City of Leesburg, Florida I.T. Data Center 130551 APPENDIX A TOSHIBA UPS INFORMATION



Similar documents
LTR Series Uninterruptible Power Systems 700 VA KVA. General Specification

TOSHIBA G /100/160/225 kva

APC Smart-UPS RT. GUIDE SPECIFICATIONS FOR 3000VA, 5000VA and 6000 VA Smart-UPS RT 230VAC Uninterruptible Power Supply

UNINTERRUPTIBLE POWER SUPPLIES >9900AUPS UNINTERRUPTIBLE POWER SUPPLIES

SECTION STATIC UNINTERRUPTIBLE POWER SUPPLY SYSTEM

APC Smart-UPS RT. GUIDE SPECIFICATIONS FOR 15kVA and 20kVA Smart-UPS RT 230VAC Uninterruptible Power Supply

DC UPS. RTB.e A. IMB.e/ITB.e kva. E2001.e/E3001.e kva. Input voltage: 110/125/220 Vdc. 115/120/230 Vac, 1-phase (IMB.

Thyristor-controlled power supplies and battery chargers

Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments

SmartOnline V 5kVA 4.5kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 4U Rack/Tower, USB, DB9 Serial

SmartOnline Expandable Rack / Tower UPS System Online, double-conversion protection for mission critical applications

Always On UPS Systems Inc., # Campion Road, Kelowna, BC Canada V1X 7S8

APC Smart-UPS RT. GUIDE SPECIFICATIONS FOR 1000VA, 2000VA & 3000VA Smart-UPS RC 230VAC Uninterruptible Power Supply

TECHNICAL SPECIFICATIONS FOR 1.5 KVA ONLINE UPS

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

SmartOnline V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire

SG Series UPS kva. high efficiency systems

Schneider Electric GALAXY VM Data Center Grade Three Phase Uninterruptible Power Supply Guide Specifications kva UPS

Specification CyberWave UPS Ver /01/00

SmartPro 230V 3kVA 2.25kW Line-Interactive UPS, Extended Run, SNMP, Webcard, Tower, USB, DB9 Serial

D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.

TLE Series UPS kw for best-in-class multi-mode operating efficiency

Uninterruptible Power Supply

APC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

Galaxy 7000: Unitary Specification guide: Single UPS, three-phase, 160 to 500 kva

Specification Requirements DBL 700MX and 1000MX Series UPS

Single Phase, (3 to 20KVA) & (3 to 15 KW) Harsh Environment Outdoor Application NEMA 3R Cabinet

Phase Modular Finally the benefits of Modular ups are for all

Parallel Redundant Uninterruptible Power Supply

GE Digital Energy. TLE Series UPS kw three phase 400 Vac. with best-in-class efficiency. gimagination at work

Galleon 6-10K Online UPS. Voltronic Power Technology Corporation

SmartPro 120V 500VA 300W Line-Interactive UPS, SNMP, Webcard, 1U Rack/Tower, USB, DB9 Serial

Model #: SMART2200CRMXL

AIS 3000 APC AIS kVA 208V w/2 Batt. Module Exp. To 4, Start-Up 5X8, Internal Maintenance Bypass

SG Series UPS kva three phase 400 Vac

SmartPro 120V 2.2kVA 1.92kW Line-Interactive Sine Wave UPS, SNMP, Webcard option, 2U Rack/Tower, LCD, USB, DB9 Serial

GE Digital Energy. SG-CE Series UPS kva three phase 400 Vac Uninterruptible Power Supply (UPS) imagination at work

PowerGem Pro Uninterruptible Power Supply

Specification guide no. 9 Active harmonic conditioner from 20 to 480 A

10000HXL31/15000HXL31/20000HXL31

MAJORSINE Power Inverter

TAA-Compliant SmartPro 120V 1kVA.8kW Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack, USB, DB9 Serial

TLE Series UPS kva/kw three phase 400 Vac with best-in-class efficiency

SmartPro 120V 1kVA 800W Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack, USB, DB9 Serial

Multi DIALOG MDM/MDT. MDM 10-20kVA single/single-phase and three/single-phase MDT 10-80kVA three/three-phase NETWORK RANGE

Working definitions of terms: Commercial vs. Industrial UPS Systems:

SmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack-Mount, USB, DB9 Serial

SmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, 1U Rackmount, SNMPWEBCARD Option, USB, DB9 Serial

GE Digital Energy. SG-CE Series UPS kva three phase 400 Vac Uninterruptible Power Supply (UPS) imagination at work

SECTION VARIABLE FREQUENCY DRIVES

SmartPro 100/110/120V 1.5kVA 900W Line-Interactive Sine Wave UPS, Tower, SNMP, Webcard, USB, DB9 Serial

SG Series UPS kva. with ultra-high efficiency eboost technology

Audio/Video AVR Series UPS - Intelligent Automatic Voltage Regulated Power Management System

USER MANUAL Online UPS 1K/2K/3K

3U, 2200 VA Audio/Video Pure Sine Wave UPS System

SD Series. SD Series Rectifiers. EPC Energy & Power Conversion

SmartPro 230V 750VA 500W Line-Interactive Sine Wave UPS, SNMP, Webcard, Tower, USB, DB9 Serial

GENERIC REQUIREMENTS FOR UNINTERRUPTIBLE POWER SYSTEMS (UPS) TABLE OF CONTENTS

Smart Pro Rack/Tower UPS Intelligent, line interactive network power management system

OmniVS Series 1500VA Line-Interactive Tower 120V UPS with USB port

32VFD Variable Frequency Drives for Centrifugal Chillers

Power Management Module 2. Installation

Power Quality. Uninterruptible Power Supply

User Manual 1K/2K/3K Online UPS

Online UPS. PowerWalker VFI 1000R/1U

LAP ENERGIA PARA DATACENTERS

LIBRA USV-Anlagen von EBT (10-800KVA) LIBRA pro. UPS kva three-phase / single-phase kva three-phase / three-phase.

Smart-UPS APC Smart-UPS 1000VA USB & Serial 230V

Uninterruptible power supplies Meissner. Efficient and reliable backup where electricity is critical to you

RIELLO ELETTRONICA. Master HP

Model #: SMART2200VS. 2200VA / 2.2kVA line interactive tower UPS. Maintains 120V nominal output over an input range of 79 to 147V

Series 7400 M (10/20/30/40/60 kva) Maximum Protection For Mission Critical Network Applications. Series 7400 M

Liebert GXT MT+ CX UPS, 1000VA VA Intelligent, Reliable UPS Protection. AC Power for Business-Critical Continuity

O WA-120U series IP W Single Output Switching Power Supply. Features. Aplications

Specifying a Variable Frequency Drive s

Inverter / Charger Installation General Operations and AC and DC Connections

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5

Industrial Tower Uninterruptible Power Supply Specifications Bulletin Numbers 1609-P

Tender Technical Specification. For Three phase UPS, on line double conversion (VFI) 30 kva 30 kw

SmartPro 230V 1000VA 900W Line-Interactive Sine Wave UPS, SNMP, Webcard, 2U Rack/Tower, USB, DB9 Serial

USER MANUAL Online UPS 1K/2K/3K Rack

NEWTECH PRO KVA ONLINE UNINTERRUPTIBLE POWER SUPPLY USER MANUAL

Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches

APC by Schneider Electric MGE GALAXY 3500 Uninterruptible Power Supply Guide Specifications 10 kva to 40 kva in / V Solution

BC Pro UPS System Standby UPS System

Power Meter Series 700

Intersection Preassembled 19-inch Rack

Uninterruptible Power Supplies. Section BuyLog Catalog 20-1

Back-UPS 650 VA 120 V with AVR (BX650CI-LM)

Mobile Data Power Model: MDP-25

Galaxy VM. Three-phase power protection. schneider-electric.com

CONSTRUCTION STANDARDS DIVISION 23 HEATING VENTILATING AND AIR CONDITIONING

Internet Office 750VA Ultra-compact Standby 120V UPS with USB port

CPCI-3U-AC-300W-R. Rugged 300W AC Input 3U CompactPCI Power Supply. Electrical Specification for: Telkoor Part Number:

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

PC Personal 120V 600VA 375W Standby UPS with Pure Sine Wave Output, Tower, 6 Outlets

Transcription:

City of Leesburg, Florida I.T. Data Center 130551 APPENDIX A TOSHIBA UPS INFORMATION This Appendix A includes technical documents and specifications for the Toshiba 4200 FA 30 kva Uninterruptable Power System (UPS) to be provided and installed by the City. The UPS is a single input system (single AC input). Any questions regarding the UPS not answered in this Appendix A should be submitted as a question and the City can obtain the information from our UPS Contractor.

TOSHIBA International Corp GUIDE SPECIFICATIONS THREE PHASE UNINTERRUPTIBLE POWER SYSTEM TOSHIBA 4200FA 30 kva CT Internal Battery UPS GUIDE SPECIFICATIONS 1

(30 kva CT) 1.0 SCOPE 1.1 System This specification describes a continuous duty, three-phase, on-line, solidstate uninterruptible power supply system, hereafter referred to as the UPS. 2.0 SYSTEM DESCRIPTION 2.1 Applicable Standards The UPS shall be designed in accordance with and be compliant with the following sections of the current revisions of the following standards: 2.2 Components ANSI C62.41 (IEEE 587) Standard for Surge Withstandability UL 1778 (CUL) National Electrical Code (NFPA-70) NEMA PE-1 OSHA ASME ISO 9001, 14001 The UPS shall consist of the following components: A. Converter B. Chopper / Charger C. Pulse-Width Modulated (PWM) Inverter D. Static Switch Bypass E. Microprocessor Controlled Logic and Control Panel F. Input Circuit Breaker G. Battery System 2

H. Input / Output EMI / RFI Filters 2.3 System Operation The UPS shall operate as an on-line, fully automatic system in the following modes: A. NORMAL - Incoming AC power is boosted using a chopper circuit, and converted into DC power. The DC power is then used to charge the battery bank while at the same time providing clean, DC power to the inverter circuitry. The inverter converts DC power to regulated AC power which feeds the load. B. EMERGENCY - Upon failure of commercial AC power, the UPS shall derive power from the battery bank and continue feeding the load with clean, regulated AC power. There is no interruption to the critical load upon failure or restoration of commercial AC power. C. RECHARGE - Upon restoration of the commercial AC source, the rectifier/chopper powers the inverter while simultaneously recharging the battery bank. The UPS shall have the following recharge process: a) a constant level of current is used to recharge the batteries (the process shall utilize a current-limit function to prevent overcharging batteries, thus extending the life of the batteries) b) as the batteries reach the normal charge level, a constant-voltage control shall begin which causes the battery recharge current to gradually decrease c) Under normal operation, the UPS battery bank "floats" at the 2.25-2.27 volts per cell DC level to stay fully charged and ready for the next discharge. D. BYPASS MODE - Upon detection of an internal fault or output overload, the UPS shall automatically switch from inverter power to an internal bypass via the static switch. Transfer shall be within 4 milliseconds, causing no interruption to the critical load. While in bypass, the UPS shall protect against spikes and common/normal mode noise by utilizing a dual-winding output isolation transformer. Return from Bypass mode shall be an automatic function, without interruption to the critical load. Transfer to Bypass may also be performed as a manual operation via the UPS front panel. E. POWER CONDITIONING MODE - Should the batteries be removed from the UPS, the UPS shall continue to function and still provide 3

protection against spikes, common/normal mode noise, load steps and frequency shifts (without battery back-up capability). 3.0 SYSTEM PARAMETERS A. UPS Input 1) Input Voltage 208/120VAC 2) Input Voltage Requirement 3 Phase, 4 Wire + Ground 3) Voltage Variation +10% to -30% * 4) Rated Frequency 50/60 Hz 5) Frequency Range 45-65 Hz 6) Power Factor > 0.98 lagging 7) Input Capacity 110% of UPS Output Capacity 8) Walk-In Function From 20% to 100% over 5 seconds 9) Input Current Limit 116% of nominal capacity 10) Inrush Current < 600% under synchronous condition 11) Input Current THD < 3% Total Harmonic Distortion (THD) 12) Surge Withstandability Meets ANSI C62.41 (IEEE 587) 13) Input Phase Rotation Standard front-panel alarm panel shall (Protection/Detection) notify user that unit has been supplied with incorrect phase rotation on input to allow for correct installation. The UPS shall be fully protected to prevent damage from this event. * For continuous operation at -30%, derate the maximum operating temperature to 90 F (32 C.) B. UPS Output 1) Rated Voltage 208/120VAC 2) Output Voltage Requirements 3 Phase, 4 Wire + Ground 3) Output Capacity 30 kva 4) Rated Load Power Factor 0.8 lagging 5) Voltage Regulation +/- 2% nominal (balanced load) +/- 3% nominal (unbalanced load) 6) Voltage Adjust. Range +/- 5% manually (by front panel user interface) 7) Phase Displacement +/- 2 deg. (balanced load) +/- 4 deg. (100% unbalanced load) 8) Rated Frequency 50/60 Hz (jumper selectable) 9) Frequency Regulation +/- 0.01% free running 10) Frequency Synch. Range +/- 0.5/1.0/1.5 Hz (+/- 1.0 Hz Standard) User selectable 4

C. Batteries 11) Frequency Slew Rate 1.0 Hz/second to 3.0 Hz/second 12) Voltage Transients +/- 5% (100% step load change) +/- 3% (loss or return of input power) +/- 8% (bypass to inverter) 13) Transient Voltage Recovery 50ms maximum to within 2% of nominal 14) Overload Cap. (on inverter) 125% for 90 sec., 150% for 30 sec. 15) Overload Cap. (on bypass) 1000% for 10ms, 125% for 10 min. 16) Crest Factor 2.5 3.0 within the kw range. 17) Harmonic Voltage Distortion 1.5% THD maximum, 1% maximum for any single harmonic (linear load) 18) Inrush Current Protection Automatic transfer to bypass, then autoreturn to inverter ( retransfer may be inhibited by jumper) 19) Output Overcurrent Hall-Effect Current Transformer and Fusing 1) Battery Type: Sealed, Valve Regulated Lead Acid cells 2) Protection Time: Each standard matching battery pack shall provide the minimum run-time: - 3.5 minutes back-up time @ 30 kva 3) DC Voltage Range: UPS Capacity 30 kva Nominal Voltage 288 VDC Alarms Voltage(V low) 252 VDC Shutdown Voltage (V min) 216 VDC 4) Ripple Voltage: 2% RMS maximum D. Environmental 1) Efficiency: 85% (AC/AC); 87% (DC/AC) 2) Operating Temperature: UPS: 32 to 104 F (0 to 40 C) Battery: 68 to 77 F (20 to 25 C) 3) Storage Temperature: UPS: -4 to 140 F (-20 to 60 C) Battery: prolonged storage above 104 F (40 C) causes rapid battery degradation 4) Relative Humidity: 30-90% (non-condensing) 5) Audible Noise: 60 db ( A scale @ 1 meter) 6) Altitude: < 6,000-ft. maximum (< 2,000 m) 5

4.0 FUNCTIONAL DESCRIPTION A. Converter / Charger / DC Chopper DESCRIPTION - The converter/charger shall consist of a solid-state three phase rectifier, DC to DC converter (chopper), output filter, and transient suppresser network to regulate and maintain DC power to the inverter. 1) TRANSIENT SUPPRESSER - The incoming AC utility shall first be connected to a molded case circuit breaker as a means of disconnecting power to the UPS. Power shall flow through a surge absorber to prevent large transients from passing through to the load or damaging the batteries. Power shall then flow through a line filter to prevent sags or surges from passing to the load. 2) CONVERTER/CHARGER - The converter shall serve to change incoming AC power to DC, which shall be supplied to the DC chopper. From this point, DC power is used to recharge the battery bank while simultaneously providing power to the inverter. a) Input Frequency Range: 45-65 Hz, continuous, without battery operation b) Capacity: Battery recharge shall be to within 90% of nominal from a fully discharged state in 10 times the discharge time. 3) DC CHOPPER - The chopper circuit shall consist of inductors, capacitors, diodes and IGBT's (Insulated Gate Bipolar Transistors). The chopper shall have the function of providing start-up protection (by checking phase rotation of incoming utility power), boosting the DC to the inverter (during low AC input voltage conditions), providing power factor enhancement, and reducing reflected harmonics to incoming utility power. B. Pulse Width Modulated (PWM) Inverter DESCRIPTION - The PWM (Pulse Width Modulated) inverter shall incorporate an advanced IGBT design, an output isolation transformer, and output overcurrent protection for clean, regulated output power to the critical load. 1) INVERTER - The inverter network shall consist of a high speed IGBT switching network designed to supply non-linear loads with a clean and 6

steady voltage waveform. The inverter switching speed shall be fast enough to limit audible noise to 60 dba at 3 feet (measured on A scale). 2) OVERCURRENT PROTECTION - The output circuitry shall be equipped with a Hall Effect Current Transformer to detect and protect the inverter from excessively high currents. C. Static Bypass Switch 1) TRANSFER - The static bypass switch shall consist of thyristor switches in conjunction with an output contactor to permit manual switching from bypass to UPS and UPS to bypass without power interruption. The UPS shall instantaneously transfer to bypass should a component fail during normal operation (provided the UPS and bypass are in synchronization). Auto-retransfer to UPS after an overload condition shall be completed within one second after the bus has dropped to 100% of nominal. 2) REMOTE RUN/STOP - A set of normally open dry contacts shall be provided to remotely transfer the UPS on-line and off-line. When the UPS is in this mode of operation, the UPS front control panel shall be disabled to provide a secured configuration. D. Microprocessor Control System 1) DESCRIPTION - The UPS system shall be provided with a highly reliable microprocessor internal control system to perform start-up, transfers, monitoring, and battery recharging. The microprocessor shall provide important information to the user (via a liquid crystal display) with such as system status, fault messages and input and output parameters. 2) LED INDICATORS - The following LED indicators shall be provided on the UPS front panel displays, which mimic power flow through the UPS: a) AC INPUT (Green Lamp) - Lights when normal AC input power is being supplied to the unit. b) INVERTER (Green Lamp) - Lights when the UPS unit s inverter is normal. c) BATTERY (Green Lamp) - Lights when the batteries are discharging: flickers when the battery voltage is below minimum. d) BYPASS (Green Lamp) - Lights when in circuit-bypass mode. d) FAULT (Red Lamp) - Lights when a fault has been detected. See System Diagnostics for specific fault. 7

3) SYSTEM METERING - The UPS shall be provided with a single readout display which displays, upon request, the following information: AC INPUT VOLTAGE (Line to Line) AC OUTPUT VOLTAGE (Line to Line, Line to Neutral) AC OUTPUT CURRENT BATTERY VOLTAGE BATTERY CHARGING CURRENT INPUT FREQUENCY OUTPUT FREQUENCY INPUT/ OUTPUT kw POWER FACTOR 4) SYSTEM DIAGNOSTICS - The following diagnostic information shall be provided to troubleshoot the UPS should a fault occur: UPS Ok Memory Error Wrong Phase Rotation of AC Input Internal AC Circuit Fault Internal DC Circuit Fault Heatsink Overheat DC unbalanced DC Circuit Over/Under voltage DC Circuit Overcurrent Chopper Input Overcurrent Inverter Overcurrent Inverter Over/Under voltage Inverter Overload UPS Overload (including Bypass) Inverter Output Current Limit Low Battery Voltage I/O not Synchronized Auto-transfer Mode Fuse Open Battery Discharging Mode UPS Output Disabled 5.0 MECHANICAL DESIGN A. UPS Enclosure The UPS shall be in a freestanding, NEMA1 enclosure equipped with casters and leveling feet. The overall dimensions and weights shall be as follows (without internal batteries): UPS Size Dimensions Weight 30 kva 20.0 W x 36.3. D x 59.7 H 915 lbs. B. Cable Entry 8

The UPS shall be provided with cable entry from the bottom, top and rear of the UPS enclosure. C. Ventilation and Maintenance Requirements The UPS shall require the following minimum space for ventilation and maintenance: 28 (front), 18 (top), 6 (rear), and 0 (side). 6.0 STANDARD FEATURES A. Emergency Power Off (EPO) Emergency Power Off (EPO) terminals which trip open the UPS and battery circuit breakers. B. RS232 Communication Interface Serial data link will enable the UPS to interface with a computer to provide power status and diagnostic information. C. DB9 Dry Contact interface The following normally open dry contacts shall be provided through a DB9 male connector located inside the front door: D. Battery Test Function 1) UPS On 2) Bypass Active 3) Input Power Loss 4) Battery Voltage Low The UPS shall be provided with a Battery Test pushbutton to periodically check the condition of the batteries. Upon detection of a battery problem, the UPS shall notify the user of this condition allowing the user to perform a detailed check of the battery string. 7.0 SERVICE AND WARRANTY A. Reliability 9

System mission reliability 240,000** hours and including bypass MTBF (Mean-Time-Between-Failure) shall be in excess of 3,000,000**hours. B. Maintainability C. Warranty Calculated and demonstrated MTTR (Mean-Time-To-Repair) shall be 30 minutes including time to diagnose the problem and replace subassembly. The UPS system shall be provided with a comprehensive three-year onsite warranty (when purchased with a Factory-Authorized Start-up). The warranty shall cover parts, labor, travel and freight for the UPS. The battery system has a full 2 year warranty with 3 year s prorata total of 5 year warranty. Typical on-site response time shall be 4 hours (24 hours maximum). The warranty period shall expire three years for UPS and two years for the battery system from date of shipment from manufacturer s facility. *Specification subject to change without notices. **Times are accurate provided normal Preventative Maintenance procedures are followed. 10

TOSHIBA /XT UPS Installation Planning Guide for 15-80kVA UPS Standard System: 208/120V Input, 208/120V Output UPS kva/ kw Rating General Mechanical Information Dimensions (W x D x H) Weight Approximate Full-Load Heat Loss Inches Lbs. kbtu/hr 15 kva/12 kw 20 x 36.3 x 59.7 900 9 25 kva/ 20 kw 20 x 36.3 x 59.7 910 12 30 kva/ 24 kw 20 x 36.3 x 59.7 915 14.4 50 kva/ 40 kw 35.5 x 38.3x 59.3 2,548 18.6 80 kva/ 64 kw 44 x 31 x 74 1,560* 27 Primary AC Input (208/120V 3-Phase / 4-Wire) Maximum Input Power Demand Suggested External Feeder Breaker Suggested Minimum Feeder Wire Size Per Phase / Neutral Suggested Maximum Feeder Length For Min. Wire Size in Steel Conduit kva PF Amps Amps AWG or kcmil at 75º C Temp. Rating Feet 15 >0.97 45 60 A (1) x 6 / (1) x 4 380 25 >0.97 70 90 A (1) x 3 / (1) x 1 380 30 >0.97 83 110 A (1) x 2 / (1) x 1 380 50 >0.97 138 175 A (1) x 2/0 / (1) 250 380 80* >0.97 218 300 A (1) x 300 / (1) x 500 380 Maximum Input Power Demand Optional Alternate AC Input (208/120V 3-Phase / 4-Wire) Suggested External Feeder Breaker Suggested Minimum Feeder Wire Size Per Phase / Neutral Suggested Maximum Feeder Length For Min. Wire Size in Steel Conduit kva PF Amps Amps AWG at 75º C Temp. Rating Feet 15 >0.97 39 60 A (1) x 6 / (1) x 4 380 25 >0.97 65 90 A (1) x 3 / (1) x 1 380 30 >0.97 78 110 A (1) x 2 / (1) x 1 380 50 >0.97 131 175 A (1) x 2/0 / (1) 250 380 80* >0.97 209 300 A (1) x 300 / (1) x 400 380 Battery Input (288VDC Nominal) Battery Capacity Required for Full Load Output Maximum Discharge at Full Load Output Suggested External Feeder Breaker Suggested Minimum Feeder Wire Size Per Phase Suggested Maximum Feeder Length For Min. Wire Size in Steel Conduit kwb Amps DC Amps AWG or kcmil at 75º C Temp. Rating Feet 15 14 61 70 A (1) x 4 70 25 23 100 100 A (1) x 1 70 30 28 120 125 A (1) x 1 70 50 45 195 200 A (1) x 250 70 80* 73 316 350 A (2) x 4/0 70 AC Output (208/120V 3-Phase / 4-Wire) Rated Output Power Suggested External Feeder Breaker Suggested Minimum Feeder Wire Size Per Phase / Neutral Suggested Maximum Feeder Length For Min. Wire Size in Steel Conduit kva PF Amps Amps AWG or kcmil at 75º C Temp. Rating Feet 15 0.8 39 60 A (1) x 6 / (1) x 4 380 25 0.8 65 90 A (1) x 3 / (1) x 1 380 30 0.8 78 110 A (1) x 2 / (1) x 1 380 50 0.8 131 175 A (1) x 2/0 / (1) 250 380 80* 0.8 209 300 A (1) x 300 / (1) x 400 380 * 80kVA UPS uses external battery cabinet, and has no internal transformers. Rev. 2.0 Page 1 of 2 4200FA-IPG-208v

Important Notes: TOSHIBA /XT UPS Installation Planning Guide for 15-80kVA UPS Standard System: 208/120V Input, 208/120V Output 1. Maximum Current required at Primary AC Input based on full load output and maximum battery charging current. 2. Output load conductors are to be installed in separate conduit from input conductors. 3. Control wires and power wires are to be installed in separate conduits. 4. Recommended AC input and output overcurrent protection based on continuous full load current per NEC. 5. Wiring shall comply with all applicable national and local electrical codes. 6. Grounding conductors to be sized per NEC Article 250-122. Neutral conductors to be sized per NEC Article 310.15. - Primary AC Input: 3, 3-wire + ground. - AC Output: 3, 4-wire + ground. - DC Input: 2-wire (Positive/Negative) + ground. 7. Power cable maximum size: 15/25/30kVA: #1 AWG 50kVA: 250 kcmil 80kVA: 500 kcmil, Battery Terminals 600 kcmil 8. Nominal battery voltage based on the use of VRLA type batteries (2.0 volts / cell nominal). 9. Maximum battery discharge current based on lowest permissible discharge voltage of 1.6 VPC. 10. DC wires should be sized to allow not more than a 2-volt drop at maximum discharge current. 11. Weights include internal batteries. 12. Sizing calculations based on the following assumptions: - Not more than 3 current-carrying conductors installed in steel conduit in ambient temperature of 30 degrees C. - Temperature rating of conductors and terminals: 75 deg. C. - Feeder distance calculations based on NEC Tables 8 and 9 data, allowing for 2% AC voltage drop. - Reference: 2002 NEC Handbook. Consult latest edition of applicable national and local codes for possible variations. 13. Ratings of wires and overcurrent devices are suggested minimums. Consult with a registered Professional Engineer within your local area for proper size selections. TOSHIBA INTERNATIONAL CORPORATION 13131 West Little York Road Houston, TX 77041 Telephone: 800.231.1412; 713.466.0277 Fax: 713.896.5212 Corporate Web Site: www.tic.toshiba.com Group Web Site: www.toshibaups.com Rev. 2.0 Page 2 of 2 4200FA-IPG-208v

A B C D E F G H I J 1 Customer Utility Supply 1 2 2 3 Maintenance Bypass 3 Static Switch Bypass 4 5 6 AC Input 208/120V, 3Ph/4W, 50/60Hz MCCB High Freq. Noise Filter Contactor Converter SYNC Inverter DC Chopper/ Charger Contactor High Freq. Noise Filter Make-Before-Break AC Output 208/120V 3Ph/4W, 50/60Hz, 30kVA, 0.8 PF 4 5 6 7 7 8 Internal Battery: 288 VDC Nominal 8 9 9 10 Customer supplied wiring Customer supplied wiring 10 NOTES 1) This drawing is for illustration purposes only and is subject to change without notice. TIC is not responsible for any errors or omissions. Drawn by EO DATE 03/25/04 Approved by JIS DATE 03/25/04 TOSHIBA INTERNATIONAL CORPORATION Houston Texas, USA THIS MATERIAL IS THE EXCLUSIVE PROPERTY OF TOSHIBA INTERNATIONAL CORPORATION AND SHALL NOT BE REPRODUCED, USED, OR DISCLOSED TO OTHERS UNLESS PRIOR WRITTEN AUTHORIZATION IS OBTAINED. TITLE DRAWING NO. One-Line Drawing UPS, 30kVA Capacity Single Input Internal Battery Model T42F3F300XAMBN REV. 1.2