DEMAND COOLING FOR COPELAND STREAM COMPRESSORS

Similar documents
Technical Information

Why and How we Use Capacity Control

Technical Information

*.ppt 11/2/ :48 PM 1

MP-4000 Alarm List (Software version or later)

, User s Manual

Failure code manual. content

Skills Canada National Competition Instructions and Competition Details 38 Refrigeration and Air Conditioning / Post - Secondary May 27-30,

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

AE R6 December Digital Capacity Control for Copeland Scroll Refrigeration Compressors AE R6

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

OPL BASIC. Dosing System for Professional Laundry machines. Contents

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

Compressors, Chillers & Condensers

Application Engineering

HENRY TECHNOLOGIES - OIL LEVEL REGULATORS (CONVENTIONAL)

A/C refrigerant system, overview

Service Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTM3-SF-1. Split System Cooling 4TTM3018-4TTM3060

Phone: Fax: Web: info@clrwtr.com

REFRIGERATED TYPE COMPRESSED AIR DRYERS INSTRUCTION MANUAL. For Sales & Service please contact:

INSTALLATION MANUAL INSIDE ENGINE COMPARTMENT ZZT22#R (1ZZ-FE / 3ZZ-FE) / AZT220R (1AZ-FE) FOR EUROPEAN SPEC. AIR CONDITIONING ENGLISH.

ECOCIAT. Domestic hot water heat recovery unit

Duct Humidity Transmitter

SELECTION, APPLICATION AND MAINTENANCE

ice 3 FLUID TO FLUID HEAT PUMP

3. SEISCO PARTS & SERVICE REMOVAL AND REPAIR GUIDE

INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX

DESIGN STANDARDS SECTION

EC3-D72 Superheat & Digital Scroll Controller Technical Data

MAC-120HE-01 Air-Cooled Chiller

Geothermal Alliance of Illinois. TXVs Theory and Fundamentals John Haug Senior Application Engineer Emerson Climate Technologies - Flow Controls

THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS.

with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.

LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems

Cooling system components, removing and installing

MDT5N25 & MTD5N40 SERVICE PARTS

Table Z. Troubleshooting Chart for Air Conditioners. Cause

Refrigeration Basics 101. By: Eric Nelson

Service Guide 12/27/03 TESTING, SERVICE & REPAIR GUIDE (For SH Space Heating Models & RA Water Heating Models)

Chapter 5. Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit

Hoshizaki America, Inc.

REMOVAL AND INSTALLATION

The Child Reminder System Installation Manual

Before installation it is important to know what parts you have and what the capabilities of these parts are.

TMS TANK MANAGEMENT SYSTEM


XL PREMIUM OIL COOLER KIT

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL AW64AL /05

POLICY BULLETIN Tecumseh Compressor Company Compressor Group

Application Engineering

SERVICE MANUAL REFRIGERATION

Volkswagen Golf > VW Rabbit GTI 2006->

PANASONIC TROUBLE SHOOTING GUIDE

Refrigeration System Installation & Operation Manual


TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin Inch PowerVent LED Indicator Explanations & Troubleshooting Table

SYSTEM 4C. C R H Electronics Design

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.

NO-FROST CUSTOMER SUPPORT INFORMATION INFORMATION ON THE NO-FROST TECHNOLOGY WHITE GOODS

SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS

FUEL-16, Troubleshooting Fuel Supply Problems

WALL MOUNTED PACKAGE HEAT PUMPS REPLACEMENT PARTS MANUAL WH483 WH602. Contents. General Notes. Important. Description

Oil and Coolant Circulating Heating System. Model - OCSM

Section 7. Evaporator thermistor. Under-and-over pressure safety switches. Connections to the ECU

I nstallation. M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications. Tools Needed.

Heat. Investigating the function of the expansion valve of the heat pump. LD Physics Leaflets P Thermodynamic cycle Heat pump

SERVICE MANUAL. Room Air Conditioner Multi Split type Outdoor unit /R410A DC Inverter/

SERVICE MANUAL REFRIGERATION

OASIS SERVICE & TROUBLESHOOTING MANUAL (WITH DM10 OR DM12)

Models: WA182, WA242. Contents. Cabinet Components. Functional Components " Exploded View... 3 " Usage List Control Panel.

PSR The compact range Description

Applied Electronics. Commercial Dimming System UPDATE NOTICE

ABC-1000 Automatic Boiler Level Controller Operation and Installation Manual

ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE

Service manual. Website: CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

E2 Series Electric Furnaces

HPC Radiator Fan Control Module with Sensor PN:

Test Code: 8297 / Version 1

SHOWER WATER HEATER MODEL BS 35 / 45 / 60 BS 35 E / 45 E / 60 E OPERATION AND INSTALLATION INSTRUCTIONS

Air conditioning, electrical testing

SERVICE MANUAL FOR 12 VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOF TOP UNITS ONLY

User Manual. Air-conditioner Controller SB-DN-HVAC (MAC01.331)

SYSTEM 45. C R H Electronics Design

INSTALLATION AND MAINTENANCE INSTRUCTIONS 4AC16LT SERIES. Split System Air Conditioner. Save these instructions for future reference WARNING

TECHNICAL SUPPORT MANUAL 3 Phase Air Conditioner Component R2A3**GHR

MAINTENANCE INSTRUCTIONS. Thermia Robust heat pump

LS-1 Series Tungsten Halogen Light Sources Installation and Operation Instructions

TYPE 65UV CEX Integrated Flame Scanner with Internal Flame Relay and Analog Output

Models: Contents. Cabinet Components. Functional Components " Exploded View... 3 " Usage List Control Panel. Blower Housing

Electronic Control Devices The European Product Catalogue 2007

INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL

ELECTRONIC THERMOSTAT AND THERMOMETER With SPEED CONTROL

Digi-Motor Installation Guide

Thermo Top - Troubleshooting Tree

evo+ Installation, Service & Troubleshooting DUCTLESS SYSTEM

VIBRATION MONITORING OF FANS INSTALLED IN ROAD TUNNELS

Cold Room & Refrigeration System (Casserole Assembly) No of units: 1

Transcription:

Date of last update: Jul-15 Ref: D7.19.2/1113-0715/E Application Engineering Europe DEMAND COOLING FOR COPELAND STREAM COMPRESSORS WITH DEMAND COOLING DRIVER (XEV01D) Demand Cooling for Copeland Stream Compressors with Demand Cooling Driver (XEV01D)... 1 1 Introduction... 2 2 Demand Cooling operation... 2 3 Components... 2 3.1 Temperature sensor... 2 3.2 Injection valve kit... 3 3.3 Demand Cooling driver (XEV01D)... 4 3.3.1 Technical data... 4 3.3.2 Driver electrical connections... 5 3.3.3 Driver installation... 5 4 Demand Cooling application... 5 4.1 Reducing the demand for injected cooling... 5 4.2 Demand Cooling operation set points... 6 4.2.1 Liquid injection control... 6 4.2.2 Modulating output for Demand Cooling... 6 4.2.3 High temperature alarm... 6 4.2.4 Low temperature alarm... 6 5 Demand Cooling installation... 7 5.1 Temperature sensor... 7 5.2 Injection valve parts... 7 5.3 Installation procedure... 7 5.4 Installation of Demand Cooling on 4M* Stream compressors... 8 5.5 Installation of Demand Cooling on 6M* Stream compressors... 9 5.6 Use of inverter... 9 5.7 Demand Cooling wiring diagram... 10 6 Functional checks... 11 6.1 Checking the NTC Thermistor sensor... 11 6.2 Checking the driver... 11 6.2.1 Test n 1... 12 6.2.2 Test n 2... 12 D7.19.2/1113-0715/E 1/12

1 Introduction Experience has shown that the R407 series of refrigerants and R22 can cause problems in low temperature applications because under some conditions the internal compressor discharge temperature exceeds the safe temperature limit for long term stability of refrigeration oil. The Demand Cooling system uses modern electronics to provide an effective solution to this problem. It is required for low evaporating temperatures with R407A, R407F, R448A, R449A, and all R22 applications with saturated suction temperatures below -20 C (operating envelopes with Demand Cooling are available in Select Software). 2 Demand Cooling operation The Demand Cooling driver uses the signal of a discharge head temperature sensor to monitor discharge gas temperature. If a critical temperature is reached, the driver energizes a long life injection valve which meters a controlled amount of saturated refrigerant into the compressor suction cavity to cool the suction gas. To minimize the amount of refrigerant that has to be injected, the suction gas cooling process is performed after the gas has passed around and through the motor. This process controls the discharge temperature to a safe level. If, for some reason, the discharge temperature rises above a pre-set maximum level for 2 seconds, the CoreSense Diagnostics will switch the compressor off for 2 minutes before automatic resetting. 3 Components The Demand Cooling system consists of a temperature sensor, an injection expansion valve, the Demand Cooling driver, the tubing sight glass and filter drier, and mounting brackets. This system can be delivered as a variation together with the compressor or as a separate kit. 3.1 Temperature sensor The Copeland Demand Cooling system uses a Negative Temperature Coefficient (NTC) Thermistor (resistance drops on temperature rise) to give temperature signals to the driver. The resistance at ambient temperature (25 C) is 86,000 Ohms. Figure 1: Temperature sensor D7.19.2/1113-0715/E 2/12

3.2 Injection valve kit The injection valve was developed to operate under the usual voltage and ambient conditions plus withstand any vibration that can be expected from being mounted to a compressor. The injection valve kit comprises of the tubing, filter drier, mounting brackets, solenoid coil with PG9 cable gland. The parts are NOT pre-assembled for transport reasons. Injection valve kit for 4M* Injection valve kit for 6M* Figure 2: Injection valve kit parts The parts need to be assembled before installation as shown below. 1 7 4 7 3 1 2 3 6 4 7 5 6 Figure 3: Injection valve kits when assembled 5 D7.19.2/1113-0715/E 3/12

Designation 4M* 6M* 1 Demand Cooling expansion valve Alco EX2-100 2 Mounting bracket to mount the injection valve to the cylinder head 3 Head studs with washers to fasten mounting bracket to compressor 4 Sight glass Alco MIA M10 Alco MIA M10S 5 Filter drier Alco ADK 1610 MMS 6 Clamp for Demand Cooling fixing 7 Male flare union 3/8 -NPT to 3/8" 3.3 Demand Cooling driver (XEV01D) The XEV01D driver is designed for Demand Cooling applications. It is connected to a temperature sensor (see chapter 3.1). The driver has a digital output (relay) which is used for alarm indication and a modulating output (TRIAC type). There are also two configurable digital inputs, the first one is free of voltage and the other one is isolated in order to simplify connections with cooling request signal (high voltage input). The display enables to visualise the temperature value or the output percentage activation. To complete instrument equipment, a RS485 serial port allows connection of the driver to any modbus network. The Demand Cooling allows monitoring of the compressor head temperature (measured by a temperature sensor) and acts on a cold gas injection valve (through a TRIAC or a digital output) placed directly in the head, if the measured temperature is higher than a set value. Modulating is proportional and is based on the values read by the temperature sensor. The lower and upper temperature limits within which the gas injection inside the compressor head must be regulated, are defined by parameters LS and US. 3.3.1 Technical data Housing:... Self-extinguishing ABS Case:... 4 DIN modules 70x135mm with male and female connectors; depth 60 mm Mounting:... DIN RAIL mounted in an omega (3) din rail Protection:... IP20 Connections:... Screw terminal block 2.5 mm 2 wiring Power supply:... 230VAC ± 10% Power absorption: Depending on connected valve 20VA max Display:... 3.5 digits with icons, red LEDs, height 14.2 mm Inputs:... 1 temperature sensor: NTC86k probe: -40 to 180 C Digital inputs:... 1 free of voltage... 1 isolated (high voltage) TRIAC output:... Max 500W at 230VAC Data storage:... On the non-volatile memory (EEPROM) Operating temp:... 0 to 60 C Storage temp:... -25 to 60 C Relative humidity:. 20 to 85% (no condensing) D7.19.2/1113-0715/E 4/12

3.3.2 Driver electrical connections Figure 4 NOTE: Connect the injection valve directly to terminals 23 and 24. The XEV01D driver is able to issue the required power supply (by using the same power supply as input terminals 11 and 12). 3.3.3 Driver installation The driver XEV01D has to be installed inside the system control panel/electrical box. 4 Demand Cooling application The Demand Cooling system should be considered as the back-up for a well-designed low temperature refrigeration system. Normally the Demand Cooling valve only operates during high condensing temperature conditions. The refrigerant injected by the valve cools the compressor to operate safely. Due to the relatively small amounts of liquid injected, no excessive system pressure fluctuations (normally < 0.15 bar) occur during injection valve cycling. Compressor capacity and efficiency drops are almost insignificant since the suction gas is cooled by the liquid and becomes denser. This enables the compressor to handle the additional mass flow with a minimal loss of evaporator capacity. Performance data for Demand Cooling compressors include the effects of injection. They can therefore be used in the conventional manner for compressor and condenser selection. NOTE: Liquid subcooling must be sufficient at the Demand Cooling injection valve to prevent flashing. 4.1 Reducing the demand for injected cooling There are several methods to reduce Demand Cooling operation in order to optimize the energy efficiency. Suction lines should be well insulated to reduce suction line heat gain. Return gas superheat should be as low as possible but consistent with safe compressor operation. Evaporator and system control settings should provide the maximum suction pressure consistent with the application in order to have as low a compression ratio as possible. D7.19.2/1113-0715/E 5/12

The condensing temperature should be kept as low as possible to reduce the compression ratio as well as the discharge temperature. Otherwise condensers should be sized using conventional methods. The exact application range must be taken from Select Software. NOTE: A vertical cylinder head fan is always required for usage with R22 only! NOTE: Demand Cooling is not approved for compressors with capacity modulation. 4.2 Demand Cooling operation set points The Demand Cooling driver controls the liquid injection and also behaves as an alarm. 4.2.1 Liquid injection control Injection start: Sensor resistance < 2100 Ohms (T > 140 C); Demand Cooling On Injection stop: Sensor resistance > 2400 Ohms (T > 130 C); Demand Cooling Off 4.2.2 Modulating output for Demand Cooling If one of the digital inputs is set as onf, then the modulation will be enabled only if the related digital input signal is active. If temperature is below LS (130 C), the valve is always Off. If temperature is between LS (130 C) and US (140 C), the valve will be proportionally modulated (between 0 and 100%) with cycle time tdg. If temperature is higher than US (140 C), the valve is always On (or at 100% value). If temperature is lower than LS (130 C), the valve is always Off (or at 0% value). 4.2.3 High temperature alarm This process controls the discharge temperature to a safe level. If the compressor temperature sensor detects a discharge temperature higher than 154 C for 2 seconds, CoreSense Diagnostics will switch the compressor off until the temperature cools down to an acceptable level. Automatic resetting will occur after 2 minutes. The CoreSense module will trip by default (either trip or lockout alarm can be selected by user using the PC interface software). Trip alarm: Automatic reset after 2 minutes if discharge temp < 130 C. Lockout alarm: Manual reset is necessary. A sensor short circuit (low resistance value) will result in the same tripping. 4.2.4 Low temperature alarm Low temperature can occur if a compressor has been standing in a very cold environment for a long time. To avoid the triggering of an alarm in such a case, a time delay of 2 minutes is installed. The delay allows the discharge temperature to rise to a normal operating level. If the discharge temperature remains too low the module signals an open circuit. If the temperature sensor P2 measures a value lower than the one set in parameter ALL and if this condition persists for longer than the value set in parameter dll: General alarm LED and digital output set as alarm (oax=alr) will be activated. If a digital output is set as compressor output (oa1=cpr) this will be deactivated. Expansion control output will be deactivated. Buzzer will be activated (depending on the ben parameter). Alarm reset is manual by means of controller On-Off procedure. A sensor circuit cut ( infinite resistance value) will result in the same tripping. NOTE: In case of improper liquid feed (choked / dirty liquid line filter drier or poor pipe assembly / manufacturing) the EX2 valve will open trying to inject liquid until the CoreSense trips the compressor due to high temperature. D7.19.2/1113-0715/E 6/12

5 Demand Cooling installation NOTE: The injection expansion valve and module must be appropriate to voltage and frequency. Check that the Demand Cooling kit is complete before installation. The Demand Cooling kit is delivered with an Installation Manual. The various parts should be installed according to the Installation Manual for proper operation and warranty of the compressor. 5.1 Temperature sensor The Demand Cooling sensor must be installed into the left head looking from oil pump view, both for 4M* and 6M* models. A cable AWG20 (0.5 mm 2 ) with 2 wires must be used (not delivered with the kit). For cables longer than 10 meters, we recommend to use a shielded cable and to ground one end of the shield near the driver (not on the driver). Figure 5: Temperature sensor 5.2 Injection valve parts The injection valve is not pre-assembled: the injection tubing assembly has to be assembled before installation according to Chapter 3.2 and to the Installation Manual delivered together with the Demand Cooling kit. The white Teflon washer included in the kit can be fitted between the solenoid coil and the blue clip to prevent the coil from moving. 5.3 Installation procedure IMPORTANT Protect valve against excessive heat while brazing (using inert gas). Do not swage the inlet tubing on the injection valve itself. 1) Before the Demand Cooling system can be installed the compressor has to be depressurized by qualified service personnel and in accordance with local regulations. 2) On a brand new compressor the holding charge must be removed. 3) Before installing the Demand Cooling kit, braze securely the injection parts (expansion valve filter drier, sight glass, tubing...). Use Solder Fontargen A3005V for brazing copper on copper. 4) Remove the plug on the cylinder head (left when looking from the oil pump side) and insert the Discharge temperature sensor. Torque to 19-22 Nm. 5) Remove the 2 cylinder head bolts to mount the filter drier bracket with the studs provided. Place the washers and nuts on the studs. Do not fully tighten nuts. 6) Remove the 3/8"-NPT plug on the compressor body. Mount male flare union (3/8"-NPT/3/8") instead. 7) Connect the female flare fitting to the male flare union mounted to the compressor body. Do not fully tighten. 8) Fix the filter drier with the clamp on the bracket. 9) Torque the flare fitting of step 6. Torque to 21 Nm with Loctite 192026. 10) Torque the stud nuts of the mounting bracket. Torque to 62 Nm. 11) Torque the bolts between the filter drier clamp and the bracket. Torque to 10 Nm. 12) Braze the liquid line to the inlet tubing of the injection expansion valve (use inert gas when brazing). D7.19.2/1113-0715/E 7/12

Figure 6: Injection parts on 4M* compressors Figure 7: Injection parts on 6M* compressors 5.4 Installation of Demand Cooling on 4M* Stream compressors NOTE: An additional fan is needed only for application of Demand Cooling with R22. D7.19.2/1113-0715/E 8/12

5.5 Installation of Demand Cooling on 6M* Stream compressors NOTE: An additional fan is needed only for application of Demand Cooling with R22. 5.6 Use of inverter Demand Cooling is not compatible with speed variation/inverter. D7.19.2/1113-0715/E 9/12

5.7 Demand Cooling wiring diagram D7.19.2/1113-0715/E 10/12

Wiring diagram Legend A1... CoreSense module A4... Sensor module A5... Compressor terminal box A6... Demand Cooling Driver / XEV01D B1... Room thermostat B11... CoreSense discharge temperature sensor B12... Demand Cooling discharge temperature sensor CCH. Crankcase heater E2... Crankcase heater F1... Fuse for control circuit F10... Fan motor thermal protection F12... Compressor over-current protection F13... High pressure safety switch F14... Low pressure safety switch F15... Oil pressure sensor H1... Signal lamp / CoreSense alarm H2... Signal lamp / Demand Cooling driver K11... Time relay-delay part winding start M1... Compressor motor M2... Additional fan motor N... Neutral Q11 Contactor for first part winding Q14.. Contactor for second part winding Q15 Contactor for additional fan motor T1... Transformer 230/24V; 5VA Y1... Solenoid valve liquid line Y3... Solenoid valve for unloaded start Y6... Demand Cooling injection valve WH = White BK = Black OG = Orange 6 Functional checks IMPORTANT The compressor must be thoroughly checked for leaks before proceeding to the Demand Cooling functional checks. 6.1 Checking the NTC Thermistor sensor Disconnect the electrical supply and unplug the modular plug from the module case. Measure the resistance of the thermistor with an ohmmeter at the modular plug attached to the sensor cable. When the temperature sensor is connected to the compressor, resistance can read from more than 100,000 Ohms (very cold compressor) to less than 1600 Ohms (very hot compressor). Readings within these limits usually indicate a satisfactory sensor. 6.2 Checking the driver WARNING Jumpers should be removed with system power Off! Never force a compressor to run by bypassing a safety contact! IMPORTANT The tests should not last longer than is required to verify operation. Do not fail to remove any jumpers added to the module alarm relay, the modular connector and the control circuit when tests have been completed! There are two driver operational tests. Each of these tests trips the driver alarm relay after a 2-minute delay and switches off the compressor. D7.19.2/1113-0715/E 11/12

6.2.1 Test n 1 This test simulates too low a compressor discharge temperature or an open thermistor sensor connection at the driver, eg, broken wire. 1) Disconnect the electrical supply and unplug the temperature sensor modular plug from the module case. 2) Restore power to the driver. 3) The contact normally closed between 4-5 will switch to 5-6 after 30 sec. and error code P2 will be displayed. The Demand Cooling injection valve (Y6) will be immediately deactivated. Under actual temperature conditions, ie, when the compressor starts, the 2-minute delay before trip allows the compressor temperature to rise, and the sensor resistance to decrease to a level the driver recognizes as normal. The temperature sensor was disconnected for this test. Therefore after one minute of operation, the continuous signal to the driver registers that there is an open sensor and trips the driver alarm relay to provide the open sensor protection. 4) Remove system power, reconnect the temperature sensor to the driver, reset the alarm relay, then restore system power. 6.2.2 Test n 2 IMPORTANT This test should not last longer than is required to verify operation. This test simulates an excessive compressor discharge temperature or a shorted module sensor connection at the driver terminal. 1) Remove system power then disconnect the temperature sensor (B12) from the driver. Connect (jumper) the input terminals of the temperature sensor on the driver (14-13) with a small piece of wire. 2) Restore power to the driver. 3) The contact normally closed between 4-5 will switch to 5-6 after 30 sec. and error code P2 will be displayed. The Demand Cooling injection valve (Y6) will be deactivated After one minute of testing the alarm relay will trip indicating a shorted sensor. 4) Remove the "short" from the control driver sensor input terminals and restore module power. D7.19.2/1113-0715/E 12/12