FIELDVUE DVC5000 Series Digital Valve Controller

Similar documents
Fisher FIELDVUE DVC6200 SIS Digital Valve Controller for Safety Instrumented Systems (SIS)

Fisher FIELDVUE DVC2000 Digital Valve

AMS ValveLink SNAP-ON Application

Fisher 377 Trip Valve

Fisher FIELDVUE DVC6200 Digital Valve

Fisher FIELDVUE Instrumentation Improving Safety Instrumented System Reliability

Fisher 4320 Wireless Position Monitor, with On/Off Control Option

Control Valve Training Course Program

Fisher 646 Electro Pneumatic Transducer

Fisher FIELDVUE DVC6200f Digital Valve Controller for FOUNDATION fieldbus

Baumann Little Scotty Bronze Control Valve

ValveLink Mobile Software

Fisher 657 and 667 Diaphragm Actuators

SIS. Fisher FIELDVUE DVC6200 Series Digital Valve Controllers. Contents. Before You Begin... 2

A descriptive definition of valve actuators

Fisher 3710 and 3720 Positioners and 3722 Electro-Pneumatic Converter

Fisher FIELDVUE DVC6200 Digital Valve

MTI10 Insertion and MTL10 In-line Thermal Mass Flowmeter and Temperature Transmitter

Baumann Flexsleev Sanitary Control Valve

Baumann Way Bronze or Stainless Steel Control Valve

Rosemount 333 HART Tri-Loop

ValveLink DTM ValveLink PLUG IN for PRM

Fisher 2625, 2625SST, and 2625NS Volume Boosters

SKP Series SKP15U.. Gas Valve Actuator with Safety Shutoff Function

Fisher FIELDVUE DVC6200 Digital Valve Controller / Magnet Assembly Dimensions

Fisher 846 Electro-Pneumatic Transducer

ValveLink Software Quick Start Guide

I nstallation. M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications. Tools Needed.

SM6 Series Circuit Breaker Monitors CONSOLIDATED. Electronics, Inc. MONITORING THE FUTURE

Model 43AP Pneumatic Controller, Style B

Baumann Mikroseal Control Valve

Fisher D3 Control Valve

Rosemount 333 HART Tri-Loop

Technical Information RIA14

PRODUCT PROFILE FEATURES

Intelligent Device Management: Device Diagnostics

FIELDVUE. DVC6200 Series Digital Valve Controller A Single Instrument Solution Across Your Facility

Practical Application of Industrial Fiber Optic Sensing Systems

Microcor Wireless Transmitter (MWT)

CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version)

Electro-Magnetic Flowmeters COPA-XT 2-Wire DT43

Duct Humidity Transmitter

4310/4320 Wireless Position Monitor

Fisher 1052 Size 20 Diaphragm Rotary Actuator with F and G Mounting Adaptation

Automation System TROVIS 6400 TROVIS 6493 Compact Controller

Micro Motion Series 3000 MVD Transmitters and Controllers

3500/93 System Display

APT3200 SMART PRESSURE TRANSMITTER. Application Areas: For Gauge And Absolute Pressure Measurement

IFC 070 Technical Datasheet

Electronic pressure switch with display Model PSD-30, standard version Model PSD-31, with flush diaphragm

KNC Model 3666 Automatic Pressure Calibration System

AMS Suite: Intelligent Device Manager

M Series Manual Handwheel Gear Actuators for Fisher Butterfly Valves

TX OPEN RS232/485 module

POWERS CONTROL RC 195 Single Input Receiver-Controller

Centro-Matic Automatic Lubrication Systems System Controls

Powers Controls TH 192 S Single Temperature Room Thermostat

System 6000 Electropneumatic Converter for Direct Current Signals Type 6116 i/p Converter

SuperIOr Controller. Digital Dynamics, Inc., 2014 All Rights Reserved. Patent Pending. Rev:

AMS Suite: Intelligent Device Manager with the DeltaV system

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410

3DLevelScanner II TECHNICAL DATA SHEET

Model 3051 Pressure Transmitter with HART Protocol

Models SFP33 & SFP32 Pressure Transmitters

SELECTION, APPLICATION AND MAINTENANCE

BURSTCHECK LINE OF RUPTURE DISC BURST INDICATORS

Sanitary Type Electronic Flow Switches

TYPE 65UV CEX Integrated Flame Scanner with Internal Flame Relay and Analog Output

DREXELBROOK. USonic-R Series. Ultrasonic Level Measurement System. User Friendly

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

ISA108 Intelligent Device Management (IDM)

Pump_PT580. Optional. Optional. Modbus. Remote Reset Local Display PLC/DCS PT580-CFG PCM370 DTM96. Buffered Output. Dual Relay Output.

In-Line Electronic Flow Switches

Diesel Engine Driven Generators Page 1 of 6

TAC I/NETTM MR-VAV-AX. Application Specific MicroRegulator TM

Everything you need for protection scheme testing

API Marine. BMS Presentation. Ballast Measurement Systems

Fisher 377 Trip Valve

THYRISTORS T1-1PH from 850A to 2700A Specifications Universal 1 Phase Thyristor Unit , March 2012

Quick Start Guide , Rev DA March Rosemount 8714D (Calibration Standard) Magnetic Flowtube Simulator

Safety Requirements Specification Guideline

Fisher 846 Current-to-Pressure Transducer

R4D0-FB-IA* FieldBarrier. Features. Assembly. Function. Connection IN + - S OUT Spur 2. Spur 1. Zone 1. Zone 0

HARDWARE MANUAL. Ixx24-A 1/20. Val Controls A/S Limfjordsvej 3 DK-6715 Esbjerg N Tel vc@valcontrols.com

EDI Distributor Control Interface Wiring and Setup Instructions

Device Management Jonas Berge Emerson Process Management

M-series FOUNDATION Fieldbus I/O

RTX 1000 Series. Versatile Transmitters for a World of Pressure. GE Measurement & Control Solutions. Features

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

TECHNICAL DATASHEET #TD1404AX PWM CONTROLLED SOLENOID DRIVER

Fisher 1061 Pneumatic Piston Rotary Actuator with Style F & G Mounting Adaptations

Actuators & Positioners LP - Linear Pneumatic Piston Actuator. Cylinder Actuators. High resolution, sensitivity, and fast response

JUMPFLEX 857 Series ma V ma. Transducers / Relay and Optocoupler Modules

Powers Controls Free Energy Band TH 193 HC Heating/Cooling Room Thermostat

For Multi-Parameter Meters see mvx

Operation and Installation Manual

Technical Data Sheet. 3DLevelScanner

S4000TH HART. HART Communication Manual

TABLE OF CONTENT

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

Transcription:

January 2001 Bulletin 62.1:DVC5000 FIELDVUE DVC5000 Series Digital Valve Controller DVC5000 Series digital valve controllers (figures 1 and 2) are communicating, microprocessor-based current to pneumatic instruments. In addition to the traditional function of converting a current signal to a pressure signal, these instruments, using HART communications protocol, provide easy access to information critical to process operation. Tables 1 and 2 list the information that is accessible through FIELDVUE ValveLink software or the Rosmount Model 275 HART Communicator, shown in figure 6. Much of the information is also available on a HART compatible distributed control system. Because the digital valve controller receives feedback of the valve travel position, the instrument can not only diagnose itself but also the valve and actuator on which it is mounted. This provides you with very cost effective maintenance information, so that required maintenance can be performed on the instrument and valve when there really is a need. W6164 B/IL Wiring is economical because DVC5000 Series digital valve controllers use two-wire 4 to 20 ma loop power. This provides for low cost replacement of existing analog instrumentation and avoids the high cost of running separate power and signal wiring. Features Improved Process Control Two-way digital communication provides current valve conditions. You can rely on this real-time information to make sound process management decisions. By analyzing valve dynamics with AMS ValveLink software, you can identify those control areas that need improvement and maintain a high level of system performance. W6341/IL W6164/IL (continued on page 3) Figure 1. FIELDVUE DVC5000 Series Digital Valve Controllers D200440X012

Specifications Available Configurations Type DVC5010: Sliding-stem applications Type DVC5020: Rotary and long-stroke sliding-stem applications Type DVC5030: Quarter-turn rotary applications Type DVC5040: Sliding-stem application Fisher Controls System 9000 actuator DVC5000 Series digital valve controllers mount on Fisher Controls and other manufacturers rotary and sliding-stem actuators. Input Signal Point-to-Point: Analog Input Signal: 4 to 20 ma dc, nominal Minimum Voltage Available at instrument terminals must be 11.5 volts dc for analog control, 12 volts dc for HART communication (see instrument instruction manual for details) Minimum Control Current: 4.0 ma Minimum Current w/o Microprocessor Restart: 3.5 ma Maximum Voltage: 30 volts dc Overcurrent Protection: Input circuitry limits current to prevent internal damage Reverse Polarity Protection: No damage occurs from reversal of loop current Multi-drop: Instrument Power: 12 to 30 volts dc at approximately 8 ma Reverse Polarity Protection: No damage occurs from reversal of loop current Output Signal (1) Pneumatic pressure as required by the actuator, up to 95% of supply pressure. Minimum Span: 0.4 bar (6 psig) Maximum Span: 6 bar (90 psig) Action: Direct only Supply Pressure (1) Minimum and Recommended: 0.3 bar (5 psig) higher than maximum actuator requirements Maximum: 6.9 bar (100 psig) or maximum pressure rating of the actuator, whichever is lower. Steady-State Air Consumption (1),(2) At 1.4 bar (20 psig) supply pressure: Less than 0.3 normal m 3 /hr (10 scfh) At 2.4 bar (35 psig) supply pressure: Less than 0.4 normal m 3 /hr (15 scfh) At 4.1 bar (60 psig) supply pressure: Less than 0.6 normal m 3 /hr (22 scfh) (continued) At 6.9 bar (100 psig) supply pressure: Less than 0.9 normal m 3 /hr (34 scfh) Maximum Output Capacity (2) At 1.4 bar (20 psig) supply pressure: 7.6 normal m 3 /hr (285 scfh) At 4.1 bar (60 psig) supply pressure: 17.6 normal m 3 /hr (658 scfh) Independent Linearity (1) ±0.5% of output span, typical Electromagnetic Interference (EMI) These instruments have the CE mark in accordance with the Electromagnetic Compatibility (EMC) Directive. They meet the requirements of EN50081-1 (emissions for light industry) and EN50082-2 (immunity for industrial environment). Electrical Classification Hazardous Area: Explosion-proof, intrinsically safe, Division 2, and flameproof constructions are available to CSA, FM, CENELEC, and SAA standards. Refer to the hazardous-area classification bulletins. Electrical Housing: Meets NEMA 4X, IEC 529 IP65 Connections Supply Pressure: 1/4-inch NPT female and integral pad for mounting Type 67CFR regulator Output Pressure: 1/4-inch NPT female Tubing: 3/8-inch metal, recommended Vent (pipe-away): 1/4-inch NPT female Electrical: 1/2-inch NPT female conduit connection, M20 adaptor optional Operating Ambient Temperature Limits 40 to 80 C ( 40 to 175 F) Construction Materials Housing, module base, and terminal box: ANSI B360.0 low copper aluminum alloy Cover: Valox Elastomers: Nitrile Stem Travel DVC5010: 0 to 102 mm (4 inches) maximum 0 to 9.5 mm (3/8 inches) minimum DVC5020: 0 to 606 mm (23-7/8 inches) maximum Shaft Rotation (DVC5020 and DVC5030) 0 to 50 degrees minimum 0 to 90 degrees maximum Mounting Designed for direct actuator mounting. For weatherproof housing capability, mount the instrument upright to allow the vent to drain. 2

Specifications (continued) Dimensions See figures 9 and 10. For dimensions of a Type DVC5040 digital valve controller, see Bulletin 41.1:FloVue. Weight Less than 2.7 kg (6 lbs) Options Standard Diagnostics or HART communicating; Supply and output pressure gauges or tire valves; Integrally mounted filter regulator 1. These terms are defined in ISA Standard S51.1. 2. Normal m 3 /hr Normal cubic meters per hour (0 C, 1.01325 bar, absolute); Scfh Standard cubic feet per hour (60 F, 14.7 psia). and installation cost savings by replacing other devices in the process loop, such as positioners and limit switches. Because the digital valve controller is loop powered, it can replace analog instrumentation in new or existing installations, no additional wiring is required. Built to Survive Field-tough DVC5000 Series digital valve controllers have fully encapsulated printed wiring boards that resist the effects of vibration, temperature, and corrosive atmospheres. As shown in figure 7, a separate weather-tight field wiring terminal box isolates field wiring connections from other areas of the instrument. Increased Uptime With the self-diagnostic capability of DVC5000 Series digital valve controllers, you can answer questions about a valve s performance, without pulling the valve from the line. You can compare the present valve/actuator signature (bench set, seat load, friction, etc.) against previously stored signatures to discover performance changes, before they cause process control problems. W6564/IL Figure 2. DVC5000 Series Digital Valve Controller Mounted on FloVue System 9000 Actuator Enhanced Safety Check instrument and valve operation from a remote location. Access is possible at a field junction box, marshalling panel, or within the safety of the control room using either a HART Communicator, a notebook PC, or a system workstation. Minimize exposure to hazardous environments and avoid having to access hard-to-reach locations. Environmental Protection Avoid additional field wiring by connecting a leak detector or limit switch to the digital valve controller auxiliary terminals. If limits are exceeded, the instrument will issue an alert. Hardware Savings When placed in an integrated system, DVC5000 Series digital valve controllers allow you to realize significant hardware Faster Commissioning Quickly commission loops by using the HART communications protocol to remotely identify each instrument, verify its calibration, review stored maintenance notes, and more. Easy Maintenance With its patented design, digital valve controller field repair consists of quick and easy replacement of a single master module, without disconnecting field wiring, pneumatic tubing, or valve stem linkages. The master module may be then taken to the instrument shop for fast and easy troubleshooting of critical components. Diagnostics Valve Assembly Diagnostics When integrated with a HART communication-based system, the DVC5000 Series digital valve controller user-configurable alerts provide real-time notification of current and potential valve and instrument problems. With AMS ValveLink software, tests can be 3

communicate with non-hart distributed control systems through the Modbus interface, as shown in figure 4. This allows integrating critical information such as valve travel and alerts into the process operation. HART-Based Control Systems A control system with HART communication capabilies has the ability to directly gather information from DVC5000 Series digital valve controllers. Information such as valve travel and alerts can be seamlessly integrated into operational displays. Communication Figure 3. The Valve Signature Diagnostic Test Can Reveal Areas of Degradation performed to identify problems with the entire control valve assembly. Figure 3 shows an example of a ValveLink display. Valve stem travel feedback and actuator pressure sensors, permit evaluating the health of the control valve. When compared with a benchmark Valve Signature, a later signature will reveal areas of valve degradation. This helps to pinpoint problems before the equipment fails. Emerson Performance Solutions Emerson Performance Solutions can use instruments with on-line diagnostic capability to evaluate the valve and the process while the loop is running. Performance Diagnostics permit identifying and isolating the process element that is currently causing quality problems. Integration Non-HART Systems Because they operate with a traditional 4 to 20 milliamp dc control signal, DVC5000 Series digital valve controllers can replace older analog instruments. Microprocessor-based electronics provide improved performance along with repeatable and reliable configuration and calibration. HART Multiplexers and AMS ValveLink Software with Modbus Interface Integrating DVC5000 Series instruments into a multiplexer network and using AMS ValveLink software allows monitoring multiple instruments for alarms. Additionally, tasks such as configuration, calibration and diagnostic testing do not require special trips to the field. AMS ValveLink software can also HART Protocol The HART (Highway Addressable Remote Transducer) protocol gives field devices the capability of digitally communicating instrument and process data. This digital communication occurs over the same two-wire loop that provides the 4 to 20 ma process control signal, without disrupting the process signal. The analog process signal, with its faster response, is used for control. At the same time, the HART digital communication provides access to calibration, configuration, diagnostic, maintenance, and additional data. The HART protocol uses frequency shift keying (FSK). Two individual frequencies of 1200 and 2200 Hz are superimposed over the 4 to 20 ma current signal. These frequencies represent the digits 1 and 0, as shown in figure 5. The average value of the HART signal is zero, therefore no dc value is added to the 4 to 20 ma signal. Thus, true simultaneous communication is achieved without interrupting the process signal. The HART protocol also provides the capability of multidropping several devices to a single communications line. This type of connection is well suited for remote applications such as pipelines, custody transfer sites, and tank farms. Model 275 HART Communicator You can perform configuration and calibration at the valve or anywhere on the two-wire loop via a Model 275 HART Communicator (figure 6). Powerful tools such as the Setup Wizard and Auto Travel Calibration automate the tasks of commissioning DVC5000 Series digital valve controllers. These automation tools not only save time, but also provide accurate and repeatable results. 4

DISTRIBUTED CONTROL SYSTEM (DCS) MODBUS AMS ValveLink Software FIELD TERMINATION ASSEMBLY (FTA) 4-20 ma RS232-TO-RS485 CONVERTER HART Control System I/O 4-20 ma + HART HART MULTIPLEXER W8082-1 / IL Figure 4. Integrate Information from the Digital Valve Controller into a Non-HART Compatible Control System With AMS ValveLink Software s Modbus Interface +0.5 ma 0 ANALOG SIGNAL 0.5 ma 1200 Hz 1 2200 Hz 0 AVERAGE CURRENT CHANGE DURING COMMUNICATION = 0 A6174/IL Figure 5. HART Frequency Shift Keying Technique AMS ValveLink Software AMS ValveLink software is a Windows-based software package that allows easy access to the information available from DVC5000 Series digital valve controllers. Use AMS ValveLink software to monitor the performance characteristics of the valve and obtain vital information without having to pull the valve from the line. Results from diagnostic tests such as W7125 / IL Figure 6. Model 275 HART Communicator Valve Signature, Dynamic Error Band, and Step Response are displayed in an intuitive user-friendly environment that allows easy interpretation of the data. Diagnostic graphs can be superimposed over 5

TERMINAL BOX ASSEMBLY TERMINAL BOX COVER PRINTED WIRING BOARD ASSEMBLY MODULE BASE ASSEMBLY I/P CONVERTER SHROUD TRAVEL SENSOR ASSEMBLY HOUSING GASKET PRESSURE GAUGES (OPTIONAL) W8153all / IL PNEUMATIC RELAY RELAY CAP COVER ASSEMBLY Figure 7. DVC5000 Series Digital Valve Controller Assembly those previously stored to view areas of valve degradation. This allows plant personnel to concentrate efforts on equipment that needs repair, avoiding unnecessary maintenance. This diagnostic capability is readily accessible and available to you either in the control room or on the plant floor. In addition to the diagnostic features, AMS ValveLink software contains an Audit Trail, Batch Runner for automating repetitive tasks, and Trending to view valve performance. Principle of Operation As shown in figure 7, DVC5000 Series digital valve controllers have a single master module that contains the I/P converter, printed wiring board assembly, pneumatic relay submodules, and gauges. The master module can be rebuilt by replacing the submodules. The digital valve controller receives the 4 to 20 ma input signal and power through a single twisted pair of wires brought into the terminal box, as shown in figure 8. The input signal is routed to the printed wiring board assembly submodule, where any characterization, limits, and other signal preconditioning may be applied. The printed wiring board assembly submodule sends a signal to the I/P converter submodule. The I/P converter transforms the input signal to a pressure signal. This signal is sent to a pneumatic relay, where it is amplified and delivered as the output signal to an actuator. The output signal is also sensed by a pressure sensor located on the printed wiring board assembly submodule and used for valve/actuator diagnostics. Stem position of the valve and actuator is brought as an input to the printed wiring board assembly submodule and used as feedback for the digital valve controller. Gauges are available in the digital valve controller to give visual indication of supply pressure and output pressure. Installation The Type DVC5010 digital valve controller yoke-mounts on sliding stem actuators, as shown in figure 9. The Type DVC5020 digital valve controller typically mounts on rotary actuators, as shown in figure 10. The Type DVC5030 mounts on most quarter-turn rotary actuators, including both Fisher and other manufacturers actuators (figure 11). The Type DVC5040 digital valve controller is designed for integral mounting on the FloVue System 9000 actuator (figure 12). 6

Figure 8. Digital Valve Controller Principle of Operation Figure 9. Type DVC5010 Digital Valve Controller Mounted on Type 657 Actuator All pressure connections on the digital valve controllers are 1/4-inch NPT female connections. Typically, 3/8-inch (9.5 mm) outside diameter tubing is used between the digital valve controller output connection and the actuator. Electrical connections to the terminal box are through a 1/2-inch NPT conduit connection. If necessary, a remote vent may be connected to the digital valve controller. 7

MOUNTING ADAPTOR 1 1/2-14 NPT CONDUIT CONNECTION BOTH SIDES 4.88 (124.0) CENTERLINE OF ACTUATOR BODY 9.19 (233.4) 3.94 (100.1) 1/4-18 NPT CONNECTION FOR GAS TIGHT APPLICATIONS 6.31 (160.3) 8.00 (203.2) INSTRUMENT REMOVAL CLEARANCE 2.81(71.4) 1/4-18 NPT SUPPLY CONNECTION 1/4-18 OUTPUT CONNECTION NOTE: 1 MOUNTING ADAPTOR REQUIRED FOR TYPE 1051 SIZE 33 AND TYPE 1052 SIZE 20 OR SIZE 33 ONLY. E0525 / IL INCH (mm) Figure 10. Type DVC5020 Digital Valve Controller Mounted on Type 1052 Actuator Ordering Information Refer to the specifications on page 2. Carefully review each specification and indicate your choice whenever a selection is to be made. When ordering, specify: 1. Type number 2. Actuator type and size 3. Maximum actuator travel or rotation 4. Options a. HART Communicating or Standard Diagnostics b. Integrally-mounted supply pressure regulator c. Supply and output gauges or tire valves 8

ACTUATOR FEEDBACK ARM 27B6733-B / DOC MOUNTING BRACKET Figure 11. Type DVC5030 Digital Valve Controller Mounted on Typical Quarter-Turn Actuator A6870*A/IL Figure 12. Type DVC5040 Digital Valve Controller Mounted on FloVue System 9000 Actuator 9

Table 1 Information Accessible through AMS ValveLink Software or a Model 275 HART Communicator INFORMATION CATEGORY Measure Variables Identification Input/Output Characteristics Failure TYPE OF INFORMATION Analog Input Actuator Pressure Travel Temperature Auxiliary Input Tag Instrument Serial Number Valve Serial Number Descriptor Date Calibration Location Revision Level Message Engineering Units Travel Cutoffs Feedback Connection Minimum Opening and Closing Time Travel Limits Dynamic Bypass Manual Output Protection Restart Control Mode Selftest Shutdown DESCRIPTION The input current value on the primary terminals, in milliamps or percent The actuator presssure in psig, kpa, or bar The actual stem or shaft position in percent The internal instrument temperature in F or C The contacts connected to the auxiliary terminals are open or closed The instrument or loop tag The serial number assigned to the digital valve controller The serial number of the valve on which the digital valve controller is mounted A description of the application The last date the instrument was calibrated or the next date assigned for instrument calibration The instrument was calibrated in the field or at the factory The instrument and firmware revision level A user entered message of up to 32 characters. May be used for maintenance history information. Psig, kpa, bar, or % Low cutoff drives valve to seat when travel is less than a user configurable point. High cutoff drives valve open when travel is greater than a user configurable point. The specific valve mounting choice of sliding stem or rotary The minimum time for full travel or rotation of the valve stem or shaft The user configurable software upper and lower travel limit The dynamic response of the digital valve controller to emulate a transducer The command for the digital valve controller to move to a determined position Prohibits unauthorized changes to configuration and calibration Selects the control mode in the event of a restart Selects type of failure that causes an instrument shutdown Calibration Input Range Sets the input current range (4 to 20 ma, typical) Diagnostics Deviation Alert Travel Alert Drive signal Alert Cycle Counter Cycle Alert Travel Accumulation Travel Accumulation Alert Auxiliary Terminal Alert Instrument Status Configuration Changed Flag Alerts when the valve travel deviates from the correct value Establishs alert points based on stem or shaft position Alerts when the internal drive signal is out of bounds Records the number of changes in stem direction Alerts when a user configurable number of cycles are exceeded Records total accumulated stem or shaft travel Alerts when a user configurable travel accumulation is exceeded Alerts when the contacts connected to the auxiliary terminals are open or closed (alert can be configured to occur with either open or closed contacts) The status of internal instrument checks The instrument configuration has been changed Table 2. Additional information Accessible with AMS ValveLink Software INFORMATION CATEGORY Diagnostics TYPE OF INFORMATION Dynamic Error Band Valve Signature Step Response DESCRIPTION Runs an input versus travel test of the instrument and valve Runs an actuator pressure versus travel test to determine valve/actuator friction, bench set, spring rate, and seating load Runs a multipoint travel versus time test for various step inputs These products are covered under the following patents (5,265,637; 5,434,774; 5,439,021; 5,451,923) and may be covered by one or more pending patents. FIELDVUE, ValveLink, Fisher, and Fisher-Rosemount are marks owned by Fisher Controls International, Inc. or Fisher-Rosemount Systems, Inc. HART is a mark owned by the HART Communication Fourndation All other marks are the property of their respective owners. Fisher Controls International, Inc. 1994, 2001; All Rights Reserved For information, contact Fisher: Marshalltown, Iowa 50158 USA Cernay 68700 France Sao Paulo 05424 Brazil Singapore 128461 10 Printed in U.S.A. N97