Power Quality Centre VOLTAGE FLUCTUATIONS IN THE ELECTRIC SUPPLY SYSTEM. Technical Note No. 7 August 2003



Similar documents
HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM

Power Quality A guide to voltage fluctuation and light flicker

Introduction. Harmonics and IEEE 519 Page 1 of 19

Electromagnetic Compatibility (EMC) Low-Frequency Standards. Standards on Low-Frequency Emission: IEC

Power Quality Standards for Electric Service

Power Quality & Custom Power

Three phase circuits

Product Data Bulletin

Ingegneria Elettrotecnica. Development of Human Visual System Analysis Methods for the Implementation of a New Instrument for Flicker Measurements

The design and performance of Static Var Compensators for particle accelerators

Electricity Service Standards

CERN Accelerator School. Electrical Network and Power Converters. Hans Ulrich Boksberger Paul Scherrer Institute 5232 Villigen PSI Switzerland

System Standard For the Installation of New Loads

Typical Data Requirements Data Required for Power System Evaluation

POWER SYSTEM HARMONICS. A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS

English version. Voltage characteristics of electricity supplied by public distribution systems

How To Limit Voltage Unbalance

Improvements of Reliability of Micro Hydro Power Plants in Sri Lanka

USE OF ARNO CONVERTER AND MOTOR-GENERATOR SET TO CONVERT A SINGLE-PHASE AC SUPPLY TO A THREE-PHASE AC FOR CONTROLLING THE SPEED OF A THREE-PHASE INDUCTION MOTOR BY USING A THREE-PHASE TO THREE-PHASE CYCLOCONVERTER

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies

Power measurement in balanced 3 phase circuits and power factor improvement. 1 Power in Single Phase Circuits. Experiment no 1

Power Electronics. Prof. K. Gopakumar. Centre for Electronics Design and Technology. Indian Institute of Science, Bangalore.

Three-phase monitoring relay CM-PFE

8 Speed control of Induction Machines

SECTION DVD01: VOLTAGE DROP/VOLTAGE FLICKER AND TRANSFORMER SIZING GUIDELINES

7. Reactive energy compensation

Variable Frequency Drives - a Comparison of VSI versus LCI Systems

Arc Terminator Active Arc-Resistant Switchgear

Power-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800

Specifying a Variable Frequency Drive s

13 ELECTRIC MOTORS Basic Relations

Session 10: General Overview of Interconnection Standards & Grid Codes for High Penetration PV October 21, 2015 Santiago, Chile

Power Quality for Information Technology System

TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY

POWER FACTOR CORRECTION

SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE WELDERS

UNDERSTANDING POWER FACTOR AND INPUT CURRENT HARMONICS IN SWITCHED MODE POWER SUPPLIES

How To Understand The Electrical Power Supply Of A Power Supply System

Trends in Power Quality

Modeling and Simulation of a Large Chipper Drive

Specification guide no. 9 Active harmonic conditioner from 20 to 480 A

Power Quality Issues, Impacts, and Mitigation for Industrial Customers

INTRODUCTION TO HARMONIC ASSESSMENT IN POWER SYSTEMS

WYE-DELTA AND SOLID STATE STARTER APPLICATION GUIDE

415V DISTRIBUTION FOR GREEN DATA CENTERS

FREQUENCY CONTROLLED AC MOTOR DRIVE

Impact of Leading Power Factor on Data Center Generator Systems

Load Tap Changing Control

Voltage Tolerance Boundary

General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System

Equipment Performance Due to Voltage Sags Test Results for Contactor and Induction Motor

Size template. Grid Connection Masterclass Energex John Lansley Senior Network Solutions Engineer

Type: DILM115(RAC240) Article No.: Sales text Contactor,55kW/400V,AC operated. Ordering information

BALANCED THREE-PHASE CIRCUITS

Simulation and Analysis of PWM Inverter Fed Induction Motor Drive

However, industrial applications may utilize a relay, which short-circuits the ICL path after the inrush sequence.

ANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H.

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.

MOBILE SYSTEM FOR DIAGNOSIS OF HIGH VOLTAGE CABLES (132KV/220KV) VLF-200 HVCD

Inverter technology. bulletin

Step Voltage Regulators

Green Energy Solutions

Power Quality. Uninterruptible Power Supply

Supply Standards: Electricity Supply Standard July JULY 2011 ISSUE 6 UNCLASSIFIED UNCONTROLLED COPY IF PRINTED

COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS

Scholars Research Library

De Jaeger, Emmanuel ; Du Bois, Arnaud ; Martin, Benoît. Document type : Communication à un colloque (Conference Paper)

Calculating voltage dips in power systems using probability distributions of dip durations and implementation of the Moving Fault Node method

Modelling, Simulation and Performance Analysis of A Variable Frequency Drive in Speed Control Of Induction Motor

Transfer Equipment Controls

415V DISTRIBUTION FOR GREEN DATA CENTERS

Heat-pump performance: voltage dip/sag, under-voltage and over-voltage

ENERGY AND ENVIRONMENTAL SAVINGS IN STEEL MAKING BY MEANS OF SVC LIGHT

Current Loop Tuning Procedure. Servo Drive Current Loop Tuning Procedure (intended for Analog input PWM output servo drives) General Procedure AN-015

Paralleling Power Sources Which Share a Common Neutral

Part 1 System Modeling & Studies for Existing Systems

SYNCHRONOUS MACHINES

VCO Phase noise. Characterizing Phase Noise

Mathematical Modeling and Dynamic Simulation of a Class of Drive Systems with Permanent Magnet Synchronous Motors

TURBOtech srl. SED-635 Digital Excitation System. Industrial Electronics Sector FEATURES

Rotary Phase Converters

Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE

LOW COST MOTOR PROTECTION FILTERS FOR PWM DRIVE APPLICATIONS STOPS MOTOR DAMAGE

EET272 Worksheet Week 9

Simulation and Analysis of Parameter Identification Techniques for Induction Motor Drive

ABB i-bus KNX Switch Actuator, x-fold, 16/20 A, MDRC SA/S x , 2CDG 110 1xx R0011

CE Marking and Technical Standardisation

Maximum Demand Control

Performance Enhancement of Wound Rotor Induction Motor by VSI with Dynamic Capacitor Controlled Rotor Circuit

Power factor correction. An introduction to technology and techniques

DYNACOMP The top-class dynamic response compensator

3-PHASE LOW VOLTAGE NETWORK LOAD BALANCER : A COST EFFECTIVE SOLUTION TO LINE VOLTAGE VARIATIONS

XFE. The cost effective starter for all AC induction motors from 4A 2800A The choice for small to medium industrial applications

THE PER-UNIT SYSTEM. (2) The per-unit values for various components lie within a narrow range regardless of the equipment rating.

ANN Based Fault Classifier and Fault Locator for Double Circuit Transmission Line

EDEXCEL NATIONAL CERTIFICATE/DIPLOMA UNIT 5 - ELECTRICAL AND ELECTRONIC PRINCIPLES NQF LEVEL 3 OUTCOME 4 - ALTERNATING CURRENT

Measurement, Modeling and Simulation of Capacitor Bank Switching Transients

AC Power. by Prof. Dr. Osman SEVAİOĞLU Electrical and Electronics Engineering Department

DOE FUNDAMENTALS HANDBOOK ELECTRICAL SCIENCE Volume 3 of 4

Transcription:

Technical Note No. 7 August 2003 Power Quality Centre VOLTAGE FLUCTUATIONS IN THE ELECTRIC SUPPLY SYSTEM This Technical Note discusses voltage fluctuations, their causes and adverse effects, what levels are acceptable and how to reduce their consequences. Integral Energy, your local Network Operator or the Integral Energy Power Quality Centre can give you additional advice if you have particular concerns with these issues. Summary Voltage fluctuations are defined as repetitive or random variations in the magnitude of the supply voltage. The magnitudes of these variations do not usually exceed 10% of the nominal supply voltage. However, small magnitude changes occurring at particular frequencies can give rise to an effect called lamp flicker. This term is used to describe the impression of unsteadiness of visual sensation induced by a light source whose luminance or spectral distribution fluctuates with time [1]. Flicker is essentially a measure of how annoying the fluctuation in luminance is to the human eye. Standards limit the magnitudes of starting currents and load fluctuations of equipment to control the level of voltage fluctuations. Where the levels of indices specified in the standards are exceeded, mitigation techniques to reduce the effects of voltage fluctuations are required. Contents 1. What are voltage fluctuations? 2. Effects of voltage fluctuations 3. Causes of voltage fluctuations 4. Calculation of the flicker indices 5. Voltage fluctuation standards and planning levels 6. Reducing the effects of voltage fluctuations 7. References and additional reading 8. Integral Energy Power Quality Centre

1. What are voltage fluctuations? Voltage fluctuations can be described as repetitive or random variations of the voltage envelope due to sudden changes in the real and reactive power drawn by a load. The characteristics of voltage fluctuations depend on the load type and size and the power system capacity. Figure 1 illustrates an example of a fluctuating voltage waveform. The voltage waveform exhibits variations in magnitude due to the fluctuating nature or intermittent operation of connected loads. The frequency of the voltage envelope is often referred to as the flicker frequency. Thus there are two important parameters to voltage fluctuations, the frequency of fluctuation and the magnitude of fluctuation. Both of these components are significant in the adverse effects of voltage fluctuations. Voltage envelope Magnitude Time Voltage waveform Figure 1 Terminal voltage waveform of fluctuating load In Figure 1 the voltage changes are illustrated as being modulated in a sinusoidal manner. However, the changes in voltage may also be rectangular or irregular in shape. The profile of the voltage changes will depend on the current drawn by the offending fluctuating load. Typically, voltage changes caused by an offending load will not be isolated to a single customer and will propagate in an attenuated form both upstream and downstream from the offending load throughout the distribution system, possibly affecting many customers. 2. Effects of voltage fluctuations The foremost effect of voltage fluctuations is lamp flicker. Lamp flicker occurs when the intensity of the light from a lamp varies due to changes in the magnitude of the supply voltage. This changing intensity can create annoyance to the human eye. Susceptibility to irritation from lamp flicker will be different for each individual. However, tests have shown that generally the human eye is most sensitive to voltage waveform modulation around a frequency of 6-8Hz. The perceptibility of flicker is quantified using a measure called the short-term flicker index, P st, which is normalised to 1.0 to represent the conventional threshold of irritability. The perceptibility of flicker, a measure of the potential for annoyance, can be plotted on a curve of the change in relative voltage magnitude versus the frequency of the voltage changes. Figure 2 illustrates the approximate human eye perceptibility with regard to rectangularly modulated flicker noting that around the 6-8Hz region fluctuations as small as 0.3% are regarded as perceptible as changes of larger magnitudes at much lower frequencies [1]. Figure 2 is often referred to as the flicker curve and represents a P st value of 1.0 for various frequencies of rectangular voltage fluctuations. Although regular rectangular voltage variations are uncommon in practice they provide the basis for the flicker curve, defining the threshold of 1

irritability for the average observer. It is worth noting that the flicker curve is based on measurements completed using a 60W incandescent light bulb. This is used as a benchmark measurement, however the perceptibility of lamp flicker will vary depending on the size and type of lamp used. Relative voltage change (%) 10 1 230 V 120 V 100 V 0.1 0.1 1 10 100 1000 10000 Number of rectangular voltage changes per minute Figure 2 Flicker curve for rectangular modulation frequencies [1] Voltage fluctuations on the public low voltage power system are required to be within accepted tolerances specified in the standards. In general the acceptable region of voltage fluctuations falls below the flicker curve illustrated in Figure 2. Voltage fluctuations may also cause spurious tripping of relays; interfere with communication equipment; and trip out electronic equipment. Severe fluctuations in some cases may not allow other loads to be started due to the reduction in the supply voltage. Additionally, induction motors that operate at maximum torque may stall if voltage fluctuations are of significant magnitude. 3. Causes of voltage fluctuations Voltage fluctuations are caused when loads draw currents having significant sudden or periodic variations. The fluctuating current that is drawn from the supply causes additional voltage drops in the power system leading to fluctuations in the supply voltage. Loads that exhibit continuous rapid variations are thus the most likely cause of voltage fluctuations. Examples of loads that may produce voltage fluctuations in the supply include Arc furnaces Arc welders Installations with frequent motor starts (air conditioner units, fans) Motor drives with cyclic operation (mine hoists, rolling mills) Equipment with excessive motor speed changes (wood chippers, car shredders) Often rapid fluctuations in load currents are attributed to motor starting operations where the motor current is usually between 3-5 times the rated current for a short period of time. If a number of motors are starting at similar times, or the same motor repeatedly starts and stops, the frequency of the voltage changes may produce flicker in lighting installations that is perceivable by the human eye. 2

Consider the simple model representing a fluctuating load drawing real power P, and reactive power Q, connected to a power system with an impedance of resistance R, and reactance X, as illustrated in Figure 3. The voltage V R seen by the customer can usually be regulated by operating the system voltage V S at a slightly higher value to ensure V R remains at the required value, e.g. 230V for a single-phase system. During steady state operation this can be achieved through the use of automatic tap changers on transformers, line drop compensators and voltage regulators. For more rapid changes in load current the operation of such devices is not fast enough in response to effectively regulate the voltage to stay at the required value. The resultant voltage due to the current drawn by the load is illustrated in the phasor diagram of Figure 4 where V S is the supply voltage and V R is the resultant voltage seen by the load at the point of common connection (PCC). R X I PCC Supply V S System impedance V R Fluctuating load (P + jq) Figure 3 Simple model of power system V S V R j IX I = Id - ji q IR Figure 4 - Phasor diagram of supply voltage The complex power drawn by the fluctuating load and the voltage phasors can be described by equations (1) and (2) respectively. V * R I = P + jq (1) V S = V R + I (R + jx) (2) Expanding equation (2) for the voltage phasors provides the following V S = V R + (I d - ji q ) (R + jx) (3) = (V R + R I d + X I q ) + j(x I d R I q ) (4) Ignoring the phase differences between V R and V S in equation (4) and equating only the real parts V S = V R + R I d + X I q (5) 3

Assuming V S is a very strong supply system, i.e. V S remains constant regardless of the current drawn by the fluctuating load, for any changes in I d and I q the changes in V R will be as follows 0 = V R + R I d + X I q (6) V R = - (R I d + X I q ) (7) Equation (7) can be re-written in per unit, i.e. in terms of the changes in real and imaginary power drawn by the fluctuating load V R = - (R P + X Q) (8) If R is negligible, then the reactance X = 1 / Fault level, leading to equation (9) V R = - Q / Fault level (9) Thus, it can be seen that the voltage at the point of common connection is essentially a function of the reactive power variation of the load and supply system characteristics. Note that for low voltage systems where R is considerably larger the real power may also contribute significantly to voltage variations. 4. Calculation of flicker indices There are two major indices used in the evaluation of flicker in power systems, the short-term flicker index, P st as stated before, and the long-term flicker index, P lt. The P st index represents the perceptibility of flicker based on a criterion that flicker levels created by voltage fluctuations will annoy 50% of population. This index is calculated on a 10-minute basis to evaluate short-term flicker levels. For a periodic rectangular voltage fluctuation, this index, normalised to a value of 1.0, is illustrated in Figure 2 as the flicker curve. Calculation of P st values is performed by a flickermeter. The design specification and functionality of a flickermeter is outlined in Australian standards AS 4376 and AS 4377. Figure 5 illustrates the functional block diagram of a flickermeter as per the standards. The first three blocks of the design perform the signal conditioning operation on the measured voltage waveform v(t). More specifically these blocks represent how the voltage fluctuations are transformed to light fluctuations, determine the perceptibility to the human eye and then simulate the brain response (annoyance) to lamp flicker. This process is often referred to as the lamp-eye-brain response. The final block performs the statistical analysis required to calculate P st and P lt. AS 4376 AS 4377 v(t) Square law demodulator Weighting filters Squaring and smoothing Statistical evaluation of flicker level P st P lt 1 2 3 4 Instantaneous flicker sensation level P f (t) Figure 5 Functional block diagram of a flickermeter 4

The filtering (smoothing) and weighting in the first three blocks of the flickermeter adjust the fluctuation frequency components according to the perceived human annoyance. The output of the signal conditioning blocks may look similar to that illustrated in Figure 6 for a single 10-minute interval. Weighted signal P f (t) Divided into 64 classes Scanned at 50 Samples per second Time, t 10min Figure 6 Output of flickermeter at the 3 rd block The output of the 3 rd block of the flickermeter, the instantaneous flicker level signal, is sampled and divided into 64 different time-at-level classifications. This allows a statistical evaluation of the flicker levels to be established. The measure of the severity of short term flicker, P st is then calculated every 10 minutes using weighted cumulative probability values of the flicker levels exceeding 0.1, 1, 3, 10 and 50% of the time using equation (10). P = 0.0314 P + 0.0525 P + 0.0657 P + 0.28 P + 0.08 P (10) st 0.1 1 3 10 50 People's tolerance to flicker over longer periods is less than for the short term. For this reason the second index is introduced by the standards, the long-term flicker index, P lt. P lt is an average of P st values evaluated over a period of two hours using a cubic law as defined in equation (11). P 1 = (11) 12 3 3 lt P st As a short-term flicker index of 1.0 suggests that the sensation of flicker will be annoying to the human eye, utilities must ensure that flicker levels arising as a result of voltage fluctuations remain below 1.0. For the long-term flicker index the values should be kept even lower as long-term flicker is generally more annoying to customers. 5. Voltage fluctuation standards and planning levels 5.1 AS 4376 and AS 4377 AS 4376 and AS 4377 cover the functionality and design of a flickermeter. A flickermeter may be a stand-alone device or, as is usually the case, incorporated as part of the functionality of a multipurpose power quality monitoring device. AS 4376 includes design specifications of a flickermeter capable of indicating light flicker perception due to all practical voltage fluctuation waveforms. This standard also includes type test specifications for compliance with 5

Rectangular and sinusoidal voltage fluctuations (for specified frequency and percentage change in voltage), and Environmental tests such as EMC and climatic tests. AS 4377 provides details for the statistical evaluation methods for both short-term and long-term flicker severity. The statistical analysis emulates the perception of the lampeye-brain chain providing the quantified outputs P st and P lt. Calculations are completed on-line resulting in P st values for each 10-minute interval and P lt values using the cube law every two hour interval. 5.2 AS/NZS 61000.3.3 AS/NZS 61000.3.3 specifies the emission limits for low voltage equipment rated less than or equal to 16A to ensure excessive voltage fluctuations are not caused by their normal operation. The standard outlines the test conditions for type tests on the equipment (cookers, lighting equipment, washing machines, tumbler dryers, refrigerators, copying machines, laser printers, vacuum cleaners, food mixers, portable tools, hair dryers, consumer electronics, direct water heaters). To measure voltage fluctuations caused by the operation of specific loads the magnitude of change in the rms voltage is considered every half cycle (10ms) of mains frequency for all the rms values of voltage over each 10-minute interval. The voltage change characteristics V(t) shown in Figure 7 is then determined for periods between when the voltage has been in steady state for at least one second. A reference system impedance is specified to be used during the type tests. V(t) V V max Time, t Figure 7 Histogram evaluation of V(t) 5.3 AS/NZS 61000.3.5 AS/NZS 61000.3.5 covers the specifications outlined in AS/NZS 61000.3.3 for low voltage equipment with rated current greater than 16A. This standard differs however in that it uses the actual point of connection to perform the compliance tests rather than a reference impedance. Thus to perform the evaluation of this equipment the consumer and electricity supplier must cooperate and provide the necessary data to allow an evaluation to take place. Such data may include load details, system impedance, existing level of disturbance, and cost of power supply improvements. 5.4 AS/NZS 61000.3.7 The Australian standard which specifies the limits for fluctuating loads in MV and HV power systems is based on the IEC report of the same name, IEC 61000-3- 7:1996. This IEC report is a Technical Report Type 3, meaning it does not have the same standing as an international standard but may be referred to for assistance in setting limits for customers. However in Australia this document has been adopted as V 6

a standard. This standard is required to ensure the interaction of all loads connected to the power system does not cause excessive voltage fluctuations. Each customer is allocated certain limits to ensure the impact of the operation of their loads is acceptable with regards to flicker. The primary objective of this standard is to provide guidance for engineering practices. The given guidelines are based on certain simplifying assumptions and hence recommended approaches are to be used with flexibility and judgement. The final decision for connection of a customer s fluctuating load will always rest with the electricity supplier. Compatibility levels for voltage fluctuations are set as shown in Table 1 for the shortterm and long-term flicker indices. Utilities should endeavour to ensure flicker indices do not exceed the compatibility levels recommended by the relevant standards. For this reason utilities should allocate planning levels below the compatibility levels. The planning levels for MV and HV systems recommended in the standard are given in Table 2. Table 1 - Compatibility levels for LV and MV systems P st 1.0 P lt 0.8 Table 2 - Planning levels for MV and HV and EHV systems MV HV-EHV P st 0.9 0.8 P lt 0.7 0.6 The general procedure for evaluating fluctuating loads as per the AS/NZS 61000.3.7 standard is completed in stages. Stage 1 is a simplified evaluation of disturbance emission. If the fluctuating load or the customers maximum demand is small compared to the short circuit capacity at the point of common connection, no detailed evaluation is necessary. Stage 2 calculates emission limits proportional to maximum demand. Equipment is evaluated against system absorption capacity that is allocated to individual customers according to their demand. Absorption capacity is derived from planning levels. In allocating to individual customers at MV levels, disturbances derived from HV levels should be considered. The final stage is acceptance of higher emission levels on an exceptional and precarious basis where utility and consumer may agree on the connection with special conditions. 5.5 AS/NZS 61000.3.11 This standard covers the conditional connection of loads that come under the specifications outlined in AS/NZS 61000.3.5 but do not meet compliance. 6. Reducing the effects of voltage fluctuations To allow equipment connected to the power system to operate correctly it is important for both the utility and their customers to ensure that the operating voltage of the system remains within the boundaries set by the appropriate standards. As mentioned previously power system equipment does not usually provide adequate response time for mitigation of rapid voltage changes. It is inherent that complete compensation of flicker is not possible [7]. However, the magnitude of the voltage fluctuations may be 7

reduced using one of the following network strategies Increasing the fault level at the point of connection. Strengthening the system or reconnecting the offending load at a higher voltage level can achieve this. Decrease the reactive power flow through the network due to the load. This may be achieved through the use of a Static VAr Compensator (SVC) and will help reduce voltage sags. Strengthening the network reactive power compensation. A larger number of smaller capacitor banks distributed throughout a system will allow finer tuning of reactive power requirements [7]. Frequent motor starting has been highlighted as a significant cause of flicker. This is especially significant for larger single-phase air conditioner compressor motors connected to weak low voltage distribution systems. In order reduce the magnitude of voltage fluctuations a reduction in the starting current of a motor must be accomplished. This can be achieved through the use of various starting techniques. [7] suggests the use of the following motor starting techniques Inclusion of an intermediate star-delta resistance-delta starting configuration for three-phase motor applications. Installing a series resistance or inductance with the motor stator to effectively apply reduced voltage starting. Use of an exclusive autotransformer matched to the design of the motor. Soft start using power electronic soft starters. Full inverter control of motor. This has the advantage of controllable speed and torque providing efficient motor operation. As frequency is also an important parameter of voltage variations a reduction in the number of motor starts may also lessen the effects of flicker. This may be achieved through coordinated control of motors or by providing sufficient storage of heat for the case of air conditioners and heat pumps [8]. 7. References and additional reading 1. AS/NZS 61000.3.3:1998, Electromagnetic compatibility (EMC) Part 3.3: Limits Limitation of voltage fluctuations and flicker in low-voltage supply systems for equipment with rated current less than or equal to 16A, Australian Standards, 1998. 2. AS/NZS 61000.3.5:1998, Electromagnetic compatibility (EMC) Part 3.5: Limits Limitation of voltage fluctuations and flicker in low-voltage supply systems for equipment with rated current greater than 16A, Australian Standards, 1998. 3. AS/NZS 61000.3.7:2001, Electromagnetic compatibility (EMC) Part 3.7: Limits Assessment of emission limits for fluctuating loads in MV and HV power systems, Australian Standards, 2001. 4. AS/NZS 61000.3.11:2002, Electromagnetic compatibility (EMC) Part 3.11: Limits Limitation of voltage changes, voltage fluctuations and flicker in public low-voltage supply systems Equipment with rated current less than or equal to 75A and subject to conditional connection, Australian Standards, 2002. 5. AS/NZS 4376:1996, Flickermeter Functional and design specifications, Australian Standards, 1996. 6. AS/NZS 4377:1996, Flickermeter Evaluation of flicker severity, Australian Standards, 1996. 8

7. Iglesias et al, Power Quality in European electricity supply networks, 1 st Edition, Euroelectric, Brussels, 2002. 8. Morcos and Gomez, Flicker sources and mitigation, IEEE Power Engineering Review, November 2002. 8. Integral Energy Power Quality Centre In July 1996, Integral Energy set up Australia's first Power Quality Centre at the University of Wollongong. The Centre's objective is to work with industry to improve the quality and reliability of the electricity supply to industrial, commercial and domestic users. The Centre specialises in research into the control of distortion of the supply voltage, training in power quality issues at all levels, and specialised consultancy services for solution of power quality problems. You are invited to contact the Centre if you would like further advice on quality of supply. ABOUT THE AUTHORS Duane Robinson is a Lecturer in the School of Electrical, Computer and Telecommunications Engineering at the University of Wollongong. The Integral Energy Power Quality Centre sponsors his position. Sarath Perera is a Senior Lecturer in the School of Electrical, Computer and Telecommunications Engineering at the University of Wollongong. Vic Gosbell is the Technical Director of the Integral Energy Power Quality Centre and Professor of Power Engineering in the School of Electrical, Computer and Telecommunications Engineering at the University of Wollongong. Vic Smith is a Research Engineer for the Integral Energy Power Quality Centre. 9

FURTHER INFORMATION CAN BE OBTAINED BY CONTACTING: Professor V.J. Gosbell Technical Director Integral Energy Power Quality Centre School of Electrical, Computer & Telecommunications Engineering University of Wollongong NSW AUSTRALIA 2522 Ph: (02) 4221 3065 or (02) 4221 3402 Fax: (02) 4221 3236 Email: vgosbell@uow.edu.au