A Demonstration Plant of a Liquid Desiccant Air Conditioning Unit for Drying Applications



Similar documents
Initial Experiments of a Novel Liquid Desiccant Dehumidifier for Industrial and Comfort Air Conditioning Systems

Thermochemical Storage for Air-Conditioning using Open Cycle Liquid Desiccant Technology

Performance Test of Solar Assisted Solid Desiccant Dryer

THE PSYCHROMETRIC CHART: Theory and Application. Perry Peralta NC State University

New absorption chillers for high efficient solar cooling systems

Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning System

Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment

A NEW DESICCANT EVAPORATIVE COOLING CYCLE FOR SOLAR AIR CONDITIONING AND HOT WATER HEATING

Application of sandy bed solar collector system for water extraction from air

ALONE. small scale solar cooling device Project No TREN FP7EN Project No TREN/FP7EN/ ALONE. small scale solar cooling device

Transient Analysis of Integrated Shiraz Hybrid Solar Thermal Power Plant Iman Niknia 1, Mahmood Yaghoubi 1, 2

Refrigeration Basics 101. By: Eric Nelson

Question: Can a gymnasium floor be restored after being exposed to water damage?

1 Overview of applications and system configurations

Lesson 36 Selection Of Air Conditioning Systems

CFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER

Coupling Forced Convection in Air Gaps with Heat and Moisture Transfer inside Constructions

Research on the Air Conditioning Water Heater System

TRNSYS Modelling of a Hybrid Membrane Liquid Desiccant Air Conditioning System

EXPERIMENTAL EVALUATION AND MODELING OF A SOLAR LIQUID DESICCANT AIR CONDITIONER

Because here you can see a simple an elementary direct evaporative cooling system this is called as a single stage system you can see from the

saving energy in comfort Factsheet Recair Enthalpy

New Trends in the Field of Automobile Air Conditioning

Modelling and Simulation of the Freezing Systems and Heat Pumps Using Unisim Design

APPLICATION OF SANDY BED SOLAR COLLECTOR SYSTEM FOR EXTRACTION OF WATER FROM AIR

Testing methods applicable to refrigeration components and systems

SOLAR-POWERED COOLING, DEHUMIDIFICATION AND AIR CONDITIONING

Solar Desiccant Air Conditioner

Grant Agreement No SFERA. Solar Facilities for the European Research Area SEVENTH FRAMEWORK PROGRAMME. Capacities Specific Programme

LONG-TERM SOLAR THERMAL ENERGY STORAGE USING AQUEOUS CALCIUM CHLORIDE

How To Understand Evaporator

Vapor Chambers. Figure 1: Example of vapor chamber. Benefits of Using Vapor Chambers

2A.1 Features of Chiller Control Components A.3 Chilled-Water Supply Temperature Control A.4 Cooling-Water Supply Control...

Automobile Air Conditioning Primer

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

Integration of a fin experiment into the undergraduate heat transfer laboratory

Long-Term Hygrothermal Performance of Green Roofs

Comparison of Heat Transfer between a Helical and Straight Tube Heat Exchanger

SDH ONLINE-CALCULATOR

Sheet 5:Chapter 5 5 1C Name four physical quantities that are conserved and two quantities that are not conserved during a process.

FLUID FLOW Introduction General Description

Mold Preventing I nterior System

ME Heat Transfer Laboratory. Experiment No. 7 ANALYSIS OF ENHANCED CONCENTRIC TUBE AND SHELL AND TUBE HEAT EXCHANGERS

CFD Analysis of Application of Phase Change Material in Automotive Climate Control Systems

Experimental Evaluation Of The Frost Formation

Evaluation Of Hybrid Air- Cooled Flash/Binary Power Cycle

Vicot Solar Air Conditioning. V i c o t A i r C o n d i t i o n i n g C o., l t d Tel: Fax:

PERFORMANCE EVALUATION OF WATER-FLOW WINDOW GLAZING

International Journal of Latest Research in Science and Technology Volume 4, Issue 2: Page No , March-April 2015

Air-sourced 90 Hot Water Supplying Heat Pump "HEM-90A"

Simulation of a small size solar assisted adsorption air conditioning system for residential applications

Creating the Ideal Environment for Accelerated Drying Times on Construction and Restoration Projects

STR-600 Plate Dryer. 1. What it s meant for?

COMPARISON OF PROCESS FLOWS: FLUID BED COMBUSTOR AND GLASSPACK

Moisture Control. It s The Dew Point. Stupid! Its not the humidity.

Lesson. 11 Vapour Compression Refrigeration Systems: Performance Aspects And Cycle Modifications. Version 1 ME, IIT Kharagpur 1

Use and Care Manual. Model CPA12KH AIR CONDITIONER

SWIMMING POOL AIR-HANDLING UNITS KU-DB Series

Processi della Tecnologia Alimentare - Prof. Davide Barbanti. The frying process

Frost Damage of Roof Tiles in Relatively Warm Areas in Japan

Heat Pipe Cooling of Concentrating Photovoltaic (CPV) Systems

Total Heat Versus Sensible Heat Evaporator Selection Methods & Application

TEMA DESIGNATIONS OF HEAT EXCHANGERS REMOVABLE BUNDLE EXCHANGERS NON REMOVABLE BUNDLE EXCHANGERS SOURCE:

Performance of the Boiler and To Improving the Boiler Efficiency Using Cfd Modeling

Testing and Performance of the Convex Lens Concentrating Solar Power Panel Prototype

SOLAR WATER PURIFICATION WITH THE HELP OF CSP TECHNOLOGY

Optimum Solar Orientation: Miami, Florida

A discussion of condensate removal systems for clarifier and thickener drives for water and wastewater facilities.

Horizontal Pond Domestic Hot Water Heater

TEXTILE FABRICS AS THERMAL INSULATORS

VITOSOL r 200-T SP2A. VITOSOL 200-T Type SP2A

Solar Energy in Egypt Advantages and Obstacles

The soot and scale problems

Experimental Study on Super-heated Steam Drying of Lignite

Experimental Study of Free Convection Heat Transfer From Array Of Vertical Tubes At Different Inclinations

DEVELOPMENT OF A TWIN SCREW EXPRESSOR AS A THROTTLE VALVE REPLACEMENT FOR WATER-COOLED CHILLERS

UNIT 2 REFRIGERATION CYCLE

Heat and cold storage with PCM

THERMOCHEMICAL SEASONAL SOLAR HEAT STORAGE WITH MgCl 2.6H 2 O: FIRST UPSCALING OF THE REACTOR

Fractional Distillation and Gas Chromatography

PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM WITH R404A, R407C AND R410A

Test Report No. C1319LPEN

DETERMINATION OF THE HEAT STORAGE CAPACITY OF PCM AND PCM-OBJECTS AS A FUNCTION OF TEMPERATURE. E. Günther, S. Hiebler, H. Mehling

AIR CONDITIONING - ENERGY CONSUMPTION AND ENVIRONMENTAL QUALITY

Small-Scale Solar Heating and Cooling Systems

Heat Pipe Selection Revision 12/04/2001

Mohan Chandrasekharan #1

A Comprehensive Laboratory Test to Analyze the Compatability of Leading Cleaners and Sanitizers on Today's Industrial Refrigeration Evaporator Coils.

CONDENSATION IN REFRIDGERATED BUILDINGS

European technical approval

Heat. Investigating the function of the expansion valve of the heat pump. LD Physics Leaflets P Thermodynamic cycle Heat pump

HEAT TRANSFER ANALYSIS IN A 3D SQUARE CHANNEL LAMINAR FLOW WITH USING BAFFLES 1 Vikram Bishnoi

Transcription:

A Demonstration Plant of a Liquid Desiccant Air Conditioning Unit for Drying Applications Mustafa Jaradat, Klaus Vajen, Ulrike Jordan Institut für Thermische Energietechnik, Universität Kassel, 34125 Kassel, Germany Phone: +49-561 804 3890, Fax: +49-561 804 3993 solar@uni-kassel.de www.solar.uni-kassel.de Abstract A demonstration plant of a liquid desiccant system in order to dry hay bales was set up in an agricultural domain. The system consists of an absorber for the dehumidification of the supply air and a regenerator to re-concentrate the diluted desiccant solution. Laboratory experiments of a small prototype showed promising results for the temperature increase and humidity decrease of the air. Moreover, first experimental results of the demonstration plant showed a significantly reduced drying time of the hay bales, while the supply air was increased by more than 10 K and the relative humidity was reduced from more than 60% to below 30%. 1. Introduction Drying of agricultural products is the greatest energy consuming process on the farm [1]. The target of drying is to remove moisture from the agricultural product in order to process and store it safely for increased periods of time. For hay drying the moisture of the hay needs to be reduced to about 20% to allow the storage without the risk of rot. Hot air drying increases the temperature of the air (and product) and lowers the air relative humidity and thus allows the air to carry moisture from the product. The basic concept of liquid desiccant dehumidification system is to directly reduce the moisture and warm up the air, which is used for drying, only a few degrees above the ambient temperature. In the absorber, moisture absorbed from the process air stream dilutes the desiccant solution by loading the desiccant with water vapour (Fig. 1). Fig. 1: Schematic of the liquid desiccant system.

The solution weakened by absorption of moisture is re-concentrated in the regenerator, where it is heated to elevate its water vapour pressure. The heat drives out the moisture from the solution and the strengthened solution is returned to the dehumidifier. A scavenging air stream contacts the heated solution in the regenerator. There, water evaporates from the desiccant solution into the air and the solution is re-concentrated. 2. Experimental Setup Experiments were conducted to measure the moisture transfer as well as the temperature difference during the absorption and desorption processes. In all the absorber and regenerator prototypes used, the air stream and the LiCl-H 2 O solution are set up in a cross flow configuration. Textile fibers are used in order to increase the exposure time of the desiccant and thereby enhance the desired mass transfer and heat exchange. The distribution system of the sorbent uses Plexiglas tubes to horizontally distribute the solution over the textile. The tubes penetrate the absorber or regenerator horizontally and spread the desiccant solution over the coated plates or tubes through a number of equally spaced holes. The size and number of the holes are selected according to distribution tests carried out in [2] to provide the desired liquid flow. The LiCl-H 2 O solution flows through the distribution system, it is then throttled over the textile and trickles down along the plates or tubes by gravity. Lithium chloride is used as the liquid desiccant because of its favorable physical properties [3]. 2.1. Laboratory Pilot Plant The overall exposed surface area of a small laboratory prototype used as absorber and regenerator, is about 3.9 m 2. The heat and mass exchanger consists of a stack twin wall polycarbonate plates. Fig. 2 Schematic diagram of the experimental setup, pilot plant stage

The air is conditioned according to the required set-value with a series of instruments (electric air heater, air cooler/dehumidifier, steam generator). For monitoring of the air, a vortex flow meter, and HygroFlex humidity and temperature transmitters are used at the inlet and outlet of the component. The density and the temperature of the LiCl-H 2 O solution are monitored before and after the heat and mass exchanger, the flow rate is measured with a magneto-inductive flow meter. All values were continually monitored during the experiments. 2.2. Demonstration Plant for Drying Hay Bales The desiccant absorber in the demonstration plant consists of a plate type heat and mass exchanger with a total exposed surface of about 75 m 2. The dried and heated air is blown through a hose to a wide air channel with a circular opening for one hay bale. The desiccant regeneration system consists of a heat and mass exchanger made of copper pipes, protected from corrosion with a thin powder coating layer. Textile sleeves are applied over the copper tubes. The total exposed surface area of the regenerator is about 9 m 2. Hot water supplied by solar collectors flows through the copper tubes to heat the desiccant solution in order to concentrate it again. Schematic diagram of the exp. setup Demonstration plant during installations Construction of the solar collector field (155m 2 ), The drying-sorption plant connected to the hay April 2012 bale, July 2013 Fig. 3: Demonstration plant in Frankenhausen (near Kassel)

3. Inlet Values for Laboratory Experiments The prototype was tested in an adiabatic dehumidifier mode. 12 experimental runs were conducted in three experimental sequences. Table 1: Inlet conditions for the laboratory tests in dehumidification mode (absorption). kg/h, ºC, g/kg Test seq.1 var:14.1-56.3 24.6 ± 0.1 14.36 ± 0.27 Test seq.2 14.2 ± 0.63 var:24.5-30.1 14.69 ± 0.21 Test seq.3 44 ±0.54 25.3 ± 0.2 var:13.64-20.20 The air mass flow rate was kept constant of 375 kg/h ± 4 kg/h, desiccant inlet temperature of 27 ºC ± 1.1 ºC and desiccant mass fraction (ξ) of 0.43 kg/kg. Moreover, the prototype was tested in a non-adiabatic regenerator mode by using hot air and water streams. Six experimental runs were conducted in two experimental sequences. The air mass flow rate was kept constant of 302 kg/h ± 4 kg/h, desiccant inlet temperature of 27 ºC ± 1.1 ºC, inlet heating-water temperature of 50.3 C and desiccant mass fraction of 0.36 kg/kg, while varying the air humidity ratio and the desiccant mass flow rate. 4. Results and Discussion 4.1. Laboratory Experiments of a Small Heat and Mass Exchanger The results of the supply air adiabatic dehumidification show a consistent reduction in the relative humidity, a consistent reduction in the humidity ratio, and an increase in the air temperature. Figure 4 shows an example of one of the experiments; the change in the relative humidity reaches about 42 percent-points and an increase in the air temperature of about 5.2 K. Fig. 4: Example measurement: Dehumidification in a small laboratory prototype. The mass transfer performance of the dehumidifier was evaluated in terms of the moisture removal rate. The moisture removal rate, ṁ v, is calculated by Eq. 1 [4]. =,, Eq.1

Moisture removal rate, g/s 0,5 0,45 0,4 0,35 0,3 0,25 0,2 0,15 0 5 10 15 20 LiCl-H 2 O mass flow rate, g/s Moisture removal rate, g/s 0,6 0,5 0,4 0,3 0,2 0,1 0 12 14 16 18 20 22 Inlet air humidity ratio, g/kg Experimental F.D. Model Fig. 5: the moisture removal rate as a function of desiccant flow rate and air inlet humidity ratio for the dehumidification experiments. As shown in Figure 5, the moisture removal rate in both directions increased remarkably with increasing desiccant flow rate for both of absorption and regeneration systems. The moisture removal rate increases with increasing the air inlet humidity ratio in the absorber and vice versa for regeneration. The effect on the moisture removal rate was caused by the increased average water vapor pressure difference between the air and the desiccant with increasing air inlet humidity ratio. The experimental results were compared with an ideal numerical finite difference model. In Figure 5, the blue points represent the experimental results and the red points represent the finite difference results. The comparison between the experimental and numerical results shows divergences, both, due to uncertainties of experimental data and due to idealized assumptions of the numerical model. A more detailed analysis of the deviations will be carried out in future investigations. 4.2. First Experimental Results of the Demonstration Plant Table 2: Initial measurements from the demonstration plant for a drying experiment of a hay bale. 5. Conclusions Plate and tube bundles type heat and mass exchangers were built and tested in a pilot plant stage and in a demonstration plant as an air dehumidifier and desiccant regenerator.

Parameter variations were carried out in the laboratory. The experimental results of a small laboratory prototype show a reduction in the supply air humidity ratio in the absorption process of about 4.8 g/kg for typical reference conditions. The results show a consistent reduction in the relative humidity and an increase in the air temperature, which are the main factors that affect how readily moisture moves from the drying product. The parametric analysis results in reduction of the air relative humidity in the range of 18-46% points and an increase in the air temperature in the range of 3.7-8.0 K are observed, depending on the inlet parameters. The mass fraction of the diluted desiccant solution (from 0.38 to 0.43 kg/kg) was possible by using hot water of 55-60ºC. The results were analyzed and compared with results from a finite difference model. In a demonstration plant, first measurements showed promising results of the dehumidification of hay bales. The drying time for a hay bale could be reduced significantly. The air stream temperature was increased by more than 10 K while relative humidity was reduced by more than 40%-points during the tests. Acknowledgements This research project is supported by the German Federal Ministry for Education and Research in the framework of the research program KLIMZUG Nordhessen Climate Change in Regions. References [1] Gunasekaran, S., Optimal energy management in grain drying, CRC Critical Reviews in Food Science and Nutrition, Vol. 25 Issue 1, pp. 1-48, 1986. [2] Jaradat, M., Heinzen, R., Jordan, U., Vajen, K., A Novel Generator Design for a Liquid Desiccant Air Conditioning System, Proceedings of the EuroSun 2008 Conference, Lisbon (PO), 07.10-10.10.2008. [3] Conde, M.R. Properties of aqueous solutions of lithium and calcium chlorides: formulations for use in air conditioning equipment design, International Journal of Thermal Sciences, vol. 43,pp 367 382. [4] Lävemann, E. Peltzer, M.,Solar Air Conditioning of an Office Building in Singapore Using Open Cycle Liquid Desiccant Technology, Proceedings of the International Conference on Solar Air Conditioning, Staffelstein (DE), 06.-07.10.2005.