This document provides additional assistance with wiring your Extron IP Link enabled product to your device. Different components may require a different wiring scheme than those listed below. For complete operating instructions, refer to the user s manual for the specific Extron IP Link enabled product or the controlled device manufacturer supplied documentation. Device Specifications: Device Type: Manufacturer: Firmware Version: Model(s): Lighting Control Lutron Grafik Eye QS - CODE:5.30, BOOT:4.1, HW:2.1 QSE-CI-NWK-E - CODE:7.15, BOOT:2.9, HW:1.0 Sivoia QS - CODE:0.100, BOOT:2.9, HW:8.6 seetouch QS - CODE:2.50, BOOT:2.3, HW:1.1 QSN-2ECO-S- CODE:5.17, BOOT:0.3, HW:3.1 QSNE-2DAL-D - CODE:5.8, BOOT:5.1, HW:3.1 QSN-4S16-S - CODE:5.15, BOOT:1.5, HW:1.1 Grafik Eye QS, QSE-CI-NWK-E, Sivoia QS, seetouch QS, QSN-2ECO-S, QSNE-2DAL-D, QSN-4S16-S, Quantum System Minimum Software and Firmware Requirements: IP Link Compiler IP Link Firmware GC Version 1.6.0 1.17 3.5.1 Version History: Driver Version Date Notes 8 9/24/2103 7 1/3/2012 6 12/4/2012 Extron Certified. Tested on QSE-CI-NWK-E. Updated driver to be compatible with GC 3.5.1 Fixed delay issue when sending commands. Added model. Quantum System. 5 9/7/2011 Extron Certified. Added models QSNE-2DAL-D and QSN-4S16-S. Tested on both models. 4 5/27/2011 Extron Certified. Added model QSN-2ECO-S. Tested on QSN-2ECO-S. 3 10/1/2010 Extron Certified. Tested on QSE-CI-NWK-E system with a Grafik Eye, two seetouch QS panels, and a Sivoia QS shade. Added models Sivoia QS and seetouch QS. Added Button, Button Mode, Device select and Shade Position. 2 8/2/2010 Modified the driver to accept serial numbers 1 2/18/2010 Initial version. Page 1 of 6
Driver Notes: Zone Select includes Fade Time; default Fade Time is 1 second. The Configuration Notes on pg.3 explain how to set up the driver. Control Commands & States: Area Level 7 0 to 100 in steps of 1 Area Level (Step) 7 Up Down Stop Area Scene 7 0-32 Area Select 4 1-200 Button 1-100 Button Mode 1 Execute Stop Daylight Automation 7 Active Inactive Device Select 1-3 Fade 1-59 2 1-10 Min 15 Min 20 Min Select Integration ID 7 1-200 Master Level (Step) 1 Up Down Stop Output Level 7 0 to 100 in steps of 1 Output Level (Step) 7 Up Down Stop Preset Scene 1-16 Off Serial Digit 1-8 0-9 A-F Shade Group Level 7 0 to 100 in steps of 1 Shade Group Level (Step) 7 Up Down Stop Shade Group Preset 7 1-30 Shade Position 0-100 Zone Select 3 1-100 Level 0-100 in steps of 1 Page 2 of 6
1 This command has press/release functionality. The stop command is used for configuration purposes only. 2 This value is in seconds. 3 Zones 25-100 are for the QSN-2ECO-S. QSN-2ECO-S. Zones 1-32 are for the QSNE-2DAL-D, and zones 1-4 are for the QSN-4S16-S. 4 When using the QSN-2ECO-S, select an area before sending the preset scene command. Only areas 1-32 will work on the QSNE-2DAL-D and 1-4 on the QSN-4S16-S. 7 Will only work with Quantum System. Status Available: Connection Status Connected Disconnected Area Scene 0-32 Daylight Automation Active Inactive Shade Group Preset 1-30 Output Level 0 to 100 in steps of 1 Preset Scene 1-16 Off Level 0-100 Shade Position 0-100 Zone 1-24 Page 3 of 6
Configuration Notes: 1. Use the Device Select command to select the type of device being controlled according to the following table: Device Select Device 1 Grafik Eye QS 2 QS Shade 3 seetouch QS 4 QSN-2ECO-S 5 QSN-4S16-S 6 QSNE-2DAL-D 2. Next use Serial Digit 1-8 in the driver to match the serial digit on the device that you are trying to control. This will have to be configured for every device in the system. For example, if the serial number on a Grafik Eye is 00AC123D, then you will configure the Serial Digits in the driver as the following: Serial Digit 1 will be 0 Serial Digit 2 will be 0 Serial Digit 3 will be A Serial Digit 4 will be C Serial Digit 5 will be 1 Serial Digit 6 will be 2 Serial Digit 7 will be 3 Serial Digit 8 will be D Note: If you are going to control/monitor another device, such as a QS Shade, then you also need to configure the Serial Digits to match that device before controlling it and use the correct Device Select in the driver. 3. In addition to the first two steps, to control a seetouch QS keypad or the front panel of a Grafik Eye QS, you must select the button in the driver that corresponds with the buttons on the device. See Appendix A in integration protocol or contact manufacturer to see what button number in the driver corresponds to what button on the device. 4. Light intensity levels on a Grafik Eye QS or QSN-2ECO-S, QSNE-2DAL-D, or QSN-4S16-S can be changed by using the Level command in the driver. In order to change Level command, you must select Zone Select and Fade commands. Level Status will only show level of currently selected zone. Page 4 of 6
Configuration Notes for Quantum System: 1. Use the Device Select command to select the type of device being controlled according to the following table: Device Select Device 7 Quantum System 2. Next use Integration ID 1-200 in the driver to match the device that you are trying to control. This will have to be configured for every device in the system. Page 5 of 6
Network communication: When configuring the Ethernet driver, be sure device settings match that of the GC configuration. Multi-connection can only work with 2 devices; the second user name is nwk2. Port Type: Ethernet Logon Credentials Yes Supported: Default User Name: nwk Default Password: N/A Default Port: 23 Multi-Connection Yes Capable: Port Changeable: Yes Ethernet Driver Configuration Description: Please refer to user manual for settings and changes to the network communication parameters such as: User Name, Passwords. Notes for the Device: Page 6 of 6