MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 26 ELECTRICAL SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES

Similar documents
SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES

East Central College HANSEN HALL LEVEL 300/400 RENOVATIONS PACKAGE

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables

800 Communications Circuits

Entrances to and from Electrical Equipment Rooms

Electrical Code Regulation

DIVISION 26 - ELECTRICAL SECTION CABLES FOR INSTRUMENTATION

SECTION HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, Underground branch circuit feeding a detached garage:

SECTION /600 VOLT CABLE, WIRE AND CONNECTORS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: 1.2 DESCRIPTION OF WORK: 1.

Code Compliance for Spring Steel Fasteners Based on the 2005 NEC

ELECTRICAL: WIRE, CABLE, AND TERMINATIONS

RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS:

2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property

SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less.

SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

MANUFACTURER S CERTIFICATE OF COMPLIANCE

SECTION FACILITY STORM DRAINAGE PIPING

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL (352) ; FAX: (352)

UNDERSTANDING. C&M Corporation 51 South Walnut Street, Wauregan, CT Phone: Fax:

Requirements for Electrical Installations

Complete Firestop Systems Guide

SECTION VOICE AND DATA COMMUNICATION CABLING

ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT

2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE

STABILOY BRAND FeeDeR SOLuTIONS

STABILOY BRAND FeeDeR SOLuTIONS

Electrical Extension Cords & Relocatable Power Taps: (RPT s)

SECTION CABLE TRAYS FOR COMMUNICATIONS SYSTEMS

SECTION WINDOW WASHING SYSTEMS

SYSTEM 1850-SE SERVICE ENTRANCE CABLE SYSTEM

SECTION SIGNAL WIRE AND CABLE

ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION PAGE 1

CONTENTS. Yale University Design Standards. Underground Electrical Duct Bank. A. Summary. B. System Design and Performance Requirements

Sub-Bid Contractor Update Statement. Tab A - Invitation for Bids. Tab B - Instructions to Bidders

Raceway and Boxes for Electrical Systems Page 1 of 7

HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE:

STABILOY BRAND FEEDER SOLUTIONS ASSISTED LIVING FACILITIES

All work shall comply with applicable codes and ordinances. Work shall comply with the BOCA National Plumbing Code, latest edition.

A. Accessible Fixture: Emergency plumbing fixture that can be approached, entered, and used by people with disabilities.

B. Related Sections: 1. Section Raceway and Boxes for Electrical Systems.

A. Accessible Fixture: Emergency plumbing fixture that can be approached, entered, and used by people with disabilities.

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings

DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS

FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851

INTRODUCTION TO CHAPTER 3 WIRING METHODS AND MATERIALS

Compliant Healthcare Technologies, LLC. NFPA 99, 2012 Changes" November 13, 2013!

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5

Conduit Fittings & Accessories Directional Drilling Conduit Utility Duct Telephone Duct Residential Boxes

Common Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.)

American National Standard. Fittings, Cast Metal Boxes, and Conduit Bodies for Conduit, Electrical Metallic Tubing, and Cable

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code

A. Shop Drawing submittals shall include, but not be limited to, the following:

SECTION COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)

BRANCH CIRCUIT AND FEEDER REQUIREMENTS

SECTION LOW VOLTAGE LIGHTING CONTROLS

SECTION ALUMINUM HANDRAIL AND RAILING SYSTEMS WITH DECORATIVE METAL PANEL INFILLS

INSPECTION GUDELINES

The Contractor shall furnish and install all shielded power cable suitable for use on this project.

BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET

2012 Electrical Code Changes Module 2 Sections 6-16

Installation and Application Guide. for 600V Conductors

A. Accessible Fixture: Emergency plumbing fixture that can be approached, entered, and used by people with disabilities.

Chapter 3 Pre-Installation, Foundations and Piers

NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS

SECTION TABLE OF CONTENTS. H Proposed Material, Product or Equipment Substitution Request

SECTION HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

The Embassy of the United States of America invites you to submit an offer for supply and install the following A/Cs:

SECTION MEDIUM VOLTAGE SWITCHGEAR

RayClic Connection System Installation Instructions

FIRESTOPPING & SMOKE SEALS

SECTION CABLE TRAYS. A. Continuous, rigid, welded steel or stainless steel wire mesh cable management system.

B. NICET: National Institute for Certification in Engineering Technologies.

LEAD FREE FIREX. Interlock Armored Cables TECK90 and MC Industrial Cables. w w w. n e x a n s e n e r g y. c o m

SECTION ACCESS CONTROL SYSTEM. CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section.

Top Commercial / Residential Electrical Requirements *

Excerpts from the Canadian National Building Code (NBC)

D Youville College July 31, 2008 New Academic Building Cannon Design Project No

GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS

H-Stud Area Separation Wall System

SERVICE ENTRANCE - UNDERGROUND Single & Three Phase 200, & 320/400 Amp

SECTION HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT

Residential Electrical Inspection. Checklist

4 Installation Requirements

ELECTRICAL SAFETY Information Bulletin

PART 1 GENERAL 1.1 SECTION INCLUDES

CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION

SECTION COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND SECURITY

Crawford Inspection Services C.C.B. #

DIVISION 27 COMMUNICATIONS. A. System design shall be completed by a Registered Communications Distribution Designer (RCDD).

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

Transcription:

SECTION 260519 - LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Building wires and cables rated 600 V and less. 2. Connectors, splices, and terminations rated 600 V and less. 3. Sleeves and sleeve seals for cables. 1.2 SUBMITTALS A. Product Data: For each type of product indicated. B. Field quality-control test reports. 1.3 QUALITY ASSURANCE A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use. B. Comply with NFPA 70. PART 2 - PRODUCTS 2.1 CONDUCTORS AND CABLES A. Copper Conductors: Comply with NEMA WC 70. B. Conductor Insulation: Comply with NEMA WC 70 for Types THW THHN-THWN XHHW. C. Multiconductor Cable: Comply with NEMA WC 70 for armored cable, Type AC metal-clad cable, Type MC mineral-insulated, metal-sheathed cable, Type MI nonmetallic-sheathed cable, Type NM with ground wire. 2.2 CONNECTORS AND SPLICES A. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519-1

B. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. AFC Cable Systems, Inc. 2. Hubbell Power Systems, Inc. 3. O-Z/Gedney; EGS Electrical Group LLC. 4. 3M; Electrical Products Division. 5. Tyco Electronics Corp. C. Description: Factory-fabricated connectors and splices of size, ampacity rating, material, type, and class for application and service indicated. 2.3 SLEEVES FOR CABLES A. Steel Pipe Sleeves: ASTM A 53/A 53M, Type E, Grade B, Schedule 40, galvanized steel, plain ends. B. Cast-Iron Pipe Sleeves: Cast or fabricated "wall pipe," equivalent to ductile-iron pressure pipe, with plain ends and integral waterstop, unless otherwise indicated. C. Coordinate sleeve selection and application with selection and application of firestopping specified in Division 07 Section "Penetration Firestopping." 2.4 SLEEVE SEALS A. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: B. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. Advance Products & Systems, Inc. 2. Calpico, Inc. 3. Metraflex Co. 4. Pipeline Seal and Insulator, Inc. C. Description: Modular sealing device, designed for field assembly, to fill annular space between sleeve and cable. 1. Sealing Elements: EPDM interlocking links shaped to fit surface of cable or conduit. Include type and number required for material and size of raceway or cable. 2. Pressure Plates: Carbon steel. Include two for each sealing element. 3. Connecting Bolts and Nuts: Carbon steel with corrosion-resistant coating of length required to secure pressure plates to sealing elements. Include one for each sealing element. LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519-2

PART 3 - EXECUTION 3.1 CONDUCTOR MATERIAL APPLICATIONS A. Feeders: Copper. Solid for No. 10 AWG and smaller; stranded for No. 8 AWG and larger. B. Branch Circuits: Copper. Solid for No. 10 AWG and smaller; stranded for No. 8 AWG and larger. 3.2 CONDUCTOR INSULATION AND MULTICONDUCTOR CABLE APPLICATIONS AND WIRING METHODS A. Service Entrance: Type THHN-THWN, single conductors in raceway. B. Exposed Feeders: Type THHN-THWN, single conductors in raceway Armored cable, Type AC. C. Feeders Concealed in Ceilings, Walls, Partitions, and Crawlspaces: Type THHN-THWN, single conductors in raceway. D. Feeders Concealed in Concrete, below Slabs-on-Grade, and Underground: Type THHN- THWN, single conductors in raceway. E. Exposed Branch Circuits, Including in Crawlspaces: Type THHN-THWN, single conductors in raceway Armored cable, Type AC. F. Branch Circuits Concealed in Ceilings, Walls, and Partitions: Type THHN-THWN, single conductors in raceway. G. Branch Circuits Concealed in Concrete, below Slabs-on-Grade, and Underground: Type THHN-THWN, single conductors in raceway. H. Cord Drops and Portable Appliance Connections: Type SO, hard service cord with stainlesssteel, wire-mesh, strain relief device at terminations to suit application. I. Class 1 Control Circuits: Type THHN-THWN, in raceway. J. Class 2 Control Circuits: Type THHN-THWN, in raceway Power-limited cable, concealed in building finishes or Power-limited tray cable, in cable tray. 3.3 INSTALLATION OF CONDUCTORS AND CABLES A. Conceal cables in finished walls, ceilings, and floors, unless otherwise indicated. B. Use manufacturer-approved pulling compound or lubricant where necessary; compound used must not deteriorate conductor or insulation. Do not exceed manufacturer's recommended maximum pulling tensions and sidewall pressure values. LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519-3

C. Use pulling means, including fish tape, cable, rope, and basket-weave wire/cable grips, that will not damage cables or raceway. D. Install exposed cables parallel and perpendicular to surfaces of exposed structural members, and follow surface contours where possible. E. Support cables according to Division 26 Sections "Hangers and Supports for Electrical Systems." F. Identify and color-code conductors and cables according to Division 26 Section "Identification for Electrical Systems." G. Tighten electrical connectors and terminals according to manufacturer's published torquetightening values. If manufacturer's torque values are not indicated, use those specified in UL 486A and UL 486B. H. Make splices and taps that are compatible with conductor material and that possess equivalent or better mechanical strength and insulation ratings than unspliced conductors. 1. Use oxide inhibitor in each splice and tap conductor for aluminum conductors. I. Wiring at Outlets: Install conductor at each outlet, with at least 6 inches of slack. 3.4 SLEEVE INSTALLATION FOR ELECTRICAL PENETRATIONS A. Coordinate sleeve selection and application with selection and application of firestopping specified in Division 07 Section "Penetration Firestopping." B. Concrete Slabs and Walls: Install sleeves for penetrations unless core-drilled holes or formed openings are used. Install sleeves during erection of slabs and walls. C. Fire-Rated Assemblies: Install sleeves for penetrations of fire-rated floor and wall assemblies unless openings compatible with firestop system used are fabricated during construction of floor or wall. D. Cut sleeves to length for mounting flush with both wall surfaces. E. Extend sleeves installed in floors 2 inches above finished floor level. F. Size pipe sleeves to provide 1/4-inch annular clear space between sleeve and cable unless sleeve seal is to be installed or unless seismic criteria require different clearance. G. Seal space outside of sleeves with grout for penetrations of concrete and masonry and with approved joint compound for gypsum board assemblies. H. Interior Penetrations of Non-Fire-Rated Walls and Floors: Seal annular space between sleeve and cable, using joint sealant appropriate for size, depth, and location of joint according to Division 07 Section "Joint Sealants." LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519-4

I. Fire-Rated-Assembly Penetrations: Maintain indicated fire rating of walls, partitions, ceilings, and floors at cable penetrations. Install sleeves and seal with firestop materials according to Division 07 Section "Penetration Firestopping." J. Roof-Penetration Sleeves: Seal penetration of individual cables with flexible boot-type flashing units applied in coordination with roofing work. K. Aboveground Exterior-Wall Penetrations: Seal penetrations using sleeves and mechanical sleeve seals. Size sleeves to allow for 1-inch annular clear space between pipe and sleeve for installing mechanical sleeve seals. L. Underground Exterior-Wall Penetrations: Install cast-iron "wall pipes" for sleeves. Size sleeves to allow for 1-inch annular clear space between cable and sleeve for installing mechanical sleeve seals. 3.5 SLEEVE-SEAL INSTALLATION A. Install to seal underground exterior-wall penetrations. B. Use type and number of sealing elements recommended by manufacturer for cable material and size. Position cable in center of sleeve. Assemble mechanical sleeve seals and install in annular space between cable and sleeve. Tighten bolts against pressure plates that cause sealing elements to expand and make watertight seal. 3.6 FIRESTOPPING A. Apply firestopping to electrical penetrations of fire-rated floor and wall assemblies to restore original fire-resistance rating of assembly according to Division 07 Section "Penetration Firestopping." 3.7 FIELD QUALITY CONTROL A. Perform tests and inspections and prepare test reports. B. Tests and Inspections: 1. After installing conductors and cables and before electrical circuitry has been energized, test service entrance and feeder conductors, and conductors feeding the following critical equipment and services for compliance with requirements. a. Ice Maker b. Coolers c. Freezers 2. Perform each visual and mechanical inspection and electrical test stated in NETA Acceptance Testing Specification. Certify compliance with test parameters. LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519-5

3. Infrared Scanning: After Substantial Completion, but not more than 60 days after Final Acceptance, perform an infrared scan of each splice in cables and conductors No. 3 AWG and larger. Remove box and equipment covers so splices are accessible to portable scanner. a. Follow-up Infrared Scanning: Perform an additional follow-up infrared scan of each splice 11 months after date of Substantial Completion. b. Instrument: Use an infrared scanning device designed to measure temperature or to detect significant deviations from normal values. Provide calibration record for device. c. Record of Infrared Scanning: Prepare a certified report that identifies splices checked and that describes scanning results. Include notation of deficiencies detected, remedial action taken, and observations after remedial action. C. Test Reports: Prepare a written report to record the following: 1. Test procedures used. 2. Test results that comply with requirements. 3. Test results that do not comply with requirements and corrective action taken to achieve compliance with requirements. D. Remove and replace malfunctioning units and retest as specified above. END OF SECTION 260519 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519-6