Model 97A00-1 KNX Gateway

Similar documents
USER GUIDE. Ethernet Configuration Guide (Lantronix) P/N: Rev 6

TCP/IP MODULE CA-ETHR-A INSTALLATION MANUAL

Configuring an A Series LED Sign Controller for your Network

User Manual. EtherUSB

3.1 RS-232/422/485 Pinout:PORT1-4(RJ-45) RJ-45 RS-232 RS-422 RS-485 PIN1 TXD PIN2 RXD PIN3 GND PIN4 PIN5 T PIN6 T PIN7 R+ PIN8 R-

for Windows Media Center User's Guide

BiPAC 7404V series. VoIP/(802.11g) ADSL2+ (VPN) Firewall Router. Quick Start Guide

WxGoos-1 Climate Monitor Installation Instructions Page 1. Connections. Setting an IP Address

ACU-1000 Manual Addendum Replacement of CPM-2 with CPM-4

Ethernet Connection Setup for CCU

IDDERO HOME SERVER. Quick start guide

HWg-STE HWg-STE PoE MANUAL

SNMP Web Management. User s Manual For SNMP Web Card/Box

BIT COMMANDER. Serial RS232 / RS485 to Ethernet Converter

Internet Telephony PBX system IPX-1980

Assign a static IP address for your computer. Please refer to the T3 in Troubleshooting guide if you need assistance.

KNX IP INTERFACE IN00A02IPI. Operating and installation manual

User s Manual TCP/IP TO RS-232/422/485 CONVERTER. 1.1 Introduction. 1.2 Main features. Dynamic DNS

Turn on all of your network devices and then check to see if the LEDs on the Access Point display normally as the diagram below describes.

Quick Installation Guide Network Management Card

1 INTRODUCTION. This document describes the procedure to upgrade LTMR.

To perform Ethernet setup and communication verification, first perform RS232 setup and communication verification:

USER MANUAL. PingBrother EPIW104 managed passive poe switch & IP watchdog

User Manual. EtherUSB

Setting up the Swann HD IP cameras

Voice Over Internet Protocol (VoIP) Configuration

Assign a static IP address ( ) for your computer. Please refer to T3 in Troubleshooting guide on page 10 if you need assistance.

Industrial L2+ Managed Gigabit/ 10 Gigabit Ethernet Switch. IGS-5225 Series. Quick Installation Guide

Connecting the DG-102S VoIP Gateway to your network

Assign a static IP address for your computer. Please refer to the T3 in Troubleshooting guide if you need assistance.

BEC 6200WZL. 4G/LTE Cellular Broadband Router. Quick Start Guide

Intel Active Management Technology with System Defense Feature Quick Start Guide

Innovative Electronics for a Changing World INDEX

ETHERNET WEATHER STATION CONNECTIONS Application Note 33

Networking Guide Redwood Manager 3.0 August 2013

Quick Installation Guide. Overview. GULFSIP ATA-G1S Quick Installation Guide

The GV-I/O Box 8 Ports provides 8 inputs and 8 relay outputs, and supports both DC and AC output voltages.

Quick Start Guide. DVR DS-7200HWI-SH Series DVR. First Choice For Security Professionals

How to setup EW-7438RPn with a Windows computer to extend an existing Wi-Fi network

EMBEDDED ACCESS CONTROL Hardware Installation Guide

Installation and Operation Guide

HC Products ILF-100WD User Manual

Easy Setup Guide for the Sony Network Camera

Starting Guide - Poseidon 3265 First steps for remote monitoring with Poseidon & GSM

Configuring Switch Ports and VLAN Interfaces for the Cisco ASA 5505 Adaptive Security Appliance

RouteFinder SOHO. Quick Start Guide. SOHO Security Appliance. EDGE Models RF825-E, RF825-E-AP CDMA Models RF825-C-Nx, RF825-C-Nx-AP

WLAN Outdoor CPE For 2.4G. Quick Installation Guide

Vantage RADIUS 50. Quick Start Guide Version 1.0 3/2005

Manual. IP Sensor and Watchdog IPSW2210. I P S W M a n u a l P a g e 1. Relay Output. Power input. 12VDC adapter LED Indicators. 2 Dry.

Table of Contents. Chapter1. Introduction Before Installation System Requirements... 1

801.11n Wireless Broadband Router

The GV-I/O Box 16 Ports provides 16 inputs and 16 relay outputs, and supports both DC and AC output voltages.

Ethernet. Customer Provided Equipment Configuring the Ethernet port.

Olson Electronics Remote Power Monitoring Meter

Ithaca itherm, POSjet & BANKjet Printers Ethernet Adapters Setup Guide

Allworx Installation Course

Configuring a Trimble Sps 461 using the Ethernet Connection GETTING THE GPS ON THE NETWORK HTTP PORT. By Bob Glover

Quick Installation Guide DAP Wireless N 300 Access Point & Router

3.5 EXTERNAL NETWORK HDD. User s Manual

User Guide for Windows 10

SLC 5/05 Processors Firmware/Operating System ControlFLASH Upgrade

RS-232/422/485, Power over Ethernet

DSL-G604T Install Guides

BASLER ACE QUICK INSTALLATION GUIDE

ADSL Router Quick Installation Guide Revised, edited and illustrated by Neo

LGAC-KNX PROGRAMMING MANUAL. Integrations V1.0 TECHNICAL SUPPORT. Tel (+34)

IPX AUTOMATIC IP NETWORK LOSS BACKUP A/B SWITCH INSTRUCTION BOOK IB

DWL-2000AP. Before You Begin. Check Your Package Contents

Web Power Switch III User s Guide Revision LPC-3

APPLICATION NOTE. Ethernet Configuration Guide for D-500 D-700

Dominion KX II-101-V2

Honeywell Internet Connection Module

Application & Quick-Start Guide

SNMP Web card. User s Manual. Management Software for Uninterruptible Power Supply Systems

PRODUCTIVITY THROUGH INNOVATION 600 CONTROL DIRECT DRIVE TECHNICAL/OPERATION MANUAL

Gigabit Content Security Router CS-5800

IPD2220ES/LD2222E. Quick Installation Guide. 1080P HD Dome IP Camera IPD2220-IVS. 1080P HD IVS Dome IP Camera SD2222E

ABB solar inverters. User s manual ABB Remote monitoring portal

DRO-210i LOAD BALANCING ROUTER. Review Package Contents

Wired / Wireless / PoE. CMOS Internet Camera ICA-107 / ICA-107W / ICA-107P. Quick Installation Guide

FINS Gateway For OMRON PLCs

Quick Installation Guide DSL-2750U. 3G/ADSL/Ethernet Router with Wi-Fi and Built-in Switch

Quick Installation Guide DSL-2750U/NRU. 3G/ADSL/Ethernet Router with Wi-Fi and Built-in Switch

ENET-710. ENET Ethernet Module ENET-710 JAN / 06 FOUNDATION

Configuring a BEC 7800TN Wireless ADSL Modem

Kurz MODBUS Client User s Guide

Deployment Guide: Transparent Mode

How to configure DVR and computer for running Remote Viewer via IP network

AW-HE60 Firmware Upgrade Procedure

SNMP-1 Configuration Guide

Type Message Description Probable Cause Suggested Action. Fan in the system is not functioning or room temperature

Prestige 324. Prestige 324. Intelligent Broadband Sharing Gateway. Version 3.60 January 2003 Quick Start Guide

Prestige 324 Quick Start Guide. Prestige 324. Intelligent Broadband Sharing Gateway. Version V3.61(JF.0) May 2004 Quick Start Guide

Cisco SPA Phones User Guide Bicom Systems

Broadband Router ESG-103. User s Guide

DNS-312H Network Attached Storage

DVQ-2, DMR8RT, DMR16RT QUICK-START GUIDE

BabyWare Imperial PC Software

Tutorial: Configuring GOOSE in MiCOM S1 Studio 1. Requirements

TN Using FileZilla FTP Server with a DT80 Series Logger

Transcription:

Model 97A00-1 KNX Gateway Description The HAI by Leviton KNX Gateway allows an HAI controller (Omni LTe, Omni IIe, OmniPro II, Lumina, and Lumina Pro) to communicate with and control KNX devices on the bus. Lighting, temperature and energy management, and motors (window coverings, shades, shutters, etc.) are among the many KNX devices that can be controlled. The KNX Gateway provides an interface between the HAI controller and the KNX network by mapping specific data points of each KNX device to a unit or thermostat number on the HAI controller. Overview The following is an overview of the inputs and outputs on the KNX Gateway: Ethernet (PoE) KNX Gateway Top View 1 2 3 RS-485 Port Shield 485-485+ N/C N/C N/C PWR PWR Connector Reset Status Status Reset Button Program Power Status Status 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 RS-485 Modular Port RS-485 Terminals Power Terminals Ethernet (PoE) Port Program Status LED Power Status LED Connector Reset Status LED Status LED 10 Reset Button RJ-25 modular connector which provides an RS-485 serial interface to the HAI controller. The 485+ and 485- terminals can be used as an alternative to the RS-485 Modular Port. The PWR terminals can be used as an alternative or backup to the PoE Ethernet Port. Provides a connection to the local network for configuring the KNX Gateway using its built-in web interface. It also allows the KNX Gateway to be powered when using a Power Sourcing Equipment (PSE) device, such as a PoE network switch, hub, or power injector. The Program Status LED is illuminated during a firmware update, flashes when it is first powered up (while it checks for a new firmware update), and it is turned off while it is in normal operation mode. The Power Status LED is illuminated when the KNX Gateway is powered using either the PoE Ethernet Port or by providing 12-24V AC/DC to the PWR terminals. Connects the KNX Gateway to the KNX bus. The Reset Status LED provides status while operating the Reset Button. The Status LED is used to monitor the interface. The LED is illuminated when there is proper voltage on the bus and the LED is turned off when the voltage on the bus is <=18V. The Reset Button is used to reset the KNX Gateway to its factory default settings. 97I00-1

Installation Install the KNX Gateway as follows: 1. Connect the KNX Gateway to the KNX bus using the Connector. 2. Connect the KNX Gateway to a serial port on the HAI controller. The interface between the KNX Gateway and the HAI controller utilizes an RS-485 serial connection. a. Connect the supplied straight-through modular cable (i.e. opposite from a standard telephone cable) to the RS-485 Modular Port on the KNX Gateway. Note: the pin out for this cable is Pin 1 to Pin 1, Pin 2 to Pin 2, Pin 3 to Pin 3, and Pin 4 to Pin 4. Alternatively, the terminals marked 485+ (Pin 5 on the modular connector), 485- (Pin 4 on the modular connector), and Shield (optional) can be used. b. Connect the other end of the modular cable to one of the built-in serial ports on the HAI controller. Configure the serial interface on the HAI controller for RS-485 communications by moving the corresponding interface jumper (JP1-JP5) to the "485" position. 3. Power the KNX Gateway and connect it to the local network. When connecting the KNX Gateway to the network, it can also be powered using a Power Sourcing Equipment (PSE) device, such as a PoE network switch, hub, or power injector which provides the power. A Cat-5 or better (4-pair) cable is required. Run the Cat-5 cable between the location of a PoE network switch, hub, or power injector and the location of the KNX Gateway and plug it into the Ethernet (PoE) Port. Alternatively, the KNX Gateway can be powered using the two terminals marked PWR. When powering the KNX Gateway using the PWR terminals, use a 12-24 Volt AC or DC power supply. The PWR terminals are not polarity sensitive. Configuring the KNX Gateway It is important that the KNX programmer make available all of the device parameters that you will need. This is especially important in the case of thermostats since not all of the features for a standalone thermostat would need to be configured (e.g. setpoints being set remotely). If the KNX programmer does not assign this feature a Group Address, you will not be able to associate it with the HAI controller through the KNX Gateway. To set up the KNX Gateway mapping, it is recommended that you obtain a Group Addresses Details Report from the KNX programmer. This can be printed from ETS4 software through the Print function. The configuration for the KNX Gateway is performed through a built-in web interface. To access the web interface: 1. Configure the network settings of the KNX Gateway. By default, the IP address of the KNX Gateway is set to 192.168.0.4. Based on your current network configuration, there are several methods to initially access the device. a. If your local network is using the 192.168.0.X subnet and IP address 192.168.0.4 is available (no other device on the network is using this IP address), you can access the web interface directly by opening a web browser and entering the IP address (i.e. 192.168.0.4) into the address bar. i. If the IP address is already used by another device, you can locate the device with this address and physically remove it from the network, change its IP address, or use a crossover cable and change your computers IP address to match the subnet. b. If your network uses a different IP subnet (e.g. 192.168.1.X), you will need to change your computers IP address to match the subnet and use a crossover cable for initial configuration. 2. Once your computer is on the same subnet as the KNX Gateway, you can access the web interface by opening a web browser and entering the IP address into the address bar (i.e. 192.168.0.4). Page 2

3. A Security Warning may be displayed. If so, a. Check the I accept risk and want to run this application checkbox. b. Click on the Show Options arrow. c. Check the Always trust content from this publisher checkbox. d. Click the Run button. a b c 4. You will be prompted with a login screen. By default, the user name is admin and the password is admin. Settings Page: Allows you to assign an IP address and subnet mask to match your existing network, assign the KNX Physical Address of the KNX Gateway, and change the username and password. a. If previously changed to access the KNX Gateway web interface, you can now set your computer s network settings back to correct settings for your existing network. b. You can now access the KNX Gateway using the new IP address. If desired, you can also change the username and password for the device at anytime by accessing the Settings page. Once all changes are made, click the Update Settings button to apply the changes. Firmware Update: Allows you to update the firmware in the KNX Gateway. To update the firmware: a. Click the Firmware Update button. b. Select the firmware file from the location on the PC where it was saved. c. Click Open. The firmware will begin updating. During this process, you will not see any visible status. When the process is complete (about 2 minutes), a confirmation dialog is displayed. Click the OK button. The firmware has been updated. Page 3

Adding Devices into the KNX Gateway Once the HAI controller is configured for KNX (see HAI Controller Setup in this document) and you have a list of the Group Address Detail, you can begin to add devices into the KNX Gateway. Press the Configuration Page button. Configuration Page: Allows you to add KNX devices (as defined in the Group Addresses Details Report from the ETS software), assign HAI Opcodes, and map them to units on the HAI controller. It also allows you to make a backup of the configuration file and restore from a previous backup of a configuration file. Below is a brief description of the fields on the Configuration Page of the KNX Gateway: Enable: This box must be selected to enter anything in the current line. If you uncheck this selection after you have entered a device, it will be removed when the Update Configuration operation is performed. Description: Enter a user friendly name for identifying the device/function. KNX Type: Enter the data type that the selected device uses. Options are 1 bit (on/off), 6 bit (scene), 1 byte (dimmer value), or 2 byte (temperature). KNX ID: This is a placeholder for the table. It is recommended that this value is incremented sequentially (0, 1, 2, etc.). KNX Function: The function determines the device s capabilities. Options are Read, Write, or Read and Write. KNX Main-Group: The main group of KNX devices which identifies the KNX devices. KNX Mid-Group: The mid group address of KNX devices which further identifies KNX devices. KNX Sub-Group: The sub group and final identifying address of the device on the KNX system. HAI Opcode: The HAI function/command assigned to the device for either the unit or the thermostat. HAI ID: The address assigned to the device in the HAI system. Adding a Unit (Dimmer, Relay, or Motor) For example, Unit 1 will control Relay 1 on a 4-Relay Actuator. In the HAI controller, give Unit 1 a name (such as Relay 1) and change the House Code format to KNX. Save the changes in your file and write Names and Setup to the HAI controller. On the KNX Gateway: 1. Check the Enable box for the first line. 2. Give the association a description (e.g. Relay 1). 3. Set the KNX Type to 1 1 bit (on/off) since this is a device that will simply turn on and off. 4. Since this is the first device added, set the KNX ID to 0. 5. The KNX function is assigned 3 Read-Write so that the unit can be commanded and so that it can report its status (the device must be set up on the KNX system to allow for both control and status). 6. From the Group Address Report, you can determine the assigned address for the device. In this example, the device is assigned an address of 1/0/1 (Main-Group/Mid-Group/Sub-Group) so each should be configured accordingly. 7. Set the HAI OpCode for On/Off functionality 01-Unit. 8. Set the HAI ID to match the unit number on the controller. In this case, it is Unit 1 9. Click the Update Configuration button to write the changes to the KNX Gateway You should now be able to control the KNX device through the HAI controller. Page 4

Adding a Thermostat The thermostat setup is very similar as adding a unit, except that each parameter of a thermostat that will be controlled or viewed must be setup and individually mapped in the KNX Gateway. In this example, data points have been added for the Current Temperature, the Heating Set Point, and the Mode (Heating or Cooling). On the KNX Gateway: 1. Check the Enable box for the next available line. 2. Give the association a description (e.g. Current Temp). 3. Set the KNX Type to 4 2 byte (temperature). 4. Since this is the second device added, KNX ID is set to 1. 5. The KNX function is assigned 1 Read since the current temperature is reported and cannot be commanded. 6. From the Group Address Report, you can determine the assigned address for the device. In this example, the device is assigned an address of 1/0/4 (Main-Group/Mid-Group/Sub-Group) so each should be configured accordingly. 7. Set the HAI OpCode for 10-Therm Current. 8. Set the HAI ID to match the thermostat address on the controller. In this case, it is Thermostat 1. 9. Click the Update Configuration button to write the changes to the KNX Gateway. For the rest of the items, follow the steps as above but replace the key parameters as shown to match the devices properties as well as their KNX addresses. Once all of the changes are made, click the Update Configuration button to write the changes to the KNX Gateway. Backup Configuration: Allows you to create a backup for the configuration file that is stored in the KNX Gateway. This file will be useful if you ever need to replace the KNX Gateway or reset it to its factory default settings. a. Press the Backup Configuration button. b. Enter a file name and browse to the folder location where the file will be stored. c. Click the Save button. The file is stored in comma-separated values (CSV) format. Restore Configuration: Allows you to restore the configuration of a KNX Gateway from a previously backed up configuration file. This is useful if you needed to replace the KNX Gateway or reset it to its factory default settings. a. Press the Restore Configuration button. b. Browse to the folder location where the file is stored and select it. c. Click the Open button. When the process is complete, a confirmation dialog is displayed. Click the OK button. The configuration has been updated. Press the Update Configuration button to store the configuration in the KNX Gateway. Page 5

HAI Controller Setup To configure the KNX Gateway, the HAI controller must be utilizing controller firmware 3.11 or later: 1. Configure the serial port on the HAI controller where the KNX Gateway is connected to KNX Gateway. 2. Any units or thermostats that will be associated with the KNX system must be changed to use KNX. For units, this means changing the House Code Format to KNX (this affects a group of 16 unit numbers) and for thermostats and temperature devices, this means changing the Protocol Address for each thermostat to KNX. Resetting to Factory Default To reset the KNX Gateway to its factory default configuration: 1. Make sure that the KNX bus is plugged into the Connector and the Status LED is illuminated. 2. Press the Reset Button momentarily to illuminate the Reset Status LED. Press the Reset Button again. 3. The factory default configuration is complete when the Reset Status LED is turned back off. 4. Cycle power to the KNX Gateway. Page 6