Types 5207 to 5277 Temperature Sensors

Similar documents
Self-operated Temperature Regulators Temperature Regulator Type 1u

Automation System TROVIS 6400 TROVIS 6493 Compact Controller

Pneumatic Shut-off Butterfly Valve Type 3335/31a SRP or DAP

Type 3353 Angle Seat Valve

Type and Type Pneumatic Control Valves Type 3510 Micro-flow Valve

System 6000 Electropneumatic Converter for Direct Current Signals Type 6116 i/p Converter

Power Supply and Indicator Unit Type Fig. 1 Type Mounting and Operating Instructions EB 9539 EN

Self-operated Temperature Regulators Type 1 to Type 9. PN 16 to 40 Class 125 to 300 DN 15 to 250 NPS ½ to 10 G ½ to 1 Up to 350 C Up to 660 F

HERZ-Thermal Actuators

Self-operated Pressure Regulators Universal Pressure Reducing Valve Type 41-23

Pneumatic Control and Shut-off Butterfly Valve Pfeiffer Type BR 14b/31a and Type BR 14c/31a

Material test chamber with mechanical convection

Valve series MN-06 acc. to NAMUR, 3/2-way G1/4 750 Nl/min (0.762 Cv)

DiwiTherm, Resistance Thermometers Model TR75, with digital Display Battery or Solar Powered

T-05-S2. Rotary drive without spring return. Technical data sheet. Description. Technical data. Actuators

Series 240 Type and Type Pneumatic Control Valves Type 3244 Three-way Valve

Incubator with mechanical convection

Thermostatic Actuators

Electric Rotary Actuator - On/Off or programmable control actuator

N20xxA, N34xxA NON-SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS FOR FLOATING AND 2-POSITION CONTROL

Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS

Heating oven with mechanical convection

Portable digital microprocessor thermometers with interchangeable probes

Mikrotherm. Manual radiator valves. To be precise.

Knürr Miracel. Knürr Miracel. 19 Network and Server Rack Platform 1.12 to

Messko. Messko. MTraB - Maintenance Free Dehydrating Breather Ordering specifications XX - XX - XXX - XX

Solenoid Valve Type 3962

225C-024T-05. Continuous control rotary drive without spring return. Technical data sheet. Description. Technical data. Actuators

Product data sheet. JUMO MIDAS Pressure Transmitter. Sales No. Order code JUMO AS /

G26 Corp L11 Revised LENNOXOEMPARTS.COM. Service Literature G26 SERIES UNITS

Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate

Hydraulic Control Solutions

Vacuum drying oven for non-flammable solvents

DIESEL-FUELED, BLOWN AIR, DUCTABLE HEATERS

MANUAL. * Supply plugs may differ to suit your wall socket. EN 3. Continue to press the MODE-button to combine charging program with charging options.

Butterfly Valves PN 6/10/16 for flanged connection

Safety at a high level!

RRV934. Multi-controller. Synco living

B MOTORSPORT COMPONENTS B13. Max Circuit Measurement Characteristic Current Thread Part Number Range Curve [A] Size Connector Figure Comment

Assisted lift operated 2/2-way solenoid valves Type EV250B

Elegant ECM. ELEGANT ECM air conditioners allow. The range is made up of 12 models: Ceiling Air Conditioner

USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR

Défumair XR. ventilation and cmv. fire grade - label CE. smoke-extraction fan extraction casing for kitchen at F advantages.

Heating, air-conditioning, cooling

Threaded Resistance Thermometers Model TR10-D, Miniature Design

2-Port Self-acting Temperature Control Valve Selection for Heating and Cooling Applications

T7079A,B Solid State Remote Temperature Controllers

Climate chamber with illumination

3/2-way Solenoid Valve, direct-acting, NC or NO

SEISMIC VELOCITY TRANSDUCER T1-40

Heating oven with mechanical control

Actuator for modulating control AME 435

DSRQ - DSRSQ - DSRSQ-THERM

Power consuption Motor (Motion) Power consuption Standby (end position) 1,0 W. Position feedback - Switching point

- Designed to meet with the environmental stresses of ships and heavy industry. SESOBS

Terminal Boxes Series 8146

PolyGard Carbon Monoxide CO Transmitter ADTX3 1110

Instruction Manual Differential Pressure Transmitter

3/2- and 2/2-way cartridge valve type BVE

SELECTION, APPLICATION AND MAINTENANCE

PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES

Compact pressure switch Flameproof enclosure Ex d Model PCA

Thermostatic actuator RAVV - for 2-way valves RAV-/8 (PN 10), VMT-/8 (PN 10), VMA (PN 16)

Installation, operation and maintenance manual TX 35A

Technical Data. Dimensions

MANUAL EN 3 SUPPLY PLUG* MAINS CABLE CTEK COMFORT CONNECT ABSORPTION, READY TO USE ANALYSE FLOAT, FULLY CHARGED PULSE, MAINTENANCE CHARGING

OEM Relative and differential pressure switch type 605

Data Sheet VITOSOL 100. Flat collectors for the utilisation of solar energy. Vitosol 100. Part nos. and prices: see price list

Solenoid Valve Island Type 3965

Pneumatic actuators The Original! Technics of the top class.

SCHMIDT ManualPress 300 Series Manual Presses with Process Monitoring

3-Component Measuring System

EN 3 ABSORPTION, READY TO USE ANALYSE BULK DESULPHATION SOFT START. L: 2000 mm MODE- BUTTON SUPPLY PLUG* SUPPLY

Single sub-base valve

Contents. Document information

DEK-REL- 24/1/SEN. Extract from the online catalog. Order No.:

HVAC Sensors Catalogue

Richter Twin Piston Quarter-turn Actuators

Turbine Flow Sensor Series VTR

Cold Room & Refrigeration System (Casserole Assembly) No of units: 1

MOUNTING AND OPERATING INSTRUCTIONS

CoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60

Control and Distribution Boxes made of Stainless Steel Series 8150

Introduction. Refrigerant Leak Detecting System. Feature and Benefits

BLACK TIE. Instructions Manual

KA/8000/M, KA/8000, ISO cylinder (Stainless steel) Magnetic & Non-magnetic piston, double acting

ECOCIAT. Domestic hot water heat recovery unit

kymanual or Automatic - it s your Choice

CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version)

VDL 53 - Vacuum drying oven for flammable solvents

TPM 006/99 Revision 1 VALID FROM: 8/2/2013 REPLACEMENT FOR TPM 006/99 FIRE SHUTTER

XL PREMIUM OIL COOLER KIT

Max primary circuit temperature 90ºC Max primary circuit temp. 90ºC Max secondary circuit temperature 45ºC Max secondary circuit temp.

Combi switchbox with integrated 3/2 way pilot valve

Pipe Temperature Sensors

H45 LED - Direct and indirect pendant

Control- and feedback head for integrated mounting on Robolux valves Type 2036

Proportional pressure regulators VPPE

SMD Rework Station TABLE OF CONTENTS

Rotary actuators Rotary wing drives Series RAK. Brochure

Transcription:

Types 507 to 577 Temperature Sensors with resistors Application Sensors for measuring temperatures in HVAC systems. Versions with resistors. Basic values according to Class B of DIN EN 6075. Table : Screw-in-, duct, contact, and outdoor sensors with resistors Screw-in sensor Duct sensor Contact sensor Outdoor sensor Number of resistors resistors See Table 4 Sensor length mm 80 60 50 60 50 400 60 to 80 Sensor shaft G ½ made of ) Brass.457 Nominal pressure Permissible temperatures Nickelplated brass PN 6 40 Medium C 0 to 50 60 to 400 0 to 50 0 to 0 35 to 85 Ambient C 0 to 70 0 to 70 0 to 70 0 to 0 35 to 85 Degree of protection acc. to EN 6059 Weight kg (approx.) IP 54 54 4 4 44 0.4 0.4 0.5 0.4 0.5 0.6 0.6 0.04 0. Compliance Type 507-507-7 507-6 507-47 507-46 507-48 57 567-57- Style Preferable scope of application Flow or return flow pipes, domestic hot water heating, heating systems Supply air, Flow or return mixed air, exhaust air flow pipes (non-corrosive air and gases) Exterior walls of buildings ) Flange connection with duct sensors instead of G ½ Edition October 05 Data Sheet T 50 EN

I II Table : Room sensors with resistors Room sensor with potentiometer kω with potentiometer and button with potentiometer and mode selector switch with potentiometer and step switch Number of resistors resistors See Table 4 Permissible temperatures Medium C 35 to 70 0 to 60 35 to 70 0 to 60 Ambient C 35 to 70 0 to 60 35 to 70 0 to 60 Degree of protection acc. to EN 6059 Weight kg (approx.) IP 0 30 0 30 Compliance 0. 0.08 0. 0.08 Type 557-557- 557-3 557-5 557-6 557-7 Style 0 Preferable scope of application Recreation rooms and offices Connection to controllers 557-557- 557-3 557-5 557-6 557-7 Automation system TROVIS MODULON TROVIS 6600 Controllers for HVAC systems TROVIS 5475- TROVIS 5476 TROVIS 5573 TROVIS 5575 TROVIS 5576 TROVIS 5578 TROVIS 5579 TROVIS 557 (PLC) (BE only) GPRS gateway Modbus I/O Electric process controllers TROVIS 6493-0/-3 TROVIS 6495- Electric actuators with process controllers TROVIS 575-7 TROVIS 5757-7 T 50 EN

Table 3: Immersion sensors with resistors (can also be used as contact sensors) ) Immersion sensor with thermowell/ contact sensor Number of resistors resistors See Table 4 Sensor length mm 50 Permissible temperatures Medium C 50 to 80 Ambient C 50 to 80 Degree of protection acc. to EN 6059 Weight kg (approx.) IP 5 0.3 0.3 0.5 Length of connecting cable m 3 5 Compliance Type 577-577-3 577-5 Style Preferable scope of application Immersion sensor with connecting cable. Thermowell required Flow or return flow pipes, domestic hot water heating, heating systems ) Accessories for Types 577-/-3/-5 Brass thermowell, G ½, PN 6 Immersion length 80 mm Order no. 099-0807 Immersion length 60 mm Order no. 855-5005 CrNiMo steel thermowell, G ½, PN 40 Immersion length 80 mm Order no. 099-0805 Immersion length 50 mm Order no. 099-0806 Immersion length 60 mm Order no. 855-50 Mounting kit for contact sensor Order no. 854-000 T 50 EN 3

Note It is not necessary to calibrate the line with temperature sensors with resistors. In cases where the length of line between sensor and controller exceeds 00 m, the cross-section of the wire must be at least.5 mm². The connecting cable between temperature sensor and controller must be routed separately from live power cables. Type 567 Contact Sensor suitable for pipes up to Ø 60 mm. On assembly, the supplied heat-conducting paste must be applied between the sensor (copper protective tube) and the pipe. Terminals for sensors (Types 57, 557 and 567) must have a maximum wire cross-section of.5 mm². Table 4: Resistance values for Type 507 to 577 Sensors with resistors Temperature C 35 30 5 0 5 0 5 0 5 0 5 0 Resistance Ω 86.5 88. 90.9 9.6 94. 960.9 980.4 000.0 09.5 039.0 058.5 077.9 Temperature C 5 30 35 40 45 50 55 60 65 70 75 80 Resistance Ω 097.3 6.7 36. 55.4 74.7 94.0 3. 3.4 5.6 70.8 89.9 308.9 Temperature C 85 90 95 00 05 0 5 0 5 30 35 40 Resistance Ω 38.0 347. 366. 385. 404.0 4.9 44.8 460.7 479.5 498.3 57. 535.8 Temperature C 45 50 55 60 65 70 75 80 85 90 95 00 Resistance Ω 554.6 573.3 59.9 60.5 69. 647.7 666.3 6.8 703.3 7.7 740. 758.6 Screw-in sensors Type 507- H/SW 7 Ø70 G½" M0x.5 80 89 60 50 Type 57; immersion depth adjustable between 60 and 80 mm Ø9 Sample application Pipe installations: a) On elbows, against the direction of flow b) In smaller pipes, positioned at an angle against the direction of flow c) At a right angle to the flow Ø70 H/SW4 65 M0x.5 85 90 0 0 Ø6 Ø6.3 Ø6.3 a b Type 507-4 H/SW4 H/SW7 c Ø70 G½ Ø9 M0x.5 85 0 60 50 400 4 T 50 EN

Contact sensor Outdoor sensor Type 567 Type 57- (color: RAL 906) 50 36 60 50 30 75 Ø4 3 8 Immersion sensors Type 577- Type 577-3 and Type 577-5 Thermowell for immersion sensor Type 577-, Type 577-3 and Type 577-5 Ø6 Ø6 SW 7 50 45 G½ 80 50 l ~45 Ø9 Length of connecting cable Type 577-: l = m, silicone connecting cable Type 577-3: l = 3 m, silicone connecting cable Type 577-5: l = 5 m, silicone connecting cable Bracket and cable tie in a mounting kit (order no. 854-000) A mounting kit (order no. 854-000) is required if a Type 577 Sensor is intended to be used as a contact sensor. The application range is between 40 and 05 C (briefly up to 45 C), the sensor is resistant against oil, fuel oil and grease. Apply heat-conducting paste (syringe) to the sensor. Clamp the sensor between the pipe and bracket. Fasten the sensor on a clean pipe using the cable tie.. 0.5 4.6 300 55 Min. tightening force 356 N T 50 EN 5

Room sensors Mounting On the wall of the room concerned at a height of.5 m Do not mount the sensor in alcoves or close to appliances which give off heat Type 557- Room Sensor 3 Type 557- Room Sensor R = k Pot. k 3 4 5 6 7 8 9 0 3 30 Type 557-3 Room Panel Pot. k Button 3 4 5 6 7 8 9 0 3 30 6 T 50 EN

Room sensors (continued) Type 557-5 and Type 557-7 Remote control with room sensor for changing the room temperature set point, with heating program switch Type 557-5 Room Sensor 0 Pot. 00 86 65 R = k 65 8 3 Continuous automatic operation Continuous night mode (reduced operation) Continuous day mode (rated operation) Type 557-6 Room Sensor 0 I II 3 4 5 6 7 I 8 II 9 0 3 30 Type 557-7 Room Panel 0 Pot. 00 lin 86 65 k 65 3 4 8 3 Continuous day mode (rated operation) Off/frost protection Continuous night mode (reduced operation) T 50 EN 7

Specifications subject to change without notice SAMSON AG MESS- UND REGELTECHNIK Weismüllerstraße 3 6034 Frankfurt am Main, Germany Phone: 49 69 4009-0 Fax: 49 69 4009-507 samson@samson.de www.samson.de T 50 EN 05--06 English