Drives and motors. A guide to using variable-speed drives and motors in data centres
|
|
- Eleanor Miles
- 8 years ago
- Views:
Transcription
1 Drives motors A guide to using variable-speed drives motors in data centres
2 The power behind the data Private public businesses, from banks to supermarkets, to telecommunications companies internet providers depend on data centres for gathering, storing managing vast volumes of data in a reliable, efficient secure way, powering everything from online shopping transactions through to storage retrieval of hospital records. Any form of data loss can have a disastrous impact on the business. As such, data centres suffer high operating maintenance costs. Not surprisingly, they require massive amounts of power to keep them running smoothly efficiently. The everincreasing dem for computing power has a significant impact: with the new technologies, between kw of power is required for each single rack, compared to 4-5 kw normally needed in the past. In the future, these environments will become one of the main consumers of power in the world. With the continued growth of the internet electronic banking, the need to deliver data storage solutions that also help improve energy efficiency the levels of power used within such a centre has never been greater. All of which affects plant costs: the electrical mechanical aspects of a new office building are usually equal to 15 percent of the investment, but with a data centre this value increases to 70 percent. Cutting the power overhead It is estimated that IT applications, including data centres, consume 2 percent of all electrical energy produced. The EU estimates that the power consumption of data centres is set to rise to 93 TWh by Most of this power consumption is represented by the IT load, accounting for 40 percent, while the cooling system runs a close second at 35 percent, with the UPS lighting accounting for a further 25 percent. Power Usage Effectiveness, or PUE, is the most commonly used method of determining the energy efficiency of a data centre. This ratio is the total power entering the data centre divided by the power used by the IT equipment. PUE = Total facility power IT equipment power The average data centre has a PUE of 2.0. This means that the facility uses one watt of overhead power for every watt delivered to IT equipment. Improving this ratio means reducing overhead power use, mainly by cutting the percentage of power used by the cooling system. This can most readily be achieved by using variable-speed control to reduce the speed of motors driving pumps fans. 2 The power behind the data l A guide to using variable-speed drives motors in data centres
3 Because many pump fan systems run at less than full capacity for much of the time, VSDs can produce huge savings. If a 100 kw fan is throttled by 20 percent, for example, the investment in a VSD will have a payback of typically six months based on continuous operation. Benefits of variable-speed drives Commercial Reduced energy consumption from 20 to 50 percent Fast payback from six months Reduced CO 2 emissions CRC Energy Efficiency Scheme (CRC) UK Government s matory initiative to reduce carbon dioxide (CO2) emissions from organisations meeting certain qualification criteria. Enhanced Capital Allowances UK Government s programme of tax relief for companies investing in equipment that meets energy saving criteria Variable-speed drives Data centre running costs can be significantly reduced from 20 to 70 percent with VSDs. These devices control the flow of pumps air conditioning fans to eliminate the energy waste that is common with conventional pump fan control methods. Typical savings Typical data centre may have approx. 70 fixed speed motor applications Average power per motor is 7.5 kw Typical motor power could be > 0.5 MW Typical running costs could be > 450 k per annum Typical financial savings could be > 20 percent i.e 90 k per annum Payback < 2 years How variable-speed drives work Many existing pump fan systems are based on throttling arrangements: the motor is driven at full speed then the flow of liquid or air is regulated by dampers, valves, vanes or similar throttling mechanisms. Throttling the output in this way, wastes energy. A VSD can increase the system s efficiency by adjusting the motor speed to the correct operation point eliminating the need for throttling. A small reduction in speed can make a big difference in energy consumption. A centrifugal pump or fan running at 80 percent speed consumes only half as much energy as a unit running at full speed. This is because the power required to run a pump or fan changes with the cube of the speed. Technical Lower maintenance costs Starting, stopping braking can easily be programmed to reduce stress on mechanical equipment Increases equipment life reduces maintenance requirements for pumps, motors pipework Easily retrofitted into an installation Real time clock Can easily set up programmes with different running speeds at different times or on different days Low harmonic solutions available as part of installation design Financial controller Significantly reduced energy bills Rapid return on investment Qualify for Enhanced Capital Allowances Lower maintenance costs Substantial contribution to environment by lower CO 2 emissions Facilities manager Gain control of air conditioning costs Easily retrofit VSD to installation Maintenance engineer Reduced maintenance on pumps fans, hence lower costs Adjusting speed according to dem saves wear tear on pumps, fans motors The power behind the data l A guide to using variable-speed drives motors in data centres 3
4 Data centre applications for variable-speed drives Challenges facing air conditioning As the servers are always operating around the clock, one of the highest operating costs is the air conditioning, which is normally set to 20 C requires one watt per watt used in computing functions. Air conditioning is used to control the temperature humidity in the data centre. The recommended temperature range is between 20 to 25 C (68 to 75 F) humidity range of 40 to 55 percent with a maximum dew point of 17 C as optimal for data centre conditions. The electrical power consumed by the servers heats the air in the data centre. Unless the heat is removed, the ambient temperature will rise, resulting in electronic equipment malfunction. By controlling the air temperature, the server components at the board level are kept within the manufacturer s specified temperature/humidity range. Air conditioning systems help control humidity by cooling the return space air below the dew point. Too much humidity, water may begin to condense on internal components. In case of a dry atmosphere, ancillary humidification systems may add water vapour if the humidity is too low, which can result in static electricity discharge problems which may damage components. ABB s electrical solutions for data centres Low voltage switchboards ipdus (Power Distribution Units) Active filters Power factor correction ipdus (Power Distribution Units) Remote power panel Power measurement Automation switchboards Variable-speed drives PLCs Control gear Air-isolated medium voltage switchboards Dry-type transformers i-bus EIB/KNX High-efficiency motors Variable-speed drives 4 Data centre applications for variable-speed drives l A guide to using variable-speed drives motors in data centres
5 Supply fan (A) Room air quality is controlled by changing the speed of the supply fan according to the CO 2 content of the exhaust air. The outdoor air damper will be opened when the fan is started. Operation is enabled when the damper is fully open (damper end switch). Accurate control to keep desired air quality/co 2 content Reduced maintenance of mechanical equipment such as belts bearings due to reduced operating speeds AC drive soft starting stopping Easier to maintain low noise levels Approximately 30 percent reduction in CO 2 emissions Return fan (B) Room pressure is controlled by changing the speed of the return fan according to the exhaust duct pressure. Return fan keeps up constant pressure in the exhaust duct by using PID control. Exhaust air dampers will be opened when the fan is started. Operation is enabled when damper is fully open (damper end switch). Accurate control to keep desired duct pressure Reduced maintenance of mechanical equipment such as belts bearings due to reduced operating speeds AC drives soft starting stopping Easier to maintain low noise levels Approximately 30 percent reduction in CO 2 emissions C Liquid cooler fans (C) Liquid cooler fans are controlled according to the temperature of the condenser water outlet. Condenser water temperature is kept constant with PID control. To prevent unnecessary cooling, liquid cooler fans are not started until the condenser water pump exceeds maximum speed. If water temperature falls too low, circulation can be stopped with a solenoid valve. Fans can also be programmed to run fixed speed for a certain time, for example once a week, to avoid condensation in the motors. B Easier to maintain low noise levels Accurate control to keep desired condenser water temperature Approximately 15 percent reduction in CO 2 emissions A Data centre applications for variable-speed drives l A guide to using variable-speed drives motors in data centres 5
6 Condenser water pump (D) Condenser water pump is controlled with a PID controller according to the temperature of the condenser water. Operation is enabled when the chilled water pump the chiller compressor are running. Accurate control to keep desired condenser water temperature Elimination of water hammer due to soft starting stopping Reduced pump pipe sizes Approximately 25 percent reduction in CO 2 emissions Chilled water pump (F) Chilled water pump circulates chilled water in a cooling coil according to the temperature of the supply air. Operation is enabled when the duct temperature rises above a preset level chiller compressor is running. Accurate control to keep desired duct temperature Elimination of water hammer due to soft starting stopping Reduced pump pipe sizes Approximately 25 percent reduction in CO 2 emissions Chiller compressor (E) The need for chilled water or CO 2 cooled racks can lead to space problems for one square metre of technical space, one square metre of plant space is required plus two square metres of ancillary accommodation space. This excludes any main substation(s) that may be required. An AC drive optimizes compressor motor speed to actual cooling dem. The compressor is controlled according to the temperature of the chilled water. The compressor s minimum speed is 60 per cent of its normal speed. Operation is enabled when chilled water pump condenser water pump are running. Approximately percent energy reduction E F D Reduced peak dem charges Elimination of water hammer or hydraulic shock due to soft starting stopping Increased chiller life Tighter chilled water temperature control Reduced maintenance dem Approximately 20 percent reduction in CO 2 emissions 6 Data centre applications for variable-speed drives l A guide to using variable-speed drives motors in data centres
7 Expertise at every stage of the value chain Pre-purchase Order delivery Installation commissioning Operation maintenance Upgrade retrofit Replacement recycling Training learning Technical support Contracts The services offered for ABB s VSDs span the entire value chain, from the moment a customer makes the first enquiry through to disposal recycling of the drive. Throughout the value chain, ABB provides training learning, technical support contracts. All of this is supported by one of the most extensive global VSD sales service networks. Pre-purchase ABB provides a range of services that help guide the customers to the right products for their applications. Examples of services include correct drive selection dimensioning, harmonic survey EMC assessment. Order delivery Orders can be placed through any ABB office or through ABB s authorised value providers. Orders can be placed tracked online. ABB s sales services network offers timely deliveries including express delivery. Installation commissioning While many customers have the resources to undertake installation commissioning on their own, ABB its authorised value providers are available to advise or undertake the entire VSD installation start-up. Operation maintenance With remote monitoring, ABB can guide the customer through a fast efficient fault-finding procedure as well as analyse the operation of the VSD the customer s process. From maintenance assessment to preventive maintenance reconditioning of drives, ABB has all the options covered to keep HVAC installations operational. Should corrective maintenance of drives be needed, ABB offers on-site workshop repair, fully backed up by the most extensive spare holding. Upgrade retrofit An existing ABB VSD can often be upgraded to the latest software or hardware to improve the performance of the application. Existing installations can be economically modernised by retrofitting the latest drive technology to mechanical control equipment, such as inlet guide vanes or dampers or older generations of VSDs. Instead of replacing an entire VSD or system, it is often more economical to modernise the old installation by reusing all relevant parts of the original equipment purchasing new where necessary. Replacement recycling ABB can advise on the best replacement VSD while ensuring that the existing one is disposed in a way that meets all local environmental regulations. Entire value chain services The main services available throughout the value chain include: ABB s Bristol Training Centre offers product application training in the classroom. ABB also offers training courses at customer sites on the Internet. Technical support At each stage of the value chain, an ABB expert is available to offer advice to keep the customer s process or plant operational. Contracts DriveCare contracts other types of agreements, from individual services through to complete drive care covering all repairs even drive replacements, are available. Life cycle support l A guide to using variable-speed drives motors in data centres 7
8 Contact us ABB Limited Daresbury Park Daresbury Warrington Cheshire WA4 4BT Tel: +44 (0) Fax: +44 (0) Notes: We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document in the subject matter illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB. Ref: Data Centre brochure/july 2014 Copyright 2014 ABB All rights reserved Printed in UK ( )
Drives and motors. A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC)
Drives and motors A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC) The power behind the data Private and public businesses, from banks to
More informationA guide to using variable-speed drives and motors in swimming pool halls
A guide to using variable-speed drives motors in swimming pool halls Meeting the energy CO 2 reduction challenge Swimming pool halls are expensive to run, consuming large amounts of electricity. They are
More informationDrives and motors. A guide to using variable-speed drives and motors in car parks
Drives and motors A guide to using variable-speed drives and motors in car parks Helping car parks meet the energy and CO 2 reduction challenge In the UK, as population density increases and space becomes
More informationDrives and motors. A guide to using variable-speed drives and motors in retail environments
Drives and motors A guide to using variable-speed drives and motors in retail environments Improving energy efficiency and lowering the carbon footprint Retailers across the UK take their corporate responsibility
More informationData Center Uninterrupted efficiency, guaranteed reliability and continuous modularity. ABB solutions always work.
Data Center Uninterrupted efficiency, guaranteed reliability and continuous modularity. ABB solutions always work. Data security is first of all electrical Maximizing security while providing efficiency
More informationDirect Fresh Air Free Cooling of Data Centres
White Paper Introduction There have been many different cooling systems deployed in Data Centres in the past to maintain an acceptable environment for the equipment and for Data Centre operatives. The
More informationDesign Guide. Retrofitting Options For HVAC Systems In Live Performance Venues
Design Guide Retrofitting Options For HVAC Systems In Live Performance Venues Heating, ventilation and air conditioning (HVAC) systems are major energy consumers in live performance venues. For this reason,
More informationVariable-Speed Fan Retrofits for Computer-Room Air Conditioners
Variable-Speed Fan Retrofits for Computer-Room Air Conditioners Prepared for the U.S. Department of Energy Federal Energy Management Program Technology Case Study Bulletin By Lawrence Berkeley National
More informationState of the Art Energy Efficient Data Centre Air Conditioning
- White Paper - State of the Art Energy Efficient Data Centre Air Conditioning - Dynamic Free Cooling - Release 2, April 2008 Contents ABSTRACT... 3 1. WHY DO I NEED AN ENERGY EFFICIENT COOLING SYSTEM...
More informationHeat Recovery from Data Centres Conference Designing Energy Efficient Data Centres
What factors determine the energy efficiency of a data centre? Where is the energy used? Local Climate Data Hall Temperatures Chiller / DX Energy Condenser / Dry Cooler / Cooling Tower Energy Pump Energy
More informationData Center. Ultra-Efficient chilled water system optimization. White paper. File No: 9.236 Date: december 03, 2015 Supersedes: new Date: new
Data Center Ultra-Efficient chilled water system optimization White paper File No: 9.236 Date: december 03, 2015 Supersedes: new Date: new Data Center - Ultra-Efficient white paper 3 abstract The primary
More informationEnergy Efficient Data Centre at Imperial College. M. Okan Kibaroglu IT Production Services Manager Imperial College London.
Energy Efficient Data Centre at Imperial College M. Okan Kibaroglu IT Production Services Manager Imperial College London 3 March 2009 Contents Recognising the Wider Issue Role of IT / Actions at Imperial
More informationI-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 8, Loughborough University, 29 th June 2015
I-STUTE Project - WP2.3 Data Centre Cooling Project Review Meeting 8, Loughborough University, 29 th June 2015 Topics to be considered 1. Progress on project tasks 2. Development of data centre test facility
More informationEuropean Code of Conduct for Data Centre. Presentation of the Awards 2014
European Code of Conduct for Data Centre Presentation of the Awards 2014 Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 The Code of Conduct for Data Centre Results European
More informationABB drives for water Medium voltage drives for energy savings and life-cycle improvements
ABB drives for water Medium voltage drives for energy savings and life-cycle improvements 2 ABB drives for water Water Increasing demand for a limited resource Freshwater is one of the world s most important
More informationKU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM
KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM AIR HANDLING UNITS... 1 CHILLERS... 2 COOLING TOWERS... 2 CLOSED LOOP COOLERS... 2 MISCELLANEOUS SUPPLY FANS...
More informationCentrifugal Fans and Pumps are sized to meet the maximum
Fans and Pumps are sized to meet the maximum flow rate required by the system. System conditions frequently require reducing the flow rate. Throttling and bypass devices dampers and valves are installed
More informationLeveraging the Power of Intelligent Motor Control to Maximize HVAC System Efficiency
Leveraging the Power of Intelligent Motor Control to Maximize HVAC System Efficiency Because HVAC systems comprise a large amount of a building s operating costs, it makes sense to ensure these systems
More informationLegacy Data Centres Upgrading the cooling capabilities What are the options?
Legacy Data Centres Upgrading the cooling capabilities What are the options? Presentation Structure What is a Legacy Data Centre? What is CRAC cooling? ASHRAE Standards Overview Available Cooling Systems
More informationDefining Quality. Building Comfort. Precision. Air Conditioning
Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air
More informationHEATING, VENTILATION & AIR CONDITIONING
HEATING, VENTILATION & AIR CONDITIONING as part of the Energy Efficiency Information Grants Program Heating and cooling can account for approximately 23 % of energy use in pubs and hotels 1. Reducing heating
More informationHVAC Applications. VFD considerations for HVAC systems...
HVAC Applications VFD considerations for HVAC systems... 1 COMMON TERMINOLOGY VFD (VARIABLE FREQUENCY DRIVES) AFC (ADJUSTABLE FREQ. CONTOLLER) ASD (ADJUSTABLE SPEED DRIVES) VSD (VARIABLE SPEED DRIVES)
More informationDataCenter 2020: first results for energy-optimization at existing data centers
DataCenter : first results for energy-optimization at existing data centers July Powered by WHITE PAPER: DataCenter DataCenter : first results for energy-optimization at existing data centers Introduction
More informationScrew Compressors ESM 30 132 Fixed Speed & VS 30 132 Variable Speed
Screw Compressors ESM 30 132 Fixed Speed & VS 30 132 Variable Speed Rely on GD to provide the perfect fit The perfect fit to maximise productivity The growing industrial demand for compressed air requires
More informationGUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group
GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY Public Sector ICT Special Working Group SERVER ROOM ENERGY EFFICIENCY This guide is one of a suite of documents that aims to provide guidance on ICT energy efficiency.
More informationInternational Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES
More informationCase Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program
More informationHVAC Processes. Lecture 7
HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump
More informationABB drives and motors for improving energy efficiency
ABB drives and motors for improving energy efficiency Improving energy efficiency worldwide is the fastest, the most sustainable and the cheapest way to reduce greenhouse gas emissions and enhance energy
More informationService Power Technologies. Retrofitting A future-oriented concept in lifecycle management
Retrofitting A future-oriented concept in lifecycle management Retrofit solutions for gas-insulated switchgear > 50 kv to 170 kv ABB-supplied high-voltage substations generally have a service life of approx.
More informationSaving Energy For Your Organisation. Top 10 energy saving tips
Saving Energy For Your Organisation Top 10 energy saving tips How can you increase efficiency, reduce costs and cut your carbon emissions? The UK s Climate Change Act (2008) sets a legally-binding target
More informationyour comfort. our world. DNSS EcoSave A/C remote monitoring and malfunction prediction
your comfort. our world. DNSS EcoSave A/C remote monitoring and malfunction prediction What is DNSS EcoSave? The Daikin Network Service System (DNSS EcoSave) is a Daikin developed internet based remote
More informationEnergy Efficiency Opportunities in Federal High Performance Computing Data Centers
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
More informationVISIT 2010 Fujitsu Forum Europe 0
VISIT 2010 Fujitsu Forum Europe 0 Virtualization & Automation Room 13a Shaping tomorrow with you. Green Data Center Services Martin Provoost Director, Data Centers and Networks, Fujitsu UK & Ireland 14:00
More informationEnergy saving technology to deliver the fastest returns. Top 10 energy saving options
Energy saving technology to deliver the fastest returns Top 10 energy saving options How can you increase efficiency, reduce costs and cut your carbon emissions? Unstable energy prices, increased costs,
More informationAir Conditioning. The opportunity for energy efficiency. Low cost actions to reduce energy usage now
Fact Sheet #6 Air Conditioning In this fact sheet you will discover: The opportunity for energy efficiency How air conditioning works Low cost actions to reduce energy usage now Investments to reduce costs
More informationyour comfort. our world. R22 replacement A complete solution for R22 Sky Air systems
your comfort. our world. R22 replacement A complete solution for R22 Sky Air systems Daikin Airconditioning UK Ltd provides a complete solution for the replacement of R22 systems. Previously, R22 pipe
More informationUnidrive M Energy Savings
Unidrive M Energy Savings Why is this important? Some Data: Money, Lots of Money >13.5m electric motors 1Hp or greater installed in US industrial process operations. Industry spends >$33b annually on electricity
More informationChapter 3.4: HVAC & Refrigeration System
Chapter 3.4: HVAC & Refrigeration System Part I: Objective type questions and answers 1. One ton of refrigeration (TR) is equal to. a) Kcal/h b) 3.51 kw c) 120oo BTU/h d) all 2. The driving force for refrigeration
More informationGuidance for Calculation of Efficiency (PUE) in Data Centers
Guidance for Calculation of Efficiency (PUE) in Data Centers White Paper 158 Revision 1 by Victor Avelar > Executive summary Before data center infrastructure efficiency can be benchmarked using PUE or
More informationPaul Oliver Sales Director. Paul Oliver, Airedale Tom Absalom, JCA
Paul Oliver Sales Director Paul Oliver, Airedale Tom Absalom, JCA Airedale an overview 25,000m 2 UK premier test centre 450 staff Global distribution A Modine company Modine centre of excellence Airedale
More informationPrinting and Publishing Energy Savings Guide
Printing and Publishing Energy Savings Guide Oregon printing and publishing plants face challenges of rising operating costs, environmental and other regulations, outdated equipment and customer demand
More informationGuidance for Calculation of Efficiency (PUE) in Data Centers
Guidance for Calculation of Efficiency (PUE) in Data Centers White Paper 158 Revision 3 by Victor Avelar Executive summary Before data center infrastructure efficiency can be benchmarked using PUE or other
More informationMinimising Data Centre Total Cost of Ownership Through Energy Efficiency Analysis
Minimising Data Centre Total Cost of Ownership Through Energy Efficiency Analysis Sophia Flucker CEng MIMechE Ing Dr Robert Tozer MSc MBA PhD CEng MCIBSE MASHRAE Operational Intelligence Ltd. info@dc-oi.com
More informationHVAC Systems: Overview
HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct
More informationFederal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415. Table of Contents
Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 TITLES... 2 GRADE LEVELS... 2 HELPER AND INTERMEDIATE JOBS...
More informationSECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
More informationData Center Precision Cooling: The Need For A Higher Level Of Service Expertise. A White Paper from the Experts in Business-Critical Continuity
Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise A White Paper from the Experts in Business-Critical Continuity Executive Summary Today s data centers are changing rapidly,
More informationGAS HEATING IN COMMERCIAL PREMISES
ENERGY EFFICIENCY OFFICES GAS HEATING IN COMMERCIAL PREMISES www.energia.ie www.energia.ie Typically, energy reductions of 10% or more can be made easily through maintenance and low cost improvements.
More informationData Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures
Data Realty Colocation Data Center Ignition Park, South Bend, IN Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures Project Overview Data Realty is a data center service provider for middle
More informationExample Retrocommissioning Measure: Opening Throttled Discharge Valves
Opening Throttled Discharge Valves This 21-story building, constructed in 1997, is located in Oregon and contains 589,000 gross square feet of mostly office occupancy. The HVAC system includes six large
More informationMetrics for Data Centre Efficiency
Technology Paper 004 Metrics for Data Centre Efficiency Workspace Technology Limited Technology House, PO BOX 11578, Sutton Coldfield West Midlands B72 1ZB Telephone: 0121 354 4894 Facsimile: 0121 354
More informationEnergy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie
Energy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie Mukesh Khattar, Energy Director, Oracle National Energy Efficiency Technology Summit, Sep. 26, 2012, Portland, OR Agenda
More informationAdvanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings
Advanced Energy Design Guide LEED Strategies for Schools and High Performance Buildings Today s Presenters Stephen Koontz, LEED AP Energy Services Leader Tampa Bay Trane Allen Irvine General Sales Manager
More informationNational Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook
National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook Trainee:... Training Provider:... Year:... Trainee Contact no:... Competency Based Skill Training Logbook Introduction
More informationModular Chiller Plants for data centers. Downtime isn t acceptable
Modular Chiller Plants for data centers Downtime isn t acceptable Reducing risk with Quick Start A direct solution to your most important challenge uptime. At Johnson Controls we protect our customers
More informationInternational Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES
More informationElement D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
More informationred zone management white paper Making the most of Distribution Use of System (DUoS) Charges
red zone management white paper Making the most of Distribution Use of System (DUoS) Charges 1. Distribution charges 2. Measuring usage 3. Component parts 4. Time is of the essence 5. Solution provider
More informationvacon hvac ac drives
vacon hvac ac drives comfort & control in building automation 1 the smarter way to reduce co 2 emissions Heating, ventilation and air-conditioning (HVAC) is all about efficiency. Room temperatures need
More informationHow To Find A Sweet Spot Operating Temperature For A Data Center
Data Center Operating Temperature: The Sweet Spot A Dell Technical White Paper Dell Data Center Infrastructure David L. Moss THIS WHITE PAPER IS FOR INFORMATIONAL PURPOSES ONLY, AND MAY CONTAIN TYPOGRAPHICAL
More informationproducts 22 º C Ventilation Air Conditioning Refrigeration Energy & Cost Saving Products Inside PROVIDED BY HEINEN & HOPMAN
products > Energy & Cost Saving Products OUTSIDE 35 C HUMIDITY 90% 22 º C Inside PROVIDED BY HEINEN & HOPMAN Heating Ventilation Air Conditioning Refrigeration HVAC energy & COST SAVING POSSIBILITIES A
More informationCURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers
CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building
More informationFree Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions
Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the
More informationAIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries
AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries Hot tips and cool ideas to save energy and money! Air conditioning units or systems are often used by foundries
More informationPresentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks
Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same
More informationPoor Performing AC? High Electric Bills? High Humidity?
Poor Performing AC? High Electric Bills? High Humidity? If you answered yes to any or all of these questions, it may be time to consider a new Air Conditioning system. Read on for useful information when
More informationGlossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
More informationHow To Improve Energy Efficiency Through Raising Inlet Temperatures
Data Center Operating Cost Savings Realized by Air Flow Management and Increased Rack Inlet Temperatures William Seeber Stephen Seeber Mid Atlantic Infrared Services, Inc. 5309 Mohican Road Bethesda, MD
More information- White Paper - Data Centre Cooling. Best Practice
- White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH
More informationUniversity of St Andrews. Energy Efficient Data Centre Cooling
Energy Efficient Data Centre Cooling St. Andrews and Elsewhere Richard Lumb Consultant Engineer Future-Tech Energy Efficient Data Centre Cooling There is no one single best cooling solution for all Data
More informationCranes Power, Control and Automation application solutions
Cranes Power, Control and Automation application solutions One source for all your industrial product needs. Complete crane technology solutions from one company ABB has developed a comprehensive range
More informationLG Electronics AE Company, Commercial Air Conditioning
www.lgeaircon.com New concept Ecofriendly Highefficiency Heating solution Total heating & Hot water Solution for MULTI V LG Electronics AE Company, Commercial Air Conditioning 2 Yeouidodong, Yeongdeungpogu,
More informationLesson 36 Selection Of Air Conditioning Systems
Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section
More informationEnergy efficiency in buildings A must, both economically and ecologically
Energy efficiency in buildings A must, both economically and ecologically 2 Protecting the climate is one of the greatest challenges of our time, and one which will affect the existence of future generations.
More informationHow To Design A Building In New Delhi
ENERGY EFFICIENT HVAC DESIGN FOR COMPOSITE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce energy consumption
More informationBIG SAVINGS FOR A LOT MORE APPLICATIONS
MSF SOFT STARTERS BIG SAVINGS FOR A LOT MORE APPLICATIONS Soft Starters from Emotron Unique features built into Emotron MSF Soft Starters reduce costs significantly for many more applications when compared
More informationENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE
ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce
More informationProduct Brochure. Controlled start transmission
Product Brochure Controlled start transmission What CST does The Dodge CST (Controlled Start Transmission) is a 2 in 1 gearbox which combines a planetary gear reducer with an integral wet clutch system.
More informationImproving Sustainability in Campus Data Centers Click To Edit Master Title Style
Improving Sustainability in Campus Data Centers Click To Edit Master Title Style March 31, 2015 12:10-1:00 PM ET Agenda Welcome and Better Buildings Overview Michigan State University Partnering with the
More informationCapgemini UK Infrastructure Outsourcing
Together. Free your energies Capgemini UK Infrastructure Outsourcing Project Arthur Improved Data Centre Efficiency Paul Feeney Capgemini Tony Mills Spie Matthew Hall Project Arthur The Toltec data centre,
More informationvacon ac drives for mining & minerals
vacon ac drives for mining & minerals 1 strong experience in mining & minerals Vacon AC drives are robust to handle your most demanding requirements from simple ventilation to the most complex load sharing
More informationGuidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems
Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems If you're a designer or a BCA, this guidance on the energy efficiency of HVAC systems in commercial buildings may
More informationInformation Guide Domestic Air Source Heat Pumps
Information Guide Domestic Air Source Heat Pumps Issue 41 Domestic Air Source Heat Pumps This is an independent guide produced by Mitsubishi Electric to enhance the knowledge of its customers and provide
More informationIncreasing Energ y Efficiency In Data Centers
The following article was published in ASHRAE Journal, December 2007. Copyright 2007 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes
More informationHVAC For Schools How to purchase an HVAC system that meets your school s unique requirements and stays within your budget
A PRIMER Educational HVAC For Schools How to purchase an HVAC system that meets your school s unique requirements and stays within your budget Contents: Introduction: The best HVAC system is durable, reliable
More informationTop Technology for Industry, Agriculture, Business and Communities
Top Technology for Industry, Agriculture, Business and Communities CHP The Technology with a Potential for Saving Energy Combined Heat and Power (CHP) is a highly efficient technology for the conversion
More informationOptimization of Water - Cooled Chiller Cooling Tower Combinations
Optimization of Water - Cooled Chiller Cooling Tower Combinations by: James W. Furlong & Frank T. Morrison Baltimore Aircoil Company The warm water leaving the chilled water coils is pumped to the evaporator
More informationTour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015
Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015 Presentation Outline Mechanical Overview Chillers and Pumps Pipework and Ancillaries In Row Cooling Units
More informationClassification and Qualification STANDARDS
Classification and Qualification STANDARDS HVAC Series Classification Title Class Code Date Established Date Revised Operating Engineer Building Service Engineer Air Conditioning/Refrigeration Mechanic
More informationPanorama. Softstarters The complete range
Panorama Softstarters The complete range Why does soft starting matter? Controlling industrial electricity. The vast majority of the world s industrial applications are driven by motors. It is estimated
More informationA Cover HVAC ENERGY EFFICIENT
A Cover HVAC ENERGY EFFICIENT EQUIPMENT toolkit 1 CONTENTS AND PARTNERS 2 Introduction 3 equipment & processes 3 Optimise operating settings 2 upgrade equipment 4 Seal the building 5 Rearrange air conditioning
More informationExcool Indirect Adiabatic and Evaporative Data Centre Cooling. World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling
Excool Indirect Adiabatic and Evaporative Data Centre Cooling World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling Indirect Adiabatic and Evaporative Data Centre Cooling Solutions by
More information32VFD Variable Frequency Drives for Centrifugal Chillers
32VFD 32VFD Variable Frequency Drives for Centrifugal Chillers ENERGY-SAVING CONTROL FOR CENTRIFUGAL CHILLERS Reduce energy consumption in your existing centrifugal chiller Your chiller was specified to
More informationRittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy
Rittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy Executive Summary Data center owners and operators are in constant pursuit of methods
More informationElectronic Diesel Control EDC 16
Service. Self-Study Programme 304 Electronic Diesel Control EDC 16 Design and Function The new EDC 16 engine management system from Bosch has its debut in the V10-TDI- and R5-TDI-engines. Increasing demands
More informationDATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates
More informationCreating clean energy from waste Power and automation solutions for waste-to-energy plants
Creating clean energy from waste Power and automation solutions for waste-to-energy plants 40 years of waste-to-energy expertise ABB has been supplying turnkey electrical and automation solutions for waste-to-energy
More informationInverter technology. bulletin
Inverter technology application bulletin What is the inverter component? The inverter is an electronic power component that continuously varies the electricity supply frequency of an electric motor. The
More informationXcel Business Customers: Program and Rebate Summary
Xcel Business Customers: Program and Rebate Summary Rebates for New Energy-Efficient Equipment Xcel offers prescriptive rebates to its business customers. What s a prescriptive rebate? It simply means
More information