1 Data Center Energy Efficient Cooling Control Demonstration PIR (formerly Federspiel Controls)

2 Background 2009 PIER sponsored project resulted in the installation of intelligent supervisory control and wireless mesh network sensing systems to reduce cooling energy at the California Franchise Tax Board s Sacramento data center. Elements of the energy saving system: perforated floor tiles for the under floor air distribution system variable frequency drives (VFDs) for fans, wireless temperature and humidity sensors connected in a mesh network components are connected to intelligent control software and adapts to changing conditions to ensure data center reliability and minimize cooling energy consumption

3 Major Accomplishments from the 2009 Project Cutting costs in Data Centers (State Partnership for Energy Efficient Demonstrations) Data centers consume over 9 billion kwh/year Partners: California Franchise Tax Board, Federspiel Controls, Lawrence Berkeley National Labs Purpose: Install data automation software and hardware system that uses wireless sensors and web based software to control computer room air conditioning units. Results: Lowered total energy use by 21.3% Saved 475,000 kwh/yr Payback of 3.1 years Bottom line: $42,722 per year saved Technology Transfer: FTB plans to use this technology in other data centers. Federspiel Controls subsequently secured a federal grant to expand this technology to 12 other state owned data centers. 3

4 Background (Continued) In 2010, the U.S. Department of Energy and the California Energy Commission granted funds to Federspiel Controls to replicate the success of the 2009 project under varying conditions in eight State of California data centers. These grant awards would not have been possible without the success of the 2009 project. In May 2011, Federspiel Controls changed its name to Vigilent.

5 DOE Information and Communication Technology Portfolio Commenting on the 14 project U.S. Department of Energy portfolio of energy grants that includes this project, U.S. Secretary of Energy Steven Chu announced: By reducing energy use and energy costs for the information technology and telecommunications industries, this funding will help create jobs and ensure the sector remains competitive.

6 Project Uniqueness and Approach Tested technology at eight data centers of varying sizes from small localized data centers (< 1000 square feet) to medium and large data centers (up to 40,000 square feet). The sites and results are listed on the following slide. Tested data center reliability with variations in cooling unit types, equipment ages, and data center layouts. The American Society of Heating, Refrigerating, and Air Conditioning Engineers (ASHRAE) publishes acceptable temperature ranges for inlet air to data center equipment. This project produced energy savings by implementing an intelligent energy management system that measures, monitors and actively controls cooling units, providing just enough cooling to meet ASHRAE requirements.

7 Data Center Sites and Results Site Name Gold Camp Employment Development Department Franchise Tax Board Department of Water Resources Caltrans 2nd Floor Secretary of State Ziggurat Caltrans 9th Floor Totals City Rancho Cordova Sacramento Sacramento Sacramento Los Angeles Sacramento West Sacramento Los Angeles Square Feet Sensors CRAHs Annual kwh Savings Annual Dollar Savings Cooling Energy Reduced 40, ,174 $48,417 19% 12, ,049 $43,305 54% 12, ,045 $69,705 78% 5, ,348 $28,835 40% 4, ,555 $17,947 64% 2, ,084 $3,708 30% 2, ,134 $11,358 50% ,135 $16,816 64% 79, ,313,524 $240,091 Average 41%

8 Funding and Job Creation Source of Funds Cost Share U.S. Department of Energy $584,079 California Energy Commission PIER Program $250,000 California Department of General Services and Office of Technology Services $50,000 Federspiel Controls, Inc. / Vigilent $205,399 Supplier Cost Match and Utility Incentives $118,939 Job Creation Eleven jobs were created as a result of this project. Two companies directly benefited from this project and increased their workforce: Vigilent added four highly skilled positions that were full-time advanced technical or managerial positions, and one part-time position. UMAI, which manufactures Vigilent hardware, added six full-time employees to its staff as a result of Vigilent orders. This website indicates the total 11 jobs that were created in California: IdSur=90014

9 Gold Camp floor plan

10 Gold Camp thermal map before active controls went live (February 2011)

11 Gold Camp thermal map after active controls went live (July 2011)

12 Summary of System Benefits Major energy savings and carbon reduction Improved thermal management Cooling capacity increases, reducing capital expenditure Improved resilience and risk management due to the system s predictive model The system learns and adjusts to new equipment configurations (self maintaining) Quick payback and ROI Works with varying data center capacity, floor plan, and equipment type and age Quick installation

Energy Research and Development Division FINAL PROJECT REPORT

Energy Research and Development Division FINAL PROJECT REPORT Energy Research and Development Division FINAL PROJECT REPORT RECOVERY ACT: FEDERSPIEL CONTROLS (NOW VIGILENT) AND STATE OF CALIFORNIA DEPARTMENT OF GENERAL SERVICES DATA CENTER ENERGY EFFICIENT COOLING

More information

How Eight California Data Centers Reduced Energy by 20%

How Eight California Data Centers Reduced Energy by 20% How Eight California Data Centers Reduced Energy by 20% Sponsored by the California Energy Commission Public Interest Energy Research David Weightman, Energy Commission Specialist California Energy Commission

More information

Control of Computer Room Air Handlers Using Wireless Sensors. Energy Efficient Data Center Demonstration Project

Control of Computer Room Air Handlers Using Wireless Sensors. Energy Efficient Data Center Demonstration Project Control of Computer Room Air Handlers Using Wireless Sensors Energy Efficient Data Center Demonstration Project About the Energy Efficient Data Center Demonstration Project The project s goal is to identify

More information

How To Save Energy With A Smart Thermostat

How To Save Energy With A Smart Thermostat American Recovery and Reinvestment Act Public Interest Energy Research (PIER) Program FINAL TECHNICAL PROJECT REPORT DA Recovery Act: Federspiel Controls (now Vigilent) and State of California Department

More information

Prepared For: California Energy Commission Public Interest Energy Research Program

Prepared For: California Energy Commission Public Interest Energy Research Program Demonstration of Datacenter Automation Software and Hardware (DASH) at the California Franchise Tax Board Prepared For: California Energy Commission Public Interest Energy Research Program Prepared By:

More information

Wireless Sensor Technology for Data Centers

Wireless Sensor Technology for Data Centers Wireless Sensor Technology for Data Centers Richard Oberg and Ed Sanchez, Sacramento Municipal Utility District Patricia Nealon, Synapsense Corporation ABSTRACT This paper describes the development and

More information

Re Engineering to a "Green" Data Center, with Measurable ROI

Re Engineering to a Green Data Center, with Measurable ROI Re Engineering to a "Green" Data Center, with Measurable ROI Alan Mamane CEO and Founder Agenda Data Center Energy Trends Benchmarking Efficiency Systematic Approach to Improve Energy Efficiency Best Practices

More information

Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers

Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers Prepared for the U.S. Department of Energy s Federal Energy Management Program Prepared By Lawrence Berkeley National

More information

HPPR Data Center Improvements Projects Towards Energy Efficiency (CFD Analysis, Monitoring, etc.)

HPPR Data Center Improvements Projects Towards Energy Efficiency (CFD Analysis, Monitoring, etc.) HPPR Data Center Improvements Projects Towards Energy Efficiency (CFD Analysis, Monitoring, etc.) Felipe Visbal / March 27, 2013 HPPR Data Center Technologies Team Services Data Centers: Thermal Assessments

More information

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory

More information

AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings

AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings WH I TE PAPE R AisleLok Modular Containment vs. : A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings By Bruce Long, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies,

More information

Increasing Energ y Efficiency In Data Centers

Increasing Energ y Efficiency In Data Centers The following article was published in ASHRAE Journal, December 2007. Copyright 2007 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes

More information

Catalyst RTU Controller Study Report

Catalyst RTU Controller Study Report Catalyst RTU Controller Study Report Sacramento Municipal Utility District December 15, 2014 Prepared by: Daniel J. Chapmand, ADM and Bruce Baccei, SMUD Project # ET13SMUD1037 The information in this report

More information

How To Improve Energy Efficiency Through Raising Inlet Temperatures

How To Improve Energy Efficiency Through Raising Inlet Temperatures Data Center Operating Cost Savings Realized by Air Flow Management and Increased Rack Inlet Temperatures William Seeber Stephen Seeber Mid Atlantic Infrared Services, Inc. 5309 Mohican Road Bethesda, MD

More information

80% of. 50% of. 30% of. 67% of enterprises. Environmental and business demands are converging

80% of. 50% of. 30% of. 67% of enterprises. Environmental and business demands are converging Delivering the Green Datacenter Jerome Riboulon, HP 2008 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice 2 24 Abril, 2008 Environmental and

More information

Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling

Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling Joshua Grimshaw Director of Engineering, Nova Corporation

More information

General Recommendations for a Federal Data Center Energy Management Dashboard Display

General Recommendations for a Federal Data Center Energy Management Dashboard Display General Recommendations for a Federal Data Center Energy Management Dashboard Display Prepared for the U.S. Department of Energy s Federal Energy Management Program Prepared By Lawrence Berkeley National

More information

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Lars Strong, P.E., Upsite Technologies, Inc. Kenneth G. Brill, Upsite Technologies, Inc. 505.798.0200

More information

Introducing AUDIT- BUDDY

Introducing AUDIT- BUDDY Introducing AUDIT- BUDDY Monitoring Temperature and Humidity for Greater Data Center Efficiency 202 Worcester Street, Unit 5, North Grafton, MA 01536 www.purkaylabs.com info@purkaylabs.com 1.774.261.4444

More information

REAL OPERATING COST SAVINGS FROM RETRO- COMMISSIONING OPPORTUNITIES FOR SAVINGS IN ACADEMIC MEDICAL CENTERS

REAL OPERATING COST SAVINGS FROM RETRO- COMMISSIONING OPPORTUNITIES FOR SAVINGS IN ACADEMIC MEDICAL CENTERS REAL OPERATING COST SAVINGS FROM RETRO- COMMISSIONING OPPORTUNITIES FOR SAVINGS IN ACADEMIC MEDICAL CENTERS Ken L. Hansen P.E. University of Nebraska Medical Center hansenkl@unmc.edu 402-559- 5301 402-630-

More information

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the

More information

Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint

Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint Energy usage in the data center Electricity Transformer/ UPS Air 10% Movement 12% Cooling 25% Lighting, etc. 3% IT Equipment

More information

Adaptive Cooling in Data Centers. Silicon Valley Leadership Group Energy Efficient Data Center Demonstration Project October, 2009

Adaptive Cooling in Data Centers. Silicon Valley Leadership Group Energy Efficient Data Center Demonstration Project October, 2009 Adaptive Cooling in Data Centers Silicon Valley Leadership Group Energy Efficient Data Center Demonstration Project October, 2009 Maximizing Cooling Efficiency in a Concurrently Maintainable and Fault

More information

Harmonizing Global Metrics for Data Center Energy Efficiency

Harmonizing Global Metrics for Data Center Energy Efficiency Harmonizing Global Metrics for Data Center Energy Efficiency Dan Azevedo, Symantec Chairman - Metrics & Measurements Work Group Industry Trends Energy Efficient IT The Climate Group: Smarter technology

More information

National Grid Your Partner in Energy Solutions

National Grid Your Partner in Energy Solutions National Grid Your Partner in Energy Solutions National Grid Webinar: Enhancing Reliability, Capacity and Capital Expenditure through Data Center Efficiency April 8, 2014 Presented by: Fran Boucher National

More information

RESEARCH BRIEF. Savings and Operational Efficiencies for the Industrial/Warehouse Environment

RESEARCH BRIEF. Savings and Operational Efficiencies for the Industrial/Warehouse Environment Savings and Operational Efficiencies for the Industrial/Warehouse Environment October, 2015 3 Internet of Things Savings and Operational Efficiencies for the Industrial/ Warehouse Environment THE (IoT)

More information

Focus on Cold Storage Evaporator Fan VFDs Is a Market Transformation Success

Focus on Cold Storage Evaporator Fan VFDs Is a Market Transformation Success Focus on Cold Storage Evaporator Fan VFDs Is a Market Transformation Success Andy Ekman, Northwest Energy Efficiency Alliance Philipp Degens, Northwest Energy Efficiency Alliance Rob Morton, Cascade Energy

More information

DataCenter 2020: first results for energy-optimization at existing data centers

DataCenter 2020: first results for energy-optimization at existing data centers DataCenter : first results for energy-optimization at existing data centers July Powered by WHITE PAPER: DataCenter DataCenter : first results for energy-optimization at existing data centers Introduction

More information

Energy management White paper. Greening the data center with IBM Tivoli software: an integrated approach to managing energy.

Energy management White paper. Greening the data center with IBM Tivoli software: an integrated approach to managing energy. Energy management White paper Greening the data center with IBM Tivoli software: an integrated approach to managing energy. May 2008 2 Contents 3 Key considerations for the green data center 3 Managing

More information

ENERGY SOLUTIONS FOR BUSINESS CUSTOMERS

ENERGY SOLUTIONS FOR BUSINESS CUSTOMERS ENERGY SOLUTIONS FOR BUSINESS CUSTOMERS Electric League, March 25, 2016 Lori Moen Manager Solutions Design and Managment AGENDA 1. What is Customer Energy Solutions? 2. What do we do? 3. How do you work

More information

Unique Airflow Visualization Techniques for the Design and Validation of Above-Plenum Data Center CFD Models

Unique Airflow Visualization Techniques for the Design and Validation of Above-Plenum Data Center CFD Models Unique Airflow Visualization Techniques for the Design and Validation of Above-Plenum Data Center CFD Models The MIT Faculty has made this article openly available. Please share how this access benefits

More information

Cisco Data Center Facilities Assessment Service

Cisco Data Center Facilities Assessment Service Cisco Data Center Facilities Assessment Service Increase the availability, capacity, and life of your data center facility. Service Overview Data centers must respond to changing business needs, environmental

More information

Energy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie

Energy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie Energy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie Mukesh Khattar, Energy Director, Oracle National Energy Efficiency Technology Summit, Sep. 26, 2012, Portland, OR Agenda

More information

Vigilent shows market awareness with datacenter dynamic cooling update

Vigilent shows market awareness with datacenter dynamic cooling update Vigilent shows market awareness with datacenter dynamic cooling update Analyst: Rhonda Ascierto 15 Jan, 2014 Vigilent, formerly known as Federspiel Controls, appears to be pulling ahead in the small yet

More information

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Kenneth G. Brill, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies, Inc. 505.798.0200

More information

Case Study 27 Energy Savings from Preventative Maintenance of Small to Medium Sized Ducted Air Conditioning Units

Case Study 27 Energy Savings from Preventative Maintenance of Small to Medium Sized Ducted Air Conditioning Units Case Study 27 Energy Savings from Preventative Maintenance of Small to Medium Sized Ducted Air Conditioning Units Objective: To reduce the energy consumption of ducted air conditioners through preventive

More information

Data Center RD&D at EPRI

Data Center RD&D at EPRI Data Center RD&D at EPRI Mukesh Khattar Technical Executive Critical facilities Round Table Meeting Palo Alto, CA 16 October 2015 EPRI Focus for Data Centers RD&D Address problems facing the member electric

More information

Boosting the Energy efficiency of a Server Room: experimental + virtual approach.

Boosting the Energy efficiency of a Server Room: experimental + virtual approach. Boosting the Energy efficiency of a Server Room: experimental + virtual approach. Nowadays, the increase in computing power allows the successful applications of the CFD simulation methods in civil environments.

More information

Extend the Life of Your Data Center By Ian Seaton Global Technology Manager iseaton@chatsworth.com

Extend the Life of Your Data Center By Ian Seaton Global Technology Manager iseaton@chatsworth.com C P I C O N TA I N M E N T S O L U T I O N S WHITE PAPER Extend the Life of Your Data Center By Ian Seaton Global Technology Manager iseaton@chatsworth.com Published August 2013 800-834-4969 techsupport@chatsworth.com

More information

Managing Energy Consumption for Optimal Productivity and Higher Profitability. Rockwell Automation solutions for energy management

Managing Energy Consumption for Optimal Productivity and Higher Profitability. Rockwell Automation solutions for energy management Managing Energy Consumption for Optimal Productivity and Higher Profitability Rockwell Automation solutions for energy management Experience the Transformation Transform your production. How will you adapt

More information

Networked Wireless Building Control

Networked Wireless Building Control Networked Wireless Building Control Jump start to the Enterprise IoT Danny Yu Daintree Networks Tuesday, May 19, 2015 Our industry still needs a connectivity breakthrough Persistent value for advanced

More information

Managing Data Centre Heat Issues

Managing Data Centre Heat Issues Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design

More information

Dealing with Thermal Issues in Data Center Universal Aisle Containment

Dealing with Thermal Issues in Data Center Universal Aisle Containment Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe Daniele.Tordin@Panduit.com AGENDA Business Drivers Challenges

More information

Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre

Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre S. Luong 1*, K. Liu 2, James Robey 3 1 Technologies for Sustainable Built Environments, University of Reading,

More information

GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group

GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY Public Sector ICT Special Working Group SERVER ROOM ENERGY EFFICIENCY This guide is one of a suite of documents that aims to provide guidance on ICT energy efficiency.

More information

FAC 2.1: Data Center Cooling Simulation. Jacob Harris, Application Engineer Yue Ma, Senior Product Manager

FAC 2.1: Data Center Cooling Simulation. Jacob Harris, Application Engineer Yue Ma, Senior Product Manager FAC 2.1: Data Center Cooling Simulation Jacob Harris, Application Engineer Yue Ma, Senior Product Manager FAC 2.1: Data Center Cooling Simulation Computational Fluid Dynamics (CFD) can be used to numerically

More information

Improving Data Center Energy Efficiency Through Environmental Optimization

Improving Data Center Energy Efficiency Through Environmental Optimization Improving Data Center Energy Efficiency Through Environmental Optimization How Fine-Tuning Humidity, Airflows, and Temperature Dramatically Cuts Cooling Costs William Seeber Stephen Seeber Mid Atlantic

More information

Blade Server & Data Room Cooling Specialists

Blade Server & Data Room Cooling Specialists SURVEY I DESIGN I MANUFACTURE I INSTALL I COMMISSION I SERVICE SERVERCOOL An Eaton-Williams Group Brand Blade Server & Data Room Cooling Specialists Manufactured in the UK SERVERCOOL Cooling IT Cooling

More information

Environmental Data Center Management and Monitoring

Environmental Data Center Management and Monitoring 2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor

More information

Bells and Whistles, or Just Plain Effective? The New Generation of Wireless Controls in Existing Commercial Buildings.

Bells and Whistles, or Just Plain Effective? The New Generation of Wireless Controls in Existing Commercial Buildings. Bells and Whistles, or Just Plain Effective? The New Generation of Wireless Controls in Existing Commercial Buildings. Sandra LaFlamme, PE Energy Consultant Vermont Energy Investment Corporation Burlington,

More information

Prediction Is Better Than Cure CFD Simulation For Data Center Operation.

Prediction Is Better Than Cure CFD Simulation For Data Center Operation. Prediction Is Better Than Cure CFD Simulation For Data Center Operation. This paper was written to support/reflect a seminar presented at ASHRAE Winter meeting 2014, January 21 st, by, Future Facilities.

More information

ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM

ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM J.S. Hu, Philip C.W. Kwong, and Christopher Y.H. Chao Department of Mechanical Engineering, The Hong Kong University of Science and Technology Clear Water Bay,

More information

The Benefits of Supply Air Temperature Control in the Data Centre

The Benefits of Supply Air Temperature Control in the Data Centre Executive Summary: Controlling the temperature in a data centre is critical to achieving maximum uptime and efficiency, but is it being controlled in the correct place? Whilst data centre layouts have

More information

Introducing Computational Fluid Dynamics Virtual Facility 6SigmaDC

Introducing Computational Fluid Dynamics Virtual Facility 6SigmaDC IT Infrastructure Services Ltd Holborn Gate, 330 High Holborn, London, WC1V 7QT Telephone: +44 (0)20 7849 6848 Fax: +44 (0)20 7203 6701 Email: info@itisltd.co.uk www.itisltd.com Introducing Computational

More information

Demonstration of Data Center Energy Use Prediction Software

Demonstration of Data Center Energy Use Prediction Software LBNL-6608E Demonstration of Data Center Energy Use Prediction Software Henry Coles, Steve Greenberg and William Tschudi Environmental Energy Technologies Division September 2013 DISCLAIMER This report

More information

AIRAH Presentation April 30 th 2014

AIRAH Presentation April 30 th 2014 Data Centre Cooling Strategies The Changing Landscape.. AIRAH Presentation April 30 th 2014 More Connections. More Devices. High Expectations 2 State of the Data Center, Emerson Network Power Redefining

More information

Data Center Components Overview

Data Center Components Overview Data Center Components Overview Power Power Outside Transformer Takes grid power and transforms it from 113KV to 480V Utility (grid) power Supply of high voltage power to the Data Center Electrical Room

More information

Thermal Monitoring Best Practices Benefits gained through proper deployment and utilizing sensors that work with evolving monitoring systems

Thermal Monitoring Best Practices Benefits gained through proper deployment and utilizing sensors that work with evolving monitoring systems NER Data Corporation White Paper Thermal Monitoring Best Practices Benefits gained through proper deployment and utilizing sensors that work with evolving monitoring systems Introduction Data centers are

More information

Rules of Thumb Energy Efficiency in Buildings

Rules of Thumb Energy Efficiency in Buildings Energy Efficiency in Buildings Energy Savings Cost Savings Increased Productivity Economic Development Other Standard lighting retrofits: $0.90-$1.20 per square foot. High-efficiency packaged and split

More information

Data Centers: How Does It Affect My Building s Energy Use and What Can I Do?

Data Centers: How Does It Affect My Building s Energy Use and What Can I Do? Data Centers: How Does It Affect My Building s Energy Use and What Can I Do? 1 Thank you for attending today s session! Please let us know your name and/or location when you sign in We ask everyone to

More information

Energy consumption and heat recovery of refrigeration system in modern Arena

Energy consumption and heat recovery of refrigeration system in modern Arena Energy consumption and heat recovery of refrigeration system in modern Arena By Alexander Cohr Pachai Johnson Controls Building Efficiency Christian X s Vej 201 8270 Hoejbjerg Denmark alexander.c.pachai@jci.com

More information

Managing Cooling Capacity & Redundancy In Data Centers Today

Managing Cooling Capacity & Redundancy In Data Centers Today Managing Cooling Capacity & Redundancy In Data Centers Today About AdaptivCOOL 15+ Years Thermal & Airflow Expertise Global Presence U.S., India, Japan, China Standards & Compliances: ISO 9001:2008 RoHS

More information

Benefits of Cold Aisle Containment During Cooling Failure

Benefits of Cold Aisle Containment During Cooling Failure Benefits of Cold Aisle Containment During Cooling Failure Introduction Data centers are mission-critical facilities that require constant operation because they are at the core of the customer-business

More information

Data Center Cooling & Air Flow Management. Arnold Murphy, CDCEP, CDCAP March 3, 2015

Data Center Cooling & Air Flow Management. Arnold Murphy, CDCEP, CDCAP March 3, 2015 Data Center Cooling & Air Flow Management Arnold Murphy, CDCEP, CDCAP March 3, 2015 Strategic Clean Technology Inc Focus on improving cooling and air flow management to achieve energy cost savings and

More information

Access Server Rack Cabinet Compatibility Guide

Access Server Rack Cabinet Compatibility Guide Access Server Rack Cabinet Compatibility Guide A Guide to the Selection and Evaluation of Access Server Rack Cabinets for Compatibility and Use with Third Party Server Chassis Kalkenstraat 91-93 B-8800

More information

Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001

Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue

More information

Variable-Speed Fan Retrofits for Computer-Room Air Conditioners

Variable-Speed Fan Retrofits for Computer-Room Air Conditioners Variable-Speed Fan Retrofits for Computer-Room Air Conditioners Prepared for the U.S. Department of Energy Federal Energy Management Program Technology Case Study Bulletin By Lawrence Berkeley National

More information

Improving Data Center Efficiency with Rack or Row Cooling Devices:

Improving Data Center Efficiency with Rack or Row Cooling Devices: Improving Data Center Efficiency with Rack or Row Cooling Devices: Results of Chill-Off 2 Comparative Testing Introduction In new data center designs, capacity provisioning for ever-higher power densities

More information

Strategies and Incentives for Retrofitting Commercial Buildings to Reduce Energy Consumption

Strategies and Incentives for Retrofitting Commercial Buildings to Reduce Energy Consumption Strategies and Incentives for Retrofitting Commercial Buildings to Reduce Energy Consumption Cory Vanderpool Business Development Director EnOcean Alliance Harrisonburg, VA USA ABSTRACT Rising electricity

More information

SIFMA 2009. Data Center Design. IBM Research. Tom Keller, Austin Lab. Hendrik Hamann, T.J. Watson Lab

SIFMA 2009. Data Center Design. IBM Research. Tom Keller, Austin Lab. Hendrik Hamann, T.J. Watson Lab SIFMA 2009 Securities Industry and Financial Markets Association Technology Conference June 2009 Data Center Design Tom Keller, Austin Lab tkeller@us.ibm.com Hendrik Hamann, T.J. Watson Lab hendrikh@us.ibm.com

More information

The Other Half of the Problem Server Closets and Small Server Rooms

The Other Half of the Problem Server Closets and Small Server Rooms The Other Half of the Problem Server Closets and Small Server Rooms Bill Tschudi Lawrence Berkeley National Laboratory October 24, 2012 wftschudi@lbl.gov SVLG Data Center Summit NEED TO CONVERT OT NON-STANFORD

More information

Wireless Sensors Improve Data Center Energy Efficiency

Wireless Sensors Improve Data Center Energy Efficiency Wireless Sensors Improve Data Center Energy Efficiency Technology Case Study Bulletin: September 2010 As data center energy densities, measured in power per square foot, increase, energy savings for cooling

More information

How to Build a Data Centre Cooling Budget. Ian Cathcart

How to Build a Data Centre Cooling Budget. Ian Cathcart How to Build a Data Centre Cooling Budget Ian Cathcart Chatsworth Products Topics We ll Cover Availability objectives Space and Load planning Equipment and design options Using CFD to evaluate options

More information

Leveraging the Power of Intelligent Motor Control to Maximize HVAC System Efficiency

Leveraging the Power of Intelligent Motor Control to Maximize HVAC System Efficiency Leveraging the Power of Intelligent Motor Control to Maximize HVAC System Efficiency Because HVAC systems comprise a large amount of a building s operating costs, it makes sense to ensure these systems

More information

User interfaces: smart phone/web-based Control algorithms: schedule, optimization, demand response. Database (Time series service) smap driver

User interfaces: smart phone/web-based Control algorithms: schedule, optimization, demand response. Database (Time series service) smap driver Software-Defined Solutions for Managing Energy Use in Small to Medium Sized Commercial Buildings 2014 Building Technologies Office Peer Review Building Operating System Services (BOSS) Security/Authorization

More information

A Comparative Study of Various High Density Data Center Cooling Technologies. A Thesis Presented. Kwok Wu. The Graduate School

A Comparative Study of Various High Density Data Center Cooling Technologies. A Thesis Presented. Kwok Wu. The Graduate School A Comparative Study of Various High Density Data Center Cooling Technologies A Thesis Presented by Kwok Wu to The Graduate School in Partial Fulfillment of the Requirements for the Degree of Master of

More information

Data Center Efficiency Program. Josh McKnight, Program Manager Ryan Allsop, Engineer

Data Center Efficiency Program. Josh McKnight, Program Manager Ryan Allsop, Engineer Data Center Efficiency Program Josh McKnight, Program Manager Ryan Allsop, Engineer Agenda Program Overview Target Markets Common Measures Application Process Case Study Examples Questions to Ask Customers

More information

AIA Provider: Colorado Green Building Guild Provider Number: 50111120. Speaker: Geoff Overland

AIA Provider: Colorado Green Building Guild Provider Number: 50111120. Speaker: Geoff Overland AIA Provider: Colorado Green Building Guild Provider Number: 50111120 Office Efficiency: Get Plugged In AIA Course Number: EW10.15.14 Speaker: Geoff Overland Credit(s) earned on completion of this course

More information

How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems

How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems Paul Mathew, Ph.D., Staff Scientist Steve Greenberg, P.E., Energy Management Engineer

More information

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency

More information

Los Angeles Community College District

Los Angeles Community College District Los Angeles Community College District BLUE AND GREEN TOGETHER Developing Sustainable Integrated Approaches to Green Technologies and Water Usage Green California Schools and Community Colleges October

More information

High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc.

High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. High Density Data Centers Fraught with Peril Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. Microprocessors Trends Reprinted with the permission of The Uptime Institute from a white

More information

Server room guide helps energy managers reduce server consumption

Server room guide helps energy managers reduce server consumption Server room guide helps energy managers reduce server consumption Jan Viegand Viegand Maagøe Nr. Farimagsgade 37 1364 Copenhagen K Denmark jv@viegandmaagoe.dk Keywords servers, guidelines, server rooms,

More information

5 Reasons. Environment Sensors are used in all Modern Data Centers

5 Reasons. Environment Sensors are used in all Modern Data Centers 5 Reasons Environment Sensors are used in all Modern Data Centers TABLE OF CONTENTS 5 Reasons Environmental Sensors are used in all Modern Data Centers Save on Cooling by Confidently Raising Data Center

More information

Tim Facius Baltimore Aircoil

Tim Facius Baltimore Aircoil Presented By: Tim Facius Baltimore Aircoil Slide No.: 1 CTI Mission Statement To advocate and promote the use of environmentally responsible Evaporative Heat Transfer Systems (EHTS) for the benefit of

More information

Halton - Achieving Energy Efficiency in School Design

Halton - Achieving Energy Efficiency in School Design Halton - Achieving Energy Efficiency in School Design Enabling Wellbeing Halton Design Tools Drive Energy Efficient Kitchen Ventilation and Comfort Today, nutritional guidelines for school foodservice

More information

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES

More information

380VDC Data Center At Duke Energy

380VDC Data Center At Duke Energy 380VDC Data Center At Duke Energy Dennis P. Symanski EPRI - Senior Project Manager Curtis Watkins Duke Energy - Senior Project Manager Emerging Technology (ET) Summit November 9, 2010 Sacramento, CA From

More information

Overview. PG&E and Energy Efficiency. CA Energy Efficiency Regulatory & Policy Roadmap. Financing Options for Efficiency & Demand Response

Overview. PG&E and Energy Efficiency. CA Energy Efficiency Regulatory & Policy Roadmap. Financing Options for Efficiency & Demand Response Overcoming Financial Barriers to Energy Efficiency April 6, 2010 Overview PG&E and Energy Efficiency CA Energy Efficiency Regulatory & Policy Roadmap Financing Options for Efficiency & Demand Response

More information

Control Strategies for Plenum Optimization in Raised Floor Data Centers

Control Strategies for Plenum Optimization in Raised Floor Data Centers Control Strategies for Plenum Optimization in aised Floor Data Centers Keke Chen, Clifford C. Federspiel, David M. Auslander, Cullen E. Bash, Chandrakant D. Patel Enterprise Software and Systems Laboratory

More information

Figure 1: Comparison of Projected Electricity Use, 2007-2011 1

Figure 1: Comparison of Projected Electricity Use, 2007-2011 1 Fact Sheet on National Data Center Energy Efficiency Information Program U.S. Department of Energy (DOE) and U.S. Environmental Protection Agency (EPA) March 19, 2008 Summary: The voluntary National Data

More information

SUCCESS STORY ENERGY TO CARE UF HEALTH SHANDS VISTA REHAB & UF HEALTH SHANDS CANCER HOSPITAL (SOUTH TOWER)

SUCCESS STORY ENERGY TO CARE UF HEALTH SHANDS VISTA REHAB & UF HEALTH SHANDS CANCER HOSPITAL (SOUTH TOWER) ENERGY TO CARE SUCCESS STORY UF HEALTH SHANDS VISTA REHAB & UF HEALTH SHANDS CANCER HOSPITAL (SOUTH TOWER) UF Shands uses commissioning and automation to save more than $5 million in less than five years

More information

Infrastructure & Cities Sector

Infrastructure & Cities Sector Technical Article Infrastructure & Cities Sector Building Technologies Division Zug (Switzerland), October 18, 2011 Saving Energy in a Data Center A Leap of Faith? New guidelines from ASHRAE (American

More information

RosevilleProject. LoE _ 2 Glass Products. You can reduce your cooling energy usage by 25% or more. Here is the proof.

RosevilleProject. LoE _ 2 Glass Products. You can reduce your cooling energy usage by 25% or more. Here is the proof. RosevilleProject Glass Products You can reduce your cooling energy usage by 25% or more. Here is the proof. Hot-Button Issues Residents of California, Arizona, and Nevada don t need a weather forecast

More information

Energy and Cost Analysis of Rittal Corporation Liquid Cooled Package

Energy and Cost Analysis of Rittal Corporation Liquid Cooled Package Energy and Cost Analysis of Rittal Corporation Liquid Cooled Package Munther Salim, Ph.D. Yury Lui, PE, CEM, LEED AP eyp mission critical facilities, 200 west adams street, suite 2750, Chicago, il 60606

More information

Rittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy

Rittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy Rittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy Executive Summary Data center owners and operators are in constant pursuit of methods

More information

Reducing Data Center Energy Consumption

Reducing Data Center Energy Consumption Reducing Data Center Energy Consumption By John Judge, Member ASHRAE; Jack Pouchet, Anand Ekbote, and Sachin Dixit Rising data center energy consumption and increasing energy costs have combined to elevate

More information

An Introduction to Cold Aisle Containment Systems in the Data Centre

An Introduction to Cold Aisle Containment Systems in the Data Centre An Introduction to Cold Aisle Containment Systems in the Data Centre White Paper October 2010 By Zac Potts MEng Mechanical Engineer Sudlows October 2010 An Introduction to Cold Aisle Containment Systems

More information

Rate of Heating Analysis of Data Centers during Power Shutdown

Rate of Heating Analysis of Data Centers during Power Shutdown 2011. American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions, Volume 117, Part 1. For personal use only. Additional reproduction,

More information

Elements of Energy Efficiency in Data Centre Cooling Architecture

Elements of Energy Efficiency in Data Centre Cooling Architecture Elements of Energy Efficiency in Data Centre Cooling Architecture Energy Efficient Data Center Cooling 1 STULZ Group of Companies Turnover 2006 Plastics Technology 400 Mio A/C Technology 200 Mio Total

More information