RISK MITIGATION for ELECTRICAL WORK. Feb 2013 San Diego CA

Similar documents
Choosing the Best Solution for Reducing Arc Energy

Arc Flash Hazards. Electrical Hazards. Dan Neeser Field Application Engineer Electrical Hazards 2/18/2015. Shock.

ARC FLASH CALCULATIONS & LABELING REQUIREMENTS

NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers

Technical Guide. SKM Arc Flash Line Side vs. Load Side

Arc Flash Mitigation. Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear.

INTRODUCTION ARC FLASH PROTECTION AND SAFETY MEASURES. September 2010

BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E

Roadmap to Compliance with NFPA 70E Arc Flash Requirements

Understanding Arc Flash

Part 1 System Modeling & Studies for Existing Systems

IMPLEMENTING THE NEW ELECTRICAL SAFETY REQUIREMENTS

Safety By Design. Strategies for Electrical Contractors

misconceptions about arc-flash hazard assessments

Low Voltage Switchgear

OSHA & ARC FLASH HAZARD ANALYSIS

Arc Flash Mitigation & Selective Co-ordination

ARC FLASH HAZARD OVERVIEW. Presented August 13, 2015 WWOA Lake Michigan District by Mead & Hunt, Inc.

Understanding 2015 Changes to NFPA 70E Safety-related work practices and maintenance requirements mandate more robust electrical safety programs for

ELECTRICAL SAFETY RISK ASSESSMENT

ARC FLASH HAZARD MITIGATION. Industrial Tests, Inc. [indtests.com]

What s up with Arc Flash?

2012 NFPA 70E. Ten Most Important Changes. John A. DeDad

2008 Eaton Corporation. All rights reserved.

HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE

NFPA 70E Updates Affect Your Most Valuable Assets

Introduction to Arc Flash

How to reduce exposure to arc flash hazards

The Other Hazard of Electricity. Larren Elliott Ph.D. Lindsay Polic, CSP, REHS

4160: THE GREEN 480 MEDIUM VOLTAGE ELECTRICAL SYSTEMS

Protection Considerations to Mitigate Arc-Flash Hazards

Electrical Safety Program

A USERS GUIDE TO ARC RESISTANT LOW VOLTAGE SWITCHGEAR & MOTOR CONTROL ANALYTICAL COMPARISON VS ARC FLASH TEST RESULTS

How to Build a Safe and Effective Electrical Maintenance Program

Power-Zone 4 Arc Resistant Low Voltage Switchgear

MEDIUM VOLTAGE. Michael Mosman, PE. CCG Facilities Integration Incorporated FACILITIES INTEGRATION INCORPORATED

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services

Arc Flash Avoidance and its Application to Overhead Traveling Cranes

Arc Flash Energy Mitigation Techniques

Written Program ELECTRICAL SAFETY. Based on OSHA Subpart S and NFPA 70E Standards

SAFE ELECTRICAL WORK PRACTICES & 2015 NFPA 70E

Extend the Life of Existing Switchgear

Arc Flash Safety in 400V Data Centers

MEDIUM VOLTAGE SUBSTATION PRACTICES Medium Voltage (MV) is defined as: 1000V< MV 44kV

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid

New standardized approach to arc flash protection

Demystifying arc flash hazard management

! WARNING Arc Flash and Shock Hazard Appropriate PPE Required

A Guide to Performing An Arc Flash Hazard Assessment Using Power Analysis Software

SALISBURY ASSESSMENT SOLUTIONS

Analyzing Electrical Hazards in the Workplace

OSHA and NFPA 70 Understanding NFPA 70 and its Implications in Electrical Inspections 2010

Common Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.)

Short-circuit, Protective Device Coordination & Arc Flash Analysis. By Albert Marroquin Operation Technology, Inc.

CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS

Fusible Disconnect Switch

Bypass transfer switch mechanisms

Switchgear and Metal-Enclosed Bus

Implementation of arc flash mitigating solutions at industrial manufacturing facilities

Enhancing Personnel Safety with Arc Resistant Equipment

Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves

Arc Flash Mitigation. Executive summary. by Antony Parsons, Ph.D., P.E.

Mitigation of Arc-Flash Hazards and Reduction of Costs by Selective Arc-Flash Protection

Common Sense and Knowledge Approach to Electrical Safety

Management Systems 10 Electrical Safety Audit 14 PPE 20 Arc Mitigation 22 Hazard Assessment 26

2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY

Engineering innovation

Electrical Safety in the Marine Environment

What Are the Qualifications to Conduct Arc Flash Studies? Where Do You Begin?

Union County Public Schools. Facilities Department. Electrical. Safe Work Practices

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600

Journeyman Class Schedule

Atlanta Chapter IEEE Industry Applications Society

Electrical Safety Program

NFPA 70E: What Contractors and Employers Need to Know

OSHA Published First-Ever Arc Flash Protection Requirements for the Electric Power Industry Significant changes and unprecedented compliance

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services.

ARC Flash Boundary & NFPA-70E Requirements PPE Program

Campus Safety Procedure Electrical Safety

Job Site Electrical Safety A Matter of Life and Death

PROCEDURES FOR SAFE WORKING AND TESTING OF ENERGIZED ELECTRICAL EQUIPMENT

ELECTRICAL SAFETY PROGRAM

100% Rule Alternate Method Arc Blast Arc Flash Approved Approved Equipment Authority Having Jurisdiction (AHJ) Authorized Work Bare Hand Work

Electrical Safety Program. Electrical Safety Program Audit (Appendix: X) Performed By: Date:

Electrical Predictive and Preventative Maintenance

Unified requirements for systems with voltages above 1 kv up to 15 kv

SALISBURY ASSESSMENT SOLUTIONS

Cal/OSHA Guide to. Electrical Safety. Cal/OSHA Consultation Service Research and Education Division of Occupational Safety and Health

Transcription:

RISK MITIGATION for ELECTRICAL WORK Feb 2013 San Diego CA

Agenda I. RISK Define the Risks Arc Flash Review II. MITIGATION 3 Easy Steps New Designs Vs. Existing Systems III. DUKE UNIVERSITY EXAMPLE

I. Risk Shock Arc Flash - Arc Blast Equipment Damage Unplanned Outage

II. Mitigation Understand the Hazard Have a Plan Know your System / Equipment

A. Arc Flash - Review IE = Incident Energy Variables: Fault Current & Time Overcurrent Detection Devices are typically Inverse More Current = Faster Operation Lower Currents = SLOW Operation Time is a much greater influence on Arc Flash Therefore - Lower Fault Current = Higher Arc Flash Hazard!

A. Calculated IE Example Available Primary Fault Current =12,000A Available Primary Fault Current = 13,700A %Z = 6.36 Secondary Fault Current = 22,700A Identical Settings %Z = 6.21 Secondary Fault Current = 24,400a Incident Energy = 580 cal/cm 2 Extremely Dangerous Motor Contribution = 3,300A Motor Contribution = 3,000A 480V Switchgear Incident Energy = 16 cal/cm 2 Workable with Adequate PPE

A. Trip Times Example 1000 100 CURRENT IN AMPERES 85% Arcing Current 11,030 Amps 100% Arcing Current 12,976 Amps Breaker Trips in 15.9s IE = 580 cal/cm2 1000 100 CURRENT IN AMPERES 85% Arcing Current 11,739 Amps 100% Arcing Current 13,810 Ampus 10 1 48XAM - Phase TIME IN SECONDS 10 1 48XBM - Phase TIME IN SECONDS Breaker Trips in 0.33s IE = 16 cal/cm2 0.10 0.10 26031 A 27484 A 0.01 1K 10K 100K 48XAM.tcc Ref. Voltage: 480V Current in Amps x 1 0.01 1K 10K 100K 48XBM.tcc Ref. Voltage: 480V Current in Amps x 1

B. Safety Plan 1) NFPA 70E & or NESC: a) Require a Task Hazard Assessment b) Require Arc Flash Analysis c) Require Interpretation

B. Interpretation Selection of Personal Protective Equipment When Required for Various Tasks. Where selected in lieu of the incident energy analysis of 130.5(B)(1), Table 130.7(C)(15)(a) and Table 130.7(C)(15)(b) shall be used to determine the hazard/risk category and requirements for use of rubber insulating gloves and insulated and insulating hand tools for a task. The assumed maximum short-circuit current capacities and maximum fault clearing times for various tasks are listed in Table 130.7(C)(15)(a). For tasks not listed, or for power systems with greater than the assumed maximum short-circuit current capacity or with longer than the assumed maximum fault clearing times, an incident energy analysis shall be required in accordance with 130.5.

B. Interpretation Choose Wisely: The collective experience of the task group is that, in most cases, closed doors do not provide enough protection to eliminate the need for PPE for instances where the state of the equipment is known to readily change (for example, doors open or closed, rack in or rack out). It is the collective experience of the Technical Committee on Electrical Safety in the Workplace that normal operation of enclosed electrical equipment, operating at 600 volts or less, that has been properly installed and maintained by qualified persons is not likely to expose the employee to an electrical hazard.

B. Interpretation 110.1 Relationships with Contractors (Outside Service Personnel, and So Forth). (A) Host Employer Responsibilities. (1) The host employer shall inform contract employers of the following: a. Known hazards that are covered by this standard, that are related to the contract employer s work, and that might not be recognized by the contract employer or its employees b. Information about the employer s installation that the contract employer needs to make the assessments required by Chapter 1

B. Interpretation Parallel Sources vs. Closed Transition 100mS or Less AHJ determination N E

C. Know Your System 1. Up to Date Documentation User friendly Accurate Accessible 2. Existing Conditions Age / Condition Factor Interpret the Standards Asses Existing Conditions

C. Know Your System 27MW Combustion Turbine Generator Multiple Sources On-Line LOTO / Isolation Emergency Only 2.5MW Emergency Generator Designed to Keep the Power On

C. Documentation User Friendly / Accessible / Accurate IF REQUIRED IF REQUIRED SUBSTATION EQUIPMENT - BUILDING - LETTER NUMERIC NUMBER DESCRIPTOR NUMBER IDENTIFIER IDENTIFIER 1,2,3,4,5, EXAMPLES TX, SW, PMH,... - 7530,7549, - A,B,C, 1,2,3, 1 TX - 7532 - A 1 F - 7532 - A 3 1 PMH - 7530 - B

C. Existing Conditions Interlocking No Instantaneous Function Longer Clearing Times Ventilated Enclosures Adequate PM?

C. Pad Transformer Door Interlock ANSI C57.12

C. Existing Equipment

III. Duke University Comprehensive Safety Plan Excellent Documentation Thorough Analysis

The End Conclusions Understand the Hazards = Assessment & Studies Have a Plan = Adopt & Interpret Know your System = User Friendly, Accurate, Accessible Documentation Questions? Comments? Constructive Criticism?