Instructions for the fan motor control system with integrated wiring terminals SILVER C

Similar documents
Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

USER S MANUAL. MaxPower UPS. Uninterruptible Power System 28-2MAXPO0018

NC-12 Modbus Application

PSDC PSDC 12V/8A/8x1A Power supply for up to 8 analog cameras PTC/TOPIC.

IO-RM3 3-Stage Relay Module

Series AMEPR30-AZ up to 2.5A AC-DC / DC-DC LED Driver / Converter

VLT Series 3500 Adjustable Frequency Drive Instruction Manual

TX OPEN RS232/485 module

REB 1 REB 3 REB 5 REB 6 REB 8 REB 10 REB 12 REB 16

TMS TANK MANAGEMENT SYSTEM

Operating Manual for the Electronic Built-in Interval Timer. Micro II (Countdown Timer)

AXIS T81B22 DC 30W Midspan

TIG INVERTER INSTRUCTION MANUAL

Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.

ALARM ANNUNCIATOR ME INSTRUCTION MANUAL

Vroom Hardware manual ver Code 114VROOHWE00. Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR

EPM3. Phase Sequence and Motor Rotation Tester. Users Manual

WD-AMX Water Detection Controllers

MICROSENS. Central 48 V DC Power Supplies for PoE-Components. Description. Features

Digital input modules

ACS-30-EU-EMDR-10-MOD

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

A1000 Cheat Sheet (Open Loop Vector)

Technical Description. Transistor D.C. Chopper Controller Type GS 24 S

ABB Drives. User s Manual. Pulse Encoder Interface Module RTAC-01

User s Manual Before using the inverter, you need to read and save the safety instructions.

Drayton Digistat +2RF/+3RF

HCS-3300/3302/3304 USB Remote Programmable Laboratory Grade Switching Mode Power Supply

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories

FLEXIT S4 R S6 R S7 R

Silvertel. Ag Features. 2 Description. Power-over-Ethernet Plus Module. IEEE802.3at and IEEE802.3af compliant. Maximum 30W output power

How To Use A Power Supply Unit (Upu)

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application

Duct Humidity Transmitter

User s Manual AURORA 1.2K/2.2K

Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages

LS1024B / LS2024B/ LS3024B. Solar Charge Controller USER MANUAL

1000W Single Output Power Supply 15V 24V. Protection type: Total Power limit, Latch-style (Recovery after reset AC power ON or inhibit)

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.

ELITE-L Series. ELITE - Low Voltage / Dry contact Remote Control System

Three-phase monitoring relay CM-PFE

TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC A - M8 connector

650W Single Output Power Supply 15V 24V. 27V 48V Rated Current. 0 ~ 100A 0 ~ 50A 0 ~ 40A 0 ~ 27A 0 ~ 24A 0 ~ 13.6A Rated Power

Inductive Sensors Single or Dual Loop Detectors Type LD with teach-in

EPGM1 HARDWIRED ZONE & PGM OUTPUT EXPANSION MODULE

Power Supplies 3. SDN-P DIN Rail Series

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

Antec TruePower User's Manual

Addendum to the Operating Instructions

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

RM17TE V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

PD30ETB20xxIS. Photoelectrics, Background Suppression reflective with IR light. Main features. Description

ML 1012 v.1.2 ML13,8V/1A Buffer power supply module, linear.

Introduction. Refrigerant Leak Detecting System. Feature and Benefits


Mobile Data Power Model: MDP-25

Installation and Operating Instructions for ROBA -takt Control Unit Type

BITMAIN. APW PSU Series User Guide

Oil and Coolant Circulating Heating System. Model - OCSM

Powerware 5110 UPS User s manual

Voltage Regulator SPAU 341 C. Product Guide

R.C.C.B. s two-pole LEXIC

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410

Quick Connect. quick - simple - efficient.

Panel Meters and Controllers Modular Panel Meter Type EDM 35

How To Use The Vacon 0 Machinery

R4D0-FB-IA* FieldBarrier. Features. Assembly. Function. Connection IN + - S OUT Spur 2. Spur 1. Zone 1. Zone 0

VOICE RECORDING SYSTEM ISDN PRI / BRI

Waveguide Access Point WGA631. Product Guide

Number 1 in efficiency

CPCI-3U-AC-300W-R. Rugged 300W AC Input 3U CompactPCI Power Supply. Electrical Specification for: Telkoor Part Number:

GPD 506/P5 Start-up Procedure and Checklist

650W Single Output Power Supply

Telephone- and leased line modem for industrial applications TD-36

EZmoto V2. Product description Rev. 6 10/01/2014. EZmoto V2 Product description Rev.6 10/01/2014

Operating Manual UWAPS-TINY Series

DUAL%CHANNEL BROADBAND%LINEAR%AMPLIFIER Model&A800D

is then retained absolutely without interruption.

STRATO LED Drivers 70W, Single output

ZC-24DO CANopen I/O Module: 24 Digital Outputs

TECHNICAL DATASHEET #TD1404AX PWM CONTROLLED SOLENOID DRIVER

Uninterruptible Power Supply

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.

SX460. Generator Automatic Voltage Regulator Operation Manual

AC3200 INTELLIGENT BROADBAND AMPLIFIER

INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930

5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual

Installation manual. Generator Paralleling Controller GPC multi-line C

USER MANUAL GEBRUIKSAANWIJZING GEBRAUCHSANWEISUNG

SECTION VARIABLE FREQUENCY DRIVES

Chrome DIN Rail Power Supply 12V 54W 1 Phase (Class II & NEC Class 2) / DRC-12V60W1AG

PCS0100en Persy Control Services B.V. Netherlands

EPL225 Series. 225 Watts. AC-DC Power Supplies. Models & Ratings. Summary

MCR1900 Media Converter 19-Slot Chassis

Original instructions Tina 3A/Aps Adaptor unit

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23

Multi-Protocol decoder with Load regulation

I STAR COMPUTER CO., LTD

Transcription:

Instructions for the fan motor control system with integrated wiring terminals SILVER C 1. General The motor control system is used for controlling the type EC, 0.41-6.5 kw fan motors in the SILVER C units. The motor control system is mounted on the respective fan mounting frame. Integrated functions: 0-10 V DC analogue input for controlling the speed. Control with an external hand-held micro terminal. Flying start, in both directions. Alarm for overloading, over-voltage and under-voltage. Protective motor switch with integrated current limiting function. Short-circuit protected inputs and outputs. Digital input for start/stop. Digital input for operation in fire mode. Digital input for alarm resetting. Integrated EMC filter. In-operation indication, 0-10 V output. Operation relay, free-closing relay output Alarm relay, free-closing relay output Forbidden to start operation It is forbidden to start operation until the entire air handling unit, where the above-mentioned fan motor control system is integrated, has been declared to conform to relevant regulations in Machinery Directive 98/37/EEC and to existing national legislation, if applicable. The motor control system must not be energized until the entire installation conforms to the provisions in ALL relevant EU Directives. The motor control system is covered by the factory warranty provided it is installed according to these installation instructions and applicable installation regulations. If the motor control system has been damaged, for instance during transport, it must be inspected and repaired by qualified personnel before the voltage is connected. Safety functions The motor control system is protected against phase-tophase short.circuiting, and has integrated current limiting function for protection of the motor. The electrician is accountable for ensuring correct earthing as well as protection according to local standards and regulations. An earth fault circuit breaker, multiple protective earthing or ordinary earthing can be used as extra protection, provided that the local regulations are complied with. The earth leakage currents exceed 3.5 ma. Therefore a fixed, permanent installation and heavy-duty protective earthing are required. NOTE! If an earth fault occurs, there can be a direct current component in the leakage current. Earth fault circuit breakers should therefore be designed to be able to detect this and be installed according to applicable national and international regulations, where they are used. We reserve the right to alter specifications. www.swegon.com 1

2. Technical data Motor shaft power The respective size of SILVER C is available in two capacity variants (does not apply to size 04). The lower specified capacity on the respective size in the table below applies to capacity variant 1 and the higher capacity applies to capacity variant 2. Sizes 04-40 have one fan per airflow direction, sizes 50-100 have two fans per airflow direction and the size 120 has three fans per airflow direction. Size Motor shaft power 04: 0.8 kw (0.41 kw)* 05: 0.8 kw (cap. var. 1) alt. 1.15 kw (cap. var. 2) 07: 0.8 kw (cap. var. 1) alt. 1.15 kw (cap. var. 2) 08: 1.15 kw (cap. var. 1) alt. 1.6 kw (cap. var. 2) 11: 1.15 kw (cap. var. 1) alt. 1.6 kw (cap. var. 2) 12: 1.6 kw (cap. var. 1) alt. 2.4 kw (cap. var. 2) 14: 1.6 kw (cap. var. 1) alt. 2.4 kw (cap. var. 2) 20: 2.4 kw (cap. var. 1) alt. 3.4 kw (cap. var. 2) 25: 2.4 kw (cap. var. 1) alt. 3.4 kw (cap. var. 2) 30: 4.0 kw (cap. var. 1) alt. 5.0 kw (cap. var. 2) 35: 4.0 kw (cap. var. 1) alt. 5.0 kw (cap. var. 2) 40: 5.0 kw (3.9 kw)* (cap. var. 1) alt. 6.5 kw (cap. var. 2) 50: 2 x 2.4 kw (cap. var. 1) alt. 2 x 3.4 kw (cap. var. 2) 60: 2 x 4.0 kw (cap. var. 1) alt. 2 x 6.5 kw (cap. var. 2) 70: 2 x 4.0 kw (cap. var. 1) alt. 2 x 6.5 kw (cap. var. 2) 80: 2 x 6.5 kw (cap. var. 1) 100: 2 x 6.5 kw (cap. var. 1) 120: 3 x 6.5 kw (cap. var. 1) *) The motor control system limits the output power to the value specified. Power supply Each fan has one motor control system. The motor control system should be supplied with power according to the table below. Specified voltage -10% +15%. Size Electrical data per fan Number of motor control systems per airflow direction 04: 1 x 230 V, 50 Hz, rated 2.3 A 1 05, cap. var. 1: 1 x 230 V, 50 Hz, rated 4.3 A 1 05, cap. var. 2: 1 x 230 V, 50 Hz, rated 5.5 A 1 07, cap. var. 1: 1 x 230 V, 50 Hz, rated 4.3 A 1 07, cap. var. 2: 1 x 230 V, 50 Hz, rated 5.5 A 1 08, cap. var. 1: 1 x 230 V, 50 Hz, rated 6.0 A 1 08, cap. var. 2: 3 x 400 V, 50 Hz, rated 2.8 A 1 11, cap. var. 1: 1 x 230 V, 50 Hz, rated 6.0 A 1 11, cap. var. 2: 3 x 400 V, 50 Hz, rated 2.8 A 1 12, cap. var. 1: 3 x 400 V, 50 Hz, rated 2.8 A 1 12, cap. var. 2: 3 x 400 V, 50 Hz, rated 3.8 A 1 14, cap. var. 1: 3 x 400 V, 50 Hz, rated 2.8 A 1 14, cap. var. 2: 3 x 400 V, 50 Hz, rated 3.8 A 1 20, cap. var. 1: 3 x 400 V, 50 Hz, rated 4.2 A 1 20, cap. var. 2: 3 x 400 V, 50 Hz, rated 5.9 A 1 25, cap. var. 1: 3 x 400 V, 50 Hz, rated 4.2 A 1 25, cap. var. 2: 3 x 400 V, 50 Hz, rated 5.9 A 1 30, cap. var. 1: 3 x 400 V, 50 Hz, rated 7.3 A 1 30, cap. var. 2: 3 x 400 V, 50 Hz, rated 8.9 A 1 35, cap. var. 1: 3 x 400 V, 50 Hz, rated 7.3 A 1 35, cap. var. 2: 3 x 400 V, 50 Hz, rated 8.9 A 1 40, cap. var. 1: 3 x 400 V, 50 Hz, rated 7.2 A 1 40, cap. var. 2: 3 x 400 V, 50 Hz, rated 11.9 A 1 50, cap. var. 1: 3 x 400 V, 50 Hz, rated 4.2 A 2 50, cap. var. 2: 3 x 400 V, 50 Hz, rated 5.9 A 2 60, cap. var. 1: 3 x 400 V, 50 Hz, rated 7.3 A 2 60, cap. var. 2: 3 x 400 V, 50 Hz, rated 11.2 A 2 70, cap. var. 1: 3 x 400 V, 50 Hz, rated 7.3 A 2 70, cap. var. 2: 3 x 400 V, 50 Hz, rated 11.2 A 2 80, cap. var. 1: 3 x 400 V, 50 Hz, rated 11.9 A 2 100, cap. var. 1: 3 x 400 V, 50 Hz, rated 11.9 A 2 120, cap. var. 1: 3 x 400 V, 50 Hz, rated 11.9 A 3 2 www.swegon.com We reserve the right to alter specifications.

TECHNICAL DATA OF THE MOTOR CONTROL SYSTEM Description kw The size of the control system 0.41*/0.8 kw 1.15 kw 1.6 kw 2.4 kw 4.0 kw 6.5 kw Dimensions mm 185 x 220 x 90 185 x 250 x 100 220 x 295 x 110 Weight kg 2.0 3.0 3.9 POWER SUPPLY Voltage VAC 1 x 230 VAC 50/60 Hz +/-10 % 3 x 400 VAC 50/60 Hz +/-10 Current at max. load A 4.4 6.5 3.5 5.0 8.4 13.6 Power factor COS φ for max. load >0.99 (Active PFC) >0.9 MOTOR OUTPUT Frequency Hz 0-120 Max. output voltage Vrms 3 x 0-250 V AC 3 x 0-360 V AC Max. output current Arms 3.2 4.5 4.5 6.4 11.7 19 PROTECTION Max. fuse A 16 Motor output Short-circuit protected between phases Motor To be protected by current limitation Impulse protection Transient protected with varistors Surge protection Yes, 400 V (PTC) Yes, 565 V Overload protection Overload protected for current and temperature ENVIRONMENTAL SPECIFICATIONS Operating temperature C -40 C to + 40 C Start temperature C -40 C to + 50 C Storage temperature C -40 C to + 70 C Enclosure class IP 65 54 Enclosure material Aluminium Front access panel Plastic Humidity % rh 10 95 % rh non-condensing Vibrations Stationary: IEC 60721-3-3 Class 3M6 2.0 kg Non-stationary: IEC 60721-3-3 Class 3M6 25.0 kg INTERFACES Digital communication Slave 2 x RJ12 & 2 x spring-type wiring terminals Digital communication Master 1 x RJ12 Analogue In 1 0-10 VDC, 100% vid 9.5 V DC +/-2% Analogue Out 1 +10 V DC Digital In 1 Start/stop with internal pull-up Digital In 2 Alarm reset Green LED Shines constantly: Voltage connected. Flashing: Active communication Red LED Flashing: Alarm, but still operating. Shines constantly: Critical alarm - stop the motor FUNCTION Technology Sinusoidal Back EMF controlled by signals via FOC (Field Oriented Control) Flying start Yes, typically < 30 % of max. speed, depending on the load and the weight of the fan Ramp up Sec. 15-300 Ramp down Sec. 15-300 Alarm Yes Alarm reset Via digital input, or dead for more than 60 seconds. Fan stop Sec. The braking function stops the fan as fast as possible. The braking time depends on the live force of the fan. Service data log In-operation hours, alarm, load, program version, max. temperature, max. motor voltage, max. motor current, max. ripple voltage, max. ripple current. Program update Yes. via serial interface. Motor parameters Programmable by Swegon. Fire mode Rated output for 1 hour at 70 C Field weakening Yes Short-circuit protection Yes EMC filter Integrated APPROVALS EMC EMC EN 61800-3 (C1 and C2) LVD EN 61800-5-1 Product standard EN 61800 Part 2 The RoHS Directive Yes Product approvals CE * SILVER C, size 04. The motor control system limits the output power to 0.41 kw. We reserve the right to alter specifications. www.swegon.com 3

3. Function Control The motor control system can control via the following: 0-10 V DC (100 % for 9.5 V, +/-2 %) local control with hand-held terminal (Accessory TBLZ- 2-75) potentiometer Control with 0 10 V DC The motor control system regulates the speed linearly between 0 % and 100 %, however it is limited to the regulation range between the preset lowest and highest speeds of rotation (See Fig. 2 and 3). Set the lowest and highest speed of rotation via the hand-held terminal. 100 % speed is defined as an input voltage of "0-10 V in". In order to be able to control the motor control system via 0 10 V DC, select Control = 0 10 V DC in the Startup / Control menu of the hand-held terminal, which is also the factory setting. External stop and stop from the hand-held micro terminal have higher priority than start from the hand-held terminal. If the fire mode function is not switched off, the motor control system will control the fan without the alarm and safety functions being activated. See the Firemode Section. The motor control system is supplied with the "Firemode" function switched off by means of a pre-fitted short-circuit jumper. The short-circuit jumper must be removed if the fire mode signal e.g. comes from a common fire alarm installation (ABA). Fig. 2. The ratio between the speed and the ramp up and ramp down times Control with hand-held terminal In order to be able to control the motor control system with the hand-held terminal, select Control = Modbus in the Start-up / Control menu of the hand-held terminal. For other particulars, see the instructions for the hand-held terminal. Control with a potentiometer The motor control system can be controlled via a potentiometer. The potentiometer should have a resistance of at least 4.7 kω (recommended) and not higher than 47 kω. For other particulars, refer to the "Control with 0 10 V DC" Section. Fig. 3. The ratio between the speed and the min./max. speed setting 4 www.swegon.com We reserve the right to alter specifications.

Firemode function [Fire mode] The Firemode function is the designation of a condition in the motor control system when the system is running an emergency program without monitoring of alarms. For example, the internal excess temperature protection in the motor control system is switched off and the motor does not stop when an interruption in communication arises. The function can e.g. be used for smoke extraction in connection with a fire in a building. An extract air fan will e.g. be able to continue extracting smoke from the building as long as it is at all possible when "Firemode" is activated. This occurs as well without the fan stopping due to a fault and other alarms from both the fan and from the motor control system. The speed is the preset speed, which either comes from an external 0 10 V control signal or a potentiometer. The motor control system will continue to operate for at least one hour, even if the motor control system and the fan motor are overheated. In this situation, the motor control system has priority to continue to operate, regardless of which alarm is active. Observe the following: If the temperature in the motor control system is over 75 C, the voltage supplied to the hand-held terminal is interrupted. The hand-held terminal can therefore not be used when the temperature exceeds 75 C. Automatic restart after alarm The motor control system automatically attempts to start again following an alarm, such as over voltage. This automatic restart is carried out maximally 5 times. After that, the motor control system will remain in the error mode, and must be restarted by resetting the alarm. Alarm resetting: See Section on "Alarm resetting". In-operation indication The motor control system is equipped with an 0-10 V analogue output for in-operation indication. 0% speed corresponds to a 0V output signal, 100% speed corresponds to a 10V output signal. Operation relay The motor control system is equipped with an operation relay that can transmit an in-operation signal to an external item of equipment. The signal output is a changeover relay that normally is closed between Terminals 20 and 21. When the motor control system receives a start signal, the relay changes position and closes between Terminals 21 and 22. Alarm relay/output The motor control system is equipped with an alarm output in the form of an alarm relay. The alarm relay is activated if an alarm arises in the motor control system or if an alarm is discovered in the motor or fan. The alarm output is a changeover relay that normally is closed between Terminals 24 and 25. When the motor control system receives an alarm signal, the relay changes position and closes between Terminals 23 and 24. Alarm resetting The motor control system is equipped with a digital input for resetting alarms. The alarm output is reset by shortcircuiting Terminals 06 (GND) and 07 (Din2) (See Fig. 1). The alarm output can also be reset by switching off the supply voltage to the motor control system for more than 60 seconds. Switching frequency The motor's switching frequency (SwitchMode) can be set in the hand-held terminal to the following values. 0 = Auto 1 = Low = 4 khz 2 = High = 8 khz If the switching frequency increases, the level of audible noise from the motor control system will decrease, but this will simultaneously increase the losses in the motor. The motor will consequently run at lower efficiency and this will impair its operating economy. In position 0 = Auto, the motor control system's switching frequency changes automatically. When an increase in speed of rotation is required, the motor control system switches from 2 = High = 8 khz to 1 = Low = 4 khz, if the speed exceeds 60 % of the rated maximum speed. When a decrease in speed of rotation is required, the motor control system switches from 1 = Low (4 khz) to 2 = High = (8 khz), if the speed drops below 50 % of the rated maximum speed. In mode 1 = Low = 4 khz the motor control system always runs with a low switching frequency while the air handling unit is operating. In mode 2 = High = 8 khz the motor control system always runs with a high switching frequency while the air handling unit is operating. LED indications The motor control system has a two-colour, built-in LED, which is located on the underside of the motor control system by the cable grommets for supply voltage. The LED shines constantly green when the supply voltage is connected. It flashes green when the Modbus communication is active. It shines constantly red when at least one critical alarm is active. It flashes red when at least one non-critical alarm is active. Warning The chassis on the motor control system can become very warm! Warning! Do not repair the motor control system at the site. Never attempt to repair a defective control system unit. Contact Swegon to obtain a replacement unit. Important! Contact the supplier if you want further technical particulars. We reserve the right to alter specifications. www.swegon.com 5

4. Electrical connections The fan mounting frame is equipped with one motor control system. For access, open the inspection covers of the fans and unscrew the bolts that secure the blue cover of the motor control system casing. I/O module SILVER 8-15 mm Max. 24VAC/DC, 1A res. GND Thermistor 0-10V in Dig. in 3 Dig. in 4 0-10V out +10V out +24V out GND Relay 1 Running Relay 2 Alarm NC C NO NC C NO 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 Fig. 1. Wiring terminals in the motor control system Function selector switch: Normally in Position 1. For communication with hand-held terminal, Position 0. 01 02 03 04 05 06 07 08 09 10 Bus A Bus B GND +10Vdc 0-10V In GND Din2 Din1 Dout1 GND 8-15mm A B C BR1014A15a 2015 OJ Electronics A/S -Add. Pin1 - -Add. Pin1 Din1 Din2 Dout1 Dig. in3 Dig. in4 Start/Stop Alarm Reset Not used Firemode Not used 6 www.swegon.com We reserve the right to alter specifications.

To connect control signal wiring Remove the pre-fitted sealing plug on the underside of the motor control system and install a cable fitting. Connect the 0 10 V DC control signal cable leads from an external regulator to Terminals 05 (0-10 V in) and 03 (GND) (See Fig. 1). Connect the control potentiometer cable leads to Terminals 04 (+10 Vdc), 05 (0-10 V in) and 03 (GND) (See Fig. 1 and 4). Connect the start and stop signal cable leads to Terminals 10 (GND) and 08 (Din1) (See Fig. 1). This should be a potential-free digital contact. Connect the firemode signal cable leads to the motor control system on Terminals 11 (GND) and 14 (Dig. in3) (See Fig. 1). This should be a potential-free digital contact. Connect the Alarm Reset signal cable leads to the motor control system on Terminals 06 (GND) and 07 (Din2) (See Fig. 1). This should be a potential-free digital contact. Connect the in-operation indication cable leads to Terminals 16 (0-10V out) and 19 (GND) (See Fig. 1). The in-operation signal cable is labelled R1, and should be connected to Terminals 20 (NC), 21 (C) and 22 (NO) (See Fig. 1). The alarm signal cable is labelled R2, and should be connected to Terminals 23 (NC), 24 (C) and 25 (NO) (See Fig. 1). Electric wiring of the hand-held micro terminal Connect the hand-held micro terminal to the motor control system's integrated wiring terminals, in Port "A". Use a bus cable, (type 6-core, unshielded, 30 AWG/0.066 mm 2 telecommunication cable or a similar flat cable) with RJ12/6 connectors in both ends, see the figures below. BR1014A11a 2015 OJ Electronic A/S Same order of colours A B C - We reserve the right to alter specifications. www.swegon.com 7

Electric Power Connections RX, sizes 04-40: The cables for connecting power to the motor control system are, from the factory, run to one point. This point is located within the inspection cover on the air handling unit's centre section (the section for the heat exchanger). Others: The cables for connecting power to the motor control system are located in the respective fan compartment. For appropriate connection, see Fig. 7 and 8 below. For electrical data, see Section 2. BR1014A21a 2015 OJ Electronic A/S UVWPE L NPE UVWPE L1L2L3PE Fig. 7. Power connection of the motor control system: 0.8-1.15 kw. Fig. 8. Power connection of the motor control system: 1.6-6.5 kw. 8 www.swegon.com We reserve the right to alter specifications.

5. Trouble shooting To open the motor control system Before you open the motor control system, isolate the line voltage and wait at least 3 minutes. Failure to do so will expose you to the risk of coming into contact with harmful residual voltage inside the unit. If natural draught in the duct system causes the fan impeller to rotate, but no in-operation signal has been received, there is risk that the motor will induce voltage on the motor control terminals, making them dangerous to touch. Troubleshooting when the motor control system is controlled with external (A/D) signals: Symptoms Cause Action Check whether there is voltage on the motor control system's L and N Terminals on the models for 230 V or on the "L1, L2 and L3 Terminals on the models for 3 x 400 V. The motor is not rotating There is no power supply Poor electrical connections Wrong motor the motor control system There is no in-operation signal There is no 0 10 V DC control signal Alarm active The motor has been stopped by the internal protective motor switch 5 times due to overloading or some other alarm. Defective motor control system Defective motor (The operating voltage is specified on the rating plate, affixed to the side of the motor control system.) Check that all the short-circuit protections have been activated. Check that the incoming power supply to the motor control system has not been interrupted by some other component. Check the connectors and other electrical connections Check that correct motor settings have been entered and saved in the motor control system set up. Check that the motor control system can receive in-operation signals. The motor control system must have a connected signal to the Start/Stop input, digital input Terminal 08 (Din1). Check that the 0-10 V DC control signal cable leads are correctly connected to Terminals 05 (0-10V in) and 06 (GND) in the motor control system. For potentiometer operation: Check that the potentiometer's 0-10 V DC control signal cable leads are correctly connected to Terminals 04 (+10Vdc), 05 (0-10V in) and 06 (GND) in the motor control system. The potentiometer should have an inner resistance of at least 4.7 kω. Read the relevant alarm and remedy the cause. Reset the alarm by short-circuiting Terminals 06 (GND) and 07 (Din2) in the motor control system. You can also reset the alarm by switching off the supply voltage to the motor control system and switching it back on after 60 seconds. Replace the motor control system. Replace the motor The motor rotates in the wrong direction Incorrect phase sequence in motor cable Transpose two phase wires on the motor or in the motor control system. The motor control system is noisier than the acceptable level. The motor control system switches off. due to an alarm Too low switching frequency At least one alarm active The alarm will be reactivated after resetting Increase the switching frequency. 0 = Auto 1 = Low = 4 khz 2 = High = 8 khz When the switching frequency increases, the losses in the motor will also increase, which will lower the efficiency and impair its operating economy. It is possible to change the switching frequency in the motor control system with the hand-held micro terminal. Read the alarm in the hand-held micro terminal to determine which alarm has stopped the motor control system/motor. Reset the alarm by short-circuiting Terminals 06 (GND) and 07 (Din2) in the motor control system. You can also reset the alarm by switching off the supply voltage to the motor control system and switching it back on after roughly 60 seconds. Read the alarm in the hand-held micro terminal to determine which alarm has stopped the motor control system/motor. Remedy the reason why the alarm was reactivated. We reserve the right to alter specifications. www.swegon.com 9

6. Service and maintenance No particular maintenance is required. Contact Swegon if any problem arises. To troubleshoot the unit: See Section 5. Troubleshooting. 7. Alarms The integrated alarm relay in the motor control system has changeover contacts and is marked "Alarm Relay". The motor control system stops and an alarm indicating LED is lit. If the fault ceases to exist, the alarm is reset automatically and the motor control system starts up. The motor control system tries to automatically start again. If the maximum number of restarts (5) is exceeded, the alarm must be reset. When the motor control system is controlled with 0 10 V DC and digital signals, the alarm can be reset by shortcircuiting Terminals 06 (GND) and 07 (Din2). If the line voltage is switched off for more than 60 seconds, the alarm will be automatically reset. 10. CE marking Swegon AB certifies under its own sole responsibility that this product conforms to the Commission's Directive 92/31 with subsequent modifications concerning electric compatibility as well as the Commission's Directive 73/23 dealing with electric material for use within certain voltage limitations. EMC APPROVALS EN 61800-3 (C1 AND C2) LVD EN 61800-5-1 PRODUCT STANDARD EN 61800 PART 2 THE ROHS DIRECTIVE PRODUCT APPROVALS YES CE 8. Environment and waste disposal Help to protect the environment by ensuring correct disposal of the packaging and use the products in accordance with applicable environmental regulations. Disposal of the product The product must not be disposed of as ordinary household refuse. They must be collected in separate containers according to applicable local rules. 9. Applicable standards. GB-61800-2 EN-61800-3 EN-61800-5 Electric motor operation with variable speed, General Requirements General electromagnetic compatibility Electric motor operating modes with variable speed, Safety Requirements 10 www.swegon.com We reserve the right to alter specifications.