MEASUREMENT OF SODIUM IN WATER/STEAM CIRCUITS

Similar documents
Inferred ph in Steam Plant Water Chemistry Monitoring

World Class Water Chemistry By Accident? BRO Chemistry Session 8/5/2014

DEGASSED CATION CONDUCTIVITY MEASUREMENT

Hydrogen Exchange Resin. Steam Purity Analysis

Water Efficiency. Water Management Options. Boilers. for Commercial, Industrial and Institutional Facilities. Boiler Water Impurities

The control of corrosive conditions caused by concentration of low-volatility solutes in boilers and steam generators

A Primer on Protecting Idle Boilers By Howard Benisvy, Member ASHRAE

NPL Report MATC (A) 95 Steam Turbine Operating Conditions, Chemistry of Condensates, and Environment Assisted Cracking A Critical Review

CYCLE CHEMISTRY COMMISSIONING

BASIC WATER TREATMENT OF STEAM BOILERS

How To Clean Up A Reactor Water Cleanup

The International Association for the Properties of Water and Steam. Technical Guidance Document: Steam Purity for Turbine Operation

Technical Presentation IMPORTANT TOPICS

How To Prevent Corrosion In A Steam Electric Power Plant

Best Practice in Boiler Water Treatment

DEIONIZATION IN A "NUT SHELL"

High Purity Water Resistivity/ Conductivity Measurement

Common Problems with Online Water Quality Analyzers. Greg Macy Director AquatiPro LLC

Ion Exchange Design Hand calculation. Brian Windsor (Purolite International Ltd)

THEORY AND APPLICATION OF CONDUCTIVITY

Effective Deoxygenation by a Hybrid Process Combining Gas Transfer Membranes with Catalytic Oxygen Reduction

Steam Generation Efficiency Module Blowdown Losses Section

INSTRUCTION MANUAL. Boil-Out TABLE OF CONTENTS SAFETY WARNINGS 2-3 RESPONSIBILITY 3 INTRODUCTION 3 PRE-BOIL OUT PROCEDURES 3-5 BOIL OUT PROCESS 5-9

ICON Analyzer. Dedicated online photometer for water and wastewater analysis

Industrial Water Reuse and Wastewater Minimization

APPLIED THERMODYNAMICS TUTORIAL 1 REVISION OF ISENTROPIC EFFICIENCY ADVANCED STEAM CYCLES

IMPLEMENTATION OF BOILER BEST PRACTICES

High-Pressure Steam Cycle and Boiler Water Treatment

CONTENTS. ZVU Engineering a.s., Member of ZVU Group, WASTE HEAT BOILERS Page 2

Hardness ions also interfere with many chemical processes such as chemical compounding and aqueous cleaners.

Ion Exchange Softening

Reuse of Alternative Water Sources for Cooling Tower Systems Two Case Studies Using Non-Traditional Water Sources

The Relationship between ph and Deionized Water

Pure Water. Isn t Hard to Find

Water Treatment, Cycle Chemistry, Boiler Operation and Related Problems/Failures on Steam Generator Systems > 30 bar

The National Board of Boiler and Pressure Vessel Inspectors 1055 Crupper Avenue Columbus, Ohio

Case History Report The Dolphin Nonchemical Device Boilers and Cooling Tower

ION EXCHANGE FOR DUMMIES. An introduction

Sulfites for Oxygen Control

Operational Flexibility Enhancements of Combined Cycle Power Plants. Dr. Norbert Henkel, Erich Schmid and Edwin Gobrecht

The Single Absorption Scrubbing Sulfuric Acid Process

Boiler Blowdown. Boiler Blowdown Benefits. Best Operating Practices for Boiler Blowdown

NALCO BT-25 Boiler Internal Treatment

Research for leachables of nuclear grade cation exchange resin

Boiler Calculations. Helsinki University of Technology Department of Mechanical Engineering. Sebastian Teir, Antto Kulla

Boiler Chemistry Management Using Coordinated Approach of Chemicals, Membranes and Online Monitoring

Design Factors and Water Chemistry Practices - Supercritical Power Cycles

Deionization. Power Industry Experience Using Micro-Media Filtration and

Using EDI to Meet the Needs of Pure Water Production

CYCLE CHEMISTRY ph MEASUREMENT

C. starting positive displacement pumps with the discharge valve closed.

Water for Injection (WFI) and Pure Steam Production in a Lean Manufacturing Environment. Larry Zanko Project Manager STERIS Corporation

9707 Key West Avenue, Suite 100 Rockville, MD Phone: Fax:

WATER TREATMENT THE NEED FOR CONTROL COMMON IMPURITIES FOUND IN WATER. CALCIUM CARBONATE (CaCO3) CALCIUM SULFATE (CaSO4) MAGNESIUM SULFATE (MgSO4)

Corrosion Management in Gas Treating Plants (GTP s): Comparison between Corrosion Rate of DEA and MDEA A Case Study in Sour Gas Refinery

MERCURY REMOVAL FROM NATURAL GAS AND LIQUID STREAMS ABSTRACT. Giacomo Corvini, Julie Stiltner and Keith Clark UOP LLC Houston, Texas, USA

SUGAR MILL BOILER CYCLE CHEMISTRY: AN UPDATE ON BEST PRACTICES DAVID RODMAN. Nalco Australia Pty Ltd, Townsville

DE-TOP User s Manual. Version 2.0 Beta

A meaningful, cost-effective solution for polishing reverse osmosis permeate

Technical Support Services Accelerated Learning Through the Visual Presentation of Technical Information

Best Practices: The Engineering Approach for Industrial Boilers Natalie R. Blake, ONDEO Nalco

Water Softening for Hardness Removal. Hardness in Water. Methods of Removing Hardness 5/1/15. WTRG18 Water Softening and Hardness

Chemical Decontamination and Fluid Handling Services

Description of Thermal Oxidizers

Condensing Economizers Workshop Enbridge Gas, Toronto. MENEX Boiler Plant Heat Recovery Technologies. Prepared by: Jozo Martinovic, M A Sc, P Eng

ECOAZUR BLUEWATER WATER PURIFICATION PLANTS

Design of Purified Water and Water For Injection Systems. Hugh Hodkinson Engineers Ireland Chemical & Process Division

TABLE OF CONTENT

Nitrogen, Ammonia. Known Addition ISE Method 1 Method Minimum of 0.8 mg/l NH 3 N. Ammonia ISE. Test preparation. Instrument-specific table

TRIAL CHEMICAL CLEANING OF FOULED APH BASKETS

WASTE WATER TREATMENT SYSTEM (OPERATING MANUALS )

Sustained growth in the demand

ROSS Technology Removal of Oil, Solids and Scale Formers

Basics of Kraft Pulping & Recovery Process. Art J. Ragauskas Institute of Paper Science and Technology Georgia Institute of Technology

Improved Modern Control Station for High Pressure Bypass System in Thermal Power Plant

Cadmium Reduction Method Method to 30.0 mg/l NO 3 N (HR) Powder Pillows or AccuVac Ampuls

Conductivity and TDS Meters

TREATMENT OF PHOSPHATE FERTILIZER PLANT WASTE WATER IN FLORIDA FOR DISCHARGE AND RE USE PURPOSES

IGEMA BOILER LEVEL & TDS CONTROLS

Sugar or Salt? Ionic and Covalent Bonds

Committed to make a better world

Achim Beisiegel Fouad El-Rharbaoui Michael Wich. AREVA GmbH, Technical Center, Karlstein, Seligenstädter Strasse 100, Germany

Desalination of Sea Water E7-1

Torino Nord. Cogeneration Plant. The gas turbine. The steam generator. The Torino Nord cogeneration plant produces electricity and heat for district

Current state of plant Functioning as a peak and emergency centre. Statistics Accumulated operating hours:

PPB Dissolved Oxygen Measurement - Calibration and Sampling Techniques

Operational Reactor Safety /22.903

Lead Testing and On Site Calibration for Water Testing Detection Range: 2 100ppb

Association of Water Technologies Technical Manual

A Guide to Trouble-Free Cooling Towers

Electrodeionization (EDI)

HC900 Boiler Control. Background. Solution. Application Brief Industry: Manufacturing

Drying of Woody Biomass. Process Engineering / GEA Barr-Rosin

HYBRID COMBINED CYCLE POWER PLANT

Separation by Solvent Extraction

Chapter 2.2: Boilers

5. State the function of pulveriser. The pulverisers are the equipments which are used to powdered coal.

Power Plants. BENSON Once-Through Heat Recovery Steam Generator. Power Generation

Desuperheater Online Program Sizing Guidance

Scale and Deposit Formation in Steam Assisted Gravity Drainage (SAGD) Facilities

Transcription:

APPLICATION NOTE MEASUREMENT OF SODIUM IN WATER/STEAM CIRCUITS H.P. TURBINES INTERMEDIATE AND L.P. TURBINES GENERATOR SUPER HEATERS RE-HEATER COOLING TOWER C O N D EN SER DRUM WATER SUPPLY CONDENSATE - TANK - PUMP - POLISHING DEMINERALIZATION PLANT ECONOMIZER H.P. HEATERS FEED PUMP DEAERATOR L.P. HEATERS MAKE-UP Figure 1: Points of measurement of sodium in power plants water / steam cycle Water quality is critical to the efficiency and performance of a steam generation plant and to the longevity of its associated equipment. Today, sodium concentration has become one of the most important indexes for water quality throughout the steam and water cycle in power plants. This note discusses the potential risks of poor control and the benefits of measuring sodium with on-line analyzers.

1. Steam Measurement of sodium in steam before the superheater is strongly indicative of possible stress corrosion in the superheater. Under the high pressure and temperature conditions of today s power plant, the problem of steam solubility of inorganic compounds is increasingly important. Of particular significance is the steam solubility (in addition to carry-over) of sodium salts, e.g. sodium chloride (NaCl) and sodium hydroxide (NaOH), because of the possibility of stress corrosion cracking in the superheating section. The measurement of sodium directly in steam immediately before entering the superheater is now recognized as being strongly indicative of possible stress corrosion in the superheater. It should be noted that corrosion will occur only if sodium is present together with chlorides or hydroxide anions and not, for instance, with sulfates. Chlorides and hydroxides are corrosive, not the sodium, which serves only as the carrier. Specifically for plants with low boiler pressure (40-80 bars), since non-volatile boiler treatments are typically sodium based (i.e. a mixture of sodium phosphate tribasic and sodium phosphate di-basic), the measurement of sodium in the steam is an excellent indication of mechanical carryover from the drum into the steam. 2. Condensate Sodium measurement should be the preferred option for early warnings of excursions on condensates to minimize associated risks. Condensate polishing plays a vital role in power plant cycle chemistry, providing the means to reduce the transport of metal oxide and ionic impurities to the steam generator during all modes of operation, particularly during start-up and upset conditions. The benefits of condensate polishing are: Reduced delays to commissioning and start-up as a result of chemistry transients Protection of the steam generator during impurity ingress such as with condenser in-leakage Reduced impurities fed to steam generators, thereby minimizing the frequency of chemical cleaning Improved steam purity resulting in less turbine deposition and phase transition zone corrosion Virtual elimination of chemically influenced boiler tube failures Attainment of the high degree of feedwater purity necessary for chemical programs such as oxygenated treatment for drum and once-through boilers Careful management of condensate polishing systems is essential; otherwise polishing plants can become a source of ongoing feed system pollution. Extracting the maximum benefit from condensate polishing systems continues to be a top priority among many electric utility plants. Although cation and specific conductivity are used frequently to detect excursions in the water/steam loop, it is no longer sufficiently sensitive to measure the very small condenser leaks which have assumed greater importance in modern plant designs. In everyday conditions, with possible temperature, pressure and flow upset or high conductivity background levels, the minimum meaningful variation will be 0.02 ms/cm. This corresponds to 11ppb sodium.

Sodium analysis is much more sensitive. A Hach 9245 sodium analyzer can accurately measure below 0.1ppb. This is 100 times more sensitive than a conductivity measurement. Just as water quality is critical, early signs of excursions are also critical; sodium measurement should be the preferred option to minimize risk. Steam purity can be more accurately assessed by measuring sodium concentration in both steam and condensate, thus determining the sodium balance. The two concentrations should be equal. A higher level of sodium in the condensate indicates a condenser leakage. A lower level of sodium in the condensate indicates deposition of sodium in the steam circuit (on heat transfer surfaces, on turbine blades, etc.). Sodium measurement is the only technique that achieves accurate and rapid response at any time to detect hydroxides and chlorides known to be contributory factors in the stress-corrosion of austenitic steel. The origin of the desuperheating water is the condensate water. The quality of the desuperheating water must be without any doubt. If it is contaminated, this contamination will be brought directly into the desuperheated steam. The section most likely to be affected is that part of the superheater immediately following the point at which the desuperheater spray water is injected. It is made in austenitic steel for its mechanical behavior (low thermal dilatation coefficient), but it is more sensitive to corrosion (increased percentage of iron versus carbon). To avoid the catastrophic effect of impurities in the desuperheating water, any excursion must be detected as quickly as possible. On-line sodium measurement is the only technique that achieves accurate detection of excursions. A HACH 9245 sodium analyzer will ensure a rapid response at any time through regular reactivation of the electrode. Figure 2: Reverse flow type axial desuperheater

3. Demineralization Plant For a demineralization plant, on-line sodium measurement is all about ion exchange resin management. Customer benefits are: Better utilization of the resin capacity. Minimize sodium breakthroughs. Optimize acid rinse-out Optimization of regeneration cycles. Cation resin bed exhaustion and its regeneration timing can be monitored with high sensitivity and reliability using on-line sodium analyzers. Cation resins remove cations such as sodium (Na + ). Sodium is the first cation that breaks through when the cation resin bed is exhausted. Measuring sodium immediately after cation resins gives an early warning of breakthrough. Removing the saturated resin bed and replacing it with a new (regenerated) one protects the ion exchange capacity of the mixed-bed resins installed farther down the stream. Quality of the incoming water, the resin quality itself and temperature modifies the ion exchange capacity of the cationic resin bed. This influences the time before the next regeneration. When this time is indicated by a simple volume of sample running through the resin, it is an estimate that may lead to saturation and breakthrough or underuse of resin capacity. On-line measurement of sodium allows regeneration of the cation resin as required. After mixed bed resin, on-line sodium analysis ensures the quality of the demineralized water delivered to the make-up plant. Mixed-bed resin contains a mixture of both cation and anion exchange resins for a fine polish of the pure water. It reduces any contaminant left in the pure water. Remarkable progress has been made over the past decade to reduce the levels of contaminant ions in the treated water from of mixed beds. Specifically in Nuclear plants (PWR), mixed-beds treated water purity is reported in steady state values at 25 to 35 ppt for sodium. Here, sodium analyzers are used to monitor the final water quality, acting as a final check of quality. HACH 9245 sodium analyzers are used to check the quality of the final water down to 20 ppt levels. Additionally, a malfunction of the regeneration cycle of the mixed-bed resin is detected by sodium monitoring. Release of sodium can happen by accidental caustic release when there is insufficient rinsing of the mixed-bed anion resin. Again, the warning comes earlier and with higher precision with a sodium analyzer than by conductivity. 4. Range of measurement Sodium levels lower than 1 ppb are commonly found at the mixed bed output, both in the steam circuit and in the condensate.

Levels of 0-10 ppb can be found under normal working conditions at the cation exchangers output, but this can become as high as 100 ppb at the resin exhaustion or in boiler water. Table: Steam purity requirement * Steam turbine manufacturer s purity requirement ABB GE Westinghouse Sodium, ppb (mg/l) 10 20 5 * Data from tech. paper, CONDENSATE CONSIDERATION - - DOW Chemical, 1999 Mixed bed outlet Regular Nuclear With latest resin-resin separation technique** Sodium, ppb (mg/l) < 0.1 0.015 0.035 < 0.01 ** Data from ESAA Conference paper, 2005, JD Aspden 4.1. VGB guidelines Fossil The VGB guidelines are regularly published by the European Technical Committee combining European Power Plant Supplier s Association (EPPSA), FDBR (organization of professional builders of Steam boilers, vessels and piping), and Technische Vereinigung der Großkraftwerksbetreiber e.v. (VGB). This committee includes representatives from most EU countries. The difference for sodium in the steam of Fossil power plants is revealed in Sodium (Na) Table 1 below: g/kg Steam for Steam Turbines Boiler Water Treatment AVT or Caustic Boiler Water Treatment Phosphate Normal Level < 2 < 5 Action Level 1 5 10 Action Level 2 10 20 Action Level 3 20 40 Low pressure boilers (under 900 psig - 60bar) will run with phosphate treatment and sodium levels are high (from 5 to 50ppb). Higher pressure boilers (>900psig - >60bar) required stricter water/steam quality reflected by lower sodium levels (from 2 to 20ppb) Sodium (Na) g/kg Steam for Steam Turbines Boiler Water Treatment AVT or Caustic Boiler Water Treatment Phosphate Normal Level < 2 < 5 Action Level 1 5 10

Action Level 2 10 20 Action Level 3 20 40 Table 1: VGB guidelines: Requirements on steam for condensing turbines 1 1 Source: New VGB Guideline for Feed Water, Boiler Water and Steam Quality for Power Plants / Industrial PlantsVGB R 450 Le, by Ulrich Staudt (VGB PowerTech) 4.2 VGB guidelines - Nuclear These guidelines are based on the primary and secondary side operating chemistry experience gained by VGB members since the beginning of the 1980 s. VGB recommends these values for secondary side applications (in PWR, Candu, VVER, and AGR secondary cycles). Steam generator control parameters for power operation: Control Parameter Cation conductivity² ms cm ¹ Normal Operating Value Action Level 1 Action Level 2 Action Level 3 < 0.2 > 1.0 > 2.0 > 7.0 Sodium <0.005 > 0.05 > 0.1 > 0.5 Table 2: VGB guidelines, steam generator on secondary side system 3 5. Hach 9245 Sodium Analyzer The Hach 9245 sodium analyzer provides as standard: Sample quick-loop at the bottom of the analyzer for an immediate fresh sample Minimum sample flow detection and associated alarms Vessel for manually-introduced grab sample and fully automatic return to on-line measurement ph conditioning using venturi principle with programmable ph set-point Temperature compensation based on isothermal point Automatic reactivation of sodium electrode by injection of non-hazardous chemical All items mounted on a panel The Hach 9245 Sodium Analyzer is typically used: As the enclosure version for all demineralization plants and condensate monitoring. Analyzers may be installed at many points with the attendant risks of dust, water and condensation from day/night temperature differences. In this environment, the enclosure version is preferred.

As the panel version for Drum, HP or LP steam monitoring. There is usually an analyzer room with all sample tubing running to a single panel to easily view several analyzers at the same time or to view grab samples for manual cross-checking. The room usually has standard room temperature and low risk of water splashes or leaks. Space is limited on each panel and the panel version is preferred. 2 Caused only by strong anions; organics or CO2 are not to be considered 3 Dr. Harry Neder (NPP Isar, Essenbah, Germany) VGB-Primary&Secondary-side-water-chemistry.pdf, May 2007 The fully featured 9245 Sodium Analyzer has an automatic calibration option. This works by multiple injections of known volumes of a concentrated sodium standard solution (10ppm Na + ). This type of solution is easy to prepare and is not sensitive to contamination from the environment or from the container. With only 500mL of calibration solution, the 9245 Sodium Analyzer will run 20 calibrations, which allows the analyzer to run without additional calibration for 5-6 months. The calibration frequency is freely programmable either on number of hours or a fixed date and time. Customer benefits: Increased confidence in the analyzer by eliminating all risk of deviation due to human error. Increased analyzer up-time with fully automated calibration, including return to on-line analysis. Increased availability of analyzer to on-site lab personnel ; increased availability when monitoring a critical on-line process by programming the automatic calibration in fixed date and time mode during the normal regime of the process. 6. The Hach 9240 Sodium (multi) The Hach 9240 Sodium (multi) Analyzer provides as standard: A real, fully-integrated multi-channel analyzer, capable of 1 to 4 channels. Auto-adapted rinsing sequence to reach accuracy in minimal cycle time (10 minutes possible). This eliminates carry-over effects and maximizes the number of readings per channel per unit of time. Sample quick-loop per channel for an immediate fresh sample. Minimal sample flow detection and associated alarms. Overflow vessel to allow variations in inlet pressures and for manually introduced samples. Manually prompted samples are followed by an automatic return to on-line measurement. ph conditioning using a siphon effect on a liquid sample column with programmable ph set-point. Temperature compensation based on an isothermal point. Regulated addition of conditioning solution to the sample across both ph and temperature ranges. Automatic reactivation of the sodium electrode by injection of a non-hazardous chemical. 7. Product selection depending on application The 9245 Sodium is recommended as the solution of choice when several sample points are considered and every time one of the following points is raised as a key application feature: Response time must be less than 3 minutes. Analyzers are as close as possible to sample points (minimize piping). The impact of Electronic or Mechanical failure must be minimal.

There is a strong need to separate channels and to use the 9245 Sodium when: Samples have a difference in sodium greater than 200ppb. Temperature difference may be greater than 20 C from one channel to the next. Any sample where ph is less than 5. The 9240 Sodium (Multi) is recommended when any of the following points are important: The initial cost, the cost of ownership (and spares), and the space occupied by the analyzer must be kept to a minimum. The process visualization needs to be simple and a single human-machine interface is desired. The solution must be expandable: "In the future, we will expand (adding new sample points)." 8. Product selection matrix When an application like mixed-bed, steam, condensate and boiler applications are classified standard (0.01 to 10 000ppb) For a high acidity water (ph lower than 5; 50 < [acidity] < 250 mg/l CaCO 3 ), such as water from a cation exchanger outlet, the regular gaseous conditioning is not sufficient to raise the ph above 10.3. In that case, the forced-gas conditioning system (K-kit) is required. Diisopropylamine or ethanolamine or ammonia may be used as the reagent. Select the final Part Number of the required product using Error! Reference source not found. or Error! Reference source not found. below Table 3: identification matrix for model 9245 Table 4: identification matrix for model 9245 and 9240

FOR TECHNICAL ASSISTANCE, PRICE INFORMATION AND ORDERING: Tel: 800-227-4224 E-Mail: techhelp@hach.com To locate the HACH office or distributor serving you, visit: www.hach.com LIT2115 Hach Company, 2012. All rights reserved. In the interest of improving and updating its equipment, Hach Company reserves the right to alter specifications to equipment at any time.