Storm Trapper H.E. (high energy) low-voltage distribution-class MOV surge arrester

Similar documents
New Distribution Class Arrester Ground Lead Disconnector Design Enhances Detonation Reliability and Improves Arrester Performance

Current Transformers

AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle

Secondary Unit Substations

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH

Project Name: Nortrax Section Project No: SURGE PROTECTION DEVICES Page 1

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp

BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET

Transient and Lightning Protection for the Water Industries

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV

Applications. Remote Display Mounting Kits

METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast.

Lightning Arresters P KVA P KVA. Description & Installation

Instruction / Installation Sheet DataComm Electronics WH-KIT Flat Panel TV Cable Organizer Kit with Duplex Power Solution

CURRENT TRANSFORMER MODEL 546 UL1015 #16 AWG LEAD WIRE, STANDARD LENGTH IS 24" 1 X

Mini Power-Zone Unit Substation Product Description. Product Description. Features. Typical Applications

LUXEON LEDs. Circuit Design and Layout Practices to Minimize Electrical Stress. Introduction. Scope LED PORTFOLIO

Distribution Dry Type Transformers

SURGE PROTECTIVE DEVICES

ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A

Section 21. Telecommunication Hardware. BuyLog Catalog 21-1

SF 6 Gas Insulated Switchgear Type SDF for 170 kv

HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80

1ZSC AAC en, Rev. 7. Resin impregnated paper bushing, oil to air, type GSB Technical guide

Veri*Lite Deadend & Suspension Insulators for 15-69kV Applications

Transformer Bushings for GIS

Industrial Control Power Transformers

PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES

Metallic and Non-Metallic Air Conditioning Disconnects. A Complete Family of. Disconnects with Exclusive Time Saving Features

ELECTRIC METERING COMMERCIAL & INDUSTRIAL

Stand Alone POTS Fiber Optic System. P31372 Station (Subscriber) Unit P31379 Remote (Exchanger) Unit. Description & Installation

Mini Power-Zone Unit Substation

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC EXTERNAL SIDEMOUNT SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671B SECTION 16671B

Installation Guide Content for P250xV-240 microinverters

STREETLIGHT SYSTEM GROUNDING AND BONDING

Power surges can also be generated by equipment in your facility such as:

PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors

3/2-way Solenoid Valve, direct-acting, NC or NO

TSn SERIES Surge Protective Device

Primary and Secondary Electrical Distribution Systems

12-Volt 10-Amp Regulated Power Supply

8146/5 Series Breaker Panelboards

Trade of Electrician. Three-phase Distribution Boards And Socket Circuits

NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms

Protect your home and family with Advanced Technology from Cutler-Hammer

Explosion proof enclosures

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N

Fundamentals of Power

Bulletin 150 SMC Flex Smart Motor Controller Specifications

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution

Z-TRAUQ INC. Tel.: (450) Fax: (450)

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS

CPS Y S K CPS Y S C

SANS : 2008 CODE OF PRACTICE THE WIRING OF PREMISES Part 1 : Low Voltage Installation

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

DRM75A 230V 20/100A DIN rail single phase two wire energy meter

Chapter 9. Bonding and Grounding

SWITCH! DESCRIPTION. ENVIRONMENTAL SPECIFICATIONS Operating Temperature: 0 C to +40 C SPECIFICATION SHEET:

ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS

BLUE RIBBON CORP. BC001 Birdcage Installation Manual

Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy

Series /16 DIN Multi-Mode Bar Graph Display Timer TIMERS PRODUCT HIGHLIGHTS

DC disconnects for solar photovoltaic installations. Connecting the. power of the sun

DynaVar Station Class and Intermediate Surge Arresters

Distribution Voltage Regulators

LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS

pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2, /0.65/0.

B. Related Sections: 1. Section Raceway and Boxes for Electrical Systems.

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1

Mylar polyester film. Electrical Properties. Product Information. Dielectric Strength. Electrode Size. Film Thickness

Masterclad Medium Voltage Passive Arc-Resistant Switchgear

produces and delivers products worldwide can provide the optimal are dedicated to supplying you with superior advice and global support.

Bourns Resistive Products

1ZSE en, Rev. 8. Transformer bushings, type GOE and GOE(2) Technical guide

Lightning current simulation in the laboratory - parameters, procedures and test equipment -

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU

Shunt lock function 3066

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

OASIS-PLUS 120V READ ALL INSTRUCTIONS BEFORE OPERATING READ ALL INSTRUCTIONS BEFORE OPERATING OZONE IS A POWERFUL OXIDIZER AND MUST BE USED WITH CARE

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION

Low Voltage Transformers Sealed, General Purpose, Dry Type

EARTHING SYSTEM CALCULATION

Single-phase ( V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

Dimensions, Inches (mm) No. of Poles Width Height Depth 2, (210) 16 (407) 5.5 (140) (283) 16 (407) 5.5 (140)

AC Module Installation Guide Content

Do s and don'ts of connection systems Are there any options when the clearance and creepage distances are not sufficient for UL 1059?

High power speaker arrays

5SV Residual Current Protective Devices

CITY OF LOS ANGELES CALIFORNIA

MCR1900 Media Converter 19-Slot Chassis

Type: DILM115(RAC240) Article No.: Sales text Contactor,55kW/400V,AC operated. Ordering information

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application

Table of Contents. TransformerIQ FAQs 1

38 Series - Relay interface modules A

An Overview of Lapp Insulator High Voltage Bushing Design

Testing Accessories. Test PaddleS. Insulated Socket Wrench Jumper Strips Test Lead Kit. Test Paddle Attachment Clips Plugs Binding Posts

Surgelogic Surge Protection Device EMA, EBA, and HWA Series

Transcription:

Technical Data TD235004EN Supersedes 235-16 November 2009 Storm Trapper H.E. (high energy) low-voltage distribution-class MOV surge arrester General Eaton's Cooper Power Systems Storm Trapper H.E. (High Energy), low-voltage distribution-class surge arresters are designed to provide surge protection at distribution transformer secondary bushings. The Storm Trapper H.E. arrester is the industry's first low-voltage distribution-class arrester and has successfully passed all design tests for light duty distribution class arresters per IEEE Std C62.11-1993 standard. Years of research by Eaton's Cooper Power Systems in low-voltage secondary circuits concluded that the types and magnitudes of surges that can exist in these circuits are more severe than previously thought. The Storm Trapper H.E. arrester, born out of this research, was designed to reliably handle the stresses found in these low-voltage circuits. The research further noted that transformer failure rates can be significantly reduced by adding surge protection to transformer secondary bushings. Field experiments in some of the most severe lightning areas of the United States has shown that transformer failure rates can be reduced to far below 0.1% by applying Storm Trapper H.E. arresters to transformer secondaries. Top image depicts external mount. Bottom row, left to right, displays metal enclosed and internal mount. Features The Storm Trapper H.E. family of arresters incorporates the highest energy handling Metal Oxide Varistors (MOV) when compared to other arresters promoted for similar applications. This superior energy handling ability assures long service life even in the most severe service conditions. Storm Trapper H.E. arresters were designed with a full 40 ka surge withstand capability, four times the level of traditional secondary arresters. The durable MOVs used in the Storm Trapper H.E. arrester are manufactured by Eaton's Cooper Power Systems at our ISO 9001 certified plant in Olean, New York. This allows constant QA monitoring to assure that only the highest quality high energy MOVs get selected for use in Storm Trapper H.E. arresters.

Technical Data TD235004EN Storm Trapper H.E. MOV surge arrester Features and detailed description MOV DISKS Arrester design provides a high energy 40 ka highcurrent, short duration and 5 ka duty cycle rating in accordance with the lightduty, distribution-class arrester requirements of IEEE Std C62.11-1993 standard. GROUND ELECTRODE IDENTIFICATION INFORMATION Provides convenient reference for arrester type and voltage rating. Year and quarter of manufacture are permanently marked. COOPER POWER SYSTEMS LOW VOLTAGE DISTRIBUTION SURGE ARRESTER Storm Trapper STORM TRAPPER H.E. R H.E. SPRING Ensures high pressure continuous contact. SEALING COMPOUND Fully potted arrester ensures a lifetime moisture-proof seal. 1/ 2-14 THREAD (Locknut Provided) For attaching to a standard fuse/breaker box knockout hole. BLACK LEAD WIRE Indicates connection to an energized line. WHITE LEAD WIRE Indicates connection to ground or neutral. Figure 1. Cutaway Illustration of external mount Storm Trapper H.E. arrester without mounting bracket (two pole model illustrated). Designs The Storm Trapper H.E. arrester is available in three design configurations: external mount, metal-enclosed, and internal mount. All external mount and metal-enclosed Storm Trapper H.E. arresters are CSA Listed for safety. Standard line and ground leads on the external mount and metalenclosed designs are 18 inch, #10 AWG stranded copper. The line leads that are connected to the energized source come with black wire insulation while the ground lead has white insulation. The length of the line and ground leads play an important role in the protective ability of the arrester. The longer the leads are, the higher the voltage let through to the protected equipment. Thus to improve the equipment protection, it is strongly recommended that all line and ground leads be kept to the minimum required length. External mount Storm Trapper H.E. arrester The external mount Storm Trapper H.E. arrester is designed for connection to, and protection of, the secondary bushings of overhead distribution transformers or other low voltage equipment. The external mount Storm Trapper H.E. arrester has been designed for outdoor application with a weather resistant housing over a fully-potted, void-free inner chamber. Identification information is permanently molded or stamped into the housing of the arrester for full lifetime readability. Arresters rated 175, 240, 480 and 650 volts are available in one, two and three pole designs. An optional mounting bracket is also available. Metal-enclosed Storm Trapper H.E. arrester The metal-enclosed Storm Trapper H.E. arrester provides nonfragmenting performance by fully encapsulating an external mount Storm Trapper H.E. arrester in a stainless steel housing. The enclosed Storm Trapper H.E. arrester has successfully passed 60 Hz. fault current tests exceeding 35 ka as a non-fragmenting device. The metal housing contains an indicator window which blackens in the unlikely event of arrester failure, noting the need for arrester replacement. As with the external mount Storm Trapper H.E. arrester, ratings of 175, 240, 480 and 650 volts in one, two and three pole designs are available with or without a mounting bracket. Internal mount Storm Trapper H.E. arrester The internal mount Storm Trapper H.E. surge arrester is designed for under-oil application within distribution transformers for the overvoltage protection of the secondary bushings. This design is available in a two pole, 480 volt rating which can be ordered with or without ring terminal mounting lugs. Production Tests A complete production test program assures a quality product. Tests are performed on the completed arrester assemblies. 100% Physical Inspection 100% Reference Voltage Test (Vref) 100% Radio Interference Voltage Test (RIV) Each MOV disk receives a series of tests. 100% Physical Inspection 100% 5 ka Discharge Voltage 100% V1mA/cm 2 100% Leakage Current at 80% of V1mA/cm 2 100% Batch High Current Short-Duration Test 100 Batch Thermal Stability Test 2

Storm Trapper H.E. MOV surge arrester Technical Data TD235004EN.187" (4.7mm) DIA. HOLES (4 PLACES).56 x 2.50 (14 x 64 mm) (SLOT) 2.20'' (56 mm) 1.37'' (35 mm) 1.83'' (46 mm) 1.20'' (30 mm).54'' (14 mm) 4.75'' (121 mm) 4.14'' (105 mm).96'' (24 mm) FRONT VIEW SIDE VIEW Figure 2. Dimensional information for external mount Storm Trapper H.E. arrester (shown with optional mounting bracket). NNote: Dimensions are given for reference only. Table 1. Protective Characteristics Arrester Rating MCOV Maximum Energy Capability (Joules/Phase) Front of Wave Protective Level* (kv Crest) Maximum Discharge Voltage (kv crest) 8/20 µs Current Wave 5 ka 1.5 ka 5 ka 10 ka 20 ka 40 ka 175 175 3226 1.7 1.4 1.6 1.8 2.0 2.4 240 240 3405 1.8 1.5 1.7 1.9 2.2 2.6 480 400 3776 2.0 1.7 1.9 2.1 2.4 2.9 650 540 4660 2.6 2.1 2.4 2.6 3.0 3.6 * Based on a current impulse that results in a discharge voltage cresting in 0.5 µs. Table 2. Insulation Withstand Voltages Arrester Rating 1.2/50 Impulse (kv crest) 1 min Dry (kv rms) All Ratings 10 6 6 10 sec Wet (kv rms) Table 3. Performance Test Characteristics* Description Characteristics High-current, 2 discharges of 40 ka crest, 4/10 µs current wave Short-duration Low-current, 20 surges of 75 A-2000 microsecond duration Long-duration Duty Cycle 22 operations of 5 ka crest, 8/20 µs current wave * Tests were performed in accordance with applicable sections of IEEE Std C62.11-1993 standard (Metal Oxide Surge Arresters for Alternating Current Power Circuits). 3

Technical Data TD235004EN Storm Trapper H.E. MOV surge arrester 2.49'' (63 mm) 1.37" (35 mm) 2.56'' (65 mm) 1.97'' (50 mm) AIR STAINLESS STEEL BOX 4.75'' (121 mm) Storm Trapper H.E. 4.25'' (108 mm) FULLY POTTED EXTERNAL MOUNT STORM TRAPPER H.E. FRONT VIEW FAILURE INDICATOR WINDOW SIDE VIEW Figure 3. Dimensional information for metal-enclosed Storm Trapper H.E. arrester (shown with optional mounting bracket). 2.67'' (68 mm) 1.50'' (38 mm).56'' (14 mm) 1.65'' 5.12'' (42 mm) (130 mm).51'' (13 mm).88'' (22 mm) TOP VIEW 1.12'' (28 mm) 1.9'' (48 mm) SIDE VIEW Figure 4. Dimensional information for internal mount Storm Trapper H.E. arrester (shown with optional terminal lugs). NNote: Dimensions are given for reference only. 4

Storm Trapper H.E. MOV surge arrester Technical Data TD235004EN Temporary overvoltage (TOV) capability The ability of the Storm Trapper H.E. arrester to withstand 60 Hz temporary overvoltage conditions is graphically shown in Figure 5. The graph shows for a given voltage magnitude (on a per unit of MCOV basis), the time an arrester can survive a TOV condition without going into thermal runaway. 1.6 1.5 PER UNIT OF MCOV 1.4 1.3 1.2 1.1 1 0.1 Figure 5. Temporary Overvoltage Capability. 1 10 100 1000 TIME (Seconds) 10000 Ordering information To order an Eaton's Cooper Power Systems Storm Trapper H.E. arrester, determine the arrester Maximum Continuous Operating Voltage (MCOV) rating for the intended application and specify the appropriate catalog number from Table 4 or 5. Contact Eaton's Cooper Power Systems representative for more information. Table 4. Internal Mount Storm Trapper H.E. Arrester Selection Storm Trapper H.E. Arrester Type Voltage Rating MCOV Number of Poles Catalog Number With Terminal Lugs Without Terminal Lugs Internal Mount 480 400 2 ASZH480U200* ASZH480U202** * 10 inch leads ** 24 inch leads 5

COOPER POWER SYSTEMS COOPER INDUSTRIES LOW VOLTAGE DISTRIBUTION SURGE ARRESTER ASZ4C1 RATED MCOV 2 / POLE 480V 400V Technical Data TD235004EN Storm Trapper H.E. MOV surge arrester Table 5. Storm Trapper H.E. Arrester Selection Storm Trapper H.E. Arrester Type Voltage Rating MCOV Number of Poles Catalog Number Without Hanger Bracket* External Mount 175 175 1 ASZH175C100 175 175 2 ASZH175C200 175 175 3 ASZH175C300 240 240 1 ASZH240C100 240 240 2 ASZH240C200 240 240 3 ASZH240C300 480 400 1 ASZH480C100 480 400 2 ASZH480C200 480 400 3 ASZH480C300 650 540 1 ASZH650C100 650 540 2 ASZH650C200 650 540 3 ASZH650C300 Metal-Enclosed 175 175 1 ASZH175E100 175 175 2 ASZH175E200 175 175 3 ASZH175E300 240 240 1 ASZH240E100 240 240 2 ASZH240E200 240 240 3 ASZH240E300 480 400 1 ASZH480E100 480 400 2 ASZH480E200 480 400 3 ASZH480E300 650 540 1 ASZH650E100 650 540 2 ASZH650E200 650 540 3 ASZH650E300 * To order an arrester with mounting bracket change the last digit from a 0 to a 1. (Example: Change ASZH480C200 to ASZH480C201) Recommended arrester applications IEEE Std C62.41-1991 standard, IEEE Recommended Practice on Surge Voltages in Low-Voltage AC Power Circuits, defines three areas of low voltage service from the distribution transformer secondary bushings down to electrical outlets within a home or business. (See Figure 6.) Storm Trapper H.E. arresters are designed for use in category C locations. Category C applications include use on transformer secondaries. Outlets and long branch circuits are considered category A. Typically, category A overvoltage protection has been limited to plug-in style voltage suppressors. A B C PRIMARY CIRCUIT PANEL METER Figure 6. Location categories in low-voltage circuits. 6

Storm Trapper H.E. MOV surge arrester Technical Data TD235004EN This page intentionally left blank. 7

Technical Data TD235004EN Storm Trapper H.E. MOV surge arrester Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton s Cooper Power Systems Business 2300 Badger Drive Waukesha, WI 53188 United States Cooperpower.com 2014 Eaton All Rights Reserved Printed in USA Publication No. TD235004EN Eaton, Cooper Power Systems, and Storm Trapper are valuable trademarks of Eaton in the U.S. and other countries. You are not permitted to use the these trademarks without the prior written consent of Eaton. CSA is a registered trademark of Canadian Standards Association. IEEE Std C62.11-1993 and IEEE Std C62.41-1991 standards are trademarks of the Institute of Electrical and Electronics Engineers, Inc. (IEEE). This publication/product is not endorsed or approved by the IEEE. IEEE is a registered trademark of the Institute of Electrical and Electronics Engineers, Inc. For Eaton's Cooper Power Systems Storm Trapper H.E. MOV surge arrester product information call 1-877-277-4636 or visit: www.cooperpower. com.