RADIANT HEATING SYSTEMS THREE-WAY MIXING VALVE INSTALLATION GUIDE. Three-way Mixing Valve Installation Guide

Similar documents
Powers Controls TH 192 S Single Temperature Room Thermostat

Powers Controls TH 192 HC Heating/Cooling Room Thermostat

Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS

WE-350 Series ¼ Turn Electric Actuator

Powers Controls Free Energy Band TH 193 HC Heating/Cooling Room Thermostat

Float and Thermostatic Traps Series H, C and X

INSTALLATION INSTRUCTIONS & HOME OWNERS MANUAL EEMAX ELECTRIC TANKLESS WATER HEATERS IMPORTANT SAFETY INFORMATION

Programmable Room Thermostat 7 Day (5-2 Day) Models: / Power Supply: Battery / Mains

Oil and Coolant Circulating Heating System. Model - OCSM

with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.

Cooling system components, removing and installing

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin Inch PowerVent LED Indicator Explanations & Troubleshooting Table

SERVICE MANUAL RESIDENTIAL ELECTRIC AND LIGHT DUTY COMMERCIAL ELECTRIC WATER HEATERS. Troubleshooting Guide and Instructions for Service

! WARNING. Before using product, read and understand instructions.

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS

Radiant Temperature Sensor TY7321

Service Guide 12/27/03 TESTING, SERVICE & REPAIR GUIDE (For SH Space Heating Models & RA Water Heating Models)

MCR1900 Media Converter 19-Slot Chassis

Floor Heating Warehouse.co.uk

Drayton Digistat +2RF/+3RF

STATFlow. Direct-to-Drain System. For use with STATIM 2000 and STATIM 5000 Autoclaves. Installation Guide and Operator s Manual

THERMOSTATIC MIXING VALVE TRIM K-T9493, K-T9494

Installation and Troubleshooting Instructions for Electric Tankless Residential Water Heaters.

PRESSURE REDUCING CONTROL VALVE

INSTALLATION INSTRUCTIONS & HOME OWNERS MANUAL ECO 18 ECO 24 ECO 27 IMPORTANT SAFETY INFORMATION

Max primary circuit temperature 90ºC Max primary circuit temp. 90ºC Max secondary circuit temperature 45ºC Max secondary circuit temp.

Mustang Series PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE. M115-2 (Globe) M (Angle) Schematic. Standard Components

OWNER S MANUAL FORCE 10 MARINE COMPANY HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) FAX: (604)

Thermwire. Selection Guide. Freeze Protection Heating Cable. Thermwire -Wrap. Pre-Assembled. Thermwire-Comp. Thermwire-Melt.

Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS

XE70 SERIES VC SERIES BALANCED HYDRONIC VALVES 2-WAY AND 3-WAY

CW-5000/ 5200,1'8675,$/ &+,//(5 86(5 0$18$/

Installation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008

Service manual. Website: CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

Your safety and the safety of others are very important.

T7079A,B Solid State Remote Temperature Controllers

I N S T ALLATION INSTRUCTIONS & HOME OWNERS MANUAL IMPORTANT SAFETY INFORMATION

INDIRECT WATER HEATER. Installation and Operating Instruction Manual

WON0502-B INSTALLATION INSTRUCTIONS FOR ELECTRIC FURNACES. Bulletin / March 2013

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013

IMPORTANT SAFETY INSTRUCTIONS WARNING READ AND SAVE THESE OPERATING AND SAFETY INSTRUCTIONS BEFORE USING THIS HEATER.

AMX300 DirectConnect Mixing Valve Kits

CDS TROUBLESHOOTING SECTION I. VACUUM Weak vacuum at wand. Gauge reads normal (10hg to 14hg)

STAINLESS STEEL TANK TABLE OF CONTENTS TROUBLESHOOTING... 1 TESTING WATER TEMPERATURE... 3 TANK & JACKET ASSEMBLY... 4.

Submersion/Insertion Toroidal Sensor

Air Conditioner Water Heater Model ACWH18

VC Series Zone Valves BALANCED 2-WAY AND 3-WAY HYDRONIC VALVES

1. RANGE OF APPLICATION 3. SAFETY INSTRUCTIONS 4 4. DESIGN 4

I nstallation. M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications. Tools Needed.

AMPSEAL* Automotive Plug Connector and Header Assembly

Ducoterra Radiant Heating Panel Installation Manual

HMI display Installation Guide

, User s Manual

HERZ-Thermal Actuators

Instruction Sheet X Pump Block (XPB)

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power

VX 2400 Dimmer User's Manual

ELECTRONIC THERMOSTAT AND THERMOMETER With SPEED CONTROL

IMPORTANT: BEFORE INSTALLING ANY HEATING TERMINAL UNIT TO A DOMESTIC WATER HEATER, CONSULT THE LOCAL PLUMBING CODES.

TABLE 1. Rugged cast aluminum alloy casing,celcon waterways with nichrome parts White (unless stainless steel housing)

Constantemp Double Wall Low pressure steam-water Heater F-340LDW,F-640LDW, F-940LDW and F-1240LDW

Watts Pure Water Systems

ACS-30-EU-EMDR-10-MOD

INSTALLATION GUIDE LOW VOLTAGE TRANSFORMER

Visage. Digital. Digital diverter. Installation guide. Visage Digital diverter installation instructions Page 1

Comfort Control Relay Panel (CCRP)

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin Tankless Electric (RTE) Troubleshooting

Cooling system components, removing and installing

Sanitary Type Electronic Flow Switches

VU53S; VU54S; VU443A; VU444A; VU843A; VU844A Fan Coil Valves and Actuators

Wireless 7 Day Programmable Room Thermostat

Installing the Tracer ZN517 Unitary Controller Ordering number: ,

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

Rain+Birdt. Simple To Set Timer (SST) Setup & Operation Instructions. English RAIN BIRD ( ) or visit

presents Hydraulic Separation Beyond Primary / Secondary Piping

SELECTION, APPLICATION AND MAINTENANCE

Geyser-R Heat pump water heater Installation manual

Single Station Remote Alarm

Operator: Save these instructions for future use!

PT-6000 Power Tower INSTALLATION MANUAL SPECIFICATIONS

12S, 14S, 15S Series. Time Delay Relays and Sequencers. Time Delay Relays and Sequencers. Features and Benefits. Switch Actions and Configurations

Operation Manual. 150 Watt Halogen Light Source for Endoscopy Model # s ESS-150, ESS-150A ESS-220, ESS-220A

PS6500 Storage Arrays Rack Mount Instructions

Ceiling Mount Air Handler Manual

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

Fleck Service Manual INSTALLATION AND START-UP PROCEDURE TABLE OF CONTENTS JOB SPECIFICATION SHEET

Installation and User Instructions Unvented Electric Storage Water Heater Models: S10UNV, S15UNV.

TANKLESS WATER HEATER INSTALLATION DIAGRAMS

Use & Care Manual. Electric Tankless Water Heaters. With Installation Instructions for the Installer AP15447 (10/10)

USERS GUIDE. LOGIC Combi 24, 30, 35. For installation guide see reverse of book

High kw Electric Tankless Water Heater Troubleshooting Guide

Mixing Valves. ARGUS Application Note: Mixing Valves

AWWA Butterfly Valve Operation and Maintenance Manual Series 511A & 510A 20 and Smaller

Nexus FS Point of Use Installation Guide

Why and How we Use Capacity Control

REFRIGERATED TYPE COMPRESSED AIR DRYERS INSTRUCTION MANUAL. For Sales & Service please contact:

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling

DRM75A 230V 20/100A DIN rail single phase two wire energy meter

UV100A Ultraviolet Air Treatment System

Transcription:

RADIANT HEATING SYSTEMS THREE-WAY MIXING VALVE INSTALLATION GUIDE Three-way Mixing Valve Installation Guide

Table of Contents Introduction 1 Piping Requirements 1 Application 2 Installation 3 Actuator Installation and Removal 4 Powering the Control 5 Intermittent Operation Continuous Operation Sensor Wiring 6 Outdoor Sensor General Tips for System Supply and Boiler Return Sensors System Supply Sensor Boiler Return Sensor Sequence of Operation 8 Power Up and Heat Request Reset Ratio Maximum/Minimum System Supply Temperature Minimum Boiler Return Temperature Warm Weather Shut Down (WWSD) Outdoor Reset Reset Ratio Configuration Reset Ratio Formula Troubleshooting 11 Setting Adjustments 12 Sensor Testing Product Specifications 13 Materials of Construction 14 Dimensions and Weights Three-way Mixing Valve Installation Guide Published by Uponor North America 5925 148th Street West Apple Valley, MN 55124 USA Phone: 800.321.4739 Fax: 952.891.2008 www.uponorpro.com 2014 Uponor North America All Rights Reserved. First Edition October 2013 Printed in the United States of America

Introduction The Uponor Three-way Mixing Valve (A3040075, A3040100) is a microprocessor-controlled valve designed to regulate the supply water temperature to a radiant heating system by modulating the position of the valve. Mixed supply setpoint can be configured to reset from the outdoor air temperature. An optional boiler sensor can be used to provide boiler protection in non-condensing boiler applications. Note: Do not use the Three-way Mixing Valve for potable-water tempering or in any application where scalding can occur as a result of exposure to the tempered water. Piping Requirements Refer to the following piping requirements for installing an Uponor Three-way Mixing Valve. 1. Use primary/secondary piping to hydraulically isolate the boiler loop from the injection or system loop. There can be no more than 4 pipe diameters between the tees in the boiler loop (see Note 1 in Figure 1). 2. There must be at least 6 pipe diameters of straight pipe on either side of the tees (see Note 2 in Figure 1) to prevent the momentum of water in the boiler loop from pushing flow through the injection loop. 3. Ensure a minimum of 1 ft. drop on the return pipe of the injection loop to create a thermal trap and prevent unwanted heat transfer (see Note 3 in Figure 1). Note 2 Note 1 A B C Boiler Loop Note 3 System Loop Figure 1: Three-way Mixing Valve Piping Requirements 3-way Mixing Application Three-way Mixing Valve Installation Guide 1

Application The Uponor Three-way Mixing Valve can be used to mix the hot boiler water temperature with the cooler return water temperature from the system loop. The position of the valve is modulated to inject different rates of hot water into the cool system return water. This allows the heating system to receive virtually any water temperature. Because most cast-iron boilers cannot operate at low temperatures, the Uponor Three-way Mixing Valve can be modulated back in order to prevent the boiler from operating at cold temperatures (provided a boiler return sensor is installed in the system). Flow GPM Cv = 4.5 PSI Ft. Head 1 2 0.01 0.03 1 0.05 0.11 2 0.20 0.46 4 0.79 1.82 6 1.78 4.10 8 3.16 7.29 10 4.94 11.39 12 7.11 16.41 Table 1: Pressure Drop Chart Outdoor Sensor I valve Ðð A B C Supply Sensor Boiler Sensor Figure 2: Three-way Mixing Valve Typical Piping Diagram 2 www.uponorpro.com 2

B A A B Return Supply Supply Return Mix Figure 3: Three-way Mixing Valve Installations Mix Installation Refer to the following installation instructions to properly install the Uponor Three-way Mixing Valve. 1. The valve body can install in any position and orientation. Install the power connections over the supply port to ensure proper flow direction (see Figure 3). 2. Before installing the valve body, refer to Figure 4 and the Dimensions section on page 14 for clearances. Wall Boiler Supply Outdoor C R Power Input Sensor Common 3. Before attaching the actuator, it is acceptable to submerge the valve body in water to test for leaks. Figure 4: Acceptable Clearance from a Wall 1½" Min. Actuator Removal Clearance Important! Remove the valve gaskets and the actuator from the valve body before soldering. Ensure the ball valve is in the full open position before soldering. (Note that the valve is shipped in the full closed position.) Three-way Mixing Valve Installation Guide 3

Actuator Installation and Removal 1. The actuator can attach to the valve body in either direction with the power connections over the supply port to ensure proper flow direction. 2. To remove the actuator prior to soldering, rotate it counterclockwise approximately 30 degrees and lift upward approximately ¾" (see Figure 5). Note: The D-shaped stem design allows for correct insertion every time. 4. Next, slide the valve stem into the actuator cavity and rotate it until the actuator slips over the valve s locking posts. 5. Once the actuator is flush with valve body, turn the actuator clockwise and lock it into position. 3. To reassemble the actuator to valve body, position the actuator so the D-shaped valve stem aligns properly with the D-shaped actuator drive cavity. Step 1 Rotate actuator head counter clockwise 30 degress. Step 2 Lift actuator from valve ¾" to remove. PUSH FOR PUSH FOR MANUAL MANUAL 0.2 1.2 Reset Ratio iseries MixingiSeries Valve Mixing Valve 2.2 I075U3R-1 0.2 1.2 i Series Mixing Valve Reset Ratio iseries 2.2 Mixing Valve I075U3R-1 Figure 5: Actuator Removal 4 www.uponorpro.com

Powering the Control All terminals on the Uponor Three-way Mixing Valve are removable. To prevent damage to the electronics, disconnect all plugs before applying power and check voltages and sensors. After testing the circuits, plug in the terminals. Warning: Make all wiring connections in accordance with applicable electrical codes. Caution: To prevent electrical shock, disconnect electric power to the system at the main fuse or circuit breaker box until installation is complete. When installing a service switch, more than one disconnect switch may be required to de-energize this device for servicing. Intermittent Operation 1. Connect the two wires on the end switch of the Uponor Zone Control Module (ZCM) to the R and W terminals on the Uponor Pump Relay. 2. Connect the R terminal on the Three-way Mixing Valve to the W terminal on the pump relay. 3. Connect the C terminal on the Three-way Mixing Valve to the C terminal on the pump relay. Continuous Operation For continuous operation, wire the transformer directly to the R and C terminals on the Three-way Mixing Valve. Important! Ensure no power is present during this process. A3031003 A3031004 Zone Control Module A3010100 Pump Relay A3050050 Transformer Boiler Supply Outdoor C R Power Input Sensor Common Alternative end switch wiring to Boiler/Pump relay A3031003 A3031004 Zone Control Module 120 VAC Input TT Boiler TT Enable Outdoor Temp Alternative wiring connections to Boiler/Pump relay Boiler Supply A3040075 A3040100 Mix Valve Secondary Pump Figure 6: Three-way Mixing Valve Typical Wiring Diagram Three-way Mixing Valve Installation Guide 5

Sensor Wiring Do not apply power to the sensor terminals as this will damage the Three-way Mixing Valve. The wiring terminals for the sensors may be removed for ease of installation. Outdoor Sensor 1. Remove the screw and pull the front cover off the sensor enclosure. 2. The outdoor sensor can mount either directly onto a wall or in a 2" x 4" electrical box. 3. When mounting the sensor to a wall, ensure the wiring enters through the back or bottom of the enclosure. Do not mount the sensor with the conduit knockout facing upwards as rain could enter the enclosure and damage the sensor. 4. Mount the sensor on a wall which best represents the heat load on the building (e.g., a northern wall for most buildings and a southern-facing wall for buildings with large, southfacing glass areas). Note: To prevent heat transmission through the wall from affecting the sensor reading, it may be necessary to install an insulating barrier behind the enclosure. 5. Do not expose the sensor to heat sources such as ventilation or window openings. 6. Install the sensor at an elevation above the ground that will prevent tampering. 7. Connect 18 AWG or similar wire from the outdoor sensor directly into the SENSOR COMMON and OUTDOOR terminals on the Three-way Mixing Valve. 8. Replace the front cover of the sensor enclosure. Boiler Supply Outdoor C R Power Input Sensor Common Boiler Return Sensor System Supply Sensor Outdoor Sensor Figure 7: Control Wiring Diagram 6 www.uponorpro.com

General Tips for System Supply and Boiler Return Sensors Strap the sensors directly to the pipe using a cable tie. Place insulation around the sensor to reduce the effect of air currents on the sensor measurement. Place the sensors downstream from a pump or after an elbow or similar fitting. Note: This is especially important if the system is using large-diameter pipes because the thermal stratification within the pipe can result in erroneous sensor readings. Proper sensor location requires that the fluid is thoroughly mixed within the pipe before it reaches the sensor. System Supply Sensor Wire the system supply sensor by connecting the two wires from the supply sensor directly into the SENSOR COMMON and SUPPLY terminals on the Three-way Mixing Valve. Boiler Return Sensor Wire the boiler return sensor by connecting the two wires from the boiler return sensor directly into the SENSOR COMMON and BOILER terminals on the Three-way Mixing Valve. If the System Supply Sensor is measuring duct temperature, mount the sensor in such a manner so it measures the average duct outlet temperature. Three-way Mixing Valve Installation Guide 7

Sequence of Operation Power Up and Heat Request Upon power up, the LED turns green and the control starts operation. For intermittent operation, power to the Three-way Mixing Valve can be switched through an end switch (e.g., Uponor ZCM) or a thermostat. For continuous operation, power can be connected directly to the Three-way Mixing Valve. Reset Ratio Once the Three-way Mixing Valve is powered up, it provides outdoor reset at the supply sensor location. The Three-way Mixing Valve targets a supply temperature based on the outdoor temperature measured and the Reset Ratio dial setting. The Reset Ratio is set using the formula on page 10. 4 3 2 1 4 3 2 1 OFF Maximum: 110ºF Minimum: None 4 3 2 1 Maximum: 150ºF Minimum: 85ºF ON OFF ON Maximum: 130ºF Minimum: None 4 3 2 1 Maximum: None Minimum: 85ºF OFF ON OFF ON Maximum/Minimum System Supply Temperature (DIP Switches 1 and 2) The Three-way Mixing Valve can be configured to set a maximum supply water target temperature to help protect system components, such as floor coverings, by preventing excessive water temperatures. Select the maximum target temperature using DIP Switches 1 and 2. When selecting a maximum supply target temperature of 150 F (66 C) or NONE, the Three-way Mixing Valve also enables a minimum supply target temperature of 85 F (29 C). This function is typically used in stapleup radiant floor heating applications to ensure enough heat delivery during mild outdoor temperatures. If the actual supply water temperature approaches the maximum or minimum system supply, the Three-way Mixing Valve modulates the valve down and the green LED flashes rapidly (reduced output). Note: If selecting NONE for minimum system supply temperature, the setpoint system supply temperature will equal the Warm Weather Shut Down (WWSD) of 70 F (21.1 C). Figure 8: DIP Switches 1 and 2 8 www.uponorpro.com

Minimum Boiler Return Temperature (DIP Switch 3) The boiler protection function prevents low temperatures back to the boiler (provided a boiler sensor is installed). The Three-way Mixing Valve monitors the boiler return temperature and modulates the valve down when the return temperature is near the minimum setting selected via DIP Switch 3. When DIP Switch 3 is in the on position, the minimum temperature is set to 120 F (49 C). When the switch is turned off, the minimum temperature is 135 F (57 C). When using low-temperature boilers, such as condensing or electric, it is possible to disable the boiler minimum temperature by powering up the control without a boiler return sensor. When the Three-way Mixing Valve is being modulated towards the closed position to protect the boiler, the green LED flashes rapidly (reduced output). Warm Weather Shut Down (WWSD) (DIP Switch 4) Warm Weather Shut Down (WWSD) function closes the Three-way Mixing Valve when the outdoor temperature is warmer than 70 F (21 C). WWSD is enabled by turning DIP Switch 4 to the on position. The green LED slowly flashes to signal the WWSD status. 4 3 2 1 Maximum: None Minimum: None OFF ON Figure 10: DIP Switch 4 Note: If outdoor air temperature sensor fails or is not installed, the Three-way Mixing Valve will use 32 F (0 C) as the outdoor reference. The LED light will flash 3 times, pause, flash 3 times, pause, etc. See Table 2 on page 11 for LED indicator information. 4 3 2 1 135ºF OFF ON 120ºF Figure 9: DIP Switch 3 Three-way Mixing Valve Installation Guide 9

Outdoor Reset To properly control a hot-water heating system, the heat supplied to the building must equal the heat lost by the building. The heat supplied to the building is directly proportional to the temperature of the water and the surface area of the 2.2 1.8 2.0 1.4 1.6 1.2 1.0 0.8 0.6 0.4 0.2 210 (99) 190 (88) 170 (77) 150 (65) 130 (54) 110 (43) 90 (32) 70 (21) 50ºF 90 70 50 30 10-10ºF (10)ºC (32) (21) (10) (-1) (-12) (-23)ºC Outdoor Air Temperature Figure 11: Reset Ratio Chart Supply Water Temperature heating element. The higher the temperature of the water flowing through the heating terminal, the higher the heat output. The heat lost from a building is dependent on the outdoor temperature. As the outdoor temperature drops, the building heat loss increases. These two facts lead to the concept of outdoor reset which increases the supply water temperature as the outdoor temperature drops. Using this approach, the heat lost from the building is matched by the heat provided by the terminal units, therefore providing more comfort and energy savings. Reset Ratio Configuration The Reset Ratio sets the relationship between outdoor temperature and supply water temperature. It determines the amount the supply water temperature is raised for every 1 degree outdoor temperature drop. For example, if a Reset Ratio of 1.2 is selected, the supply water temperature increases 1.2 degrees for every 1 degree of outdoor temperature drop. Reset Ratio Formula Design Supply Temp. WWSD (70 F/21.1 C) WWSD (70 F/21.1 C) Design Outdoor Temp. = Reset Ratio Example Design Supply Temp. = 110 F/43.3 C WWSD = 70 F/21.1 C (fixed value) Design Outdoor Temp. = 8 F/-13.3 C 110 70 70 8 = 0.6 10 www.uponorpro.com

Troubleshooting As in any troubleshooting procedure, it is important to isolate a problem as much as possible before proceeding. When the control flashes an error message, identify the fault and follow standard testing procedures to confirm the problem. If you suspect a wiring fault, return to the wiring section in this installation guide and carefully check all external wiring and wiring connections. LED Status Description Green Solid Power is on. Green Slow Flash Warm Weather Shut Down is enabled. Green Fast Flash Reduced Output (Boiler protection is activated.) Red Red Red Intermittent Single Flash (Flash, Pause, Flash, Pause, etc.) Intermittent Double Flash (Flash, Flash, Pause, Flash, Flash, Pause, etc.) Intermittent Triple Flash (Flash, Flash, Flash, Pause, Flash, Flash, Flash, Pause, etc.) System Supply Sensor Fault If either of the system supply temperature maximum DIP switches (1 and/or 2) is on, the actuator closes. However, if the switches are off, the valve output will open to 10%. Boiler Sensor Fault Boiler protection will be ignored. Outdoor Sensor Fault Supply setpoint will be calculated using 32 F (0 C) outdoor air. Table 2: LED Indicators Three-way Mixing Valve Installation Guide 11

Setting Adjustments If the outdoor temperature is cold and the building is cold, increase the Reset Ratio setting by one notch per day. Sensor Testing Refer to the steps below to properly test the sensors. Be sure to use a good-quality test meter capable of measuring up to 5,000 kω (1 kω = 1000 Ω) to measure the sensor resistance, and measure the actual temperature with a good-quality digital thermometer. 1. Measure the temperature using the thermometer. 2. Measure the resistance of the sensor at the Three-way Mixing Valve. Important! Ensure the wires from the sensor are not connected to the Three-way Mixing Valve while performing this test. Remove the wiring terminals by gently pulling them from the Three-way Mixing Valve. 3. Using the data in Table 2, estimate the temperature measured by the sensor. The sensor and thermometer readings should be close. If the test meter reads a very high resistance, there may be a broken wire, a poor wiring connection or a defective sensor. If the resistance is very low, there may be a short in the wiring, moisture in the sensor or the sensor may be defective. To test for a defective sensor, measure the resistance directly at the sensor location. Temperature Resistance Temperature Resistance Temperature Resistance Temperature Resistance ºF ºC Ohms ºF ºC Ohms ºF ºC Ohms ºF ºC Ohms -30-34 234196 30-1 34558 90 32 7334 150 66 2045-20 -29 165180 40 4 26099 100 38 5828 160 71 1689-10 -23 118018 50 10 19900 110 43 4665 170 77 1403 0-18 85362 60 16 15311 120 49 3760 180 82 1172 10-12 62465 70 21 11883 130 54 3050 190 88 983 20-7 46218 80 27 9299 140 60 2490 200 93 829 Table 3: Temperature and Resistance 12 www.uponorpro.com

Product Specifications Maximum Operating Pressure: 300 psi (2,100 kpa) Maximum Shutoff Pressure: 125 psi (875 kpa) Fluid Temperature Range: 20º to 240ºF, (-7º to 115ºC) at 135ºF (57ºC) ambient Service: Closed-system hot and chilled water, up to 50% glycol Seat Leakage: Drop-tight close-off Electrical Rating: 24 VAC ±10%, 60 Hz Important! Do not exceed number of valves per transformer rating. For example, do not use more than five (5) Three-way Mixing Valves per 40VA transformer. Power Consumption: 7.2 Watts, 0.3 Amps Part No. Valve Size Cv (Kv) Ft. of Pipe Equivalent A3040075 ¾" 4.5 (3.9)/44.2 A3040100 1" 4.5 (3.9)/44.2 Table 4: Three-way Mixing Valves Three-way Mixing Valve Installation Guide 13

Materials of Construction Actuator Body: High-performance Engineered Polymer Gears: High-performance Internally Lubricated Engineered Polymer Valve Body: Forged Brass Stem: Brass Press Ring: Brass Ball: Brass (Chrome Plated) Seat: Modified Teflon O-rings: EPDM Valve Size A B C D E Weight ¾" 3" 2 3 8" 5 3 8" 2 9 16" 4¾" 1.5 lbs. 1" 3" 2 3 8" 6 5 8" 2 9 16" 7¼" 1.5 lbs. Table 5: Dimensions and Weights A B D Boiler Supply C R Power Input Sensor Common C A B C E Figure 12: Three-way Mixing Valve Dimensions 14 www.uponorpro.com

Three-way Mixing Valve Installation Guide 15

3WayMixVlv_InsG_H478_0214, Copyright 2014 Uponor. Printed in the United States MKT10024_AB Uponor, Inc. 5925 148th Street West Apple Valley, MN 55124 USA Tel: 800.321.4739 Fax: 952.891.2008 Uponor Ltd. 2000 Argentia Rd., Plaza 1, Ste. 200 Mississauga, ON L5N 1W1 CANADA Tel: 888.994.7726 Fax: 800.638.9517 www.uponorpro.com