CFD STUDY OF TEMPERATURE AND SMOKE DISTRIBUTION IN A RAILWAY TUNNEL WITH NATURAL VENTILATION SYSTEM



Similar documents
NUMERICAL SIMULATION OF FLOW FIELDS IN CASE OF FIRE AND FORCED VENTILATION IN A CLOSED CAR PARK

ME6130 An introduction to CFD 1-1

CFD Based Air Flow and Contamination Modeling of Subway Stations

INITIAL ASSESSMENT OF THE IMPACT OF JET FLAME HAZARD FROM HYDROGEN CARS IN ROAD TUNNELS AND THE IMPLICATION ON HYDROGEN CAR DESIGN

Problem Statement In order to satisfy production and storage requirements, small and medium-scale industrial

CFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER

Introduction to CFD Analysis

Overset Grids Technology in STAR-CCM+: Methodology and Applications

Pushing the limits. Turbine simulation for next-generation turbochargers

COMPUTATIONAL FLOW MODEL OF WESTFALL'S 4000 OPEN CHANNEL MIXER R1. By Kimbal A. Hall, PE. Submitted to: WESTFALL MANUFACTURING COMPANY

Introduction to CFD Analysis

Turbulence Modeling in CFD Simulation of Intake Manifold for a 4 Cylinder Engine

NUMERICAL ANALYSIS OF THE EFFECTS OF WIND ON BUILDING STRUCTURES

EVALUATION OF PHOENICS CFD FIRE MODEL AGAINST ROOM CORNER FIRE EXPERIMENTS

Comparison of Heat Transfer between a Helical and Straight Tube Heat Exchanger

AIR STREAMS IN BUILDING FOR BROILERS

SINGLE TRAIN PASSING THROUGH A TUNNEL

Lecture 6 - Boundary Conditions. Applied Computational Fluid Dynamics

Express Introductory Training in ANSYS Fluent Lecture 1 Introduction to the CFD Methodology

BAFFLES AS A MEANS OF STATION PROTECTION FROM HIGH AIR VELOCITIES - COMPARISON OF ANALYTICAL AND FIELD MEASUREMENTS RESULTS

CFD Applications of PHOENICS on Building Environment and Fire Safety Design

THE CFD SIMULATION OF THE FLOW AROUND THE AIRCRAFT USING OPENFOAM AND ANSA

Full scale tunnel fire tests of VID Fire-Kill Low Pressure Water Mist Tunnel Fire Protection System in Runehamar test tunnel, spring 2009

Eco Pelmet Modelling and Assessment. CFD Based Study. Report Number R1D1. 13 January 2015

Flow distribution and turbulent heat transfer in a hexagonal rod bundle experiment

Tomasz STELMACH. WindSim Annual User Meeting 16 June 2011

Challenges for Use of Fixed Fire Suppression Systems in Road Tunnel Fire Protection

Customer Training Material. Lecture 2. Introduction to. Methodology ANSYS FLUENT. ANSYS, Inc. Proprietary 2010 ANSYS, Inc. All rights reserved.

5.14 COMPUTATIONAL MODELLING OF AIRFLOW IN URBAN STREET CANYON AND COMPARISON WITH MEASUREMENTS

2013 Code_Saturne User Group Meeting. EDF R&D Chatou, France. 9 th April 2013

AB3080 L. Learning Objectives: About the Speaker:

UPGRADING OF THE AUSTRIAN TUNNEL RISK MODEL TURISMO METHODICAL AND PRACTICAL ASPECTS

Flow in data racks. 1 Aim/Motivation. 3 Data rack modification. 2 Current state. EPJ Web of Conferences 67, (2014)

HEAT TRANSFER ANALYSIS IN A 3D SQUARE CHANNEL LAMINAR FLOW WITH USING BAFFLES 1 Vikram Bishnoi

Abaqus/CFD Sample Problems. Abaqus 6.10

INTERNATIONAL JOURNAL OF MECHANICAL ENGINEERING AND TECHNOLOGY (IJMET)

O.F.Wind Wind Site Assessment Simulation in complex terrain based on OpenFOAM. Darmstadt,

AN EFFECT OF GRID QUALITY ON THE RESULTS OF NUMERICAL SIMULATIONS OF THE FLUID FLOW FIELD IN AN AGITATED VESSEL

Part IV. Conclusions

TWO-DIMENSIONAL FINITE ELEMENT ANALYSIS OF FORCED CONVECTION FLOW AND HEAT TRANSFER IN A LAMINAR CHANNEL FLOW

Impacts of Perforated Tile Open Areas on Airflow Uniformity and Air Management Performance in a Modular Data Center

Aerodynamic Department Institute of Aviation. Adam Dziubiński CFD group FLUENT

SMOKE HAZARD ASSESSMENT USING COMPUTATIONAL FLUID DYNAMICS (CFD) MODELLING

COMPUTATIONAL FLOW MODELLING OF FORMULA-SAE SIDEPODS FOR OPTIMUM RADIATOR HEAT MANAGEMENT

CFD Application on Food Industry; Energy Saving on the Bread Oven

Learning Module 4 - Thermal Fluid Analysis Note: LM4 is still in progress. This version contains only 3 tutorials.

Numerical Simulation of the External Flow Field. Around a Bluff Car*

Piotr Tofiło a,*, Marek Konecki b, Jerzy Gałaj c, Waldemar Jaskółowski d, Norbert Tuśnio e, Marcin Cisek f

How To Model With Cfd Using Phoenics

Modelling of fire spread in car parks

MAXIMISING THE HEAT TRANSFER THROUGH FINS USING CFD AS A TOOL

Battery Thermal Management System Design Modeling

HYBRID ROCKET TECHNOLOGY IN THE FRAME OF THE ITALIAN HYPROB PROGRAM

Effect of Rack Server Population on Temperatures in Data Centers

Supporting document to NORSOK Standard C-004, Edition 2, May 2013, Section 5.4 Hot air flow

Fire Hazard Calculations for Hydrocarbon Pool Fires Application of Fire Dynamics Simulator FDS to the Risk Assessment of an Oil Extraction Platform

NUCLEAR ENERGY RESEARCH INITIATIVE

Design of heat exchangers

The ADREA-HF CFD code An overview

Use of OpenFoam in a CFD analysis of a finger type slug catcher. Dynaflow Conference 2011 January , Rotterdam, the Netherlands

Measurement and Prediction Technology of Cooling Capability for Hybrid Drivetrain Components. Tadashi Yamada TOYOTA MOTOR CORPORATION

An Investigation of the Radiative Heat Transfer through Nonwoven Fibrous Materials

The influence of mesh characteristics on OpenFOAM simulations of the DrivAer model

Set up and solve a transient problem using the pressure-based solver and VOF model.

THERMAL STRATIFICATION IN A HOT WATER TANK ESTABLISHED BY HEAT LOSS FROM THE TANK

COOKING THE ROOF CFD BEYOND THE WHITE SPACE

Using Computational Fluid Dynamics (CFD) for improving cooling system efficiency for Data centers

Basics of vehicle aerodynamics

Numerical Investigation of Heat Transfer Characteristics in A Square Duct with Internal RIBS

CFD Grows Up! Martin W. Liddament Ventilation, Energy and Environmental Technology (VEETECH Ltd) What is Computational Fluid Dynamics?

CFD SIMULATION OF NATURAL GAS COMBUSTION AND IST APPLICATION TO TUNNEL KILN FIRING

CFD modelling of floating body response to regular waves

A LAMINAR FLOW ELEMENT WITH A LINEAR PRESSURE DROP VERSUS VOLUMETRIC FLOW ASME Fluids Engineering Division Summer Meeting

ENHANCED PROBLEM SOLVING; THE INTEGRATION OF CFD AND OTHER ENGINEERING APPLICATIONS

Using Computational Fluid Dynamics (CFD) Simulation to Model Fluid Motion in Process Vessels on Fixed and Floating Platforms

Computational Fluid Dynamic Investigation of Liquid Rack Cooling in Data Centres

Ravi Kumar Singh*, K. B. Sahu**, Thakur Debasis Mishra***

Adaptive strategies for office spaces in the UK climate

External bluff-body flow-cfd simulation using ANSYS Fluent

GT ANALYSIS OF A MICROGASTURBINE FED BY NATURAL GAS AND SYNTHESIS GAS: MGT TEST BENCH AND COMBUSTOR CFD ANALYSIS

The calculation of train slipstreams using Large-Eddy Simulation techniques

Influence of fire source locations on the actuation of wet-type sprinklers in an office fire

Steady Flow: Laminar and Turbulent in an S-Bend

(1) 2 TEST SETUP. Table 1 Summary of models used for calculating roughness parameters Model Published z 0 / H d/h

Differential Relations for Fluid Flow. Acceleration field of a fluid. The differential equation of mass conservation

CFD Beyond the Whitespace. Datacentres Central & Eastern Europe

OPTIMISE TANK DESIGN USING CFD. Lisa Brown. Parsons Brinckerhoff

REAL SCALE TUNNEL FIRE: EXPERIMENTAL TEST INSIDE THE MORGEX TUNNEL AUTOSTRADA A5

CFD analysis of external aerodynamic and entry into to the air conditioning system on the roof of a bus

CFD ANALYSIS CHALLENGES IN BUILDING SIMULATION FOR SIMBUILD2004 CONFERENCE. Ferdinand Schmid and Galen Burrell Architectural Energy Corporation

CFD MODELING AND EXPERIMENTAL ACTIVITY ON REAL SCALE TUNNEL FIRES

Multiphase Flow - Appendices

CFD Analysis of Application of Phase Change Material in Automotive Climate Control Systems

CFD Code Validation Against Stratified Air-Water Flow Experimental Data

Fire Risk in Metro Tunnels and Stations

GEOMETRIC, THERMODYNAMIC AND CFD ANALYSES OF A REAL SCROLL EXPANDER FOR MICRO ORC APPLICATIONS

CONVERGE Features, Capabilities and Applications

HEAT TRANSFER IM LECTURE HOURS PER WEEK THERMODYNAMICS - IM _1

Transcription:

CFD STUDY OF TEMPERATURE AND SMOKE DISTRIBUTION IN A RAILWAY TUNNEL WITH NATURAL VENTILATION SYSTEM J. Schabacker, M. Bettelini, Ch. Rudin HBI Haerter AG Thunstrasse 9, P.O. Box, 3000 Bern, Switzerland ABSTRACT A study of safety in a railway tunnel with natural ilation system is presented. The study investigates conditions within the tunnel near a burning train. An emergency scenario is defined and criteria for the assessment of the safety of the escaping passengers are discussed. Two different approaches were employed in a coupled manner: 1-D analysis using the code SPRINT, developed by HBI, and 3- D CFD analysis using the commercial code FLUENT. It is concluded that the 1-D approach is in most cases sufficient for an overall safety assessment whereas 3-D CFD is more appropriate for gaining additional insight in regions of particular interest in complex tunnel geometry. 1 INTRODUCTION In case of emergency in railways tunnels it is usually not recommended to stop the train before the exit. Modern railway tunnels should nevertheless provide the highest possible level of the safety for the passengers in case of an incident that forces a train to stop within the tunnel. The understanding of the behavior of smoke and temperature arising from a fire on a burning train is of essential importance for the design of the tunnel's safety features as, for example, rescue areas, cross passages and the ilation system. The probably most reliable approach to check the functionality of a ilation system would be to perform full-scale fire tests prior to opening the tunnel for operation. However, these tests are very expensive and often do not consider the flow motion in the tunnel that was induced by the entering train before it came to halt. Therefore, the transferability of the results to real conditions and the prediction of the escape conditions of the passengers might be difficult. Moreover, a parametric study (fire position, train speed etc.) is impossible. Numerical (CFD) three-dimensional simulations provide an excellent mean for gaining a better insight in the neighborhood of the fire and prediction of the escape conditions for the passengers. Moreover, CFD provides the results in a format that can easily be post-processed to create animation for the training of people who have to deal with the fire in case of emergency (fire fighting forces, conductors etc.) Nevertheless, CFD simulations are still time-consuming. Their practicability for parametric studies and design is therefore limited. For this reason, the overall design of the ilation system is mostly carried out using onedimensional methods, which allow to vary the key design parameters in a very straightforward way in order to devise the optimal solution using an acceptable amount of resources. In a further step, this solution can be verified in regions of particular interest using CFD or full scale experiments. The Purpose of this paper is to compare the predictions of a one-dimensional simulation of the timedependent smoke and temperature distribution near a burning train with the results obtained from a three-dimensional CFD simulation. 1

2 BASICS The emergency scenario assumes a burning train that enters a tunnel. The train is forced to stop in the tunnel. No active ilation exists in the tunnel. Instead the smoke is extracted by natural convection through the s in the tunnel roof. 2.1 EMERGENCY SCAENARIO AND TUNNEL GEOMETRY Figure 1 shows a sketch of the tunnel with the position of the incident train. The following assumptions are made for the emergency scenario. The train stops near the middle of the tunnel in such a way that the fire is located midway between two s. No trains enter or leave the tunnel after halt of the train. driving direction 2029 m 300 m Position of the train after halt Figure 1 Geometry of the tunnel and position of the train after halt in the tunnel Tunnel geometry: Length : 2029 m Cross Section : approximately square shape 6.7 x 6.7 m 2 Geometry of the s Spacing: equally spaced at 300 m distance Cross Section: 6.7 x 2.4 m 2 Height: 2.4 m 2.2 TRAIN SPECIFICATIONS The technical specifications for the train are as follows: Train length: 400 m Train height and width: 3.89 x 2.95 m 2 Max. deceleration: 1.1 m/s 2 3 NUMERICAL SIMULATIONS 3.1 APPROACH The following approach was employed for the numerical simulations: 1. Estimation of the critical velocity. 2. One-dimensional transient analysis of the smoke and temperature propagation in the whole tunnel. 3. Three-dimensional transient analysis of the smoke and temperature propagation near the train. 3.2 PREDICTION OF CRITICAL VELOCITY The critical velocity, i.e. the minimum longitudinal air velocity required to pre backlayering, is calculated using the semi-empirical Kennedy -formula [1]. For this study, the critical velocity was estimated to 2.2 m/s. 3.3 ONE-DIMENSIONAL ANALYSIS OF THE SMOKE AND TEMPERATURE PROPAGATION For the given scenario, the smoke propagation is driven by the airflow induced by the entering train as long as the air velocity in the tunnel exceeds the critical velocity. Afterwards, more complex smokepropagation patterns are observed. The resulting flowfield, smoke propagation and temperature distri- 2

bution are simulated with the code SPRINT, developed by HBI. SPRINT [2] calculates the velocity and temperature distribution of an incompressible flow in a tunnel by means of a one-dimensional time-dependent model, based on the governing equations describing the conservation of mass, axial momentum and energy, as well as additional relations for smoke propagation. The fire is modeled as a source of heat and smoke. Temperature and speed of the upper and lower layers are calculated. This information, generally missing in one-dimensional models, is necessary in order to predict the smoke propagation correctly, which is a result of both passive convection and gravity-driven propagation. Ambient temperature is assumed for the lower layer that covers 50% of the tunnel height. Heat transfer from the upper to the lower layer is neglected. Advective energy transport occurs therefore only in the upper part of the tunnel, where higher temperatures are observed. Convective and radiative heat transfer to the wall is also limited to the upper layer. SPRINT was validated against the results from the Memorial Tunnel Fire Ventilation Test Program with good results [2]. 3.4 THREE-DIMENSIONAL ANALYSIS OF THE SMOKE AND TEMPERATURE DEVELOPMENT NEAR THE TRAIN The three-dimensional simulations were carried out using the CFD code FLUENT, release 5.5. The grid was generated using GAMBIT, FLUENT Inc. s standard preprocessor. The system of equations for mass, momentum and energy were solved simultaneously. Turbulence was modeled by means of the k-ε model. The density of the gas mixture was calculated according to the ideal-gas laws. 4 COMPUTATIONAL SETUP 4.1 1-D ANALYSIS The computational domain for the 1-D analysis is shown in Figure 1. The whole tunnel is modeled. The train enters the tunnel and stops at the position indicated in the figure. The air velocities induced by the train as well as the smoke production of the entering train are considered for the analysis. 4.2 3-D ANALYSIS 4.2.1 COMPUTATIONAL DOMAIN The computational domain for the CFD analysis is illustrated schematically in Figure 2. 300 m 150 m 150 m 300 m 2nd upstream T W 1st upstream 1st downstream 2nd downstream P, T P*(t), cc smoke (t), T fire m R, T R previous train driving direction P, ζ, T -200 m +200 m -500 m +500 m Figure 2 Computational Domain for CFD simulation 4.2.2 FIRE MODEL The fire intensity is constant, with the following characteristics. Convective heat-release rate: 30 MW, Smoke-production rate: 43 kg/s at 00 K, Smoke concentration at the source: 4.2%, Fire length: 25 m (one wagon). Radiation is not explicitly accounted for in this investigation. It is assumed that the flames leave the wagon through the open upper side. 3

4.2.3 BOUNDARY CONDITIONS The following boundary conditions were imposed. Solid walls: T = 300 K. Main outlet: Pressure outlet with additional loss coefficient set as obtained from the 1-D simulation. Vent outlets: Pressure outlet. Inlet: Pressure inlet with additional definition of the entrance smoke concentration obtained from the 1-D analysis. Fire: as specified in Chapter 4.2.2. 4.2.4 GEOMTRY AND GRID at train nose at A state-of-the-art hybrid meshing technique was used to efficiently mesh the geometry. The grid consists of 180 000 cells with variable shape: hexahedral, pyramidal and tetrahedral. Grid refinement was used in important areas near the tunnel walls. Details are shown in Figure 3 Figure 3 Details of mesh 5 EVALUATION CRITERIA FOR PASSENGER SAFETY 5.1 EXPOSURE TO CO A relationship between the concentration of CO and the time to incapacitation (loss of consciousness) is given in [5]. The following correlation was used to calculate the time to incapacitation for an average person at a high level of activity. 30 t = [min] (1) 4 4 1.036 8.2925* *( * X CO ) X co represents the volume concentration [%] of CO in air. 5.2 EXPOSURE TO HEAT [5] proposes the following correlation for the relationship between the exposure of a human to heat (convective and radiation) and the time to incapacitation (loss of consciousness): ( 5.1849 0.0273* T ) t = e [min] (2) T represents the air temperature in C. Note that this correlation is only valid under conditions of low speed (<30 m/min) air movement in the tunnel. 5.3 VISIBILITY The visibility is estimated based on the mass optical density D m as proposed in [6], A value of D m =0.25 m 2 /g and light reflecting signs were assumed. 4

6 RESULTS 6.1 ONE-DIMENSIONAL ANALYSIS The goal of the 1-D analysis is to provide an overview about the development of temperature, visibility, and time to incapacitation inside the tunnel. 6.1.1 AXIAL VELOCITY UPSTREAM OF THE FIRE axial velocity [m/s] 12 8 6 4 2 Axial Velocity Development t=0 sec, train stops in incident tunnel t=30 sec, air velocity drops below critical velocity critical velocity The development of the axial velocity upstream of the fire is shown in Figure 4. The entering train induces air velocity with a peak level of approximately m/s in the tunnel. After halt of the train, the velocity decreases quickly. The velocity drops below the predicted critical velocity (2.2 m/s see Chapter 3.2) after about 30 sec 0-2 -50-40 -30-20 - 0 20 30 40 50 60 70 80 90 0 Figure 4 Transient axial velocity upstream of the fire 6.1.2 TEMPERATURE time after halt of incident train in tunnel [s] Figure 5 shows the temperature development at 5 different time steps. The average between the temperatures of the hot smoke layer and the cool layer of tunnel air underneath is represented. The positions of the s at +/- 150 m distance from the fire are clearly visible. Downstream of the fire approximately stable conditions occur. In the region between fire and downstream, high temperatures occur that endanger the escaping passengers. The performance of the downstream increases as the axial velocity decreases. Nevertheless, the cannot completely pre the propagation of hot air in the region downstream of the train. Backlayering occurs upstream of the fire. Hot air is transported towards the 550.0 upstream creating Average Temperature [K] 500.0 450.0 400.0 350.0 300.0 70 sec 190 sec 250sec 3 sec 550 sec upstream upstream 250.0-500 -400-300 -200-0 0 0 200 300 400 500 Figure 5 Temperature development distance from fire location [m] downstream downstream unfavorable conditions for the escaping passengers. The front of hot air reaches the position of the upstream (at + 150 m) about 250 sec after halt of the train. Similar to the downstream also the upstream cannot completely pre the transport of hot air in the region behind its position. 5

6.1.3 VISIBILITY AND TIME TO INCAPACITATION 16.0 14.0 "visibility" "time to incapacitation" Incident Tube escape conditions 70 sec after train halt 0 90 16.0 14.0 "visibility" "time to incapacitation" Incident Tube escape conditions 190 sec after train halt 0 90 visibilty [m] 12.0.0 8.0 6.0 4.0 80 70 60 50 40 30 20 time to incapacitation [min] visibilty [m] 12.0.0 8.0 6.0 4.0 80 70 60 50 40 30 20 time to incapacitation [min] 2.0 2.0 0.0 0-500 -400-300 -200-0 0 0 200 300 400 500 distance from fire location [m] 0.0 0-500 -400-300 -200-0 0 0 200 300 400 500 distance from fire location [m] visibilty [m] 16.0 14.0 12.0.0 8.0 6.0 4.0 "visibility" "time to incapacitation" Incident Tube escape conditions 3 sec after train halt 0 90 80 70 60 50 40 30 20 time to incapacitation [min] visibilty [m] 16.0 14.0 12.0.0 8.0 6.0 4.0 "visibility" "time to incapacitation" Incident Tube escape conditions 550 sec after train halt 0 90 80 70 60 50 40 30 20 time to incapacitation [min] 2.0 2.0 0.0-500 -400-300 -200-0 0 0 200 300 400 500 distance from fire location [m] 0 0.0-500 -400-300 -200-0 0 0 200 300 400 500 distance from fire location [m] Figure 6 Visibility and time to incapacitation at 70, 190, 3, 550 sec after halt of the train Figure 6 shows the development of the visibility (Chapter 5.3) and the estimated time until incapacitation (Chapter 5.1). The smoke production of the fire leads to strongly reduced visibility near the train. In particular downstream of the fire, conditions occur that are not favorable for the passengers. Near the train, the visibility reduces quickly upstream of the fire as the smoke propagates towards the. The smoke that remained from the entering train in the tunnel causes reduced visibility upstream of the train. Afterwards, fresh air is transported into this region, leading to improved visibility. No danger of the passengers is expected from the concentration of CO, as the estimated time to incapacitation is sufficiently long to allow the passengers to escape. 6.2 THREE-DIMENSIONAL ANALYSIS 0 Previous train driving direction position offire 1st upstream 400 420 460 540 580 620 660 680 620 7800 800 520 480 340 340 440 520 380 380 340 380 320 360 300 300 320 rear end of train 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 620 640 660 680 700 720 740 760 780 800 Temperature [K] Figure 7 Temperature distribution near the train upstream of the fire at 280 sec after halt of the train 6

6.2.1 3-D TEMPERATURE DISTRIBUTION Figure 7 shows as an example the temperature distribution upstream of the fire 280 sec after halt of the train. The figure reveals the huge amount of information that can be obtained from 3-D CFD simulation. Thermal stratification develops upstream of the fire leading to lower temperatures and improved escape conditions towards the tunnel bottom. The layer of hot smoke has reached the position of the upstream. The performance of the is not sufficient to pre smoke from propagating further towards the rear end of the train. Note the good agreement with the 1-D predictions (Chapter 6.1.2). To simplify the discussion of the results, the temperature and visibility distributions as presented in the following chapters were extracted from a section plane located at the emergency stairway at a distance of 0.75 m from the tunnel wall. This section plane is representative for the assessment of the escape conditions for the passengers. 6.2.2 TRANSIENT TEMPERATURE DEVELOPMENT The transient temperature development at the emergency walkway is shown in Figure 8. The propagation of the zone of hot air in downstream direction is clearly visible. Thermal stratification develops downstream of the fire. After about 180 sec, the layer of hot air starts to decrease which leads to degradation of the escape conditions in this region. The performance of the downstream increases as the axial velocity in the tunnel decreases. This causes decreasing temperatures downstream of the train after about 180 sec. Upstream of the fire, the figure indicates backlayering starting after 30 sec. Consequently, the layer of hot air starts propagating in upstream direction. Similar to the downstream region, thermal stratification develops also upstream of the fire leading to relatively low temperature in the lower part of the tunnel. Steady state conditions are reached after about 540 sec. t=540 sec position of s Temperature [K] t=300 sec Simulation Time t=180 sec t=70 sec t=30 sec Height=2.3 m downstream upstream Figure 8 Transient development of the temperature in a section plane parallel to the train at a distance of 0.75 from the tunnel wall (representative for the situation on the emergency walkway - highest shown temperature is 525 K ) 7

6.2.3 TRANSIENT VISIBILITY DEVELOPMENT position of s t=540 sec Visibility [m] t=300 sec Simulation Time t=180 sec t=70 sec t=30 sec Height=2.3 m downstream upstream Figure 9 Transient development of the visibility in a section plane parallel to the train at a distance of 0.75 from the tunnel wall (representative for the situation on the emergency walkway) The transient development of visibility at the emergency walkway is shown in Figure 9. The figure reveals the strongly reduced visibility near the train. Note also the reduction of visibility upstream of the train caused by the smoke that remains in the tunnels from the entering train. Similar to the temperature, 'visibility' stratification develops and leads to better visibility conditions in the lower part of the tunnel. Nevertheless, the reduction of visibility below 5 m on the emergency walkway can represent an increased risk for the life of the passengers. 6.2.4 TIME TO INCAPACITATION The results obtained by the CFD simulation are compatible with the results of the 1-D analysis. 7 SAFETY ASSESSMENT The discussion of the safety in the tunnel will be based on the four regions A, B up, B down, and C as defined in Figure. upstream of the fire downstream of the fire upstream incident train downstream previous train driving direction A B up B down C Figure Definition of regions for the safety assessment Given normal head or body height, the following limiting values are set for the attempt to escape. Time to incapacitation 1.8 m height: > 20 min Temperature at 1.8 m height: < 0 C (=exposure time > min from equation 3) Range of vision at 1.8 m height: > 5 m 8

Table 1 summarizes the results of the 1-D and 3-D analysis with respect to tunnel safety. A very similar picture is obtained from the two approaches. Only in the region B down, differences occur during a very limited period of time. This is because the 1-D cross section mean temperature estimates the temperature at body height too high when thermal stratification occurs. In particular between the fire and the s life threatening conditions for the escaping passengers can occur. With further distance from the fire, the conditions improve. However, the strongly reduced visibility downstream of the (region C) can lead to risk for the life of the passengers. The concentration of CO in the air and the hereof resulting period of time to incapacitation is not expected to create additional risk for the passengers. Region A t [sec] Time Limit Temperature Limit Visibility Limit 30 fulfilled / fulfilled fulfilled / fulfilled fulfilled / fulfilled 70 fulfilled / fulfilled fulfilled / fulfilled fulfilled / fulfilled 180 fulfilled / fulfilled fulfilled / fulfilled fulfilled / fulfilled 300 fulfilled / fulfilled fulfilled / fulfilled fulfilled / fulfilled 540 fulfilled / fulfilled fulfilled / fulfilled violated / violated Region B up t [sec] Time Limit Temperature Limit Visibility Limit 30 fulfilled / fulfilled fulfilled / fulfilled fulfilled / fulfilled 70 fulfilled / fulfilled fulfilled / fulfilled fulfilled / fulfilled 180 fulfilled / fulfilled fulfilled / violated violated / violated 300 fulfilled / fulfilled violated / violated violated / violated 540 fulfilled / fulfilled violated / violated violated / violated Region B down t [sec] Time Limit Temperature Limit Visibility Limit 30 fulfilled / fulfilled fulfilled / fulfilled / 70 fulfilled / fulfilled violated / violated violated / violated 180 fulfilled / fulfilled violated / violated violated / violated 300 fulfilled / fulfilled violated / violated violated / violated 540 fulfilled / fulfilled violated / violated violated / violated Region C t [sec] Time Limit Temperature Limit Visibility Limit 30 fulfilled / fulfilled fulfilled / fulfilled violated / violated 70 fulfilled / fulfilled fulfilled / fulfilled violated / violated 180 fulfilled / fulfilled fulfilled / fulfilled violated / violated 300 fulfilled / fulfilled fulfilled / fulfilled violated / violated 540 fulfilled / fulfilled fulfilled / fulfilled violated / violated Table 1 Assessment of safety for the escaping passengers as obtained from the 3-D and 1-D analysis (fulfilled: safety granted, violated : safety not granted) 8 1-D VERSUS 3-D APPROACH The 1-D and 3-D approaches lead to a very similar safety assessment for the conditions of this particular study. This is attributed to the relatively simple geometry which was investigated. More detailed data is obtained from the 3-D CFD. In particular at the s and near the fire, three-dimensional flow structures develop that violate the assumptions of the 1-D analysis. However, for the safety assessment this regions are of minor importance. The escape conditions for the passengers are determined by the conditions in the lower part of the tunnel near the walls. A detailed analysis of the CFD data in this region shows that the conditions predicted by the 1-D approach represent very well the escape conditions for the passengers. The prediction of thermal stratification, which in general is excluded from the 1-D approach, can help to improve the conditions for the passengers. The CFD study 9

showed that thermal stratification develops, which leads to a different safety assessment for a very limited period of time in the region B down near the train. However, the combination of all evaluation criteria (temperature, visibility and time to incapacitation) for passenger safety can counter-balance for this limitation of the 1-D analysis as long as the 1-D assumptions for the global flow conditions are fulfilled. In consideration of its cost, the use of 3-D models should therefore be mostly restricted to more complex configurations, where the approximations used by 1-D models are not allowable anymore. This is for instance the case for the investigation of smoke propagation into cross passages or smoke extraction from rescue areas. For a simple geometry the use of 1-D methods in most cases will be more efficient. 9 CONCLUSIONS A study of tunnel safety in a tunnel with a natural ilation system was presented. The study investigated the conditions near the burning train after its halt. An emergency scenario was defined and criteria for the assessment of the safety of the escaping passengers were presented. Two different approaches were used: 1-D approach using the program SPRINT, an HBI internal development, 3-D approach using the commercial CFD program FLUENT. The following conclusions can be drawn from the study: The study gives a detailed picture of the safety of the escaping passengers. Temperature, visibility, time-to-incapacitation were derived from the simulations and used for the safety assessment. The high temperature levels and the significantly reduced visibility lead to an increased risk for the escaping passengers close to the fire. The concentration of CO in the air and the resulting period of time to incapacitation are not expected to create additional risk for the passengers. A very similar safety assessment is obtained based on both investigation methods, although the 3- D CFD simulation illustrates the development of thermal stratification near the fire, which is not possible using the 1-D approach. The study showed that SPRINT is a reliable design tool as long as the one-dimensional assumptions are valid for the investigated geometry. In this case, the 1-D approach leads to correct predictions of the relevant air-quality parameters in the tunnel and the escape conditions of the passengers. For a more complex tunnel geometry, including for example cross-passages or rescues areas, however, 3-D CFD should be employed because it will lead to more comprehensive and reliable results. Moreover, in particular for a complex flow condition, regions of high risk will be revealed by the 3-D CFD that could be overlooked by a 1-D analysis. REFERENCES [1] William D. Kennedy; 'Critical Velocity: Past, Present and Future', Seminar Smoke and Critical Velocity in Tunnels, London, UK, 2 April 1996 [2] I. Riess, M. Bettelini, R. Brandt; 'SPRINT - a design tool for fire ilation', th international symposium on Aerodynamics and Ventilation of Vehicle Tunnels, Boston, USA, 1-3 November 2000 [3] D. Drysdale, 'An Introduction to Fire Dynamics', John Wiley, 1985 [4] D.T. Gottuk, R.J. Roby, 1995, 'Effect of combustion on species production' in SFPE handbook of Fire Protection Engineering, 2 nd edition, 1995, NFPE Publication 95-68247, Section 2 / Chapter 7 [5] David A. Purser, 1995, 'Toxity Assessment of combustion products' in SFPE handbook of Fire Protection Engineering, 2 nd edition, 1995, NFPE Publication 95-68247, Section 2 / Chapter 8 [6] George W. Mulholland, 1995, Smoke production and properties' in SFPE handbook of Fire Protection Engineering, 2 nd edition, 1995, NFPE Publication 95-68247, Section 2 / Chapter 15