SANYO GHP Introduction Commercial Gas Heat Pump - VRF 01.12.2011
Agenda 1. SANYO GHP History 2. SANYO GHP Range 3. GHP Market Position 4. 2-WAY 5. GHP Power 6. 3-WAY 7. EER/COP 8. Water Heat Exchanger (Chiller) 9. GHP Needs Service 2
Introduction GHP = Gas Engine Driven Heat Pump Air-conditioner 3
History of SANYO GHP Development Increase in electric power demand & oil crisis Japan Government starts the energy leveling policy. 1980 Apr.1981 Development Apr.1984 1985 1987 Apr.1985 Mar.1999. Production of GHP prototype starts with Tokyo Gas. Participated in the national project of Gas Cooling Technology. Started joint development of GHP with major gas companies Worlds First! Released 15HP GHP in Japan Three manufacturers entered into GHP market Achieved total 1 million HP in Japan Jul.2000 JIS Establishment Released New Refrigerant (R407C) Apr.2002 Low NOx mode less than 100ppm Sep.2003 Released Overseas J2 model (8HP~20HP) 2 million HP installed in Japan 2004 Worlds First! Released R410A GHP in Japan Jan.2005 Released Overseas J2 3WAY-type Jun.2006 Released Overseas K1-type (8HP~25HP); achieved a total of 1000 systems in Europe Apr.2008 Released Overseas M2-type (13HP~25HP); achieved a total of 2000 systems in Europe 4
GHP VRF Overview 3 types of GHP are sold in Europe: W*-MULTI G Power 2-WAY M2-series W*-Multi 2-WAY M2-series Multi 3-WAY M2-series *W = Multiple Outdoor Units can be combined 5
GHP W-MULTI 2 - WAY GHP (Gas Heat Pump) 2 WAY SYSTEM Single or Combined 6
GHP M2 2-way Range 13HP: SGP-EW120M2G2W 16HP: SGP-EW150M2G2W 20HP: SGP-EW190M2G2W GHP M2 range 25HP: SGP-EW240M2G2W 50 50 W 1800 H 2248 D 1000 HP 45 40 35 30 25 20 15 10 5 0 45 40 36 32 33 29 25 26 20 16 13 Single Multi 120 150 190 240 120+120 120+150 150+150 120+190 150+190 190+190 190+240 240+240 * 1 HP 2,8 kw 7
GHP Power with Generator GHP (Gas Heat Pump) Cogeneration 8
ECO G Power Range 1 Model 20HP: SGP-EGW190M2GW Can be combined to max. 2 units. 9
GHP 3 - WAY GHP (Gas Heat Pump) Heating + Cooling Simultanously 10
3 WAY MULTI Range 3 different sizes of OU: 16 HP: SGP-EZ150M2G2 20 HP: SGP-EZ190M2G2 25 HP: SGP-EZ240M2G2 Single OU installation 11
GHP The Multitalent Small size Medium size Large size Square measure DX system RAC 700 m2 3,000m2 5,000 m2 Water cooled VRF 10,000m2 VRF PAC Split type Chiller system GHP Screw chiller HP chiller Turbo chiller Water cooled type A2W heat pump Absorption chiller 12
GHP 2-WAY W-MULTI 13
GHP 2-way Features 1 Natural Gas or LPG (Propane) Single phase small power supply DX VRF indoors (max 46) or chilled water Miller cycle engine DC fan motors Durable compressors with variable speed allow quasi inverter operation (~15 100%) Hot water function for domestic hot water included as standard Electric supply 0,85 1,54 kw / unit only, depending on model 14
GHP 2-way Features 2 Diversity ratio 50-200% (Single OU installation) 50-130% (Multi OU installation) 200 m longest pipe run and 1000 m total piping length Full heating capacity down to -21 C / No defrost cycle Silent mode offers a further 2dB(A) reduction Part load efficiencies increased by 1.85 primary 4.60 compared to EWP Easy to add additional OU or IU in the future 15
GHP 3-WAY W-MULTI COP improvement up to factor 1,8! Single OU installation Heating & Cooling Simultanously Up to 36 indoor units per system 145m (equiv. Length) longest pipe run Diversity ratio 50-200% Full heating capacity down to -21 C and cooling down to -10 C No defrost cycle Water Heat Exchangers can not be connected No Hot Water Function 16
GHP M2 3way Advantage 17
GHP M2 3way Function 18
GHP ECO G POWER 19
GHP M2 Power 20
Production Of Electricity 21
GHP Power Consumption Fuel Power Station 50%loss Total loss of energy is 62% (Average in Europe) Sending loss Sending Condensing loss loss Primary Energie 1m³ gas 10kWh heating capacity Electric Energy at customer site 38% of 10kWh = 3,8kWh Electric AC with EER = 5,0 produces 5 * 3,8kWh = 19,0kWh cooling capacity Fuel Electric energy 0,353kWh as per 1m³ Gas 22 GHP with EER = 1,92 produces 1,92 * 10kWh = 19,2kWh total capacity (14,2 kwh cooling capacity + 5 kwh hot water) * * 20HP unit rated conditions including hot water production 26%
GHP Design EER Cooling SGP-EW190M2G2W Rated condition: 56 kw cooling capacity 20 kw hot water prod. 38,3 kw gas consumption 1,35 kw electricity cons. 2007/742/EC**: Gas transport loss 10% Electric conversion 2,5 EER = 1,23 (no hot w.) EER = 1,67 (with hot w.)* Plain calculation (with electric = gas): EER = 1,41 (no hot w.) EER = 1,92 (with hot w.) * Calculated backwards for comparison with electric AC: EER = 4,18 ** ECO-label directive 23
GHP Design COP Heating SGP-EW190M2G2W Rated Condition!: 63 kw heating capacity -- kw hot water 43,0 kw gas consumption 1,01 kw electricity 2007/742/EC: Gas transport loss 10% Electric conversion 2,5 COP = 1,26 Plain calculation (with electric = gas): COP = 1,43 Ext. Air HE is faded out! T < -4 C: COP = 0,74 (2007/742/EC)* COP = 0,84 (plain) * Calculated backwards for comparison with electric AC: COP = 1,89 24
Sound Level 1 25
Sound Level 2 Sound level compared to electrical VRF systems 68,00 66,00 64,00 62,00 ECO-i 2way Company D 60,00 58,00 56,00 54,00 GHP SANYO ECO-I 3way 52,00 8HP 10HP 12HP 14HP 16HP 18HP 20HP 26
GHP M1 WHE 3 Sizes available: 25kW, 50kW, (up to 64kW)* cooling / 30kW, 60kW, (up to 72kW)* heating Great to replace chiller and boiler systems Integrated into SANYO S-Net Up to 170 m distance between GHP and WHE possible Mixed operation with DX-units possible Water temperatures cooling -15 15 C / heating +35 +55 C * Preliminary data 27
GHP WHE M1 Mixed in VRF Water Heat Exchanger in mixed operation. Can be connected like a normal DX unit. 28
Maintenance Of GHP Coolant Oil filter Air filter Neutralizer + Filter mats Front Back Driving belt Spark plug Oil tank Black colour = exchange Valve clearance Service interval: Every 5 years or 10.000 hours only! 29 Blue colour = check / clean
Periodic Maintenance 10.000 hours engine operation A car driving with 50 km/h average speed 30
GHP Service Intervals All GHP models and sizes have a service interval of 10.000 hours. Generally the lifetime is calculated for max. 30.000 hours. If the GHP is used for cooling & heating all year round take care about operating hours! One year = 8.760 hours. If the project will result in such a kind of operation the GHP is not suited for this need as it would mean replacement of the unit after only 3,5 years. Normally operating hours should not exceed 2.000 3.000 hours a year! It is recommended to use the timer functions for stopping operation at weekend, holiday, nighttime etc. As GHP basic operation principle is to keep stable room temperatures by smooth operation (low rpm.) it is very important to keep in mind this point for economic long time operation. NO! 31