Data Centers Click To Edit Master Title Style March 31, 2015 12:10-1:00 PM ET Agenda Welcome and Better Buildings Overview Michigan State University Partnering with the

More information

Power Distribution Considerations for Data Center Racks

Power Distribution Considerations for Data Center Racks Power Distribution Considerations for Data Center Racks Power Distribution Considerations for Data Center Racks Table of Contents 3 Overview 4 At what voltage do you run all the IT equipment? 4 What electrical

More information

DC MICROGRIDS A SOLAR BACK TO THE FUTURE

DC MICROGRIDS A SOLAR BACK TO THE FUTURE Making high-quality, high-power solar cells and modules using U.S.-based technology at affordable costs to address the world s energy needs DC MICROGRIDS A SOLAR BACK TO THE FUTURE SOL HAROON, LEAD SYSTEMS

More information

Energy Audits Waste Water Treatment Plants

Energy Audits Waste Water Treatment Plants Energy Audits Waste Water Treatment Plants Ohio Water Environment Association Conference June 20, 2012 Presented by: Samuel J. Morgan, P.E., LEED AP CT Consultants, Inc. World Energy Trend US Total Energy

More information

POWER YOUR TELECOM SITE WITH OLYMPIAN Hybrid Power for Telecom Applications Solar Photovoltaic Wind Diesel Battery

POWER YOUR TELECOM SITE WITH OLYMPIAN Hybrid Power for Telecom Applications Solar Photovoltaic Wind Diesel Battery POWER YOUR TELECOM SITE WITH OLYMPIAN Hybrid Power for Telecom Applications Solar Photovoltaic Wind Diesel Battery For more than 85 years, Caterpillar has created products and services that support the

More information

Rules of Thumb Energy Efficiency in Buildings

Rules of Thumb Energy Efficiency in Buildings Energy Efficiency in Buildings Energy Savings Cost Savings Increased Productivity Economic Development Other Standard lighting retrofits: $0.90-$1.20 per square foot. High-efficiency packaged and split

More information

The Efficiency Challenge

The Efficiency Challenge The Efficiency Challenge Balancing Total Cost of Ownership with Real Estate Demands written by: Mike Wagner VP & GM Embedded Power AC-DC The Efficiency Challenge Balancing Total Cost of Ownership with

More information

Univeristà La Sapienza Laurea Magistrale Ingegneria Informatica

Univeristà La Sapienza Laurea Magistrale Ingegneria Informatica Univeristà La Sapienza Laurea Magistrale Ingegneria Informatica Seminario Beyond Green: EMC and Energy Efficient IT Franco Martino EMC Consulting Manager 21 May 2010 1 EMC s Broad Product and Solutions

More information

NIST Coordination and Acceleration of Smart Grid Standards. Tom Nelson National Institute of Standards and Technology 8 December, 2010

NIST Coordination and Acceleration of Smart Grid Standards. Tom Nelson National Institute of Standards and Technology 8 December, 2010 NIST Coordination and Acceleration of Smart Grid Standards Tom Nelson National Institute of Standards and Technology 8 December, 2010 The Electric Grid One of the largest, most complex infrastructures

More information

Power Your Telecom site with olympian Hybrid Power for Telecom Applications Solar Photovoltaic Wind Diesel Battery

Power Your Telecom site with olympian Hybrid Power for Telecom Applications Solar Photovoltaic Wind Diesel Battery Power Your Telecom site with olympian Hybrid Power for Telecom Applications Solar Photovoltaic Wind Diesel Battery For more than 85 years, Caterpillar has created products and services that support the

More information

HVAC Infrastructure Retrofit Solutions

HVAC Infrastructure Retrofit Solutions Kyoto Cooling Lunch & Learn David Belleville, APA LLC March 9, 2015 Owners choose APA solutions to: Rely on our 30+ years of delivering engineered solutions; HVAC Infrastructure Retrofit Solutions Insure

More information

NetSure DC Power Solutions with esure High-Efficiency Technology. DC Power for Business-Critical Continuity TM

NetSure DC Power Solutions with esure High-Efficiency Technology. DC Power for Business-Critical Continuity TM NetSure DC Power Solutions with esure High-Efficiency Technology DC Power for Business-Critical Continuity TM NetSure solutions with esure high-efficiency technology Our Efficiency Without Compromise promise

More information

CENIC 2009 Conference

CENIC 2009 Conference Green Datacenter Initiatives at UCSD CENIC 2009 Conference Dallas Thornton SDSC Division Director, Cyberinfrastructure Services dallas@sdsc.edu Campus Quick Facts With a daily population of over 45,000,

More information

DOE Data Center Energy Efficiency Program

DOE Data Center Energy Efficiency Program DOE Data Center Energy Efficiency Program Paul Scheihing U.S. Department of Energy Energy Efficiency and Renewable Energy April 2009 1 DOE Industrial Technologies Program Worki king to improve th e energy

More information

Data Center Technology: Physical Infrastructure

Data Center Technology: Physical Infrastructure Data Center Technology: Physical Infrastructure IT Trends Affecting New Technologies and Energy Efficiency Imperatives in the Data Center Hisham Elzahhar Regional Enterprise & System Manager, Schneider

More information

Leveraging the Power of Intelligent Motor Control to Maximize HVAC System Efficiency

Leveraging the Power of Intelligent Motor Control to Maximize HVAC System Efficiency Leveraging the Power of Intelligent Motor Control to Maximize HVAC System Efficiency Because HVAC systems comprise a large amount of a building s operating costs, it makes sense to ensure these systems

More information

Business Energy Efficiency. Webinar August 29, 2012

Business Energy Efficiency. Webinar August 29, 2012 Business Energy Efficiency Webinar August 29, 2012 Today s presenters and some notes... John Pirko LeClairRyan Greg Booth PowerServices, Inc. Roy Palk LeClairRyan Welcome. With the high number of attendees,

More information

ECCN Exclusive Product Webinar Electric Vehicle Supply Equipment. Agenda. Presenter Introduction

ECCN Exclusive Product Webinar Electric Vehicle Supply Equipment. Agenda. Presenter Introduction This is a photographic template your photograph should fit precisely within this rectangle. ECCN Exclusive Product Webinar Electric Vehicle Supply Equipment 2008 Eaton Corporation. All rights reserved.

More information

Energy Savings in the Data Center Starts with Power Monitoring

Energy Savings in the Data Center Starts with Power Monitoring Energy Savings in the Data Center Starts with Power Monitoring As global competition intensifies, companies are increasingly turning to technology to help turn mountains of data into a competitive edge.

More information

Is an energy-wasting data center draining your bottom line?

Is an energy-wasting data center draining your bottom line? Abstract Is an energy-wasting data center draining your bottom line? New technology options and power distribution strategies can dramatically reduce the cost and carbon footprint of your data center.

More information

Summary of Electric Power Research Institute (EPRI) Report on Residential Off-Grid System Economics

Summary of Electric Power Research Institute (EPRI) Report on Residential Off-Grid System Economics Summary of Electric Power Research Institute (EPRI) Report on Residential Off-Grid System Economics September 11, 2014 0 Forward-Looking Statements Leading the Way in Electricity SM Statements contained

More information

Geothermal Heat Pumps: A Pathway to Zero Net Energy (ZNE) for Schools, Homes and Businesses

Geothermal Heat Pumps: A Pathway to Zero Net Energy (ZNE) for Schools, Homes and Businesses Lisa Meline, P.E. Meline Engineering Corp. lisa@meline.com Office: 916.366.3458 Geothermal Heat Pumps: A Pathway to Zero Net Energy (ZNE) for Schools, Homes and Businesses Session C: Institutional Applications

More information

Sustainable Smart Laboratories

Sustainable Smart Laboratories Sustainable Smart Laboratories Presented by Cristian Monsalves (Moderator) Program Manager, Energy Efficiency Services, NSTAR Panelists Alison Farmer, Project Manager, Andelman and Lelek Engineering John

More information

Galaxy VM. Three-phase power protection. schneider-electric.com

Galaxy VM. Three-phase power protection. schneider-electric.com Galaxy VM Three-phase power protection schneider-electric.com 2 schneider-electric.com schneider-electric.com 3 Galaxy VM trusted partner for your business continuity Features and benefits Highly efficient,

More information

Eco Server Park The Responsible Power Ready Location

Eco Server Park The Responsible Power Ready Location Eco Server Park The Responsible Power Ready Location Power generation at site, multiple redundancy, transformers in place. Green power biomass, hydro, wind and solar. Site fully owned by the local grid

More information

How Eight California Data Centers Reduced Energy by 20%

How Eight California Data Centers Reduced Energy by 20% How Eight California Data Centers Reduced Energy by 20% Sponsored by the California Energy Commission Public Interest Energy Research David Weightman, Energy Commission Specialist California Energy Commission

More information

Drives and motors. A guide to using variable-speed drives and motors in data centres

Drives and motors. A guide to using variable-speed drives and motors in data centres Drives motors A guide to using variable-speed drives motors in data centres The power behind the data Private public businesses, from banks to supermarkets, to telecommunications companies internet providers

More information

The UCSD/Calit2 GreenLight Instrument Tom DeFanti, PI

The UCSD/Calit2 GreenLight Instrument Tom DeFanti, PI The UCSD/Calit2 GreenLight Instrument Tom DeFanti, PI California Institute for Telecommunications and Information Technology: Calit2 Over 1000 Researchers in Two Buildings Linked via Dedicated Optical

More information

Looking ahead: Future Scenarios for Europe s Power Supply Grid

Looking ahead: Future Scenarios for Europe s Power Supply Grid Michael Weinhold, CTO Energy Management European Utility Week Vienna, November 04, 2015 Looking ahead: Future Scenarios for Europe s Power Supply Grid siemens.com/euw Global Wind and Photovolatic Power

More information

Server Technology, Inc.

Server Technology, Inc. Server Technology, Inc. Power Efficiency Gains by Deploying 415 VAC Power Distribution in North American Data Centers White Paper STI-100-008 2009-April-07 Headquarters Server Technology, Inc. 1040 Sandhill

More information

400V DC Microgrid Small Scale Demo System for Telecom and Datacom Applications

400V DC Microgrid Small Scale Demo System for Telecom and Datacom Applications WHITE PAPER 400V DC Microgrid Small Scale Demo System for Telecom and Datacom Applications Presented at 1. Objective This live demonstration of a 400V DC powered eco-system, validates the feasibility of

More information

Server room guide helps energy managers reduce server consumption

Server room guide helps energy managers reduce server consumption Server room guide helps energy managers reduce server consumption Jan Viegand Viegand Maagøe Nr. Farimagsgade 37 1364 Copenhagen K Denmark jv@viegandmaagoe.dk Keywords servers, guidelines, server rooms,

More information

Low Carbon Data Centres without compromise

Low Carbon Data Centres without compromise Low Carbon Data Centres without compromise Thursday 16 th September 2010 Pip Squire, Engineering & Project Director delivered by: Ark Continuity - Continuously Delivering high integrity data centres Introduction

More information

UPS Topologies & Architectures. Don Lemmon Tubbesing Solutions (214) 690-6866 don@tubbesing.com

UPS Topologies & Architectures. Don Lemmon Tubbesing Solutions (214) 690-6866 don@tubbesing.com UPS Topologies & Architectures Don Lemmon Tubbesing Solutions (214) 690-6866 don@tubbesing.com Tubbesing Solutions & Tubbesing Solutions Mike Farrell Mobile No. (214) 355-0493 Tubbesing Solutions Portfolio

More information

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates

More information

Integration of a 400W ac dc power supply into a closed system relying only on natural convection cooling

Integration of a 400W ac dc power supply into a closed system relying only on natural convection cooling Integration of a 400W ac dc power supply into a closed system relying only on natural convection cooling How potting an electronic assembly simplifies the thermal management in harsh working conditions

More information

Myth-busting: The Truth Behind Data Center Marketing Trends. Presentation Code 27631

Myth-busting: The Truth Behind Data Center Marketing Trends. Presentation Code 27631 Myth-busting: The Truth Behind Data Center Marketing Trends Presentation Code 27631 Dave Sterlace March 25, 2013 Speaker name: Speaker title: Dave Sterlace Market Development Manager Data Centers Company

More information

DC Power Solutions Overview. DC Power Solutions for EVERY Network Application.

DC Power Solutions Overview. DC Power Solutions for EVERY Network Application. DC Power Solutions Overview DC Power Solutions for EVERY Network Application. DC Power Solutions for Every Network Application Eaton recognizes the challenges that are unique to different customers applications.

More information

Data Center Leadership In the DOE Better Buildings Challenge

Data Center Leadership In the DOE Better Buildings Challenge Symposium Southern California February 18th, 2015 Data Center Leadership In the DOE Better Buildings Challenge Applying Best Practices to meet the Challenge Dale Sartor, PE Lawrence Berkeley National Laboratory

More information

Re Engineering to a "Green" Data Center, with Measurable ROI

Re Engineering to a Green Data Center, with Measurable ROI Re Engineering to a "Green" Data Center, with Measurable ROI Alan Mamane CEO and Founder Agenda Data Center Energy Trends Benchmarking Efficiency Systematic Approach to Improve Energy Efficiency Best Practices

More information

Data Centre Cooling Technologies. Jon Pettitt, EMEA DataCenter Business Development Manager

Data Centre Cooling Technologies. Jon Pettitt, EMEA DataCenter Business Development Manager Data Centre Cooling Technologies 1 Jon Pettitt, EMEA DataCenter Business Development Manager Munters Group Key facts 3.000 Employees 30 Countries Turnover of 470 M HQ in Sweden Global DC Support 25+ Data

More information

The Green/ Efficiency Metrics Conundrum. Anand Ekbote Vice President, Liebert Monitoring Emerson Network Power

The Green/ Efficiency Metrics Conundrum. Anand Ekbote Vice President, Liebert Monitoring Emerson Network Power The Green/ Efficiency Metrics Conundrum Anand Ekbote Vice President, Liebert Monitoring Emerson Network Power Agenda Green Grid, and Green/ Efficiency Metrics Data Center Efficiency Revisited Energy Logic

More information

Presented at Computing in High Energy & Nuclear Physics

Presented at Computing in High Energy & Nuclear Physics Presented at Computing in High Energy & Nuclear Physics CHEP - Prague, Czech Republic March 25, 2009 Dean Nelson Sr. Director, Global Lab & Datacenter Design Services (GDS) 1 Density is King - Moore s

More information

Convergence of Complexity

Convergence of Complexity Convergence of Complexity Optimize Existing Data Center Space Measure And Allocate Energy Cost Plan for new data centers or additional capacity How to make your Data Center Last Longer, Gartner, December

More information

Roadmap to Sustainability. Chuck Graff Director CNT April 27, 2010

Roadmap to Sustainability. Chuck Graff Director CNT April 27, 2010 Roadmap to Sustainability Chuck Graff Director CNT April 27, 2010 Agenda Aligning Verizon s Corporate EE Initiatives The Green Network TEEER Energy Efficiency Metrics New EE programs for 2010 TMST RoHS

More information

Green Data Centers. Energy Efficiency Data Centers. André ROUYER Director of Standardization & Environment. The importance of standardization

Green Data Centers. Energy Efficiency Data Centers. André ROUYER Director of Standardization & Environment. The importance of standardization Green Data Centers GOING FORWARD ENERGY EFFICIENCY TRENDS André ROUYER Director of Standardization & Environment All content in this presentation is protected 2008 American Power Conversion Corporation

More information

Increasing Energ y Efficiency In Data Centers

Increasing Energ y Efficiency In Data Centers The following article was published in ASHRAE Journal, December 2007. Copyright 2007 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes

More information

Lorraine Hudson Bristol City Council GREEN DIGITAL CITY

Lorraine Hudson Bristol City Council GREEN DIGITAL CITY Lorraine Hudson Bristol City Council GREEN DIGITAL CITY Green Digital Charter Bristol signed in 2010 Bristol s 2 strand approach: Green ICT: improving energy efficiency in ICT Smart City Bristol: using

More information

Data Centre and ICT Energy Metrics - The View from Australia

Data Centre and ICT Energy Metrics - The View from Australia 2010/TEL42/DSG/WKSP2/013 Data Centre and ICT Energy Metrics - The View from Australia Submitted by: Australia Green ICT Seminar Bandar Seri Begawan, Brunei Darussalam 3 August 2010 Data Centre and ICT

More information

Connection method for charging systems a key element for electric vehicles

Connection method for charging systems a key element for electric vehicles Connection method for charging systems a key element for electric vehicles By Claude Ricaud and Philippe Vollet > Abstract At the heart of the energy and environmental challenges, the electric vehicle

More information

World s Greenest High Performance Data Center

World s Greenest High Performance Data Center World s Greenest High Performance Data Center EcoDataCenter Sustainability for future generations Our Services Colocation Data Center for Mission Critical Requirements Lockable racks, cages, private rooms

More information

Improving Data Centers Energy Reliability & Efficiency. December 2015

Improving Data Centers Energy Reliability & Efficiency. December 2015 Improving Data Centers Energy Reliability & Efficiency December 2015 Background The challenges Alternative solutions SATEC approach Advantages Cases Summary Data Centers Energy Challenges Worldwide Data

More information

European Code of Conduct for Data Centre. Presentation of the Awards 2013

European Code of Conduct for Data Centre. Presentation of the Awards 2013 European Code of Conduct for Data Centre Presentation of the Awards 2013 Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 The Code of Conduct for Data Centre Results Started

More information