Tech Tip # 61. Why 400 CFM per Ton is used for Determining Standard Air Conditions Air Volumes

Similar documents
THE PSYCHROMETRIC CHART AND ITS USE

Greenhouse Cooling. Why is Cooling Needed?

APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application

Energy Efficient Building Design College of Architecture Illinois Institute of Technology, Chicago. Relative Humidities RH%

HVAC Calculations and Duct Sizing

Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal

Total Heat Versus Sensible Heat Evaporator Selection Methods & Application

Hospital Application Guide. Cost-effective climate control for hospitals

UNDERSTANDING AND USING THE HVAC DESIGN REVIEW FORM

Dedicated Outdoor Air Systems (D.O.A.S.)

Moisture Control. It s The Dew Point. Stupid! Its not the humidity.

By Tom Brooke PE, CEM

How do I measure the amount of water vapor in the air?

Glossary of Heating, Ventilation and Air Conditioning Terms

Characteristics of Evaporators

APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems

Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida

air conditioners how to choose a cooling system

THE PSYCHROMETRIC CHART: Theory and Application. Perry Peralta NC State University

Air Water Vapor Mixtures: Psychrometrics. Leon R. Glicksman c 1996, 2010

The formula for finding CFM is: CFM = BTUH OUTPUT_ Temp Rise (ACF)* *Altitude correction factor below 1000ft = 1.08

Humid Air. Water vapor in air. Trace Glasses 1% Argon (A) Water vapor (H 2

Air Conditioning Contractors of America

Creating the Ideal Environment for Accelerated Drying Times on Construction and Restoration Projects

UNDERSTANDING REFRIGERANT TABLES

Refrigeration Manual. Part 3 - The Refrigeration Load

Because here you can see a simple an elementary direct evaporative cooling system this is called as a single stage system you can see from the

Makeup Air For Exhaust Systems In Tight Houses. Tony Jellen Engineering Projects

Troubleshooting an Air Conditioning system. R D Holder Eng. Roger D Holder MSME

Venice Library Humidity Study. for Williams Building Diagnostics, LLC th Street West Bradenton, FL Report April 13, 2015

Measuring The Right Thing For Humidity Control It s the Dew Point Stupid!

EFFECTS OF INDOOR RELATIVE HUMIDITY ON REFRIGERATED DISPLAY CASE PERFORMANCE

Principles of Rice Drying How does rice dry?

HVAC Made Easy - Overview of Psychrometrics

How To Understand And Understand Psychrometrics

Humidification Strategies for Data Centers and Network Rooms

Energy Efficient Homes: Air Conditioning 1

Element D Services Heating, Ventilating, and Air Conditioning

THE HUMIDITY/MOISTURE HANDBOOK

How To Understand Evaporator

Innovent LASER Packaged Fresh Air Conditioning Units

Specific Volume of Liquid (Column 7). The volume per unit of mass in cubic feet per pound.

Refrigeration and Air Conditioning with Psychrometry

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.

TECH TIP # 37 SOLVING SERIES/PARALLEL CIRCUITS THREE LAWS --- SERIES CIRCUITS LAW # THE SAME CURRENT FLOWS THROUGH ALL PARTS OF THE CIRCUIT

Presented By: WALTER E. JOHNSTON, PE CEM, CEA, CLEP, CDSM, CPE

HVAC FORMULAS. TON OF REFRIGERATION - The amount of heat required to melt a ton (2000 lbs.) of ice at 32 F. 288,000 BTU/24 hr. 12,000 BTU/hr.

Below are detailed instructions for using the EMS load calculator.

A Glossary of HVAC Terms:

The Fallacies of Venting Crawl Spaces January 3, 2002 Craig DeWitt, PhD, PE

Glossary of HVAC Terms

Temperature and Humidity

Walnut Drying Design and Operation. Selecting Dryer Type. Tray Drying Before Don Osias Jim Thompson

Components HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis

Pool Dehumidification Basics

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION

Akton Psychrometric Chart Tutorial and Examples

Causes of High Relative Humidity Inside Air Conditioned Buildings. Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates

Air Conditioning Clinic

High Altitude HVAC. Silvertip Integrated Engineering Consultants

> Executive summary. Explanation of Cooling and Air Conditioning Terminology for IT Professionals. White Paper 11 Revision 2. Contents.

Why Do I Need Precision Air Conditioning?

Energy Efficient Homes: Air Conditioning

Energy Efficiency. Energy Efficient Home Cooling:

Home Energy Evaluation Report

Purpose: To determine the dew and point and relative humidity in the classroom, and find the current relative humidity outside.

Smaller. Quieter. Smarter.

Fuel and Energy Conversion and Equivalence Chart

CONDENSATION EXPLAINED

Comfort Conditioning & Indoor Air Quality

Recover Heat from Boiler Blowdown Water

Yijun Gao, Wei Wu, Zongwei Han, Xianting Li *

Optimization of Water - Cooled Chiller Cooling Tower Combinations

Refrigeration Basics 101. By: Eric Nelson

Calculating Total Cooling Requirements for Data Centers

FBQ. DC Duct Heat Pump or Cooling Only

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) March

Defining Quality. Building Comfort. Precision. Air Conditioning

AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries

Tech Byte 27: Small Computer Room and IT Closet Cooling

HVAC and REFRIGERATION

Whole House Dehumidification for Occupant Comfort and Energy Savings

The main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building.

Beware of Exaggerated Claims and Uncertified Manufacturers Ratings Regarding Commercial Boiler Efficiency

saving energy in comfort Factsheet Recair Enthalpy

COURSE TITLE : REFRIGERATION AND AIR CONDITIONING COURSE CODE : 4029 COURSECATEGORY : A PERIODS/WEEK : 5 PERIODS/SEMESTER : 90 CREDITS : 4 OBJECTIVES

Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER

Direct Energy Home Energy Audit Audit Report

1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53%

Cooling Load Calculations and Principles

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS

William A. Lotz, PE, Direct Fired Heaters Can. Result in Excessive Moisture and Condensation. By William A. Lotz, PE Consulting Engineer Acton, ME

Lesson 36 Selection Of Air Conditioning Systems

To provide good indoor air quality

HOT & COLD. Basic Thermodynamics and Large Building Heating and Cooling

Air-Conditioning Buying Guide

about your house How to Get the Ventilation That You Need in Your House Figure 1 Infiltration and exfiltration of air in a house

Low Cost. Lower Energy Costs. Higher Efficiency.

Heat Recovery Dehumidification (HRD) system. Designed for municipal swimming pools

Transcription:

Tech Tip # 61 One of a series of dealer contractor Technical advisories prepared by HARDI Wholesalers as a customer service. Why 400 CFM per Ton is used for Determining Standard Air Conditions Air Volumes Equations that explain relationship between temperature and air quantities show why CFM requirements for summer air conditioning change with varying heat loads. The conditioned air quantity for air conditioning should be about 400 CFM per ton of cooling capacity. Does this rule-of-thumb strike a familiar note? Although many dealer-contractors may say, Sure, we've known that for a long time, how many can explain the relationship? Those who can know that they have a broader base from which to seek solutions to air conditioning problems than do those who cannot. Rules-of-thumb are useful guide posts, but only the most simple air conditioning problems can be solved with such rules alone. In an air conditioning system, the circulating air serves as a carrier of heat and moisture either to or from the conditioned space. Let us first consider air as a carrier of heat. We are not so much interested in the total amount of heat the circulating air carries as we are in the change in heat between the point where it enters the conditioned space and the point where it leaves. The difference is the amount of heat which the air has either added to or removed from the space. By careful measurement it has been found that it takes 0.24 Btu to raise one pound of air one degree Fahrenheit. This is known as the specific heat of air. Since we normally deal with cubic feet, not pounds, of air in air conditioning work, we must know another fundamental value, the number of cubic feet which one pound of air will occupy. Because this value varies considerably with the temperature and pressure, calculations are generally based upon air at so called standard conditions (dry air at 70 F and 14.7 lb/sq in.) which has a volume of 13.34 cu ft/lb. The actual volume occupied by a pound of air at almost any condition may be read from a psychrometric chart. Published by the Independent Study Institute, a division of the Heating, Airconditioning & Refrigeration Distributors International. The Institute offers accredited, industry training courses in HVAC/R technology. Direct inquiries to HARDI 3455 Mill Run Drive, Ste. 820, Columbus, OH 43026. Phone 888/253-2128 (toll free) 614/345-4328 Fax 614/345-9161 www.hardinet.org

Temperature and its Relation to Quantity We are now prepared to relate air to heat. Suppose we are supplying 300 CFM to a heater. The air enters at 70 F and leaves at 120 F. How much heat has the air picked up in passing through the heater? We use the relationship: Qs = CFM x 60 x 0.24 x 1/13.34 x (T 2 - T 1 ) where: Q is sensible heat in Btuh 60 is min/hr. 0.24 is Btu/lb/deg F 13.34 is cu ft/lb T 2 - T 1 is temperature change, deg F. Simplifying: Qs = CFM x 1.08 x (T 2 - T 1 ) The simplified equation above is most important and is used both in cooling and heating problems where it is necessary to determine the relationship of air quantity and temperature difference to heat. Notice that in using the factor 1.08 it is assumed that the CFM value is adjusted to standard conditions. Most equipment is cataloged for standard air. Field measured flow can be adjusted to standard conditions by simple proportions of temperature and pressure (using absolute values). The preceding equation shows that the same amount of heat may be conveyed using a large air flow and a small temperature difference or a small air flow and a large temperature difference. Thus, instead of 300 CFM and a 50 F range, we could use 150 CFM with 100 F range or 600 CFM with a 25 F range. Although in each case the total amount of heat is the same, there are practical limitations in each direction. Larger air flows require larger air handling equipment and larger ductwork. Higher temperatures create fire and burn hazards and problems of distribution. As noted previously, air carries moisture as well as heat. Since evaluation of its moisture carrying capacity is more of a problem with cooling than with heating, we shall consider it in this connection. The cooling load is more complex than the heating load, and for that reason the relationship of air quantity to load is not as apparent for the former as it is for the latter. Normally the cooling load is broken down into the following categories: internal sensible, internal total, total sensible and grand total. Internal sensible includes all sources of heat which tend to cause a temperature rise in the conditioned space. These would include heat conducted through walls, floor and roof, solar energy entering through glass, heat from lights, people, appliances, etc., and heat from air which might infiltrate directly. Internal total heat includes internal sensible heat plus latent heat represented by the moisture originating in the conditioned space from people, appliances and direct infiltration.

Total sensible heat includes internal sensible heat required to reduce the ventilation air from design outside temperature to room temperature. Grand total heat is the sum of all sensible and latent heat sources represented by the space load calculation and the ventilation load calculation. Since the internal sensible portion of the load includes all heat sources which tend to cause a temperature rise in the conditioned space, it is this heat value which is used in our equation to determine air quantity. As was the case for heating, we can theoretically use any convenient combination of flow and temperature difference that will balance the equation. The temperature difference in this case tells us how much the selected air quantity must be cooled below room temperature in order to remove the unwanted heat. Requirements for dehumidification Just as the internal sensible load is used in determining the amount of air needed to cool a given space, so the internal latent load is used in determining the amount of air needed to dehumidify a given space. If the two problems (heat and moisture) were independent, they could be solved with independent air quantities. Moisture in a conditioned space is in the form of vapor. A pound of dry air at a given temperature can contain variable amounts of vapor up to a maximum. At 70 F, for example, a pound of dry air can have associated with it a maximum of 0.015 lb of vapor. The air is said to be saturated at this condition and the relative humidity is said to be 100%. If the pounds were only half of maximum, the relative humidity would be only 50%. Because the amount of moisture per pound of dry air is small when expressed in pounds, it is more convenient to express it in grains, there being 7,000 grains to the pound. The weight of vapor for saturated air at 70 F is 110.5 grains. Vapor is removed from air by chilling it until it condenses to water. For each pound of vapor condensed, approximately 1,050 Btu must be removed by the cooling coil. This is the heat of vaporization. Its removal takes place at constant temperature just as its addition, in the boiling process for example, takes place at constant temperature. The amount of moisture in air is determined most easily from a psychrometric chart using measured values of the dry and wet bulb temperatures. Let us assume that 300 CFM enters a room at 52 F DB, 50 F WB. The chart shows that the air carries 50 grains of moisture per pound of dry air. A corresponding measurement of air leaving the room shows 76 grains per pound. The latent heat which this air carries from the room is calculated as follows: Q L = CFM x 60 x 1/13.34 x 1/7000 x 1050 x (G 2 - G 1 ) where: Q L is latent heat in Btuh 60 is min/hr. 13.34 is cu ft/lb 7,000 is grains/lb 1,050 is heat of vaporization (nominal value) in Btu/lb water (G 2 - G 1 ) is moisture change, grains/lb dry air.

Simplifying: Q L = CFM x 0.68 x (G 2 - G 1 ) Q L = 300 x 0.68 x (76-50) = 5,300 Btuh Notice that the equation for Q L can be satisfied by having a small air quantity and large difference in moisture levels or a large air quantity and small difference in moisture levels. The relationship is similar to that described between air quantity and temperature difference in the equation for sensible heat, Q S. Supply Air Varied for Load Requirements We have seen how air is used to carry both sensible and latent heat and how each form of heat, considered independently, can be the basis for calculating the air needed to carry it. We can now proceed to the solution of practical air conditioning problems which generally require that both types of heat be carried simultaneously with the same air quantity. This requires the designer to: first, establish the air quantity; second, create the temperature difference needed for the selected air CFM to convey the sensible heat; third, create the difference in grains needed for the selected air CFM to convey the latent heat. In order to see how supply air conditions are "tailored" to meet a load requirement, let us assume that a certain room is to be maintained at 78 F DB, 50% RH. The room loads are as follows: Internal sensible heat 8,000 Btuh, internal latent heat 1,430 Btuh. The air quantity would be approximated by assuming that the air would be introduced into the room at about 58 F which is 20 degrees below room temperature. Using the equation Q S = CFM x 1.08 x (T 2 - T 1 ) and solving for CFM, we have: CFM = 8,000/1.08 x 20 = 370. If the temperature difference we choose is much larger than 20 degrees, we should have difficulty mixing the cold supply air with room air in a way that would avoid drafts. We might also approach a condition where moisture would freeze on the coil surface. On the other band, if it were much less than 20 degrees, ducts, fans, etc. would become larger and more costly due to the increased CFM. The now established 370 CFM must pick up the internal latent heat of 1,430 Btuh. Using the equation Q L = CFM x 0.68 x (G 2 - G 1 ) and solving for the change in grains of moisture per pound, we have (G 2 - G 1 ) = 1,430/0.68 x 370 = 5.7. In other words, if we introduce air into the room at the rate of 370 CFM which has a moisture level 5.7 grains/lb below the desired room level, we can remove moisture at the rate indicated by the load (1,430 Btuh). From the psychrometric chart, we find the room level of moisture at 78 F DB, 50% RH is 71 gr/lb. The supply air must, therefore, be at 71-5.7 = 65.3 gr/lb as well as at 58 F. These two conditions establish the supply air wet bulb temperature as 56.5 F. Summarizing then, 370 CFM at 58 F DB, 56.5 F WB will remove 8,000 Btuh sensible heat and 1,430 Btuh latent heat from a room and hold it at 78 F DB, 50% RH. The final step in the simple problem above would be to select a cooling coil from cataloged values which could cool the required amount of air between the two points. In trying to make a selection, we may find that practical limitations make it advisable for us to revise our original assumption of 20 degrees of cooling to a slightly lower or higher value. This would, of course, change the CFM and the other related values.

In the procedure described above, we were required to maintain an exact room condition of 78 F DB, 50% RH. In comfort air conditioning, we strive for exact control of temperature, but we are not so particular about summer humidity as long as it is less than the design value. It is this fact that makes the package or self-contained air conditioner practical. These units are factory engineered with psychrometric characteristics which meet most conditions of average application. In other words, the balance between the sensible and latent heat removing capacities is such that if they are selected for their sensible capacity, they will have at least enough and probably more latent capacity than is needed. If the latter is the case, the room will balance out at a slightly lower relative humidity than was intended by design. We usually do not object to this on a small job. In a large job, however, this might possibly mean more refrigeration capacity and higher operating cost than the design intended and so must be checked carefully. In our opening statement we quoted a rule-of-thumb about air conditioning requiring 400 CFM per ton. This value is usually the basis for rating self-contained air conditioners. Thus, we have a 2-ton unit handling 800 CFM, a 3-ton 1,200, a 5-ton 2,000, a 10-ton 4,000, etc. With 80 F DB 50% RH (77 gr/lb) air entering, these units usually will do about 70 percent sensible cooling and 30 percent latent cooling. On this basis, a 3-ton unit would do 36,000 Btuh total cooling, 25,200 Btuh sensible cooling and 10,800 Btuh latent cooling. With 400 CFM per ton, air would be cooled according to: T 2 - T 1 = 25,200/1,200 x 1.08 = 19.4 F and would leave the coil at 80 F - 19.4 F = 60.6 F. Air would be dehumidified according to: G 2 - G 1 = 10,800/1,200 x 0.68 = 13.2 grains and would leave the coil at 77-13.2 = 63.8 grains or 57 F WB.