UNO-PS/1AC/24DC/60W. Primary-switched power supply unit. Data sheet. 1 Description

Similar documents
Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1

STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase

Power Supply, Primary Switch Mode, Narrow Design MINI-PS AC/2x15DC/1

Redundancy Module QUINT-DIODE/40

Power Supply, Primary Switch Mode, Narrow Design MINI-PS AC/24DC/2

PHOENIX CONTACT - 01/2007

MCR-VDC-UI-B-DC. Voltage Transducer for DC Voltages. INTERFACE Data Sheet _en_01. 1 Description

PHOENIX CONTACT Features

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Chrome DIN Rail Power Supply 24V 30W 1 Phase (Class II & NEC Class 2) / DRC-24V30W1AZ

Chrome DIN Rail Power Supply 24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1AZ

Three-phase monitoring relay CM-PFE

Chrome DIN Rail Power Supply 12V 54W 1 Phase (Class II & NEC Class 2) / DRC-12V60W1AG

Type: EASY719 DC RC Article No.: Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N

Your automation should be permanently supplied Our compact PROeco power supplies offer that as part of an economical concept Let s connect.

RM17TE V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

MINI MCR-SL-R-UI(-SP)

LOGO!Power. Power supply. LOGO!Power. Overview. Description, device design, dimension drawing. Mounting/Disassembly 2

RM4TG20 three-phase network control relay RM4-T - range V

ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories

38 SERIES. Relay interface modules A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.

CliQ DIN Rail Power Supply 24V 120W 1 Phase / DRP024V120W1AA

38 Series - Relay interface modules A

38 Series - Relay interface modules A

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.

Single-phase ( V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2, /0.65/0.

Power Supplies 3. SDN-P DIN Rail Series

48 SERIES Relay interface modules 10 A

RM35UA13MW. range V. Main. Product or component type. Relay monitored parameters

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

Relés e Contatores de Estado Sólido SIRIUS

Safety technique. Emergency stop module BO 5988 safemaster

LOGO!Power. Power supply. LOGO!Power. Overview. Safety instructions. Description, device design, dimension drawing. Mounting/disassembly

7 - Phaseo power supplies and transformers

34 Series - Slim electromechanical PCB relays 6 A. Features SERIES 34.51

Analog signal converters CC-E I/I Current / current isolators

49 Series - Relay interface modules A. Features

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages

Digital input modules

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start * see variants. Applications.

DEK-REL- 24/1/SEN. Extract from the online catalog. Order No.:

Type: DILM115(RAC240) Article No.: Sales text Contactor,55kW/400V,AC operated. Ordering information

Series AMEPR30-AZ up to 2.5A AC-DC / DC-DC LED Driver / Converter

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

CliQ DIN Rail Power Supply 24V 120W 1 Phase / DRP024V120W1AA

Electronic overload relay EF19 and EF45

TEP 200WIR Series, Watt

PC 4/ 2-ST-7,62. Extract from the online catalog. Order No.:

MasterINTERFACE 39 Series - Relay interface modules

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)

PLC-RS /21. PLC INTERFACE With PDT Relay, Universal Version. INTERFACE Data Sheet _en_02. 1 Description

R.C.C.B. s two-pole LEXIC

Manual motor starter MS116

Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL MTE Corporation

TX OPEN RS232/485 module

Thermistor motor protection

SURGE PROTECTIVE DEVICES

is then retained absolutely without interruption.

PC 4/ 5-STF-7,62. Extract from the online catalog. Order No.:

MasterINTERFACE 39 Series - Relay interface modules

80 Series - Modular timers 16 A. Features

Electronic ballasts for fluorescent lamps Products for special applications. PC BASIC, 4 28 W Electronic ballast for system output < 25 W

Electronic overload relay EF65, EF96 and EF146

SYSTEM DESCRIPTION Termination Boards

PC 4/ 4-ST-7,62. Extract from the online catalog. Order No.:

PHOENIX CONTACT

MICROSENS. Central 48 V DC Power Supplies for PoE-Components. Description. Features

Fixed - Over/Under voltage limits, ( ) U N respectivity Link selectable - 5 min or 10 min delay. Fixed limits

STRATO LED Drivers 70W, Single output

Product and functional description

TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC A - M8 connector

Actuator-Sensor-Interface

Cross-beam scanning system to detect slim objects. 100 mm in

AC/DC Power Modules C B. TML Series, 20 & 40 Watt. Features. 20 Watt Models

Operating Manual UWAPS-TINY Series

15 Series - Electronic step relay and dimmer. Features SERIE

APD / Outputs 19" DC/DC Converter, 50 Watt

Type: DILM50(230V50HZ,240V60HZ) Article No.:

O WA-120U series IP W Single Output Switching Power Supply. Features. Aplications

1 pole, 16 A Screw terminal connection 35 mm rail (EN 60715) mounting. 2 pole, 8 A Screw terminal connection 35 mm rail (EN 60715) mounting

Three-phase monitoring relays CM-PSS CM-PSS.31 and CM-PSS.41

Telephone- and leased line modem for industrial applications TD-36

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

Type: DILM32 10(24V50HZ) Article No.:

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

H/L = Power supply. FN = Nominal Frequency. RN = Rated value of output burden. UN = Nominal input voltage. IN = Nominal input current.

Technical data UNIBLOCK UBSF

VEO. V4PF480Y/277VSYTK02 Art.Nr.: V4PF480Y/277VSYTK02P Art.Nr.: TECHNICAL DATA

GMKDS 3/ 3-7,62. Extract from the online catalog. Order No.:

MKDSN 1,5/ 3-5,08. Extract from the online catalog. Order No.:

Example of use: Fuse for a solenoid valve. If the fuse is defective, no information is sent to the electronic component.

LINETRAXX VMD460-NA. Network and system protection (NS protection) for monitoring the power feed-in of power generation systems

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

Uncompromising safety and comfort The next generation of miniature circuit breakers MCB S 200/S 200 M

Transcription:

Primary-switched power supply unit Data sheet 105547_en_00 PHOENIX CONTACT 2013-04-04 1 Description The UNO POWER power supply unit impresses in worldwide use thanks to maximum energy efficiency. Low noload losses and the high degree of efficiency save energy. Thanks to its high power density, the UNO POWER power supply unit is the ideal solution, particularly in compact control boxes. Features Worldwide use thanks to input voltage range of 85 V AC... 264 V AC Maximum system availability through reliable power supply with 24 V DC Maximum energy efficiency thanks to optimized efficiency over the entire operating range of the power supply unit and low no-load losses Particularly compact: 60 W of power from this narrow power supply, which is just 35 mm wide Make sure you always use the latest documentation. It can be downloaded from the product at phoenixcontact.net/products.

2 Table of contents 1 Description... 1 2 Table of contents... 2 3 Ordering data... 3 4 Technical data... 4 5 Intended use... 7 6 Structure... 7 6.1 Device elements... 7 6.2 Block diagram... 7 7 Assembly... 8 7.1 Unpacking... 8 7.2 Mounting the power supply unit... 8 7.3 Mounting on a DIN rail... 10 7.4 Normal mounting position... 10 8 Installing the power supply unit... 11 8.1 Safety regulations and installation notes... 11 8.2 Mains connection... 11 8.3 Device connections... 12 8.4 Connecting cables... 12 9 Operating behavior of the power supply unit... 13 9.1 Normal operation... 13 9.2 Overload response... 13 9.3 Behavior at ambient temperatures > 55 C... 13 9.4 Behavior in the case of alternative mounting positions... 14 10 Operating the power supply unit... 17 10.1 Function monitoring... 17 10.2 Operating power supply units in parallel... 18 10.3 Operating the power supply unit in series... 19 11 Removal... 19 11.1 Removing the power supply unit... 19 11.2 Notes on disposal... 19 105547_en_00 PHOENIX CONTACT 2

3 Ordering data Description Type Order No. Pcs. / Pkt. 24 V DC/60 W DIN rail power supply unit, primary-switched, single-phase UNO-PS/1AC/24DC/60W 2902992 1 Accessories Type Order No. Pcs. / Pkt. Redundancy module, 5-24 V DC, 2x 5 A, 1x 10 A STEP-DIODE/5-24DC/2X5/1X10 2868606 1 Our range of accessories is being continually extended, our current range can be found in the download area. 105547_en_00 PHOENIX CONTACT 3

4 Technical data Input data Nominal input voltage range 100 V AC... 240 V AC AC input voltage range 85 V AC... 264 V AC AC frequency range 45 Hz... 65 Hz Current consumption 1 A (120 V AC) 0.6 A (230 V AC) Inrush current limitation < 30 A (typical) I 2 t < 0.5 A 2 s Typical response time < 1 s Power failure bypass > 20 ms (120 V AC) > 85 ms (230 V AC) Protective circuit Transient surge protection Varistor Input fuse, integrated 2.5 A (slow-blow, internal) Choice of suitable fuses 6 A... 16 A (Characteristics B, C, D, K) Input connection data Connection method Screw connection Conductor cross section, solid 0.2 mm²... 2.5 mm² Conductor cross section, stranded 0.2 mm²... 2.5 mm² Conductor cross section AWG/kcmil 24... 14 Stripping length 8 mm Screw thread M3 Tightening torque 0.5 Nm... 0.6 Nm Output data Nominal output voltage 24 V DC ±1% Output current 2.5 A (-25 C... 55 C) Derating 55 C... 70 C (2.5%/K) Control deviation < 1 % (change in load, static 10%... 90%) < 2 % (Dynamic load change 10%... 90%, 10 Hz) < 0.1 % (change in input voltage ±10%) Ascent time < 0.5 s (U OUT (10%... 90%)) Residual ripple < 30 mv PP (with nominal values) Connection in parallel yes, with redundancy module Connection in series Yes Protection against surge voltage on the output 35 V DC Resistance to reverse feed Output connection data Connection method < 35 V DC Screw connection Conductor cross section, solid 0.2 mm²... 2.5 mm² Conductor cross section, stranded 0.2 mm²... 2.5 mm² Conductor cross section AWG/kcmil 24... 14 Connection method 6.5 mm Screw thread M3 Tightening torque 0.6 Nm... 0.8 Nm 105547_en_00 PHOENIX CONTACT 4

Power consumption Efficiency Maximum power dissipation NO-Load Power loss nominal load max. > 90 % (for 230 V AC and nominal values) < 0.3 W < 7 W General data Insulation voltage input/output 4 kv AC (type test) 3 kv AC (routine test) MTBF > 500000 h (According to EN 29500) Housing material polycarbonate Foot latch material Plastic POM Dimensions W / H / D 35 mm / 90 mm / 84 mm Weight 0.2 kg Security Degree of protection Protection class SELV IP20 II (in an enclosed control cabinet) IEC 60950-1 (SELV) and EN 60204 (PELV) Ambient conditions Ambient temperature (operation) -25 C... 70 C (> 55 C derating) Ambient temperature (storage/transport) -40 C... 85 C Max. permissible relative humidity (operation) 95 % (at 25 C, no condensation) Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) 15 Hz... 150 Hz, 2.3g, 90 min. Shock 30 g in each direction, according to IEC 60068-2-27 Pollution degree 2 Climatic class 3K3 (in acc. with EN 60721) Inflammability class in acc. with UL 94 (housing) V0 Standards Electrical Equipment for Machinery EN 60204-1 Electrical safety (of information technology equipment - Safety - Part 1) IEC 60950-1/VDE 0805 (SELV) Electronic equipment for use in electrical power installations EN 50178/VDE 0160 (PELV) SELV IEC 60950-1 (SELV) and EN 60204 (PELV) Safe isolation DIN VDE 0100-410 Protection against electric shock DIN 57100-410 Limitation of mains harmonic currents EN 61000-3-2 Network version/undervoltage EN 61000-4-11 Information technology equipment - Safety (CB Scheme) CB Scheme Approvals UL approvals UL Listed UL 508 UL/C-UL Recognized UL 60950 NEC Class 2 as per UL 1310 CSA CAN/CSA-C22.2 No. 60950-1-07 CSA-C22.2 No. 107.1-01 105547_en_00 PHOENIX CONTACT 5

Conformance with EMC Directive 2004/108/EC Noise immunity according to EN 61000-6-2 Electrostatic discharge EN 61000-4-2 Electromagnetic HF field EN 61000-4-3 Fast transients (burst) EN 61000-4-4 Surge current loads (surge) EN 61000-4-5 Conducted interference EN 61000-4-6 EN 61000-6-2 requirement Tested Housing contact discharge 4 kv (Test intensity 2) 6 kv (Test intensity 3) Housing air discharge 8 kv (Test intensity 3) 8 kv (Test intensity 3) Comments Criterion B Criterion B Frequency range 80 MHz... 1 GHz 80 MHz... 1 GHz Test field strength 10 V/m 10 V/m Frequency range 1.4 GHz... 2 GHz 1 GHz... 2 GHz Test field strength 3 V/m 10 V/m Frequency range 2 GHz... 2.7 GHz 2 GHz... 3 GHz Test field strength 1 V/m 10 V/m Comments Criterion A Criterion A Input 2 kv (Test intensity 3 - asymmetrical) 4 kv (Test intensity 4 - asymmetrical) Output 2 kv (Test intensity 3 - asymmetrical) 2 kv (Test intensity 3 - asymmetrical) Comments Criterion B Criterion A Input Output 1 kv (Test intensity 2 - symmetrical) 2 kv (Test intensity 3 - asymmetrical) 0.5 kv (Test intensity 1 - symmetrical) 0.5 kv (Test intensity 1 - asymmetrical) Comments Criterion B Criterion A 2 kv (Test intensity 3 - symmetrical) 4 kv (Test intensity 4 - asymmetrical) 1 kv (Test intensity 2 - symmetrical) 2 kv (Test intensity 3 - asymmetrical) Frequency range 10 khz... 80 MHz 150 khz... 80 MHz Voltage 10 V (Test intensity 3) 10 V (Test intensity 3) Comments Criterion A Criterion A Criterion A Criterion B Normal operating behavior within the specified limits. Temporary impairment to operational behavior that is corrected by the device itself. Emitted interference in acc. with EN 61000-6-3 Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) class B used in industry and residential area / EMC 1 Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) class B used in industry and residential area / EMC 1 All technical specifications are nominal values and refer to a room temperature of 25 C and 70% relative humidity at 100 m above sea level. Current approvals can be found for the product in the download area. 105547_en_00 PHOENIX CONTACT 6

5 Intended use This power supply unit features IP20 protection and is intended for installation in housing. It is suitable for use in industrial applications. 6 Structure 6.1 Device elements 6.2 Block diagram 2 3 N L 4 Element Meaning Fuse Figure 1 1 Device elements 1. Input voltage: Input AC L/N 2. Output voltage: Output DC/- 3. Green LED: DC OK 4. Universal snap-on foot: 35 mm DIN rail according to EN 60715 Decoupling Switch Transmitter Filter Disconnect transducer Controller 105547_en_00 PHOENIX CONTACT 7

7 Assembly 7.1 Unpacking Before mounting the power supply unit, it must be checked for damage: Take the device out of its packaging. Check the device for any damage sustained during transport. Retain the package slip for future use. Dispose of packaging in an environmentally-friendly way. 7.2 Mounting the power supply unit The power supply unit is intended for installation in a distributor box or control cabinet. The power supply unit is designed for convection cooling. Maintain a minimum distance from other devices in order to ensure convection cooling. Figure 2 Convection 105547_en_00 PHOENIX CONTACT 8

Please note the following before mounting the power supply unit: The minimum distance from other devices that must be observed in order to ensure convection cooling is: 30 mm vertically, 0 mm horizontally 150 75 30 The device dimensions 35 90 84 27 58 63 90 21 70 15 5 105547_en_00 PHOENIX CONTACT 9

7.3 Mounting on a DIN rail The power supply unit can be installed on all 35 mm DIN rails according to EN 60175. A Figure 3 Mounting on a DIN rail B 7.4 Normal mounting position When installed, the input terminal blocks must be at the bottom and the output terminal blocks at the top. If the power supply unit is installed in a mounting position other than the normal mounting position, the output power must be reduced. Figure 4 Normal mounting position 105547_en_00 PHOENIX CONTACT 10

8 Installing the power supply unit 8.1 Safety regulations and installation notes 8.2 Mains connection WARNING: risk of electric shock! Only qualified specialist personnel may install, start up, and operate the device. Observe the national safety and accident prevention regulations. Prior to installation, disconnect the input voltage and make sure that it cannot be switched on again unintentionally. Mains connection must be performed by specialist personnel and protection against electric shock ensured. Make sure that the device can be switched off outside the power supply according to the regulations in EN 60950 (e.g., by line protection on the primary side). Cover termination area after installation in order to avoid accidental contact with live parts (e.g., by installing in a control cabinet). Protect the device against ingress by foreign bodies, e.g., paper clips or metal parts. The device can be connected to single-phase AC or threephase power grids (TN-S, TN-C, TT, and IT) while considering the nominal input voltage. L N TN-S TT For operation on two of the phase conductors of a three-phase system, an isolating facility for all poles must be provided. - L N PE L N L N TN-C it - L PEN L1 L2 L3 WARNING: risk of electric shock! Make sure that all supply lines are sufficiently dimensioned and have sufficient fuse protection. L N - L N - Make sure that all output cables are dimensioned accordingly for the maximum device output current or have separate fuse protection. Figure 5 Network types WARNING: risk of electric shock! Never open or repair the device yourself. Internal fuses will only blow in the event of device malfunction. Do not modify or attempt to repair the device. Send the device to the factory for examination. 105547_en_00 PHOENIX CONTACT 11

8.3 Device connections Screw connection for input AC L/N 8.4 Connecting cables Use copper cables with an operating temperature > 75 C (ambient temperature < 55 C) and > 90 C (ambient temperature < 75 C). Figure 6 Screw connection for input AC L/N Screw connection for output DC /- Figure 8 Connecting cables Figure 7 Screw connection for output DC /- 1. Connect the supply lines to the input AC L/N connection terminal blocks. 2. Connect the output cables to the output DC /- connection terminal blocks. The power supply unit is operational as soon as the input terminal blocks are supplied with voltage. 105547_en_00 PHOENIX CONTACT 12

9 Operating behavior of the power supply unit 9.1 Normal operation In normal operation, the loads are supplied with a constant output voltage of 24 V DC. 9.2 Overload response In the event of overload (I > I N ), the device reduces its output voltage. If the output voltage is greater than U N x 0.9, the green DC OK LED lights up. If the output voltage drops below U N x 0.5, the device shuts down. After a short time, the device attempts to start up again. If the overload has been rectified, it will start up as normal. If the overload has still not been rectified, it will shut down again and attempt to restart again (automatic restart). [V] UN UN x 0,5 IN [A] Figure 9 Output characteristic curve 9.3 Behavior at ambient temperatures > 55 C At an ambient temperature of up to 55 C, the power supply unit supplies the nominal output current. At ambient temperatures upwards of 55 C, the output power must be reduced by 2.5% per Kelvin temperature increase (temperature-dependent derating). [A] I N 0-25 Figure 10 20 40 60 Temperature-dependent derating [ C] 105547_en_00 PHOENIX CONTACT 13

9.4 Behavior in the case of alternative mounting positions For mounting positions that differ from the normal mounting position, the output power must be reduced (position-dependent derating). The characteristic curve can be used to determine the maximum output power to be drawn for each ambient temperature for different mounting positions. Normal mounting position [%] 110 100 90 80 70 60 50 40 30 20 0-25 25 35 45 55 65 75 [ C] Y Z X Rotated mounting position 90 X-axis [%] 110 100 90 80 70 60 50 40 30 20 0-25 15 25 35 45 55 65 75 [ C] Y Z X 105547_en_00 PHOENIX CONTACT 14

Rotated mounting position 180 X-axis [%] 110 100 90 80 70 60 50 40 30 20 0-25 25 35 45 55 65 75 [ C] Y Z X Rotated mounting position 270 X-axis [%] 110 100 90 80 70 60 50 40 30 20 0-25 25 35 45 55 65 75 [ C] Y Z X 105547_en_00 PHOENIX CONTACT 15

Rotated mounting position 90 Z-axis [%] 110 100 90 80 70 60 50 40 30 20 0-25 25 35 45 55 65 75 [ C] Y Z X Rotated mounting position 270 Z-axis [%] 110 100 90 80 70 60 50 40 30 20 0-25 15 25 35 45 55 65 75 [ C] Y Z X 105547_en_00 PHOENIX CONTACT 16

10 Operating the power supply unit 10.1 Function monitoring DC OK LED The DC OK LED is available for visual function monitoring of the power supply unit. Status 1 Status 2 DC OK LED Lit OFF Meaning Output voltage > 21.5 V Output voltage < 21.5 V DC, overload mode or no mains voltage State description The device is operating, output voltage and output current are OK The device is in operation, but there is a fault on the side of the consumer; the current consumption is greater than IN or the output is short-circuited. The device is out of operation because there is no mains voltage, the fuse on the primary side has been triggered, or the device is faulty. Remedy Remove the error at the load, use a more powerful power supply unit, connect a power supply unit of the same type parallel to the existing device, remove the short circuit, apply mains voltage, enable the fuse again or replace the power supply unit. 105547_en_00 PHOENIX CONTACT 17

10.2 Operating power supply units in parallel Power supply units of the same type can be connected in parallel to increase both redundancy and power. To ensure symmetrical current distribution, all cable connections from the power supply unit to the busbar must be the same length and have the same conductor cross section. Redundant operation Redundant circuits are suitable for supplying systems which place particularly high demands on operational safety. If a fault occurs in the primary circuit of the first power supply unit, the second device automatically takes over the complete power supply without interruption, and vice versa. Using a redundancy module, it is possible for two power supply units of the same type that are connected in parallel on the output side for redundancy to be decoupled from one another. I N I N Increased performance Power supply units of the same type can be connected in parallel to increase the power to n x I N. Parallel connection is recommended if existing systems are to be extended and the power supply unit that is installed here does not cover the current consumption of the most powerful load. Otherwise, the loads should be distributed between individual devices that are independent of one another. Using a redundancy module, it is possible for two power supply units of the same type that are connected in parallel on the output side to increase power to be decoupled from one another. I N I N Figure 12 Σ =2xI N Parallel connection to increase power with a redundancy module Figure 11 Σ = I N Redundant circuit with redundancy module 105547_en_00 PHOENIX CONTACT 18

10.3 Operating the power supply unit in series Two devices can be connected in series to double the voltage. Only power supply units of the same type should be connected in series. Series connection should always be used when the output voltage of the module is not sufficient. For example, devices with 24 V DC nominal output voltage each supply 48 V DC in series. Depending on the specification of functional earth ground, output voltages of 48 V/- 48 V as well as ±24 V DC can also be made available. 11 Removal 11.1 Removing the power supply unit - - 24 V - 48 V -48 V A B Figure 14 Removal -24 V 11.2 Notes on disposal - - - Figure 13 Series operation Do not dispose of the power supply unit with household waste. It should be disposed of in accordance with the currently applicable national regulations. 105547_en_00 PHOENIX CONTACT GmbH & Co. KG 32823 Blomberg Germany 19 www.phoenixcontact.com