CITY OF MOUNT DORA LIFT STATION STANDBY POWER GENERATOR SYSTEM Minimum Specifications

Similar documents
Diesel Engine Driven Generators Page 1 of 6

32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 113 kva, 90 kw 124 kva, 99 kw 6WDQGE\ 114 kva, 91 kw 125 kva, 100 kw

DLW 8. POWER RATING 1500 rpm/50 Hz 1800 rpm/60 Hz Prime 7.5 kva, 6 kw 9.1 kva, 7.3 kw Standby 8.5 kva, 6.8 kw 10.1 kva, 8.1 kw

Magnum Mobile Generator MMG55 Specifications

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

Annex-A TECHNICAL SPECIFICATION

P 602. This generator set has been designed to meet ISO 8528 regulation. This generator set is manufactured in facilities certified to ISO 9001.

32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 10.4 kva, 8.3 kw 12.9 kva, 10.3 kw 6WDQGE\ 11.3 kva, 9 kw 14.4 kva, 11.5 kw

Medical Air Systems: Scroll

Fire Pump Plan Review March 2010

Commercial Gas Furnace Upflow

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

SECTION HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT

STANDBY 320 ekw 400 kva 50 Hz 1500 rpm 400 Volts

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

ELECTRIC/DIESEL FIRE PUMP CHECK LIST

Spark-ignited generator set

Standby Generators FEATURES. Standby Generators Liquid-Cooled Gas Engine. Standby Generators INCLUDES:

GEP550 (3-Phase) 50 HZ. 500 kva / 400 kw FEATURES. Exclusively from your Caterpillar dealer

LAKE COUNTY ANIMAL SERVICES EXPANSION SECTION 15459

XQ20 RENTAL. 60 Hz. Voltage kw (kva) kw (kva) 208/120V 3 PH 20 (25) 18 (22.5) 480/277V 3 PH 20 (25) 18 (22.5) 240/120V 1 PH 17 (17) 16 (16)

Sample - No Commercial Use

TECHNICAL DATA 50HZ MPMC POWERTECH CORP. DIESEL GENERATING SET

DIESEL GENERATOR SETS

SELECTION, APPLICATION AND MAINTENANCE

Frequently Asked Questions Generators

AGP15 Perkins Series Gen Set Stand-by Specification Sheet Stand by Rating - 15KW (20KVA) Continuous Rating 13KW(18KVA) 60HZ

Atlas Copco Generators

ENGINE COOLING SYSTEM

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling

STANDBY 40 ekw 40 kva PRIME 36 ekw 36 kva

STANDBY 150 ekw 188 kva PRIME 135 ekw 169 kva

DIESEL GENERATOR SET. 60 Hz FEATURES GENERATOR SET

DIESEL FEATURES GENERATOR SET. FUEL/EMISSIONS STRATEGY Low fuel consumption

C18 ACERT Fire Pump Tier bkw/ rpm

FTA1100-J DIESEL ENGINE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE

WHOLESALE DIRECT INC WEST 65TH STREET

STANDBY 800 ekw 1000kVA 60 Hz 1800rpm 480Volts

MAC-120HE-01 Air-Cooled Chiller

SECTION AIR CONDITIONING UNIT

Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank

Diesel Generating Set

For Models #6-5001, #6-7501, # & #10-12K1

G26 Corp L11 Revised LENNOXOEMPARTS.COM. Service Literature G26 SERIES UNITS

TECHNICAL GUIDE 95.5% SINGLE STAGE GAS-FIRED RESIDENTIAL MULTI-POSITION GAS FURNACES MODELS: TG9S DESCRIPTION FEATURES

Prime Power Services, Inc. Georgia, Carolinas NFPA 110 Standards for Emergency & Stand by Generators June 1, 2010

A. Section includes air conditioning units, controls and control panels.

THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS.

TECHNICAL DATA 60HZ MPMC POWERTECH CORP. DIESEL GENERATING SET

SECTION STANDBY GENERATOR TESTING AND COMMISSIONING

MAINTENANCE INSTRUCTIONS. Thermia Robust heat pump

Pump Specifications 405 Series Commercial Drain Pump (High-Temp) 2 Solids handling

Model 1210C Battery Powered Pump Shown. Description

HOUSTON COUNTY BOARD OF COMMISSIONERS PURCHASING DEPARTMENT

How To Use A Cat Diesel Engine

BLADDER SURGE CONTROL SYSTEM

STANDBY 2500 ekw 3125 kva 60 Hz 1800 rpm 480 Volts

EMERGENCY AND STANDBY POWER SYSTEMS

DIESEL GENERATOR SET FEATURES. FUEL/EMISSIONS STRATEGY Low Fuel consumption

FAIRBANKS NIJHUIS FIRE PUMPS.

SECTION MORTUARY REFRIGERATORS

CAT NEXT GENERATION DIESEL GENERATOR SETS. C15 ACERT and C18 ACERT kva / ekw

Service manual. Website: CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

Ceiling Mount Air Handler Manual

Mechanical Rooftop Custom Capabilities

STANDBY 1500 ekw 1875 kva 60 Hz 1800 rpm 480 Volts

LOAD BANK TESTING PROCEDURE

Element D Services Plumbing

3620 W 11th Streetб Houston, TX Telephone: sales@kellogg-american.com Website:

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A

Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments

D Youville College July 31, 2008 New Academic Building Cannon Design Project No

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

Element D Services Plumbing

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

Explosion-Proof Electric Unit Heaters

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT

BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET

3516 Industrial Engine

Installation Instructions for Alarm Module Kit A043F059

SunMaxx Solar Filling Station Operating Instructions

Commercial Gas Water Heaters

Low Profile Unit Cooler

HR Heated HB Blower. Smart Solutions for Drying Compressed Air. Dual Tower Heat Reactivated Desiccant Air Dryer

Industrial Generator Set Accessories

Trouble Shooting. Pump

NFPA31FuelOilPiping 1 Revised

48/50EJ,EK,EW,EY038, 044, 048 SINGLE-PACKAGE COOLING UNITS VARIABLE VOLUME CONSTANT VOLUME FACTORY-INSTALLED OPTIONAL HEAT

C. Burner management system to follow requirements of Industrial Risk Insurers (IRI).

Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

Compressor Service & Maintenance Manual

Note: This information obtained from internet sources and not verified- use at your own risk!!!!

The kva RAnge

FAIRBANKS NIJHUIS PACKAGED FIRE PUMP SYSTEMS.

Industrial Generator Set Accessories

INDUSTRIAL POWER GENERATION EQUIPMENT Typhoon SGT MW / 5340 KVA 50Hz 11KV Duel Fuel Power Station

ASME Packaged Indirect Fired Water Heater

Transcription:

CITY OF MOUNT DORA LIFT STATION STANDBY POWER GENERATOR SYSTEM Minimum Specifications 46.6.1 GENERAL A standby power generator system shall be provided at all wastewater pumping stations. The generator system shall be sized to allow simultaneous operation of all pumps provided for the pump station. Generator sizing shall be based on across-the-line starting for all motors 50 H.P. and less. For motors larger than 50 H.P., the use of reduced voltage starting devices will be considered by the City on an individual basis. 46.6.2 GENERATOR SET 46.6.2.1 GENERAL The generator set shall consist of a diesel or LP gas engine directly coupled to an electric generator, together with the necessary controls and accessories to provide continuous electric power to the pump station for the minimum duration of a 24 hour failure of the normal power supply. At a pre-design meeting, the City will notify the Developer as to whether the system will utilize a diesel or LP gas engine driven unit. The selection of engine type shall be at the sole discretion of the City. A complete engine generator system shall be furnished and installed with fuel storage and transfer systems, battery, battery charger, muffler, radiator, control panel, enclosure, remotely mounted automatic transfer switch (part of the control panel), and all other accessories required for an operational system. All materials and parts of the generator set shall be new and unused. Each component shall be of current manufacture from a firm regularly engaged in the production of such equipment. The set shall be of a standard model in regular production at the manufacturer s place of business. Units and components offered under the Specifications shall be covered by the manufacturer s standard warranty on new machines. 46.6.2.2 REQUIREMENTS The emergency generator set and accessories shall be of a type that complies with the latest edition of the National Electrical Code and all applicable State and local building codes. The material and workmanship used in the manufacture of this 1

equipment shall be of the highest quality consistent with the current standards for like equipment, and the equipment shall be manufactured in such a manner so as to conform to the latest applicable IEEE, ANSI, ISA, NEMA, and EEIA Standards. The equipment suppliers shall be liable for any latent defects due to faulty materials or workmanship in the equipment which may appear within one (1) year from the date of equipment start-up. 46.6.2.3 TESTS Equipment shall be completely assembled and tested at the factory prior to shipment. Certified copies of the data obtained during these tests shall be submitted to the City. Final tests shall be conducted at the site, after installation has been completed, in the presence of the City s representative. The emergency generator manufacturer shall furnish a service representative to operate the engine during the tests, to check all details of the installation and to instruct the City s representatives in proper equipment operation. Field tests shall include operating the generator set for eight (8) hours, carrying normal pump station loads. The Developer shall refill the main fuel tank at the completion of the tests. 46.6.2.4 RATINGS The rating of the generator shall be shown on the Drawings. These ratings must be substantiated by the manufacturer s standard published curves. Special ratings shall not be acceptable. The set shall be capable of supplying the specified usable KW for the specified duration, including the power required for the pump startup, without exceeding its safe operating temperature. 46.6.2.5 ENGINES Each diesel engine shall be a water-cooled, four-stroke cycle, compression-ignition unit. It shall meet performance specifications when operating on No. 2 domestic burner oil. Each LP gas engine shall be a spark-ignited, 4-cycle, water-cooled engine with natural aspiration. The LP gas engine shall meet performance requirements using commercially available LP gas. The engine and generator shall be torsionally compatible to prevent damage to either engine or generator. An engine instrument panel shall be installed on the generator set 2

in an approved location. The panel shall include oil and fuel pressure and water temperature gauges. A mechanically driven engine hour meter shall also be provided. The engine governor shall be of the isochronous electronic type. Frequency regulation shall not exceed plus/minus 0.25% under steady state conditions. The engine shall start and assume its rated load within 10 seconds, including transfer time. 46.6.2.6 GENERATOR The generator shall be three-phase, 60 hertz, single bearing, synchronous type, built to NEMA Standards. Epoxy impregnated Class F insulation shall be used on the stator and the rotor. The excitation system shall employ a generator-mounted volts-perhertz type regulator. Voltage regulation shall be plus/minus 2% from no load to full load. Readily accessible voltage drop, voltage level and voltage gain controls shall be provided. Voltage level adjustment shall be a minimum of plus/minus 5%. 46.6.2.7 ENGINE GENERATOR CONTROL PANEL A generator mounted NEMA 3R type 304, vibration isolated, 14 gage stainless steel control panel shall be provided. Panel shall contain, but not be limited to, the following equipment: Control Equipment: Control equipment shall consist of all necessary exciter control equipment, generator voltage regulators, voltage adjusting rheostat, and speed control equipment and automatic starting controls, as required to satisfactorily control the engine/generator set. In addition, an automatic safety shut down shall be provided for low oil pressure and/or high temperature conditions in the engine. An emergency shut down lever switch shall be provided on the air intake. Metering Equipment: Metering equipment shall include 3-1/2 inch meters (dial or digital type frequency meter, 2 percent accuracy voltmeter, and ammeter and ammeter-voltmeter phase selector switch). The control panel shall also include the engine water temperature, oil pressure and hour meter. Fault Indicators: Individual press-to-test fault indicator lights for low oil pressure, high water temperature, low water level, overspeed, overcrank, and, if applicable, for day tank high and low fuel level shall be provided. 3

Function Switch: A four-position function switch marked Auto, Manual, Off/Reset, and Stop shall be provided. 46.6.2.8 BATTERY CHARGER The battery charger shall be so designed that it will not be damaged and will not trip its circuit protective device during engine cranking, or it shall be automatically disconnected from the battery during cranking period. The charger shall be mounted in the emergency generator control panel. The charger shall have a 7 day/24 hour timer control. 46.6.2.9 BATTERY The battery shall be lead-acid type with sufficient capacity to provide 90 seconds total cranking time without recharging. The battery shall be adequately rated for the specific generator set. The battery shall be encased in hard rubber or plastic and shall be furnished with proper cables and connectors, together with rack and standard maintenance accessories. The battery shall be provided with a 48-month warranty for the replacement of the battery if found to be defective. 46.6.2.10 MOUNTING A suitable number of spring-type vibration isolators with a noise isolation pad shall be provided to support the set and its liquids. 46.6.2.11 UTILITY CONNECTIONS All connections to the generator set shall be flexible. 46.6.2.12 COOLING SYSTEM The generator set shall be equipped with an engine mounted radiator sized to maintain safe operation at 110 degree F maximum ambient at the pump station altitude. A blower type fan shall be used directing the air flow from the engine through the radiator. The entire cooling system shall be filled with 50% glycol-water solution. 46.6.2.13 FUEL SYSTEM Generator sets using diesel engines shall be furnished with a double-walled fuel storage tank sized to allow at least 24 hours of generator operation at full load. The tank shall be factory installed 4

in the generator set skid base and equipped with engine supply and return lines and all necessary valves and filters. The diesel fuel storage tank shall be U.L. listed and shall comply with Federal, State and local regulations pertaining to such tanks. For generator sets using LP gas engines, a separate LP gas storage tank shall be provided with a suitable concrete base. The tank shall be ASME and AGA rated and sized to allow at least 24 hours of generator operation at full load. 46.6.2.14 EXHAUST SYSTEM The generator set supplier shall provide a critical-type silencer, with flexible exhaust fittings, properly sized and installed, according to the manufacturer s recommendation. The silencer shall be mounted so that its weight is not supported by the engine. Exhaust pipe size shall be sufficient to ensure that measured exhaust back pressure does not exceed the maximum limitations specified by the generator set manufacturer. The exhaust system shall include a flexible, seamless, stainless steel connection between the engine exhaust outlet and the rest of the exhaust system. The exhaust system shall be a part of the generator enclosure. 46.6.2.15 WEATHERPROOF ENCLOSURE The enclosure and all other items shall be designed and built by generator set manufacturer as an integral part of the entire generator set and shall be designed to perform without overheating in the ambient temperature specified. The enclosure shall be constructed of 14 or 16 gauge sheet metal suitably reinforced to be vibration free in the operating mode. Four hinged doors shall be provided to allow complete access without their removal. Each door shall have at least two hatch-bearing points. Side and rear panels shall be completely and simply removable for major service access. Roof shall be peaked to allow drainage of rain water. A baked enamel finish, with primer and finish coat, shall be applied to the enclosure before assembly. All fasteners shall be rust resistant. The enclosure shall have sufficient guards to prevent entrance by small animals and padlocks shall be provided. Batteries shall be designed to fit inside enclosure and alongside the engine. Batteries under the generator are not acceptable. The enclosure shall have coolant and oil drains outside the unit to 5

facilitate maintenance. Each drain line shall have a stainless steel valve located near the fluid source. The diesel unit s fuel filter shall be inside the base perimeter and located so spilled fuel cannot fall on hot parts of engine or generator. A cleanable primary fuel strainer shall be used to collect water and sediment between tank and main engine fuel filter. Crankcase fume disposal shall terminate in front of the radiator to prevent oil from collecting on the radiator core and reducing cooling capacity. 46.6.2.16 AUTOMATIC TRANSFER SWITCH A 4-pole automatic transfer switch shall be part of the control panel furnished for the pump station. The transfer switch shall be provided with the following features: Complete protection, close differential voltage sensing relays monitoring all three phases (pick-up set for 95% of nominal voltage, drop-out set for 85% nominal voltage). Voltage sensing relay on emergency source (pick-up set for 95% of nominal frequency). Time delay on engine starting adjustable from 1 second to 300 seconds (factory set at 3 seconds). Time delay normal to emergency transfer adjustable from zero seconds to 300 seconds (factory set at 1 second). The Developer shall request time delay setting in accordance with the priority rating or their respective loads. Time delay emergency to normal transfer adjustable 30 seconds to 30 minutes (factory set at 5 minutes), and time delay bypass switch shall be provided on door of the switch cabinet. Unload running time delay for emergency engine generator cooling down adjustable from 0 to 5 minutes (factory set at 5 minutes) unless the engine generator control panel includes the cool down timer. 46.6.2.17 WARRANTY Products shall be guaranteed by manufacturer to be free from defects in material and workmanship under normal use and service 6

for a period of one (1) year after start-up. A two-year 20% maintenance bond, posted by the developer, shall also cover all dedicated improvements. 7