Spill Prevention, Control. and. Countermeasures Plan



Similar documents
SPILL PREVENTION, CONTROL AND COUNTERMEASURE PLAN

ACTIVITY NAME. Training Requirements for Spill Prevention Control and Countermeasures (SPCC) 40 CFR Part 112 Naval Air Station Corpus Christi Texas


OREGON FIRE CODE Interpretations and Technical Advisories

Spill Prevention, Control and Countermeasure (SPCC) Rule

History of the SPCC Rule

SPILL PREVENTION, CONTROL AND COUNTERMEASURE PLAN. for the PIÑON RIDGE MILL HIGHWAY 90 BEDROCK, COLORADO Prepared by:

SPILL PREVENTION, CONTROL AND COUNTERMEASURES (SPCC) PLAN

Kurt Wilson Louisiana Dept. of Environmental Quality Business & Community Outreach Division Small Business/Small Community Assistance Program

Spill Control Prevention Plan (SCPP)

Civil Engineering Sector Labour-Management Health and Safety Committee

Spill Prevention Control & Countermeasure (SPCC) for Farms

CITY OF WASHINGTON SPILL PREVENTION, CONTROL AND COUNTERMEASURE PLAN

Notes. Material 1. Appropriate Flammable Liquids

SPILL PREVENTION CONTROL AND COUNTERMEASURE PLAN PREPARED FOR: ARKANSAS STATE UNIVERSITY JONESBORO, ARKANSAS ORIGINAL DATE OF PLAN: APRIL 2005

TRAINING SPCC/SWPP Training UGA. Automotive Center. Campus Transit

SPILL PREVENTION, CONTROL AND COUNTERMEASURE (SPCC) PLAN

Inspections Standard Operating Procedure 5 Aboveground Storage Tanks

Fuel Storage Who to ask: tank farm owners/operators

ABOVE-GROUND STORAGE TANKS

for Gary Hughes GARY HUGHES SELF SERVICE LLC State of Missouri ID: ST

Waste Oil Collection / Storage

ALLEGANY WIND POWER PROJECT CONSTRUCTION SPILL PREVENTION PLAN

The following definitions apply with regard to requirements specified in this document:

Title: Aircraft Parking

How To Safely Handle A Spill

MODULE IV Secondary Containment, Oil Spill Control & Spill Prediction

Appendix VIII: Spill Prevention, Control and Countermeasure (SPCC) Plans

APPENDIX O. Spill Prevention and Emergency Response Plan. G3 Terminal Vancouver Port Metro Vancouver Project Permit Application APPENDIX O

Spill Prevention, Control and Countermeasure (SPCC) Training

Spill Prevention Control and Countermeasures (SPCC) Plan (Onshore, Nonproduction Facility) Kennesaw State University

SPCC. Created by EPA in 1973 under the Clean Water Act. 10/22/2014. Spill Prevention Control & Countermeasure Plan

Sample Written Program. For. Flammable Liquids

Management Approval/Certification Statement

SPCC for Food Services

Spill Prevention, Control and Countermeasure Plan Checklist

Safe Operating Procedure

SPILL PREVENTION, CONTROL, AND COUNTERMEASURE PLAN Community College of Rhode Island Warwick, Rhode Island

Spill Prevention, Control and Countermeasure (SPCC)

OIL STORAGE REQUIREMENTS OF THE SPCC REGULATIONS. Christopher J. Ecsedy, P.E. Fuss & O'Neill, Inc. 146 Hartford Road Manchester, CT 06040

ADMINISTRATIVE SERVICES MANUAL

FUELING AND FUEL STORAGE

The Federal Spill Prevention, Control & Countermeasures (SPCC) Rule Overview

Critical Regulations SUMMARY OF. Stormwater Management Regulations (National Pollutant Discharge Elimination System or "NPDES ) 40 CFR 122.

SPILL PREVENTION, CONTROL AND COUNTERMEASURES (SPCC) PLAN

The following definitions apply with regard to requirements specified in this document:

Section 5. Secondary Containment and Impracticability. (as applicable to APSA tank facilities)

OPERATIONS & MAINTENANCE (O&M) FOR PROPANE STORAGE FACILITIES

MAINE DEPARTMENT OF ENVIRONMENTAL PROTECTION

WESTERN CONNECTICUT STATE UNIVERSITY SPILL PREVENTION, CONTROL, AND COUNTERMEASURES PLAN PROCEDURE E-104. Prepared by:

Outdoor Liquid Container Storage

UNIVERSITY OF WISCONSIN MADISON

Safety Manual Title: Spill Prevention & Response Review Date: 6/1/2014

FACILITY ENVIRONMENTAL COMPLIANCE

Technical Requirements for Aboveground Storage Tanks (ASTs) Storing Class IIIB Liquids (other than used oil)

Clayton State University 2000 CLAYTON STATE BLVD. Morrow, Georgia DRAFT SPILL PREVENTION, CONTROL, AND COUNTERMEASURES (SPCC) PLAN

Steel Tank Institute AST Inspections. Dana Schmidt, PE STI/SPFA

SPILL PREVENTION, CONTROL AND COUNTERMEASURE (SPCC) PLAN

Application for the Construction or Installation of Aboveground Storage Tank (AST) Systems or Associated Underground or Over-water Piping Systems

U.S. ENVIRONMENTAL PROTECTION AGENCY TIER I QUALIFIED FACILITY SPCC PLAN TEMPLATE

Farm Fuel Tank Safety Guide

U.S. ENVIRONMENTAL PROTECTION AGENCY TIER I QUALIFIED FACILITY SPCC PLAN TEMPLATE

If your campus has. Oil Pollution Prevention Rules (con.) Oil Pollution Prevention Rules (con.)

Spill Prevention, Control, and Countermeasures (SPCC) Regulations Update

Environmental Standard Operating Procedure Originating Office: MCAS Miramar Environmental Management Department

Pressure Vessels (Air Compressors) and LPG Tanks

Chaffee Landfill & CID Hauling Olean Road Chaffee, New York 14030

Spill Prevention, Control, and Countermeasure Plan Daneros Mine

IAC 7/2/08 Agriculture and Land Stewardship[21] Ch 44, p.1

Good Housekeeping Practices for DPW/Fleet Maintenance Facilities

1. Site plans assist the Fire Department to determine where a potential spill can be contained. The detailed site plan shall include the following:

Spill Prevention, Control, and Countermeasures (SPCC) Course Material

Tank Environmental Regulations. Aisha Beaty Barr Engineering Company

Used Oil Guidance. Tank and Secondary Containment Requirements For Used Oil Processors

BP WIND ENERGY POLICIES AND PROCEDURES

July 1, Job No

Spill Plan Reviewer s Guidance

Spill Prevention Control and Countermeasure (SPCC) Regulations Fact Sheet

For an Incidental Oil Spill:

SPILL PREVENTION CONTROL AND COUNTERMEASURE PLAN

DISCLAIMER - APPENDIX D

Spill Prevention, Control, and Countermeasure Plan. Roger Williams University One Old Ferry Road Bristol, Rhode Island

DIRECTIVE 055: STORAGE REQUIREMENTS FOR THE UPSTREAM PETROLEUM INDUSTRY. August 2012

ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600

Spill Prevention, Control & Cleanup SC-11

FLAMMABLE AND COMBUSTIBLE LIQUIDS. n OSHA Changes

Facility Scenario - Example Tier I Qualified Facility SPCC Plan

OIL POLLUTION PREVENTION REGULATIONS

Improper storage of fuel on construction sites will increase the risk of water pollution that may occur as a result of leaks or spills.

The Federal Spill Prevention, Control & Countermeasures (SPCC) Rule Overview

MPM. Customer Service Representative Training. Class C Fuel Spill Handling

MASTER SPILL PREVENTION CONTROL & COUNTERMEASURE (SPCC) PLAN

Chapter 2 Stormwater Pollution Prevention Plan (SWPPP) for Park Operations

ATTACHMENT 1-9 CHWSF CONTAINER MANAGEMENT

TYPICAL FIRE SAFETY INSPECTION VIOLATIONS

SPILL PREVENTION, CONTROL, AND COUNTERMEASURE PLAN

W250. The Agricultural Producers Comprehensive Guide to Federal Oil Pollution Prevention Regulations

Appendix J Spill Prevention and Response Plan

~CSRMA ALERT~ REVISED SPCC RULE WILL IMPACT MOST POTW S

Transcription:

Spill Prevention, Control and Countermeasures Plan 2013

Spill Prevention, Control and Countermeasures Plan for Texas A&M University-Corpus Christi 2013 Prepared By: David Jensen, National Spill Control School Texas A&M University-Corpus Christi Roy Coons, Environmental, Health and Safety Department Texas A&M University-Corpus Christi Approved by: Authorized Facility Representative Date:

Spill Prevention, Control and Countermeasures Plan For Texas A&M University-Corpus Christi Table of Contents SPCC Certification SPCC Compliance Inspection Review Management Approval Facility Owner/Operator Facility Contacts Facility Description Facility Storage Facility Distance to Navigable Waters and Adjoining Shorelines Spill History Potential Spill Predictions, Volumes, Rates and Control Spill Prevention Measures 1. Drainage Control 2. Aboveground Storage Tanks and Secondary Containment 3. Fueling Station Transfer Operations 4. Inspections and Record Keeping 5. Site Safety and Security 6. Personnel Training 7. Spill Control Equipment and Cleanup Emergency Contacts Appendices Appendix A: Photographs of Fueling Station Appendix B: Maps and Site Diagrams Appendix C: Secondary Containment Calculations for Aboveground Storage Tanks Appendix D: Certification of the Applicability of the Substantial Harm Criteria Checklist Appendix E: Fueling Station Weekly Inspection Report Appendix F: Containment Area Drainage Discharge Report Appendix G: Sample Containment Volume Calculations, EPA Recommendations Appendix H: 40 CFR 112 Appendix I: 49 CFR 177.834 and 177.837 Appendix J: Standard Operating Procedures: Fuel Station Unloading Operations Appendix K: Fuel Transfer Procedures

Spill Prevention, Control and Countermeasures Plan Compliance Inspection Review Page In accordance with 40 CFR 112.5 (b), a review and evaluation of this Spill Prevention, Control and Countermeasures Plan (SPCC) will be conducted every three years. A registered Professional Engineer shall certify any change or amendment to the SPCC plan. This certification must be completed within six months after a change in facility design, construction, operation or maintenance occurs which affects the facility s potential for discharge of oil into or upon the Navigable Waters of the United States or adjoining shorelines. Review Dates Signature 1. March 1, 2004 2. March 1, 2007 3. March 1, 2010 4. March 1, 2013 5. March 1, 2016 * SPCC plan amended and certified by a Registered Professional Engineer per 40 CFR 112.3 (d) Management Approval Texas A&M University-Corpus Christi (TAMUCC) is committed to the prevention of discharges of any nature into navigable waters or the surrounding habitat. Therefore, a regular review and update of spill prevention, control and countermeasures procedures will be held to the highest standards. Authorized Facility Representative Title Signature Date

Facility Owner/Operator Texas A&M University-Corpus Christi 6300 Ocean Drive Corpus Christi, Texas 78412 (361) 825-5700 Facility Contacts Director of Contracts & Property John Casey 6300 Ocean Drive Corpus Christi, Texas 78412 (361) 825-2422 Manager of Maintenance Randy Haaker 6300 Ocean Drive Corpus Christi, Texas 78412 (361) 825-2328 Director of Environmental, Health, & Safety Roy Coons 6300 Ocean Drive Corpus Christi, Texas 78412 (361) 825-5555 Facility Description Texas A&M University-Corpus Christi is a public, degree-granting institution of higher education. Surrounded by the waters of Corpus Christi and Oso Bays, the University is located on Ward Island approximately ten miles southeast of downtown Corpus Christi, Texas. The University employs over 1,400 people including a teaching faculty of about 550. The student population increases every year and was over 10,500 in 2012. The University Motor Pool manages a fleet of approximately 21 vehicles owned by the various University Departments that utilize the University Fueling Station. The Texas General Land Office, Texas Commission on Environmental Quality, Texas Parks and Wildlife, Texas Department of Health, Seafood Safety, and Texas Forest Service manage their respected vehicles and utilize the fueling facility. The University Fueling Station has a ConVault Fuel storage tank designed to store both gasoline and diesel for fueling of motor vehicles, boats and equipment. The University has 10 emergency generators with fuel tanks. A common carrier delivers fuel to the generators by tanker truck via Ocean Drive as needed.

Facility Storage Tank Volume (gallons) Contents Location AST 1000 Diesel Fueling Station AST 1000 Unleaded Fueling Station Gasoline AST 350 Used Oil Motor Pool Emergency 225 Diesel University Center Generators (10) 250 Diesel Center For Instruction 225 Diesel Science & Tech 250 Diesel Central Plant (2) 250 Diesel NRC Bldg. 500 Diesel Bay Hall 750 Diesel Harte Research Cntr 750 Diesel Performing Arts 660 Diesel O Connor Building 5200/250 Diesel Dugan Wellness Cntr. Total: 11,660 gallons Facility Distance to Navigable Waters and Adjoining Shorelines The Texas A&M University-Corpus Christi Fueling Station is located ¼ mile from Oso Bay. A storm drain that empties into Oso Bay is located approximately 150 feet north of the Fueling Station. The soils beneath the Fueling Station containment structure is a very fine grain unconsolidated clay that has very low porosity and permeability conditions. The Aquifer is an unconfined water table that is composed of Holocene fluvial/marine clays deposited over the Pleistocene age Beaumont Clay formation. This aquifer has poor water quality. There is no freshwater zone in the aquifer. Groundwater is discharged through evapotranspiration and underflow that seeps into Oso and Corpus Christi Bays. Hydraulic conductivity for this aquifer is about 10 6 feet/day. Groundwater discharge is also affected by the amount of precipitation. Average rainfall for Ward Island is about 30 inches per year with extremes that can range from about 15 inches per year to 40 inches per year.

Spill History There have been no reportable quantity spills from this facility. Potential Spill Predictions, Volumes, Rates and Control Aboveground Storage Tanks not associated with emergency generators Source Type of Volume Rate of Flow Direction of Containment (Gal.) Failure (Gal.) (Gal./Hr.) Flow Diesel Rupture/leak 1000 1000 Within 1496.2/double walled tank Overfill Containment Unleaded Rupture/leak Overfill 1000 1000 Within Containment 1496.2/double walled tank Other Oil Product Storage Source Type Volume (Gal.) Emergency Generator (9) Drums/ Containers (2) Drums/ Containers Rupture/leak Overfill Rate of Flow (Gal./Hr.) volume listed in facility storage chart Direction of Flow Parking Lot * Rupture/leak 55 55 Within Building Rupture/leak 55 55 Within Portable Building Containment (Gal.) Spill kit, Containment Dike * double walled Spill kit, Spill Pallet * Spill kit, Spill Pallet * Drums/ Rupture/leak 55 55 Spill Pallet 55 Containers * Need to be installed. Spill Prevention Measures Drainage Control: a. The ConVault tank is a double walled tank. b. Tanks are located within a diked, concrete secondary containment structure. c. The secondary containment structure is equipped with a normally closed and locked manual gate valve. d. Rainwater that collects in the secondary containment structure evaporates or is drained through a manual gate valve after a careful examination of the area for oil has been conducted and documented. No oil or oily rainwater is to be released to the environment.

Aboveground Storage Tanks and Secondary Containment: a. The ConVault tank is UL2085 listed for protected aboveground storage for both combustible liquids and flammable liquids, and are designed with protection for both the primary tank and secondary containment. This makes them fire resistant, impact resistant, and bulletproof. As such they are used widely across the United States and around the world, especially in environmentally sensitive areas or areas with the possibility of terrorist attack. In addition to the double wall design, the ConVault tank is located inside a secondary containment system. b. Tank is situated within a 16 x 25 x 0.5 foot concrete secondary containment structure. Secondary containment has the capacity to hold the entire contents and has sufficient freeboard to allow for precipitation. Appendix C provides the secondary containment calculations for the Fueling Station. c. Rainwater that collects in the secondary containment structure is drained through a manual gate valve after a careful examination of the area for oil has been conducted and documented. A threaded plug must be removed from the gate valve before drainage can occur. Appendix F provides a containment area drainage discharge report form to be completed by the Inspector each time accumulated precipitation is drained from the structure. If an oil sheen is detected, the Inspector will consult with the University Environmental, Health and Safety Department and the National Spill Control School to determine the best method to remove the oil. No oil or oily rainwater is to be released to the environment as per 40 CFR 110. d. Aboveground storage tank is painted to inhibit the effects of corrosion. e. The secondary containment structure and aboveground storage tank is inspected at least weekly for signs of deterioration or leakage. Appendix E provides the fueling station weekly inspection report form for the Inspector to document these inspections. f. Every ten years, or more frequently if necessary as indicated by weekly inspection results, the tanks will be drained, cleaned, inspected, repaired as needed and painted. Prior to placing the AST s back into service, the tanks will be pressure tested for integrity according to standard industry practice recommended by the manufacturer. g. The aboveground storage tank is equipped with visual sight glass gauges. Filling procedures call for tanks to be filled to a safe fill height to prevent overfills. The designated safe fill height is 95% of the tank capacity. h. Other oil product storage containers are located within buildings and/or on spill pallets. All areas where oil products are stored have ready access to spill cleanup equipment and materials.

Fueling Station Transfer Operations: a. All tank piping, valves, piping supports and other ancillary items are above ground within the secondary containment structure. All tank piping and associated equipment are inspected during the weekly inspections and documented on the report form in Appendix E. b. Storage tanks, associated piping and the secondary containment structure are protected from vehicular traffic by steel barrier poles. c. The University requires all motor carriers who transport fuel on to the campus to comply with the DOT regulations in 49 CFR 177. All fuel transfer operations must be attended at all times by a qualified person. All fuel transfer operations will strictly adhere to Motor Pool s Standard Operating Procedures and the requirements in 49 CFR 177.834 and 177.837. A copy of these regulations is provided in Appendix I. d. A representative of the University Motor Pool will be present during the delivery of fuel to the aboveground storage tanks at the Fueling Station. Inspections and Record Keeping: a. Fueling Station inspections are conducted on a monthly basis. Inspections are documented and records are maintained at the Motor Pool for a minimum of three years. b. Drainage discharge, training, tank integrity testing and other related records are maintained at the Motor Pool for a minimum of three years. Site Safety and Security: a. The Fueling Station is located within a gated fenced compound. b. The University Police routinely patrol the entire campus 24 hours a day, seven days a week. c. Tank fill pipe caps are locked closed except during delivery of fuel to the tank. d. Secondary containment structure drainage valve is locked closed except when accumulated precipitation is released by an authorized facility representative. e. Lights illuminate the entire Fueling Station area including secondary containment. The lighting is sufficient to detect spills during the night and to prevent vandalism. f. Each tank is labeled with NFPA 704 Hazard Diamond warning signs. g. Aboveground storage tanks are properly bonded and grounded. Personnel Training: a. All Maintenance Department personnel will be trained on the contents and use of the Texas A&M University-Corpus Christi s SPCC Plan. b. Motor Pool employees will be trained in spill prevention procedures and in the use of spill cleanup equipment and materials. Refresher training will be provided annually or more frequently if needed.

c. All University employees who utilize the Fueling Station will be provided information on the proper use of the fueling equipment and spill prevention procedures. d. Mr. George Pena is the designated person responsible for Spill Prevention regarding Texas A&M University-Corpus Christi fueling operations. Spill Control Equipment and Cleanup: a. Spill control equipment on site includes absorbent pads and sorbent socks, granular sorbent, empty drums, brooms and shovels. Spill cleanup materials are located in the Motor Pool and at the National Spill Control School. b. The National Spill Control School staff and the University Safety Coordinator are trained in emergency response techniques. Emergency Contacts University Police (361) 825-4444 University Health and Safety Office (361) 825-5555 National Spill Control School (361) 825-3333 Local Police, Fire and Ambulance 911 Bay Area Medical Center (361) 761-1200 Poison Control Center 1 800 222-1222 National Response Center 1 800 424-8802 Texas Emergency Response Center 1 800 832-8224 United States Coast Guard MSO-Corpus Christi (361) 939-6349 Environmental Protection Agency Region VI (214) 665-2200 Texas General Land Office Region 3 (361) 825-3300 Texas Commission on Environmental Quality Region 14 (361) 825-3100 Safety-Kleen Corporation (361) 854-9471

APPENDIX A Photographs of Fueling Station

APPENDIX B Maps and Site Diagrams

TAMU-CC Momentum Campus

APPENDIX C Secondary Containment Calculations for Aboveground Storage Tanks

Secondary Containment Calculations for Aboveground Storage Tanks 1. Minimum containment volume = (Volume of the single largest tank + 10% to allow for precipitation) x 0.1337 cubic feet/gallon (conversion factor). (1000 gallons + 100 gallons) x 0.1337 cubic feet/gallon = 147.07 cubic feet 2. Total Diked Area = Width x Length of Containment Structure. 16 feet x 25 feet = 400 square feet 3. Available Containment Structure Volume = Total Diked Area x Dike Height 400 square feet x 0.5 feet = 200 cubic feet 4. The available containment structure volume of 200 cubic feet (1496.2 gallons) is greater than the required minimum containment volume of 147.07 cubic feet (1100.2 gallons). Ensure inspection records of Fueling Station are up to date. An inspector from the Texas General Land Office tentatively scheduled to be on campus annually for a routine inspection.

APPENDIX D Certification of the Applicability of the Substantial Harm Criteria Checklist

Certification of the Applicability Of the Substantial Harm Criteria Checklist Facility Name: Facility Address: Texas A&M University-Corpus Christi 6300 Ocean Drive Corpus Christi, Texas 78412 1. Does the facility transfer oil over water to or from vessels and does the facility have total oil storage greater than or equal to 42,000 gallons? No X, Yes _ 2. Does the facility have total oil storage capacity greater than or equal to 1 million gallons and does the facility lack secondary containment that is sufficiently large to contain the capacity of the largest tank plus sufficient freeboard to allow for precipitation within the containment structure? No X, Yes _ 3. Does the facility have total oil storage capacity greater than or equal to 1 million gallons and is it located at a distance (as calculated using the formula in Attachment C-III, Appendix C, 40 CFR 112 or comparable formula) such that a discharge from the facility could cause injury to fish, wildlife and sensitive environments? No X, Yes _ 4. Does the facility have total oil storage capacity greater than or equal to 1 million gallons and is it located at a distance (as calculated using the formula in Attachment C-III, Appendix C, 40 CFR 112 or comparable formula) such that a discharge from the facility would shut down a public water intake? No X, Yes _ 5. Does the facility have total oil storage capacity greater than or equal to 1 million gallons and has the facility experienced a reportable spill in an amount greater than or equal to 10,000 gallons within the last 5 years? No X, Yes _ As evidenced by the criteria above, the oil products storage at Texas A&M University- Corpus Christi does not qualify as a substantial harm facility and therefore does not require a facility response plan as described in 40 CFR 112.20. I certify under penalty of law that I have personally examined and am familiar with the information submitted in this document, and that based on my inquiry of those individuals responsible for obtaining this information, I believe that the submitted information is true, accurate and complete. Authorized Facility Representative Title Signature Date

APPENDIX E Fueling Station Monthly Inspection Report

Fueling Station monthly Inspection Report Date: Inspector: Facility Supervisor: Diesel Tank: Capacity: Liquid Level: Unleaded Tank: Capacity: Liquid Level: Used Oil Tank: Capacity: Liquid Level: Propane Tank: Capacity: Liquid Level: 1. Drainage: a. Any noticeable sheen on runoff? b. Standing water in containment area? c. Visible oil sheen in containment area? d. Containment area free of trash and debris? e. Containment area drainage valves are closed and locked? 2. Aboveground Storage Tanks (AST): a. Tanks checked for signs of leakage? b. Tanks checked for corrosion? c. Tanks properly labeled? d. Bolts, rivets or seams are not damaged? e. Tank supports/foundations are intact? f. Liquid level gauges are operating properly? g. Vents are not obstructed? h. Valves, flanges and gaskets are free from leaks? i. Containment walls are intact? j. Signs/barriers to protect tanks from vehicles are in place? 3. Hoses and Piping: a. Dispenser hoses free of cracks or abrasions that might cause leakage? b. Dispenser nozzles operating properly? c. Piping checked for signs of leakage? d. Piping checked for corrosion? e. Valves, flanges or other fittings are free from leaks? f. Signs/barriers in place to protect pipelines from vehicles are in place? 4. Security: a. Area fence and gates are intact? b. Gates have locks? c. Fill pipes on ASTs are locked except during fuel delivery? d. Starter controls for dispenser pumps are locked when not in use? e. Area lighting is working properly? 5. Training: a. All fueling station users are trained in operations of fueling equipment? b. Spill prevention information provided to all fueling station users? c. Training records are maintained at Motor Pool? 6. Safety: a. Tanks labeled with appropriate hazard warnings? b. Spill and overfill cleanup materials are available? c. Fire extinguisher is operational and readily accessible? d. Tanks and piping are properly bonded/grounded? 7. Record Keeping: a. A copy of the SPCC Plan will be available for review at Motor Pool, Facilities Services and the University Environmental Health and Safety Office. b. All weekly inspection, containment drainage, fuel delivery, training and fueling station/motor pool related maintenance records are maintained at Motor Pool. 8. Remarks or Recommendations: (Continue on another sheet if necessary)

APPENDIX F Containment Area Drainage Discharge Report

Containment Area Drainage Discharge Report Drain valve opened in Containment Area Date Time Drain valve closed in Containment Area Date Time Appearance of water at time of release: (Note: Remove any oil sheen prior to release from the Containment Area) Inspector: Facility Supervisor: Date:

APPENDIX G Sample Containment Volume Calculations EPA Recommendations

APPENDIX H 40 CFR 112

APPENDIX I 49 CFR 177.834 and 177.837

APPENDIX J Standard Operating Procedures: Fuel Station Unloading Operations

Standard Operating Procedures: Fueling Station Unloading Operations a. All motor carriers who transport fuel on to the campus are required to comply with DOT regulation 49 CFR 177 b. All Fuel Unloading operation must be attended at all times by a qualified person. A qualified person is defined as an individual who is knowledgeable of the hazards of the materials to be unloaded, is familiar with emergency procedures, and is authorized and capable to move the motor carrier. c. Fuel unloading operations must be attended at all times by a representative of the University Motor Pool. d. The qualified person attending the unloading operations must have an unobstructed view of the storage tank and delivery hose to the maximum extent practical during the unloading operation. e. No smoking at or near the fueling station at any time. f. Extreme care must be taken during fuel unloading operations to eliminate potential ignition sources in the area. g. No tools that may damage the integrity of the storage system or create sparks may be used during fuel unloading operations. h. No fuel shall be unloaded from any motor carrier until the handbrake is securely set and all other reasonable precautions are taken to prevent movement of the motor carrier during unloading operations. i. Unless the engine of the motor carrier is used for the operation of the pump, no fuel may be unloaded from the motor carrier while the engine is running. j. To provide against ignition of vapors by static electricity, the motor carrier, delivery hose, and storage tank must be properly bonded and grounded during unloading operations. k. A Spill Kit will be kept on standby during fuel unloading operations. l. Storm drain covers, included in the spill kit, will be placed over the nearest storm drain to the fueling station during unloading operations. m. The manual gate valve on the secondary containment structure must remain closed and plugged during unloading operations. n. Standing rainwater must be drained from the secondary containment structure prior to unloading operations to eliminate the potential for contaminated runoff. o. The storage tanks are equipped with visual sight glass gages. Tanks are to be filled to a safe height to prevent overfills. The designated safe fill height is 95% of tank capacity.

APPENDIX K Fuel Transfer Procedures

Fuel Transfer Procedures: General Safety Requirements a. No Smoking is permitted, Nor use of any Flame or Spark producing devices (i.e. Lighters, Cell Phones,...) at or near the Fueling Station at any time. b. Extreme caution must be taken during fuel transfer operations for any potential ignition source. c. Vehicle engines must shut off during fuel transfers. d. The fuel delivery hose must be attended to throughout the fueling process. Automatic trip-shutoff devices are not to be relied upon to prevent overfilling of vehicle or portable tanks. e. Portable tanks are to be placed on the pavement inside the containment structure while being filled. Do not fill portable tanks that are in, on, or around a vehicle or boat. f. Any Used Motor Oil must be sent to the Motor Pool for storage. The Used Oil Storage Tank is no longer used at the Fueling Station and a new storage tank is located at the Motor Pool. g. Report any Spills or Leaks to the Motor Pool representatives immediately. Fueling Operations: a. At the Fuel Pump, select the proper fuel (#1 Unleaded, #2 Diesel). Insert Card, type in required amortization information. Upon authorization, the selected fuel pump will be activated. b. Remove Card c. Remove nozzle from dispenser and place in tank to be fueled. d. Do Not Over Fill Vehicle or Portable Tank. e. When fueling is complete, drain nozzle into tank and replace back in the dispenser. Emergency Contacts Motor Pool (361) 825-6868 University Police (361) 825-4444 University Environmental, Health & Safety (361) 825-5555 National Spill Control School (361) 825-3333 Local Police, Fire, and EMS 9-1-1