Building Retro Commissioning Program (RCP) EAP 2015 Initiative 5 Building Energy System Retro Commissioning

Similar documents

Example Retrocommissioning Measure: Opening Throttled Discharge Valves

Energy Action Plan 2015

KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM

Printing and Publishing Energy Savings Guide

REAL OPERATING COST SAVINGS FROM RETRO- COMMISSIONING OPPORTUNITIES FOR SAVINGS IN ACADEMIC MEDICAL CENTERS

Impact of Control System Technologies on Industrial Energy Savings

for Plans Examiners and Building Inspectors

Scope of Work. See for resources available

Building Analytics Improve the efficiency, occupant comfort, and financial well-being of your building.

The Chilled Water and Hot Water Building Deferential Pressure Setpoint Calculation Chilled Water and Hot Water Pump Speed Control

UNIFIED FACILITIES GUIDE SPECIFICATIONS

HVAC Processes. Lecture 7

CONTROL STRATEGIES FOR HVAC SYSTEMS

Continuous Energy Management at UC San Diego. Anna Levitt, P.E. Assistant Energy Manager June 13, 2013

The main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building.

Commissioning - Construction Documents (Page 1 of 6)

IDEA Presentation SMALL CAMPUS CHILLED WATER PLANT OPTIMIZATION.

Wireless Pneumatic Thermostat Technology Demonstration Test. Los Angeles Unified School District 333 S. Beaudry Ave.

Using Time-of-Day Scheduling To Save Energy

Rev. No. 0 January 5, 2009

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES

Building Performance With District Cooling

HVAC Simplified Approach Option

Fundamentals of HVAC Control Systems

Variable Air Volume - VAV

Riverside City College. Math & Science Building HVAC Investigation. May 23, 2013

Applying Pressure Independent Control Valves in H.V.A.C. Systems. A Presentation to: Orange Empire ASHRAE Santa Ana Nov. 17, 2009

SECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION

Cornell University Chilled Water Best Management Practices Program

OEH Energy Efficient HVAC for Business Training Course

Enclosed Football Stadium Design History and Lessons Learned

Automated Commissioning for Energy (ACE) Platform for Large Retail Property. Overview

SAM HOUSTON STATE UNIVERSITY

SUCCESS STORY ENERGY TO CARE UF HEALTH SHANDS VISTA REHAB & UF HEALTH SHANDS CANCER HOSPITAL (SOUTH TOWER)

Case Study. Crown Melbourne & BUENO Systems: Energy and Operational Savings Across a Multi-Use Entertainment Complex.

ENERGY AUDITS AND RETRO- COMMISSIONING Local Law 87

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) March

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Sample - Existing Building Commissioning Plan

Modeling and Simulation of HVAC Faulty Operations and Performance Degradation due to Maintenance Issues

Collaborative Laboratory Commissioning and Sustaining the Optimal Building. By E. Lon Brightbill, P.E Facility Dynamics

Central Plant Air Systems: Keeping the Heart and. Title Style. Better Buildings Summit May 2016

Texas A&M University. usa.siemens.com/tamu

The District Energy Manager and Classroom Heating

COMPARATIVE LIFE-CYCLE ANALYSIS OF ENERGY-EFFICIENCY MEASURES AT TVA S CHATTANOOGA OFFICE COMPLEX: PHASE II RESULTS & FINAL DESIGN

CHAPTER 8 HVAC (Heating, Ventilation, and Air-Conditioning)

Energy Design Resources Commissioning Plan Outline Template

Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues

Using Building Energy Management Systems (BEMS) Best Practice for Energy and Carbon Savings.

ALBUQUERQUE PUBLIC SCHOOLS Facility Design & Construction / Maintenance & Operations

Venice Library Humidity Study. for Williams Building Diagnostics, LLC th Street West Bradenton, FL Report April 13, 2015

HVAC Checklist - Long Form

Bring the fresh in. Dedicated Outside Air Systems

for K-12 School Buildings

The Business Case Annual fuel cost savings of 26% worth more than 28,000 Annual fuel savings of 1.3million kwh Annual CO2 savings of over 245 tonnes

5.6 Technical Specification: Premium Efficiency Electric Air Conditioning Equipment

ENHANCED LABORATORY HVAC SYSTEM

HVAC Systems in Schools & Commercial Buildings and Radon

A. The Commissioning Authority (CxA) has been contracted or will be contracted directly with the Owner for this project.

Outline. CC objectives Site and building description Typical data floor overview CC measures Results Lessons learned

Company name Date submitted. Building address City State ZIP. * Building Sq. Ft.

2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT

Sustainable Smart Laboratories

RFI Response RFP: HSCG88-16-R-PQQ015 Replace HVAC Bldg A & C San Diego, CA.

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP

Data Center Energy Profiler Questions Checklist

Air Conditioning. The opportunity for energy efficiency. Low cost actions to reduce energy usage now

Pilot Program Description: Building EMIS

J O U R N A L. Energy Performance for. Proper Specification of Air Terminal Units Future Climate Impacts on Building Design

Case Study. Redmond Middle School: Advanced Analytics to Detect Energy Waste in HVAC System

PDATED: NOV Durham College. Conservation and Demand Management Plan

ASHRAE Level I Energy Audit June 2011

Commissioning for Performance in Critical Healthcare Environments

Optimizing BAS Information for Operator Effectiveness and Optimal Control

HVAC Systems: Overview

Communicating Thermostats. Add More Flexibility to Building Automation with New. Communicating Thermostats

C-Bus Application Messages & Behaviour Chapter 25 Air Conditioning

newsletter engineers energy-saving strategies for Water-Source Heat Pump Systems volume 36 2 providing insights for today s hvac system designer

THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS.

Building Energy Systems. - HVAC: Heating, Distribution -

STRATEGIC ENERGY MANAGEMENT PLAN ENGLEHART AND DISTRICT HOSPITAL

Building Diagnostic Market Deployment Final Report

Automated Demand Response Using OpenADR

Introduction to Building Automation Systems (BAS)

ULTRA-EFFICIENT HVAC DESIGN AND CONTROL

Continuous Commissioning of the Dallas/Fort Worth International Airport

Bells and Whistles, or Just Plain Effective? The New Generation of Wireless Controls in Existing Commercial Buildings.

Attached is a link to student educational curriculum on plug load that provides additional information and an example of how to estimate plug load:

AUDITING (WITH) BAS AEE-NY APRIL 2015

Fan Applications & System Guide

Green Buildings Guidelines for Harvard

Glossary of Heating, Ventilation and Air Conditioning Terms

HOT & COLD. Basic Thermodynamics and Large Building Heating and Cooling

Florida Power & Light Company. Business Heating Ventilation & Air Conditioning ( HVAC ) Program Standards. Effective: November 9, 2015

Description of cumulative (since initial certification) DOE-2.2 version 44d3 Bugfixes that Affect Title 24 Analysis:

Training for Building Technicians: Energy Efficiency & Sustainability (BEST) Program. Seminar Outline & Sample BEST Exam Questions

Transactive Controls: Market-Based GridWise TM Controls for Building Systems

Chapter-5 Introduction to Building Automation System (BAS)

Controller Operator Guide. VariTrac TM Central Control Panel VAV-SVU01A-EN

Transcription:

EAP 2015 Initiative 5 Building Energy System Retro Commissioning Strategy Optimize efficiency of building automation, heating ventilation and air conditioning (HVAC), mechanical, and electrical systems. The primary focus is to optimize building energy consuming systems and ensure efficient operation of both building systems and campus distribution/delivery systems, while effectively and efficiently meeting customer needs. Tactic Objective 5.1: Test and optimize building chillers, boilers, and HVAC system reliability and operating efficiencies. Objective 5.2: Raise awareness of retro commissioning and system optimization process and educate others about the benefits, while obtaining input and support to identify needs and ensure needs are met. Objective 5.3: Report on building energy consumption and cost, before, during, and after retro commissioning process to raise awareness of opportunities and results achieved. 1

99 buildings since 2002 13.8 Million Square Feet 1992 Campus EUI was 364mBtu/gsf 2012 at 214 mbtu/gsf 2015 goal is 190 mbtu/gsf Integral component of EAP 2015 Focus on: Safety Comfort Meeting customer needs Energy consumption and cost reduction 2

3000000 RC Annual Square Footage 2500000 2000000 Square Feet 1500000 1000000 500000 0 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 3

Retro Commissioning Square Feet per Year 2002 943,849 2003 1,664,814 2004 919,784 2005 401,340 2006 2,481,077 2007 795,429 2008 1,997,701 2009 1,689,246 2010 115,797 2011 0 (Energy Steward Pilot) 2012 2,821,088 Total 13,830,125 sq.ft. Average 1,257,284 sq.ft./yr 4

Retro Commission building selection based on input from several areas: Data Analysis Team Building Automation Team Facilities Services Energy Stewards Historical Work Orders 5

Prior to Retro Commissioning a building or group of buildings, we compare the Energy Use Index (EUI) measured in mbtu/gsf and the Energy Cost Index (ECI) measured in $/GSF of each building with prior year consumption and peer buildings, to identify potential opportunities. This analysis requires access to metered energy consumption and cost data for prior 12 to 36 months. Once this benchmarking analysis is complete, buildings to be commissioned are selected and prioritized on Retro Commissioning Priority List (RCPL). 6

Identify specific, itemized Energy Consumption Reduction Measures (ECRM) recommendations (including payback calculations) in a document called the Retro Commissioning Plan (RCP) Recommendations are derived using both the original building specifications (design intent) together with changes in building use with latest design standards. Standard operational items are quickly corrected, such as: Over Ridden Points Systems in Hand, rather than Auto Unnecessary preheat cooling reheat Valves & Dampers not controlling Over Ridden Schedules 7

The RCP records occupant requirements for the building and any recommended change to the building design intent. Improvements and enhancement recommendations are reviewed and approved before implementation. The RCP includes a list of action items recommended for implementation with a proposed schedule, estimated cost and simple payback calculations. Operations and Maintenance (O&M) improvements are identified in the RCP and work orders are sent to Facilities Services (FS) for correction. Metered building consumption data and cost, both before and after the RC process, is documented. 8

A Final Retro Commissioning Report (FRCR) is created that documents: EUI & ECI before and after Retro Commissioning Problems found & corrected Additional ECRM s requiring additional funding or resources along with estimated cost and pay back The report documents all work performed, as well as methods, criteria, and results of testing, measuring, and evaluation performed on building systems. The FRCR documents mechanical, electrical, HVAC and control systems and sequence of operations prior to RC, as compared to a post RC assessment. 9

# Type Observation Recommendation Quick Hit 1 Optimization AHUs O, S, and D serve offices, seminar rooms and dining areas, were running 24/7 Implement shutdown or setback schedule 2 Optimization At the time of investigation, the CHW loop DP setpoint was overridden at 18 psi and AHUs CHW valves position was less than 50%. Determine cause for operator override and release the return the setpoint to automatic control. Further Optimize the CHW loop DP reset schedule limits using coil design data. 3 Deficiency CHW loop DP was calculated by CHWST- CHWRT in PPCL program Fix CHW loop DP calculation formula 4 Optimization Existing return valve control sequence will modulate return valve to maintain loop DP when two pumps were running at minimum speed Optimize return valve and pump control sequence 10

5 Deficiency HHW loop DP sensor was failed and HHW pump was 100% speed Fix HHW loop pressure sensors 6 Optimization Preheat valve of AHUL3 was overridden at 100% open Release preheat valve control of AHUL3 7 Optimization Pump room temperature was 72 F Calibrate FCU thermostat and set room temperature at 80 F 8 Optimization Preheat setpoint was fixed at 55 F Optimize the preheat setpoint for all units 9 Optimization Energy recovery valve was modulated to maintain supply air temperature at its setpoint. Once CHW valve or preheat valve leaks by, the energy recovery valve may fully closed Optimize Energy recovery valve control sequence 10 Deficiency AHU L1 and L2 DAT sensors were out of calibration Calibrate DAT sensors for these two AHUs 11

11 Optimization Discharge static pressure setpoint was no reset Implement Static Pressure SP reset schedule for AHUs 12 Optimization Discharge air temperature setpoint was reset only according to outside air temperature Improve discharge air temperate reset schedule 13 Optimization Economizer control sequence of non-lab AHUs were reversed Improve economizer control sequence for nonlab AHUs 14 Optimization Both preheat valve and CHW valve control loops for two AHUs (B, O) were using same discharge air temperature sensor as input to maintain setpoint. This may cause the preheat valve to open to preheat air when CHW leaks by. Use preheat temperature sensor to control preheat valve 15 Optimization There are about 15% TECs minimum air flow ratio is higher than 30% Optimize TEC minimum air flow 12

16 Optimization Only 8 terminal boxes with minimum airflow setback to zero during Un-OCC mode. The majority of terminal boxes had no minimum air flow setback during Un-OCC. Reset the minimum airflow to zero during Un- OCC mode 17 Optimization Only six labs (RM221, 224, 220, 230C, 236,230) with implemented UN-OCC setbacks; the other 80 lab ventilation controllers did not have implement setback schedules Some labs minimum ACH was 10. Implement room temperature and ventilation setback schedule for labs 18 Deficiency Three exhaust air static pressure sensors were out of calibration. Calibrate exhaust air static pressure sensors 19 Optimization All of the three lab exhaust fans were overridden at 100% speed Once the exhaust air static sensors are calibrated, releasing exhausts fan speed. 20 Optimization The switch station room temperature was only 69 F Change the room temperature setpoint to 80 F 21 Deficiency Occupancy sensors cannot control the lighting in classroom 107 and 108 Fix the lighting control problem 13

Discussion 14