020: 2015 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)

Similar documents
LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & Instructions For Installation, Operation & Maintenance

SURGE PROTECTIVE DEVICES

R.C.C.B. s two-pole LEXIC

SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.

Application Switchgear for industrial and commercial applications. U e V AC 230/ (per pole)

SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR SINGLE CORE,UNARMOURED L.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA

The complete range of consumer switchboards and switchgear

Molded Case Circuit Breaker Specifications Bulletin Number 140U-D

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.

RM4TG20 three-phase network control relay RM4-T - range V

Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection

FAQs-Main switchboard design criteria

5SV Residual Current Protective Devices

UGVCL/SP/591/11KV HT AB CABLE

Type: EASY719 DC RC Article No.: Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

How To Build A Low Voltage Capacitor Lvcp

Technicaldata General

RM17TE V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

Unified requirements for systems with voltages above 1 kv up to 15 kv

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV

High-Voltage Circuit-Breakers 3AP1/ kv up to 550 kv. Power Transmission and Distribution

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2...

Electronic overload relay EF19 and EF45

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

Guidance for upgrading to GB (IEC : 2005, MOD)

Uncompromising safety and comfort The next generation of miniature circuit breakers MCB S 200/S 200 M

LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A V AC coil

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH

PSR The compact range Description

RM35UA13MW. range V. Main. Product or component type. Relay monitored parameters

Thermal-Magnetic Circuit Breaker M1-..

Type: DILM50(230V50HZ,240V60HZ) Article No.:

CLAMPS CONNECTORS & EQUIPOTENTIAL RING

UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution

ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA

High Voltage Circuit Breakers 3AP Type 72.5 kv to 800 kv Answers for energy.

Electronic overload relay EF65, EF96 and EF146

NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals

IEC >>> IEC GUIDE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

Type: DILM115(RAC240) Article No.: Sales text Contactor,55kW/400V,AC operated. Ordering information

SPECIFICATIONS FOR 220KV CAPACITOR VOLTAGE TRANSFORMER. The equipment is required for 220KV system. The system data is given as under:

Type: DILM9 10(24VDC) Article No.:

METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast.

Bimetallic Overload Relay Specifications

Bulletin 1489 Circuit Breakers. Selection Guide

Residual Current Circuit Breaker

Electrical Practices for Construction Work

DRM75A 230V 20/100A DIN rail single phase two wire energy meter

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU

ZS6-S Screw Clamp Terminal Blocks Disconnect with blade

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL MTE Corporation

DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)

Type: DILM32 10(24V50HZ) Article No.:

ZS25 Screw Clamp Terminal Blocks Feed-through

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.

W DATA SHEET: RESIDUAL CURRENT CIRCUIT BREAKER A, SERIES BCF0 AND BCF6

Vario-Series Accessories

ADM1TE 5/30A DIN rail single phase two wire energy meter

VEO. V4PF480Y/277VSYTK02 Art.Nr.: V4PF480Y/277VSYTK02P Art.Nr.: TECHNICAL DATA

AF / AF09Z stack 3-pole Contactors AC / DC Operated - with Screw Terminals

ZS4-S-T Screw Clamp Terminal Blocks Disconnect with blade - with test socket

Low Voltage Products. Switches Automatic Transfer Switches

Specification N : NPS - 63/8. Underground Power Cable Covers

Programmable Room Thermostat 7 Day (5-2 Day) Models: / Power Supply: Battery / Mains

Quick Connect. quick - simple - efficient.

ZS4-SF1-T Screw Clamp Terminal Blocks For 5 x 20 and 5 x 25 fuses - with test socket

CompactLogix Power Supplies Specifications

LightingEurope EU Compliant Requirements Products Sheets for LIGHTING COMPONENTS

40 Series - Miniature PCB/Plug-in relays A. Features

Single-phase ( V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

TYPE TEST CERTIFICATE OF SHORT-CIRCUIT PERFORMANCE. A three-phase outdoor oil-immersed distribution transformer

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle

NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N

Bulletin 150 SMC Flex Smart Motor Controller Specifications

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

KAM A Lighting Busbar System KAP A Plug-in Busbar Distribution System

Series 8146/5-V37 and Series 8150/5-V37

INTERNATIONAL STANDARD

E-STOP relays, safety gate monitors

Transformer Bushings for GIS

Trade of Electrician. Three-phase Distribution Boards And Socket Circuits

SINEAX U553 Transducer for AC Voltage

Securing your electrical installations Prisma,

Manual motor starter MS116

SF 6 Gas Insulated Switchgear Type SDF for 170 kv

Three-phase monitoring relay CM-PFE

User s Manual Before using the inverter, you need to read and save the safety instructions.

Circuit Breakers. Next Generation of Protection Capabilities

High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv

Emergency stop As an emergency switching off/emergency stop device. Standards According to IEC/EN , VDE 0113 Part 1

Transcription:

020: 2015 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 8051 Fax: +94 11 232 5387

CONTENTS Page 1.0 Scope 3 2.0 System Parameters 3 3.0 Service Conditions 3 4.0 Applicable Standards 3 5.0 Technical Requirements 4 6.0 Basic Features 4 7.0 Other Mandatory Requirements 6 8.0 Quality Assurance 6 9.0 Inspection and Testing 7 10.0 Information to be supplied with the Offer 8 11.0 Annex 8 Annex A: Schedule of Guaranteed Technical Particulars 9 Annex B: Non-Compliance schedule 10 2/10

SPECIFICATION FOR MINIATURE CIRCUIT BREAKER (MCB) 1.0 SCOPE This Specification covers the general requirements of the design, manufacture and testing of Miniature Circuit Breaker, to be used in place of Service Cut-outs to provide overcurrent and short circuit protection. Miniature Circuit Breaker shall be supplied as indicated below. a) MCB without Enclosure cover b) MCB complete with Enclosure cover 2.0 SYSTEM PARAMETERS (a) Nominal voltage 400/230 V (b) System highest voltage 415/240 V (c) System frequency 50 Hz (d) Method of earthing Effectively earthed (e) System fault level 25 ka 3.0 SERVICE CONDITIONS (a) Annual average ambient tempeature 30 C (b) Maximum ambient temperature 40 C (c) Maximum relative humidity 90% (d) Environmental conditions Humid tropical climate with polluted atmosphere (e) Operational altitude From M.S.L. to 1900 m above M.S.L. (f) Isokeraunic (Thunder days) level 100 days 4.0 APPLICABLE STANDARDS The equipment and components supplied shall be in accordance with the latest editions of the standards specified below and amendments thereof. (a) Electrical accessories Circuit Breakers for overcurrent IEC 60898-1:2003 protection for household and similar installations. Part 1: Circuit Breakers for A.C. operation (b) IEC 60529:2013 Degrees of protection provided by enclosures (IP Code) However in the event of a discrepancy CEB specification supersede above standards. Sri Lanka Customs requires the conformity of all the MCBs imported to Sri Lanka be complied with the Sri Lanka Standards (SLS 1175: 2005). Address and the contact details of the Sri Lanka Standards Institution: Sri Lanka Standards Institution 17 Victoria Place, Elvitigala Mawatha,Colombo 08. Tel: 94 11 2671567-72 Fax: 94 11 2671579 E-mail: info@slsi.lk Website: http://www.slsi.lk 3/10

5.0 TECHNICAL REQUIREMENTS Rated Current (I n ) 6A, 16A or 32A Rated voltage ( V n ) (i) 230V AC for single phase (ii) 400V AC for three phase Rated impulse withstand voltage (1.2/50 µs) 4.0 kv peak Rated Power frequency withstand voltage 1000V Rated short circuit capacity 10kA Clearance between live parts which are separated when the main contacts are in the 4mm open position (min.) Clearance between live parts of different polarity (min.) 3mm i) Overload tripping Tripping Characteristic Conventional no tripping current - 1.13 I n Conventional Tripping current - 1.45 I n ii) Instantaneous Tripping - Above 5 I n up to and including 10 I n No. of Poles Single, Two, Three or Four pole as per clause 6.2 (a) of the specification Degree of Protection IP 20 Mechanical and electrical endurance 4,000 Nos. of operating cycles at rated current Mounting MCB : DIN rail Enclosure : Surface 6.0. BASIC FEATURES 6.1 Design The Miniature Circuit Breaker shall be a compact electro-mechanical device for making, breaking and disconnecting a circuit in normal conditions and protecting circuit in abnormal conditions such as over-current and short circuit. The circuit breaker time current operating characteristics shall conform to type C, table 7 of IEC 60898-1. The Miniature Circuit Breaker shall be of wire in, wire out type and basically comprise the following features; (a) Independent Manually operated latched switching mechanism with trip free release. (b) Arc-quenching chamber. (c) Overload protection. (d) Instantaneous Short circuit protection (e) Safe Disconnection of load from the source. The single phase Miniature Circuit Breaker shall be of Single or two pole type suitable for operating on 230V supply and three phase Miniature Circuit Breaker shall be of three or four pole type suitable for operating on 400 V supply. 6.2 Construction (a) Miniature Circuit Breaker Miniature Circuit Breaker of following classification shall be supplied with enclosure or without enclosure (a) Single pole circuit breaker (b) Two pole circuit breaker with one protected pole (c) Three pole circuit breaker with three protected poles. (d) Four pole circuit breaker with three protected poles. 4/10

The insulated case of the MCB shall be made out of moulded insulating material possessing high thermal stability and good mechanical strength to reasonably withstand rough usage without any fracture or permanent distortion. The MCB shall be suitable for DIN rail mounting. (b) Enclosure The enclosure shall be made out of moulded insulating material possessing high thermal stability and good mechanical strength to reasonably withstand rough usage without any fracture or permanent distortion. The material of the enclosure shall be UV protected and fire retardant. It shall be treated to withstand ultra violet radiation to prevent the deterioration of the material due to direct sunlight and shall withstand a temperature of 150 C. The enclosure shall be suitable to fix MCB and shall be suitable for panel/surface mounting with screws. Necessary screws shall also be provided with the enclosure. 6.3 Terminals The pillar terminals of the MCB shall have provision for accommodating and securely clamping the incoming and outgoing copper service wires sizes as indicated below; Current ratings Sizes of service wire (A) (mm²) 6, 16, 32 16 Temperature rise for terminals and accessible parts shall conform to the Table 6 of IEC 60898-1. 6.4 Operating Mechanism The Operating Mechanism of the MCB shall be of independent manual operation type (for closing and opening operation) and designed for automatic tripping on over-current and short circuit. The MCB Shall be provided with trip free mechanism Both the "On" and "Off" positions of the Circuit Breaker shall be clearly indicated. The indication shall be clearly visible to the operator when the Circuit Breaker is mounted in the normal manner. The operating mechanism of all the poles shall be according to the clause 8.1.2 of IEC 60898-1. 6.5 Contacts The contacts shall comply with clause 8.1.4.4 of IEC 60898-1, be of high current carrying capacity with good arc resistance property. The breaker shall be provided with arc chutes enclosing the contacts of each pole or a similar device which should serve to quench the arc during breaking. 6.6 Overload Release A delayed over-current release shall be fitted in each phase with inverse characteristics. 6.7 Short Circuit Release An instantaneous short circuit release shall be provided to trip the circuit breaker within 0.1 sec. during short circuit condition. 6.8 Mechanical and Electrical Endurance The mechanical and electrical endurance of the Miniature Circuit Breaker shall not be less than 4,000 operating cycles conforming to IEC 60898-1. 5/10

7.0 OTHER MANDATORY REQUIREMENTS 7.1 Experience The manufacturer shall have at least 10 years experience in manufacturing and supply of offered type of MCBs and manufacturer shall furnish documentary evidence with the offer to prove his manufacturing experience. 7.2 Marking Each Miniature Circuit Breaker shall be marked in a durable manner with the following particulars conforming to IEC 60898-1 and other CEB requirements. These markings shall be located in a place such that they are visible and legible when the circuit-breaker is installed. (a) Manufacturer's name or Trade mark (b) Type designation, Catalogue Number or serial Number (c) Rated voltage (d) Rated current (I n ), and instantaneous tripping type (e) Rated frequency, if the circuit breaker is designed only for 50Hz (f) Rated Short-circuit capacity, in amperes (g) Indication of the open and closed position, with O and I respectively (h) The letters "CEB" shall be engraved on the front side of the MCB cover. Stickers are not acceptable 7.3 Packing The Miniature Circuit Breaker of same current rating, breaking capacity and number of poles shall be packed together in a box made out of biodegradable material. Each box shall contain a maximum of 100 MCB s of the same Type. Each box shall be clearly marked with the following information; (a) Name of Manufacturer (b) Country of Manufacture (c) Operating Voltage (d) Rated Continuous Current (e) Breaking Capacity (f) Number of pole (Single phase/three Phase) (g) Quantity (h) Gross Weight 7.4 Samples Two samples, for each category of MCB offered shall be submitted with the offer. These samples shall not be return to the Supplier. 7.5 Technical Literature and Drawings In addition to the literature identified in clause 9.0 and 10.0, the followings also have to be submitted. A minimum of 02 catalogues indicating the technical literature and dimensional drawings of the MCB shall be supplied with the MCB. 8.0 QUALITY ASSURANCE The manufacturer shall possess ISO 9001:2008 Quality Assurance Certification valid throughout the delivery period of this bid, for the manufacture of Miniature Circuit Breakers for the plant where the Miniature Circuit Breaker is being manufactured. The Bidder shall furnish a copy of the ISO certificate certified as true copy of the original by the manufacturer, along with the offer. 6/10

9.0 INSPECTION AND TESTING 9.1 Type Tests Following Type Test Certificates conforming to IEC 60898-1 shall be provided with the offer. (a) (b) (c) (d) (e) (f) (g) (h) (i) (j) (k) (l) (m) (n) Indelibility of marking Reliability of screws, current carrying parts and connections Reliability of terminals for external conductors Protection against electric shock Dielectric properties and isolating capability Temperature rise 28 days test Tripping characteristic Mechanical and electrical endurance Short Circuit Resistance to mechanical shock and impact Resistance to heat Resistance to abnormal heat and fire Resistance to rusting Test Certificates, performance curves, table, etc., based on the type tests conforming to the relevant standard shall be supplied along with the offer for evaluation purpose. Test certificates referred to shall be from an accredited independent testing laboratory acceptable to the purchaser. Proof of accreditation by a national/ international authority shall be forwarded with the offer. Test reports shall be complete including all the pages as issued by the testing authority. Parts of test reports shall not be acceptable. 9.2 Routine Tests The following Routine Test as per annex I of IEC 60898-1 shall be carried out on all units and test report shall be furnished for the observation of the Engineer appointed by the purchaser at the time of inspection. (a) Tripping tests (b) Verification of clearance between open contacts 9.3 Inspection The Successful bidder shall make necessary arrangements for pre-shipment inspection by an Inspector sent by the CEB and to carry out in his presence necessary Sample / Acceptance tests on equipment and material offered. Routine test reports as per IEC 60898-1 shall also be made for the observation of the inspector. CEB may waive off the inspection with the condition of carrying out the acceptance tests by an independent testing authority acceptable to CEB. In such a situation a notice of waive off will be issued in advance to the supplier. 9.4 Acceptance / Sample Tests The following Acceptance /Sample Test as per annex I of IEC 60898-1 shall be witnessed by the representative of the purchaser. (a) Tripping tests (b) Verification of clearance between open contacts 7/10

10.0 INFORMATION TO BE SUPPLIED WITH THE OFFER The following shall be furnished with the offer. (a) Catalogue specifically indicating the type, technical literature of the MCB offered (b) Duly filled schedule of particulars (Annex A) (c) ISO 9001:2008 quality assurance certification (d) Dimensional Drawing (e) Time /current characteristic curve for each type/ rating (f) Duly filled noncompliance schedule (Annex B). Even if there is no noncompliance, a nil report shall be submitted (g) List of utilities outside the country of manufacture with contact details (name, email address, telephone number, etc ), to whom the manufacturer has supplied MCB for past 10 years (h) Type test reports in accordance with clause 9.1. Failure to furnish the above information and sample in accordance with clause 7.4 will result in the offer being rejected. 11.0 ANNEX Annex A - Schedule of Guaranteed Technical Particulars - To be filled by the manufacturer. Annex B - Non-Compliance schedule To be filled by the manufacturer/bidder 8/10

SCHEDULE OF GUARANTEEDED TECHNICAL PARTICULARS Annex- A (Following Information shall be furnished with the offer for each rating) 1. Applicable Standard 2. Manufacturer s name and Trade mark 3. Type /Model no. 4. No. of Poles (i) Clearance between live parts which are separated when the main contacts are in the open position (min.) (ii) Clearance between live parts of different polarity (min.) (mm) (mm) 5. Rated frequency (Hz) 6. Rated operational voltage i) Single Phase (V) ii) Three Phase 7. Rated Continuous current (A) 8. Rated impulse withstand voltage (1.2/50 µs) (kv) 9. Rated short time withstand current (ka) 10. Type of over current release 11. Type of short circuit current release 12. Rated short circuit making capacity (peak) (ka) 13. Rated short circuit breaking capacity (rms) (ka) 14. Reference ambient air temperature ( o C) 15. Material of contacts 16. Type of moulded insulating material 17. Whether the switching mechanism is 18. (a) Manual Independent Operation Type (b) Trip Free operation type Size of the service wire which can be accommodated by the terminals of MCB (a) Maximum (b) Minimum 19. Whether the Arc Chute is provide to quench the arc. 20. Warranty period 21. Mechanical and electrical endurance (V).. Signature of the Manufacturer and seal.. Date I/We certify that the above data are true and correct Signature of the Bidder and seal 9/10.. Date

Annex B Non-Compliance Schedule On this schedule the bidder shall provide a list of non-compliances with this specification, documenting the effects that such non-compliance is likely to have on the equipment life and operating characteristics. Each non-compliance shall be referred to the relevant specification clause. Clause No. Non-Compliance. Signature of the Manufacturer/bidder and seal.. Date 10/10