Why Measure Carbon Dioxide Inside Buildings? By Rich Prill, Washington State University Extension Energy Program



Similar documents
Carbon Dioxide (CO2) HVAC Basics

HVAC Systems and Indoor Air Quality. Douglas K. Spratt, M.Sc., P.Eng.

Information paper 20. Prepared by: David Clark. book:

PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE

Venice Library Humidity Study. for Williams Building Diagnostics, LLC th Street West Bradenton, FL Report April 13, 2015

Components HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis

Construction Indoor Air Quality Management Plans for LEED. Matt Gregg, PE, LEED AP

Using Time-of-Day Scheduling To Save Energy

INDOOR AIR QUALITY ASSESSMENT

INDOOR AIR QUALITY POST-OCCUPANCY ASSESSMENT. Massachusetts Department of Revenue 100 TradeCenter, Suite 760 Woburn, MA

5.6 Technical Specification: Premium Efficiency Electric Air Conditioning Equipment

IEQ Management Plan. Denver Museum of Nature and Science ECF Addition

Indoor air quality monitoring made easy

OptiNet Applications. A Review of the Unique Requirements for a Facility Monitoring System. White Paper Series

Makeup Air For Exhaust Systems In Tight Houses. Tony Jellen Engineering Projects

THE APPLICATION OF OZONE FOR AIR TREATMENT: CASE STUDY OF A BINGO HALL HVAC SYSTEM

Breathing The Air In Your Home Is Like Living In A Closed Jar. It s Enough To Make You Sick.

SUMMARY OF ASHRAE S POSITION ON CARBON DIOXIDE (CO 2 ) LEVELS IN SPACES. Stephen Petty, P.E., C.I.H.

CHAPTER 4 VENTILATION

IEQ-15 Air Distribution System

Mechanical and Natural Ventilation

The ASHRAE HQ Building Can the energy efficiency of the different mechanical systems really be compared? RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL

HVAC Processes. Lecture 7

"An Office Building Occupant's Guide to Indoor Air Quality"

Element D Services Heating, Ventilating, and Air Conditioning

Radford University. Indoor Air Quality Management Plan

HVAC Costs. Reducing Building. Building owners are caught between two powerful forces the need to lower energy costs. By Stephen J.

WHOLE-HOUSE VENTILATION SYSTEMS

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Public Review Draft. ASHRAE Standard

IAQ - indoor ventilation Air contaminants Molds Requirements for growth Health effects Mold prevention - moisture EH&S mold checks & removal

MOLD ASSESSMENT. Charles A. Bernazzani Elementary School 701 Furnace Brook Parkway Quincy, Massachusetts

Novel Air Treatment Technology for Reducing HVAC Energy Use

Indoor Air Quality- What You Need to Know

Specification. Indoor Air Quality Management

Fan Applications & System Guide

Leveraging the Power of Intelligent Motor Control to Maximize HVAC System Efficiency

HVAC Basic Science - System Capacity

SAM HOUSTON STATE UNIVERSITY

Ventilation Solutions Fresh Air Solutions for Ductless Heating & Cooling. fantech

INDOOR AIR QUALITY INTRODUCTION WHAT ARE THE SYMPTOMS OF SICK BUILDING SYNDROME? WHEN DID POOR INDOOR AIR QUALITY BECOME A PROBLEM?

Flexibility, Efficiency In San Antonio Arena

Camfil. Technical Services Bulletin Tools for Schools Filtration for Improved Indoor Air Quality

Infrastructure & Cities Sector

There are several types of air cleaning devices available, each designed to remove certain types of pollutants.

Glossary of Heating, Ventilation and Air Conditioning Terms

Fungal Assessment. Smith Recreation Community Centre 1019 Hwy 2A, Smith, Alberta

Charles McCammon, Ph.D., CIH

ECHO System for Basements

Final Inspection Report

AG-TQS-IAQ-00 March 4, Application Guide. TQS with IAQ Inlet

By Tom Brooke PE, CEM

Molds and mildew are fungi that grow

The Impact of Demand-Controlled and Economizer Ventilation Strategies on Energy Use in Buildings

Rev. No. 0 January 5, 2009

APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems

How To Design A Building In New Delhi

Air Conditioning, Heating and Refrigeration (HVAC) Technology Diploma

ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE

Both health-care facility classification and area classification, as per CSA, determine the design requirements.

Pool Dehumidification Basics

Mistrale. Fusion Terminal

Advanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings

Engineers Newsletter. Understanding Single-Zone VAV Systems. providing insights for today s hvac system designer. volume 42 2

PEOSH. Indoor Air Quality Training for Asthma-Friendly Schools Part I PEOSH Indoor Air Quality Standard Overview. Eric Weren, MSIH

Integrating Kitchen Exhaust Systems with Building HVAC

Example Retrocommissioning Measure: Opening Throttled Discharge Valves

Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues

Liabilities of Vented Crawl Spaces And Their Impacts on Indoor Air Quality in Southeastern U.S. Homes

HVAC Systems in Schools & Commercial Buildings and Radon

HVAC For Schools How to purchase an HVAC system that meets your school s unique requirements and stays within your budget

Center for Energy Education Laboratory

Both health-care facility classification and area classification, as per CSA, determine the design requirements.

Variable Air Volume - VAV

Humidity Control in School Facilities

Ammonia Detection System Codes and Design Specifications

KEY ELEMENTS IN PREVENTING AND MITIGATING MOLD CLAIMS

Principles of Ventilation. Patrick N. Breysse, PhD, CIH Peter S.J. Lees, PhD, CIH Johns Hopkins University

Walkthrough Inspection Checklist

THE LEADER IN PERFORMANCE INDOOR AIR QUALITY MEASUREMENTS

Old Dominion University Mold Management Plan

COMPARISON OF DIFFERENT HVAC SYSTEMS IN MULTI- STOREY APARTMENT BUILDINGS IN HELSINKI

GENERAL VENTILATION HSG202

Innovation #9/12. of all Formaldehyde for up to

2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT

FAQ' s. Frequently Asked Questions. A1 Control Units. Pge 1 of 7 PUMPKIN HOOK ROAD PO BOX OGD VAN HORNESVILLE NY USA

Kitchen Ventilation Systems: Part 2 Providing Adequate Makeup Air

BCA Green Mark for Restaurants

Heating, Ventilation and Air-Conditioning (HVAC)

Transcription:

Why Measure Carbon Dioxide Inside Buildings? By Rich Prill, Indoor air quality Workers and students spend about half their waking hours at work or school. Therefore, maintaining adequate indoor air quality (IAQ) in schools and the workplace is becoming a top priority for facility managers and building operating engineers. An essential element for maintaining adequate indoor air quality is outside air to dilute indoor air pollutants and exhaust these contaminants along with moisture and odors from our buildings. Why measure carbon dioxide? Most heating, ventilation and air conditioning systems (HVAC) re-circulate a significant portion of the indoor air to maintain comfort and reduce energy costs associated with heating or cooling outside air. When occupants and building operators sense air coming out of an air supply duct, it s virtually impossible to judge how much of this air is simply re-circulated air and how much is outside air. Current technology allows easy and relatively inexpensive measurement of carbon dioxide ( CO 2 ) as an indicator to help ensure ventilation systems (for high density occupancy zones) are delivering the recommended minimum quantities of outside air to the building s occupants. What is carbon dioxide? Carbon dioxide is a natural component of air. The amount of CO 2 in a given air sample is commonly expressed as parts per million (ppm). The outdoor air in most locations contains down to about 380 parts per million carbon dioxide. Higher outdoor CO 2 concentrations can be found near vehicle traffic areas, industry and sources of combustion. Where indoor concentrations are elevated (compared to the outside air) the source is usually due to the building s occupants. People exhale carbon dioxide the average adult s breath contains about 35,000 to 50,000 ppm of CO 2 (100 times higher than outdoor air). Without adequate ventilation to dilute and remove the CO 2 being continuously generated by the occupants, CO 2 can accumulate. How much carbon dioxide is too much? The concentrations of CO 2 found in most schools and offices are well below the 5,000 ppm occupational safety standard (time weighted average for an eight-hour workday within a 40-hour work week) for an industrial workplace. While levels below 5,000 ppm are considered to pose no serious health threat, experience indicates that individuals in schools and offices with elevated CO 2 concentrations tend to report drowsiness, lethargy and a general sense that the air is stale. Researchers are looking for links between elevated CO 2 concentrations and reduced productivity and achievement.

What are the guidelines and standards for ventilation? Ventilation rates for schools and office spaces are defined by various codes and standards. The most widely accepted standard is the American Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE) Standard 62. Some state and local codes have adopted the ASHRAE Standard 62 ventilation requirements. According to ASHRAE Standard 62, classrooms should be provided with 15 cubic feet per minute (cfm) outside air per person, and offices with 20 cfm outside air per person. Ventilation rates for other indoor spaces are also specified. Standard 62 is currently being revised, so these rates may change. Using CO 2 as an indicator of ventilation, ASHRAE has recommended indoor CO 2 concentrations be maintained at or below 1,000 ppm in schools and 800 ppm in offices (see chart below). Clearly the outdoor CO 2 concentration directly impacts the indoor concentration. Therefore, it is critical to measure outdoor CO 2 levels when assessing indoor concentrations. ASHRAE recommends indoor CO 2 levels not exceed the outdoor concentration by more than about 600 ppm. The relationship between CO 2 levels and outside air ventilation rate can be illustrated with the following table when outdoor CO 2 is about 350 ppm: Carbon Dioxide Ventilation and Resultant CO 2 Concentrations Outside Air (cfm per person) 2 CO 2 Differential (inside/outside) 800 ppm suggests about 20 cfm (or less) 500 ppm 1,000 ppm suggests about 15 cfm (or less) 650 ppm 1,400 ppm suggests about 10 cfm (or less) 1,050 ppm 2,400 ppm suggests about 5 cfm (or less) 2,050 ppm Note: The CO 2 values in this table are approximate, and based on a constant number of sedentary adult occupants, a constant ventilation rate, an outdoor air CO 2 concentration of about 380 ppm, and good mixing of the indoor air. Is it that simple? Unfortunately, the interpretation of the CO 2 data is often a more significant source of error than instrument accuracy. Meaningful assumptions about ventilation rate based on CO 2 values require the building or zone to be occupied long enough to allow the CO 2 levels to reach a balance with the ventilation rate. This balance is known variously as equilibrium, unity or steady-state. In an occupied building with a very low ventilation rate the CO 2 levels will likely continue to increase throughout the day, never reaching a steady-state concentration. On the other hand, buildings with an aggressive ventilation rate and good mixing of the outside air may prevent CO 2 from accumulating much beyond outdoor levels resulting in low CO 2 concentrations throughout the day.

Unless this steady-state or equilibrium has been reached, the building ventilation rate can be overestimated. For example, consider a CO 2 measurement taken in a school classroom during first period. It is unlikely that the CO 2 concentration will have accumulated to the point where equilibrium has been reached. Therefore, assumptions of outside air ventilation rates based on this CO 2 measurement will lead to an overestimation of the ventilation rate. Thus low CO 2 readings don t necessarily mean adequate ventilation. On the other hand, consider a CO 2 measurement taken in the same classroom during the last period of the day. Assuming the ventilation rate and occupancy of the classroom have remained fairly consistent throughout the day, it is reasonable to assume that a CO 2 concentration below about 1,000 ppm indicates 15 cfm per person, assuming also that the outside air CO 2 is in the 350 ppm range (650 ppm differential inside minus outside). Sources of error include ventilation systems that modulate the amount of outside air allowed into the building over the course of a day, occupancy rates that fluctuate significantly and measurement errors (instrument or calibration problems, measurement location, and/or poor mixing of the air within the space). Using CO 2 to calculate percent outside air Direct measurement of the amount of outside air entering large air handling units can be both difficult and unreliable. Measuring the concentration of carbon dioxide in the outside air, return air and mixed air streams is often much easier than other methods. The values obtained are used in the following formula to determine the percentage of outside air for a particular air-handling unit C r - C s The formula: % Outside Air (OSA) = --------------------------- X 100 C r - C o Where: C o is the carbon dioxide concentration (ppm) in the outside air C r is the carbon dioxide concentration (ppm) in the return air C s is the carbon dioxide concentration (ppm) in the supply air (or mixed air) The total supply air volume is required in order to calculate the approximate cfm of outside air supplied to the building using the percentage: Outside Air (cfm) = % Outside Air X Total Supply Air (cfm) Today s technology and IAQ Today, the measurement of carbon dioxide is an important tool to help ensure adequate outside air ventilation while simultaneously saving energy by reducing the number of over-ventilated buildings. Technological breakthroughs have made it possible to use relatively inexpensive CO 2 sensors to continuously monitor the CO 2 in buildings. These 3

CO 2 values can be used by the heating, ventilation and air-conditioning (HVAC) control system to automatically modulate the volume of outside air to maintain indoor CO 2 at or below a preset target concentration. This strategy is known as demand controlled ventilation (DCV). DCV systems are especially useful for those spaces or zones that experience variable occupancy rates: The ventilation rate responds proportionally to changes in the occupancy density. What do these instruments cost and how accurate are they? The accuracy of most of the CO 2 measurement instruments available today is more than adequate for use as an indicator of ventilation in offices and schools. The accuracy of these devices requires occasional checks. Some of these instruments measure only CO 2 while others will simultaneously measure temperature, relative humidity and other gases such as carbon monoxide. Instruments that either record internally or have output capability to an external data logger are valuable for trending and troubleshooting. The cost of these instruments ranges from about $500 to more than $5,000 depending on features. Installed costs of complete DCV systems have a much broader price range. What about all those other indoor pollutants? Clearly, elevated indoor CO 2 levels suggest inadequate outside ventilation air and it follows that inadequate ventilation permits other potentially harmful air pollutants to build up and create health, productivity and comfort problems. It is essential to keep in mind that many indoor air pollutants are generated independent of occupancy (carpet off-gassing, stored materials, air entry from contaminated utility tunnels, etc.). Where pollutant sources are independent of occupancy, CO 2 may not be a good yardstick to evaluate the quality of the indoor air. Unusually strong sources of indoor air pollutants can easily overwhelm the ventilation rates suggested by the ASHRAE Standard 62. A general rule of thumb is that a pollutant concentration is reduced by about 50 percent for each doubling of the ventilation rate (for those sources that have a fairly constant generation rate). Not only does more and more ventilation result in less and less dilution, but high ventilation rates can have huge impacts on energy costs and comfort. Therefore many indoor air pollutant sources are best controlled with methods other than basic dilution with outside air. Not surprisingly the energy efficient approach is also the wise approach: Ventilation only reduces exposure, while removing the source can completely eliminate exposure. Therefore, methods of source control include keeping pollutant sources out of the building through wise choice of furnishings and finish materials, using exhaust fans to capture and remove pollutants, and controlling pressures between zones to keep pollutants from migrating to populated or sensitive areas. Good practice suggests that we exclude, remove and otherwise minimize pollutants suspected to have the potential to cause health problems or affect performance and comfort. 4

References 1. American Society of Heating Refrigerating, and Air Conditioning Engineers (ASHRAE). 1992. ASHRAE Standard 62: Ventilation for Acceptable Indoor Air Quality. Atlanta, GA. 2. ASTM Standard D-6245 98 Using Indoor Carbon Dioxide Concentrations to Evaluate Indoor Air Quality and Ventilation 3. IAQ Diagnostics Reference Manual: Hands-On Assessment of Building Ventilation and Pollutant Transport. University of Tulsa, College of Engineering and Applied Sciences, Department of Chemical Engineering 4. National Institute for Standards and Technology. 1994 Manual for Ventilation Assessment in Mechanically Ventilated Buildings. NISTR #5329-1994 Contact: Rich Prill 222 N. Havana #204 Spokane, WA 99202-4776 Voice: 509-477-6701 Fax: 509-477-6709 Email: prillr@energy.wsu.edu Revised 2000 WSUEEP07-003 5