Selecting an Industry-Standard Metric for Data Center Efficiency



Similar documents
Electrical Efficiency Modeling for Data Centers

Electrical Efficiency Modeling of Data Centers

Efficiency and Other Benefits of 208 Volt Over 120 Volt Input for IT Equipment

Avoiding Costs from Oversizing Data Center and Network Room Infrastructure

Avoiding Costs from Oversizing Data Center and Network Room Infrastructure

Electrical Efficiency Measurement for Data Centers

Implementing Energy Efficient Data Centers

How To Calculate Total Cooling Requirements For Data Center

Data Center Projects: Project Management

The Different Types of UPS Systems

Increasing Data Center Efficiency by Using Improved High Density Power Distribution

Calculating Total Cooling Requirements for Data Centers

Improving Rack Cooling Performance Using Airflow Management Blanking Panels

Re-examining the Suitability of the Raised Floor for Data Center Applications

Data Center Projects: Project Management

An Improved Architecture for High-Efficiency, High-Density Data Centers

Determining Total Cost of Ownership for Data Center and Network Room Infrastructure

The Different Types of UPS Systems

The Different Types of UPS Systems

Strategies for Deploying Blade Servers in Existing Data Centers

Data Center Projects: Project Management

THE GREEN GRID DATA CENTER POWER EFFICIENCY METRICS: PUE AND DCiE

The Efficient Enterprise. Juan Carlos Londoño Data Center Projects Engineer APC by Schneider Electric

AC vs DC Power Distribution for Data Centers

Guidelines for Specification of Data Center Power Density

Greener Pastures for Your Data Center

Measuring Energy Efficiency in a Data Center

Improving Rack Cooling Performance Using Airflow Management Blanking Panels

Power and Cooling Capacity Management for Data Centers

Guidelines for Specification of Data Center Power Density

AbSTRACT INTRODUCTION background

Metrics for Data Centre Efficiency

A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture

EU Code of Conduct for Data Centre Efficiency

Overload Protection in a Dual-Corded Data Center Environment

Data Center Energy Use, Metrics and Rating Systems

GREEN GRID DATA CENTER POWER EFFICIENCY METRICS: PUE AND DCIE

Calculating Space and Power Density Requirements for Data Centers

Power (kw) vs Time (hours)

Guidance for Calculation of Efficiency (PUE) in Data Centers

Calculating Total Power Requirements for Data Centers

Benchmarking results from Indian data centers

Datacenter Efficiency

Green Evaluation Metrics and Software Tool for Data Center

Data centre energy efficiency metrics. Existing and proposed metrics to provide effective understanding and reporting of data centre energy

Time Value of Money. Critical Equation #10 for Business Leaders. (1+R) N et al. Overview

Energy Efficiency Monitoring in Data Centers: Case Study at International Hellenic University. George Koutitas, Prof. L. Tassiulas, Prof. I.

AC vs. DC Power Distribution for Data Centers

A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture

Data Centers: Definitions, Concepts and Concerns

The Trellis Dynamic Infrastructure Optimization Platform for Data Center Infrastructure Management (DCIM)

Data Center Technology: Physical Infrastructure

Schedule Adherence. and Rework Walt Lipke, PMI Oklahoma City Chapter. PUBLISHER s CHOICE

Why is Insurance Good? An Example Jon Bakija, Williams College (Revised October 2013)

Managing Power Usage with Energy Efficiency Metrics: The Available Me...

Recommendations for Measuring and Reporting Overall Data Center Efficiency

StruxureWare. How to reconcile efficiency and availability in a virtualized data center. for data centers

How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems

Limits. Graphical Limits Let be a function defined on the interval [-6,11] whose graph is given as:

Guidance for Calculation of Efficiency (PUE) in Data Centers

ISSN :

Accuplacer Arithmetic Study Guide

Recommendations for Measuring and Reporting Overall Data Center Efficiency

ERE: A METRIC FOR MEASURING THE BENEFIT OF REUSE ENERGY FROM A DATA CENTER

Why Energy Management Is Driving Adoption of Data Center Infrastructure Management Solutions

Data Center Business Overview:

A Concrete Introduction. to the Abstract Concepts. of Integers and Algebra using Algebra Tiles

2.3. Finding polynomial functions. An Introduction:

Building a data center. C R Srinivasan Tata Communications

CHAPTER 8 STOCK VALUATION

Identifying Energy Saving Opportunities in the Data Center

Data Center Industry Leaders Reach Agreement on Guiding Principles for Energy Efficiency Metrics

High-Efficiency AC Power Distribution for Data Centers

Data Center Build vs. Buy

Smarter Data Centers. Integrated Data Center Service Management

> Executive summary. Data Center Projects: Standardized Process. White Paper 140 Revision 1. Contents. by Neil Rasmussen and Suzanne Niles

Understanding Power Usage Effectiveness (PUE) & Data Center Infrastructure Management (DCIM)

Auditing a data centre but to what standard?

EVALUATING ACADEMIC READINESS FOR APPRENTICESHIP TRAINING Revised For ACCESS TO APPRENTICESHIP

Data Center Efficiency Metrics: mpue, Partial PUE, ERE, DCcE

Data Center & IT Infrastructure Optimization. Trends & Best Practices. Mickey Iqbal - IBM Distinguished Engineer. IBM Global Technology Services

The Trellis Dynamic Infrastructure Optimization Platform

Reducing the Annual Cost of a Telecommunications Data Center

Measuring Power in your Data Center

Impact of Leading Power Factor on Data Center Generator Systems

Reducing Data Center Energy Consumption

Report on the Scaling of the 2013 NSW Higher School Certificate. NSW Vice-Chancellors Committee Technical Committee on Scaling

Leveraging Radware s ADC-VX to Reduce Data Center TCO An ROI Paper on Radware s Industry-First ADC Hypervisor

Transcription:

Selecting an Industry-Standard Metric for Data Center Efficiency By Neil Rasmussen White Paper #157

Executive Summary The development of standards for the measurement and specification of data center efficiency is an essential step in the global effort to reduce the environmental impact of data centers. This paper explains some of the metrics that have been used to describe the efficiency of data center physical infrastructure and suggests which metric is the most effective. 2

Introduction In today s environment, it is good public policy and good business to consider the options to control data center energy consumption. A 1MW high-availability data center can consume $20,000,000 worth of electricity over its lifetime. Recent articles suggest that for some customers the cost of electricity is greater than the cost of hardware. Many companies are beginning to consider the carbon consumption of their ongoing operations and realizing that data centers are significant contributors to the environmental burden of business and industry. Research by APC-MGE and others is showing that efficiency varies widely across similar data centers, and even more significant the actual efficiencies of real installations are well below the practical achievable best-in-class values. The result is a strong desire among users, manufacturers, and public policy makers to incent and realize improved electrical efficiency in data centers. In this paper, we will focus on the power consumption and efficiency of data center power, cooling, and other miscellaneous infrastructure, which consumes 50% or more of the electrical power in a typical installation. The power consumption and efficiency of the equipment supported by the infrastructure, while critically important to overall energy use, is not the subject of this paper. Efficiency metrics are needed to allow users to compare alternative scenarios, to allow specific data centers to be benchmarked against similar facilities, and to measure progress against internal or external targets. Holistic View of Data Center Efficiency In a whole-system view, the data center takes in and performs useful (Figure 1). Within the data center, there are two major subsystems: (1) the data center s infrastructure, which provides support and protection for (2) the equipment, which performs the real work of the data center. 3

Figure 1 Basic elements of data center efficiency analysis Data center Infrastructure Power Cooling Lighting Physical security Fire protection Servers Storage Networking Data center PUT Data center OUTPUT Also called: Power Total power consumed Total input power Facility input Total incoming power Also called: Physical infrastructure Site infrastructure Facilities NCPI Also called: power demand power load () critical power load Critical load Also called: output work work Using the model in the above figure, overall data center efficiency can be represented by the following simple equation: Overall data center efficiency = This basic view of data center efficiency, with the two-part internal breakdown shown in Figure 1, forms the foundation of the data center efficiency research and analysis currently being done by the US EPA and the EC Directorate-General. The two components of data center efficiency: Infrastructure efficiency and efficiency Overall data center efficiency can be logically and mathematically separated into infrastructure efficiency and efficiency. These two components of overall efficiency are referenced in the 2007 EPA Report to Congress, excerpted below. From the EPA report: 1 1 U.S. Environmental Protection Agency ENERGY STAR Program, Report to Congress on Server and Data Center Energy Efficiency, Public Law 109-431, August 2007, page 94 4

Brill (2007) defines the aggregate energy productivity of a data center as the product of two terms: 1) The ratio of output from the data center (like web pages served or calculations completed over some period) divided by the average of power demanded by the, storage, and networking equipment within the data center [termed the information technology (or ) critical power load]. 2) The ratio of critical power load to the total incoming power consumed by the datacenter. Multiplying these terms together yields a ratio of total output (e.g., web pages served) by total input power to the data center facility. Figure 2 EPA breakdown of data center efficiency (Refer to Figure 1) 1 efficiency Infrastructure efficiency compares useful OUT to what goes 2 FRASTRUCTURE efficiency Infrastructure Infrastructure efficiency compares useful OUT to what goes 1 efficiency X = 2 Infrastructure efficiency Data center efficiency Infrastructure Data center efficiency compares useful OUT to what goes (The subject of this paper) 5

EPA criteria for an infrastructure efficiency metric The EPA report further clarifies requirements for the metric to be used to specify the infrastructure efficiency component (called site infrastructure in the EPA report efficiency component #2 above): A meaningful measure of site infrastructure efficiency needs to meet the following criteria: 1) clearly convey its meaning, 2) correctly define an efficiency metric in which the output metric is in the numerator and the energy input in the denominator, and 3) apply only to the site infrastructure portion of the data center. To review, the EPA report defines data center efficiency as the combined (multiplied) efficiency of the data center s two major components infrastructure and (Figure 3). The second term in the multiplication is infrastructure efficiency. This has begun to appear in the industry literature as data center infrastructure efficiency, or DCiE a metric that aligns precisely with the EPA definition quoted above. The defense of DCiE as the correct metric for infrastructure efficiency is the subject of this paper. Figure 3 DCiE meets EPA criteria for an infrastructure efficiency metric efficiency FRASTRUTURE efficiency DATA CENTER efficiency X = Refer to Figure1 for the context of these elements in overall data center efficiency DCiE meets the requirements of the EPA report, plus has the convenient benefit of having the same units in the numerator and denominator (), so the resulting DCiE ratio is dimensionless and can be expressed as an ordinary percent from zero to 100%. % Ratio expressed as percent 6

Alternative Metrics For Infrastructure Efficiency There are a number of different metrics currently in use to represent the EPA concept of infrastructure efficiency, which can be confusing to both the data center community and the public. These different metrics are summarized in Table 1. Table 1 Various metrics for infrastructure efficiency currently found in the literature Metric Meaning Value Range Status DCiE Data Center Infrastructure Efficiency DCE Data Center Efficiency PUE Power Utilization Effectiveness SI-EER Site Infrastructure Energy Efficiency Ratio SI-POM Site Infrastructure Power Overhead Multiplier Ratio of load power to facility input power 0-100% Same as DCiE 0-100% Ratio of facility input power to load power (1/DCiE) Infinity - 1 Same as PUE Infinity - 1 Same as PUE Infinity - 1 Leading term compliant with EPA and EC specifications Being replaced by DCiE because it was not clear whether it included the part of the data center Non-compliant with EPA specification; nonintuitive because efficiency goes up when value goes down An alternative term for PUE that is not widely used A recent term that has been proposed to replace PUE because the language is more intuitive i.e., lower overhead is better Table 1 shows that there are really only two metrics, DCiE and PUE the others are simply different terminology representing one of these two metrics. Various public reports, such as the EPA Report to Congress, describe the confusion over metrics and the need to develop a consensus around a single metric, and a single term to describe it. We believe that under close examination, the DCiE emerges as the best and most effective metric for describing data center infrastructure efficiency. While the PUE metric conveys the same information mathematically, it is more difficult to understand and communicate effectively. 7

Comparing the DCiE and PUE Metrics There are a variety of ways to compare and evaluate these two metrics in order to discover good reasons to select one over the other. Displaying efficiency data in graphical form Every data center has a characteristic efficiency curve as a function of load, which is an essential description of the capabilities of the data center. In the future, this curve will be provided as part of a data center design, as it is today for various components such as UPS. A typical data center efficiency curve is shown in Figure 4 using the DCiE metric. Figure 4 Typical infrastructure efficiency curve, using DCiE as the metric DCiE 100% 90% 80% 70% 60% 50% 40% 30% 20% 10% 0% 0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% % Load The same data center can have its efficiency represented by the PUE metric, as shown in Figure 5. 8

Figure 5 Typical infrastructure efficiency curve, using PUE as the metric 3.5 3.0 2.5 PUE 2.0 1.5 1.0 0.5 0.0 0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% % Load When these curves are compared, it is immediately apparent that part of the data on the PUE curve, below 12% load, is truncated. This is because PUE always approaches infinity as the load approaches zero. If more of the curve is shown for light load by expanding the vertical scale, then the PUE scale becomes compressed and it is difficult to read PUE values of the curve at higher loads. By contrast, the DCiE curve is always constrained to the range 0-100% so all plots are standardized and no data is missing. This same problem affects instrumentation displays. If a display has a range limit then PUE data may be truncated. By contrast, a 0-100% display always can show any DCiE value. From this comparison, it is clear that the PUE is less effective for conveying graphical efficiency data for data center designs. Public communication Virtually every written publication about data center power consumption uses the term efficiency. Efficiency has a plain meaning to most people, which is that increased efficiency is desirable. If PUE is used as an efficiency metric then the idea that the number must go down to increase efficiency is contrary to expectation. In discussions of PUE it is common to hear comments such as I want to increase my PUE, not understanding or remembering that they actually want to decrease PUE. 9

It is very likely that people will continue to discuss data center efficiency and the need to increase it. The efficiency metric should reflect this intuitive higher is better concept, as DCiE does, and not reflect the opposite, as PUE does. Based on our interviews with data center users and members of the press, it is fair to say that DCiE is a more intuitive metric than PUE. Instrumentation Computing either DCiE or PUE requires mathematical calculations from instrumentation readings. Neither value can be read directly from basic instruments. There is no reason to prefer one over the other to simplify instrumentation. For purposes of display, however, PUE has the disadvantage of going to infinity, while DCiE can always be displayed on a 0-100% scale. DCiE vs. PUE in analysis Efficiency analysis requires breaking down the contributions to inefficiency and assigning them to different subsystems within the data center. For this type of calculation, PUE has an interesting feature: the PUE value minus one is equal to the sum of the per unit losses of all the power, cooling, and lighting devices. The per-unit calculation is a common methodology among power system engineers, which accounts for the early emergence of PUE as an efficiency metric. DCiE has the disadvantage that one additional calculation 1/ X, or taking its inverse is needed to convert to additive per-unit values. However, in the future this calculation will be performed automatically by data center efficiency monitoring instrumentation. Therefore, this minor computational distinction should be a non-issue for data center users and public policy makers. Comparing benchmarks As efficiency becomes a pervasive even dominating concern in the industry, it will become common to compare efficiency benchmarks. Consider the following comparative descriptions of two data centers: Data center A has a DCiE of 50% and data center B has a DCiE of 60% Data enter A has a PUE of 2.0 and data center B has a PUE of 1.6 Carefully consider these two sentences and see which one most clearly communicates which has better efficiency, and by how much. Consider which one is most likely to be misinterpreted. 10

Summary comparison of DCiE and PUE Table 2 summarizes the differences between DCiE and PUE as the metric for data center infrastructure efficiency. Table 2 Comparison of DCiE and PUE metrics for data center infrastructure efficiency Worst value Best value Direction of improvement Relation to other metric Meets metric requirement established by EPA report? DCiE 0% 100% Higher is better 1 / PUE Yes PUE Infinity 1 Lower is better 1 / DCiE No Use of Efficiency Metrics It is very important to understand that any efficiency metric is incomplete without data regarding the averaging period and the operating conditions of the data center. The efficiency performance of a data center varies with load and other conditions, in much the same way as the fuel economy of a car varies. To better understand how to measure efficiency, how to benchmark it, and how to interpret it, refer to APC White Paper #154, Electrical Efficiency Measurement For Data Centers. Conclusion Many metrics have been discussed in the industry to describe the efficiency of data center infrastructure. All the metrics in the literature convey the same basic information, but using a number of different acronyms and two possible mathematical representations one the inverse of the other. With the discussion of data center efficiency now becoming widespread and intense, it is time for a thoughtful consideration of the alternatives in order to lead to industry standardization on a single metric. This paper argues for data center infrastructure efficiency (DCiE) as the best metric of the ones currently appearing in efficiency discussions. Its name and concept are intuitive, it can be easily displayed on a standard scale, and it relates to our everyday understanding of what an efficiency metric should represent higher is better, and 100% is perfect. It is consistent with the requirements for an effective metric as established in the 2007 US EPA Report to Congress. 11

The most commonly used alternative, PUE, has the mathematically obscure (and graphically difficult) scale of one to infinity, and the non-intuitive property that it is a measure of efficiency that decreases as efficiency increases. A measure of effectiveness that goes down when effectiveness goes up can easily lead to unnecessary confusion and misstated comparisons. Furthermore, the PUE metric does not meet the requirements set out in the EPA guidelines to Congress regarding data center efficiency metrics. About the Author Neil Rasmussen is the Chief Technical Officer of APC-MGE. He establishes the technology direction for the world s largest R&D budget devoted to power, cooling, and rack infrastructure for critical networks. Neil is currently leading the effort at APC-MGE to develop high-efficiency, modular, scalable data center infrastructure solutions and is the principal architect of the APC-MGE InfraStruXure system. Prior to founding APC in 1981, Neil received his Bachelors and Masters degrees from M in electrical engineering where he did his thesis on the analysis of a 200MW power supply for a tokamak fusion reactor. From 1979 to 1981, he worked at M Lincoln Laboratories on flywheel energy storage systems and solar electric power systems. 12