NG-0-R -RM -RMS -TM -VM ontrol and monitoring modules for use with the Raychem NG-0 Installation Instructions Description The NG-0-RM/-RMS and NG-0-TM provide ground-fault and line current sensing, alarming, switching and inputs for five heat-tracing circuits when used with the NG-UIT. The NG-0-RM is used to control Electromechanical Relays (EMRs) and the NG-0- RMS is used to control Solid State Relays (s). Approvals/ertifications Hazardous Locations lass I, Div., Groups A,B,,D Ex n II T5 lass I, Zone, AEx n II T5 General Supply Voltage Vdc ± 0% Internal power consumption < 5 W per NG-0-RM/-RMS Ambient operating temperature 0ºF to 0ºF ( 0º to 60º) Ambient storage temperature 0ºF to 67ºF ( 0º to 75º) Environment PD, AT III Max. altitude 000 m Humidity 0 90% non-condensing Electromagnetic ompatibility Immunity Heavy Industrial Emission Industrial Environment Temperature Sensors Type Quantity urrent Sensors Mounting Quantity per NG-0-TM D B A 00-ohm platinum, -wire, α = 0.0085 ohms/ohm/º an be extended with a -conductor shielded cable of 0 ohm maximum per conductor Up to five wired directly to each NG-0-RM/-RMS Din Rail 5 mm Five for ground-current measurement Five for line current measurement Tools Required Wire cutters RJ stripping/crimping tool RJ connectors Screwdriver small blade - standard Additional Materials Required Power supply - Vdc @ 00 ma per NG-0-RM/-RMS board RJ conductor cable Kit ontents Item Qty Description A NG-0-RM or RMS (card rack module with connectors) B NG-0-TM (current transformer module) NG-0-R (card rack) D NG-0-VM (voltage monitoring module) - optional Line urrent Sensors Max current Accuracy Ground Fault Sensor Range Accuracy Voltage Sensor Range Accuracy Outputs RM output relays RMS outputs Alarm Relay ommunication to NG-UIT Type able Length Quantity 60 A ± % of reading 0 00 ma ± % of range at 0 A line current 80 90 Vac 50/60 Hz ± % of span Form A -Amp @ 77 Vac max 50/60 Hz Vdc @ 0 ma max per output Form -Amp @ 77 Vac max 50/60 Hz wire RS-85 One shielded twisted pair 000 ft. (00 M) maximum Up to 5* NG-0-RM/-RMS may be connected to one NG-UIT onnection Terminals Power supply/pilot Relay/ 8 AWG (0.8 -. mm ) /omm Port (RS85) * May require an RS-85 repeater if communication length is greater than 000 ft. WARNING: This component is an electrical device that must be installed correctly to ensure proper operation and to prevent shock or fire. Read these important warnings and carefully follow all of the installation instructions. omponent approvals and performance are based on the use of Pentair Industrial Heat Tracing Solutions-specified parts only. Do not use substitute parts. Keep components dry before and during installation. Leave these instructions with the end user for reference and future use. For technical support, call Pentair Industrial Heat Tracing Solutions at (800) 55-658. Industrial Heat Tracing SOLUTIONS EN-RaychemNG0R-IM-H577 0/5 / 8
leaning Instructions If dust accumulates on the NG-0-RM/-RMS circuit board use compressed air to remove the dust. Turn off all power to the NG-0 panel. arefully disconnect all cables from a single NG- 0-RM/-RMS card, making sure to label cables so that they can be reconnected after board cleaning. Wear an anti-static wrist strap connected to ground in order to avoid component damage. Remove the RM/RMS circuit card from the card cage and place on a clean lint-free surface. Use dry compressed air from a can for cleaning circuit boards. (Avoid factory compressed air since it may contain enough moisture or oil to cause permanent damage.) Use short quick blasts to remove dust build-up as necessary. After cleaning, replace the RM/RMS in the same card cage position and reconnect all cables. Remove only one card at a time for cleaning to avoid any problems during re-installation. NG-0-R Installation Instructions Mounting of ard Rack Use the mounting template (on page 7) to mount the rack on a panel backplane. There are four holes (0.88 in dia.) to secure it to the mounting surface using #8 screws. Once the card rack is installed, a earth bonding wire (green 8 AWG min.) terminated with a #0 Ring terminal must be connected to the card rack using the ground screw provided. Note: The card rack must be installed on a non-combustible surface. 7.0 in 0.97 in (8 mm) (79 mm).5 in (8 mm) Grounding screw Note: screw is located on the outside of the enclosure NG-0-RM/-RMS Installation Instructions NG-0-RM/RMS MSB LSB TB TB TB TB TB 5 TB 9 TB TB 7 TB 6 TB TB TB 5 TB 6 TB 7 Alarm output Relay outputs (5x) LEDs (9x) Fuse Vdc Inputs (x) End of Line (EOL) jumper RS-85 ommunications Line & ground-fault sensor inputs (5x) Inputs Address Switches Power Relay Relay Tx Alarm Relay Relay Rx Relay 5 LED functions 7.00 in (78 mm) 0.75 in (7 mm) Industrial Heat Tracing SOLUTIONS EN-RaychemNG0R-IM-H577 0/5 / 8
Power Supply The power supply connector (TB9) is a dual two pin connector. Either connector allows for power in (pin # (+), pin # ( ) and bussing of power to other NG-0-RM modules). Note: Power supply must be sized correctly based on the number of NG-0-RM/- RMS modules. RS-85 ommunications The RS-85 connector (TB6) is a dual three pin connector. Either connector allows for RS-85 input signals (pin # (shield), pin # (+), pin # ( )) and bussing of RS85 signal to other NG-0-RM modules. End of Line (EOL) Jumper If this device (NG-0-RM/-RMS) is the last device in the RS-85 network, the J jumper needs to be moved from terminals & to terminals &. Inputs Ordinary Area wire s with shield may be connected to h thru h 5 (TB - TB5). The two common wires (usually red, red) are connected to terminals &, the source (usually white) to terminal and the braid to terminal (earth ground). Note: 's are not required if monitoring per each NG-0-RM board current/ground-faults only or if 's are connected via RMMs. connected directly to RM board Inputs Hazardous Area For all terminations in a hazardous area, the field wires must be terminated on a panel-mounted terminal block. hassis Ground NG-0-RM/RMS Board 5 Terminal block Factory wired Normal position End of Line position RM PB Hazardous area Relay Output onnections to ontactors or Solid State Devices (TB7) This connector switches voltage to the contactor coils or solid state relays. The pilot relay will switch the supply voltage (up to 77 Vac) to the contactor coil (using an NG-0-RM) or Vdc to the solid state device (using an NG-0-RMS). Refer to system layout diagram for detail wiring. ommon Alarm The common alarm terminal block (TB) provides a form dry contact, rated at 77 Vac max (A). When the Raychem NG-0 system is powered on, the common alarm relay coil is energized and pin is connected to pin (common). This is the "No Alarm" condition for the RM/RMS board. 0-RLY 8-RLY -RLY 7 8 9 0 5 6 -OM 6-RLY5 -RLY OM losed Open If the alarm occurs, or the RM/RMS board loses power, the relay coil is de-energized and pin (common) is disconnected from pin and connected to pin to indicate an alarm condition exits. Address Switches (SW & SW) Each NG-0-RM/-RMS must have a unique communication address selected. The valid address switch range when using the NG-UIT is -99. SW is the ones digit (0 9) and SW is the tens digit (0 or 9). Note: When adding an NG-0-RM/- RMS to the system, you must first cycle power on the RM/RMS board and then perform a network update at the NG-UIT. Optional Voltage Sensor able Preparation Notes:. ut one end off of a groundfault /line current cable.. Strip insulation approx. inch from cut end.. Strip the red and black wire insulation approx. 0.0 in.. onnect red and black wire to the two position terminal plug. No need to be concerned about polarity. 5. Trim brown and orange wires from cut end. Optional Voltage Sensor The optional voltage sensor can monitor 80 90 Vac. This voltage connects to one of the five line current/ground-fault inputs on the NG-0-RM. Note: By using the optional voltage sensor, you lose the ability to monitor the ground-fault and current for that circuit. Red and black wires 8 MSB SW LSB SW Relay No Alarm ondition 0. in Brown and orange wires in Industrial Heat Tracing SOLUTIONS EN-RaychemNG0R-IM-H577 0/5 / 8
NG-0-TM Installation Instructions NG-0-TM Line & ground-fault sensor outputs (5x) Line current sensor (5x) Ground-fault current sensor (5x) Typical GF / L wiring through transformers DIN rail mounting foot (X) Ground-fault transformer Phase / Neu. Phase Line current transformer.5 in (89.9 mm) top of DIN rail 9.75 in (8 mm) DIN rail Each NG-0-TM mounts on a DIN 5 rail. It should be located between the circuit breaker or terminal block and contactor or in the panel. Ground-Fault/Line urrent able Assembly Note: A complete cable may be ordered as part number: 057800-XXX where XXX = Length (L) in inches. Ground-Fault/Line urrent Sensors onnections from NG-0-RM/-RMS to NG-0-TM. Using an RJ connector/cable assembly, connect one end to an RJ input (TB- TB7) and the other end to the appropriate NG-0-TM RJ connector. (L) Typical connection ( of 5) Industrial Heat Tracing SOLUTIONS EN-RaychemNG0R-IM-H577 0/5 / 8
System Layout NG-0-RM 0 Vac in Vdc Power Supply NG-UIT Touch Screen L N 0 Vac contctor power s Alarm relay output NG-0-RM A voltage up to 77Vac L 0 Vac N To contactor coils (see detail) NG-0-TM Distribution panel board with standard ci rcuit breakers Ø Ø Ø N Relay drivers 8 0 5 6 Pilot relays ontactor located on coils circuit board To heater's power junction box Industrial Heat Tracing SOLUTIONS EN-RaychemNG0R-IM-H577 0/5 5 / 8
System Layout NG-0-RMS 0 Vac in Vdc Power Supply NG-UIT Touch Screen s Alarm relay output Internal Vdc power NG-0-RMS A voltage up to 77 Vac Note: Vdc power provided by NG-0-RMS board Internal Vdc + Output driver To D input (see detail) NG-0-TM Distribution panel board with standard circuit breakers Ø Ø Ø N 5 8 0 6 To heater s power junction box (typical 5) Industrial Heat Tracing SOLUTIONS EN-RaychemNG0R-IM-H577 0/5 6 / 8
7.00 in ø 0.88 in (x) Top of ard Rack NG-0-R Wall mounted hole template (Note: Ensure the printed template has scaled correctly. 9.75 in. in Industrial Heat Tracing SOLUTIONS EN-RaychemNG0R-IM-H577 0/5 0.65 in 7 / 8
General Installation Instructions. The Raychem NG-0 components must be installed: In compliance with all local electrical and safety codes In an enclosure suitable for the application environment. When used in hazardous (lass I, Div. or Zone ) locations, a minimum IP5 enclosure is required.. The Raychem NG-0 components must be protected by external overcurrent and disconnect devices. This may be a circuit breaker or a combination of disconnect switch and fuses. The disconnect device: Must disconnect all ungrounded, current-carrying conductors Should be located in close proximity to the equipment Be within easy reach of the Operator Be marked as the disconnecting device for the equipment. Supply wiring insulation must be rated for the highest voltage and temperature to be encountered in the application. onductors must be sized for the application and be protected by an external overcurrent device.. Some wiring configurations will use more than one power source and all must be de-energized prior to performing any maintenance on a controller circuit. 5. Protection provided by this equipment may be impaired if the device is used outside of its ratings or for applications other than is intended. 6. Always be sure that the intended location is classified as an area for which the product is approved. 7. The Raychem NG-0 components have no user serviceable parts. ontact your Pentair Industrial Heat Tracing Solutions Representative for service and a Return Authorization if required. onducted and Radiated Emissions - Statement Of ompliance This equipment has been tested and found to comply with the limits for a lass A digital device, pursuant to Part 5 of the F Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: Reorient or relocate the receiving antenna. Increase the separation between the equipment and receiver. onnect the equipment into an outlet on a circuit different from that to which the receiver is connected. onsult the dealer or an experienced radio/tv technician for help. This lass A digital apparatus complies with anadian IES-00. et appareil numérique de la lasse A conforme à la norme NMB-00 du anada. NG-0 Installation Test Procedures Once assembled into a panel, the Raychem NG-0 components must be tested as a system to ensure that the ground fault detection circuitry is functional. The following tests must be conducted by qualified personnel familiar with the equipment and its operation, test procedures, and electrical code requirements. Make as many copies of this checklist as required to document successful tests for each circuit in the panel. Abbreviations: GF = Ground Fault T = urrent Transformer NG-0-RM/-RMS Board: Tested By: Date: ircuit # ircuit # ircuit # ircuit # ircuit #5 Inspect the wiring to ensure that all load conductors pass through the GF T. Verify that no ground (PE) conductors pass through the GF T. Ensure that conductors on the load side of the GF T are not grounded. Simulate a GF on the load side of the GF T large enough to cause the NG-0-RM or NG-0-RMS to trip its output off. This should occur within approx. second of applying the test GF current. ompleted forms should be retained with the panel and available for inspection by the local Electrical Inspection Authority. WWW.PENTAIRTHERMAL.OM NORTH AMERIA Europe, Middle East, Africa Tel: +.6..5 Fax: +.6..60 thermal.info@pentair.com Asia Pacific Tel: +86...688 Fax: +86..56.97 cn.thermal.info@pentair.com Latin America Tel: +.7.868.800 Fax: +.7.868. thermal.info@pentair.com Tel: +.800.55.658 Fax: +.800.57.570 Tel: +.650.6.56 Fax: +.650.7.77 thermal.info@pentair.com Pentair and NG are owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice. 006-05 Pentair. Industrial Heat Tracing SOLUTIONS EN-RaychemNG0R-IM-H577 0/5 8 / 8