Anchorage of Wood Shear Walls to Concrete for Tension and Shear 2009 IBC brings about several changes from 2006 IBC

Similar documents
Perforated Shearwall Design Method 1

TECHNICAL NOTE. Design of Diagonal Strap Bracing Lateral Force Resisting Systems for the 2006 IBC. On Cold-Formed Steel Construction INTRODUCTION

REPORT HOLDER: JENWEST ENTERPRISES LLC, DBA ADVANCED CONNECTOR SYSTEMS 321 SOUTH 1240 WEST #15 LINDON, UTAH EVALUATION SUBJECT:

Design of Cold-Formed Steel Shear Walls

ICC-ES Evaluation Report

Wisconsin Building Products Evaluation

4B The stiffness of the floor and roof diaphragms. 3. The relative flexural and shear stiffness of the shear walls and of connections.

Discipline: Structural Issued

Chapter 6 ROOF-CEILING SYSTEMS

TZ WEDGE ANCHOR FOR CRACKED AND UNCRACKED CONCRETE

Concrete Design Manual

6 RETROFITTING POST & PIER HOUSES

Formwork for Concrete

Chapter 3 DESIGN AND CONSTRUCTION FEATURES IMPORTANT TO SEISMIC PERFORMANCE

SPECIFICATIONS, LOADS, AND METHODS OF DESIGN

Hilti, Inc South 122 nd East Avenue Tulsa, OK

HUS-H Screw Anchor. Technical data. Seismic design data. HUS-H Carbon steel screw anchor. HUS-H diameter 8, 10, 14. Seismic design data

Trusted SECTION: 04 HILTI, INC. TULSA, Conformity! ICC-ES Evaluation. not specifically. Copyright 2015

1997 Uniform Administrative Code Amendment for Earthen Material and Straw Bale Structures Tucson/Pima County, Arizona

Reinforced Concrete Design

Simpson s Tyrell Gilb Research Laboratory: Where Discovery Meets Development

CPA Steel Stud Framing Page 1 of 11

Submittal Information

CITY OF LOS ANGELES CALIFORNIA

National Council of Examiners for Engineering and Surveying. Principles and Practice of Engineering Structural Examination

Featuring TJ Rim Board and TimberStrand LSL

Cover. When to Specify Intermediate Precast Concrete Shear Walls Rev 4. White Paper WP004

THE DOW CHEMICAL COMPANY Issued: August 1, LARKIN CENTER 1605 JOSEPH DRIVE MIDLAND MICHIGAN (989)

Steel joists and joist girders are

Diaphragms and Shear Walls DESIGN/CONSTRUCTION GUIDE

Connection Solutions

Report on. Wind Resistance of Signs supported by. Glass Fiber Reinforced Concrete (GFRC) Pillars

Technical Notes 3B - Brick Masonry Section Properties May 1993

Wood Truss Restraint and Bracing Guide

Chapter 3 FOUNDATIONS AND FOUNDATION WALLS

Bracing Webs in Trusses that have Dissimilar Configurations

Basics of Reinforced Concrete Design

Hilti, Inc South 122 nd East Avenue Tulsa, OK

The following excerpt are pages from the North American Product Technical Guide, Volume 2: Anchor Fastening, Edition 16.

SLAB DESIGN. Introduction ACI318 Code provides two design procedures for slab systems:

Load Design Charts. R-CONTROL SIPs STRUCTURAL INSULATED PANELS. CONTROL, NOT COMPROMISE.

Hilti HIT-V and HAS Threaded Rod and Hilti HIT-Z Anchor Rod

HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES

Chapter 3 - Structural Design

Behaviour of Prefabricated Timber Wall Elements Under Static and Cyclic Loading

POST AND FRAME STRUCTURES (Pole Barns)

TEST REPORT. Rendered to: INTEX MILLWORK SOLUTIONS, LLC. For: Rigid Cellular PVC Guardrail System Hampton RS40

Hilti KWIK HUS-EZ I (KH-EZ I) Internally Threaded Carbon Steel Screw Anchor

Bolting: Attachment Of The Mudsill To The Foundation

What is Seismic Retrofitting?

System. Stability. Security. Integrity. 150 Helical Anchor

The Principles and Practice of Effective Seismic Retrofitting

COMMONLY USED RESIDENTIAL BUILDING CODES

INTERIM REPORT ON TESTING OF TENSION- ONLY STEEL ANCHOR RODS EMBEDDED IN REINFORCED CONCRETE SLABS

SEISMIC DESIGN. Various building codes consider the following categories for the analysis and design for earthquake loading:

Untopped Precast Concrete Diaphragms in High-Seismic Applications. Ned M. Cleland, Ph.D., P.E. President Blue Ridge Design, Inc. Winchester, Virginia

Structural Seismic Retrofits For Hawaii Single Family Residences With Post and Pier Foundations

Design for Nonstructural Components

Guidelines for Earthquake Bracing Residential Water Heaters

Seismic Technical Guide

Policy on Water Heater Installations Policy No. UPC Effective: September 1, 1995 Revised: February 10, 1996

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

CH. 2 LOADS ON BUILDINGS

Seismic Retrofit Guide

Structural Design for Residential Construction

RISABase. Rapid Interactive Structural Analysis Base Plate and Anchorage Analysis & Design. Version General Reference

Code Compliant Repair and Protection Guide

TABLE OF CONTENTS. Roof Decks 172 B, BA, BV Deck N, NA Deck. Form Decks FD,.6 FDV Deck 1.0 FD, 1.0 FDV Deck 1.5 FD Deck 2.0 FD Deck 3.

Prepared For San Francisco Community College District 33 Gough Street San Francisco, California Prepared By

Collective Chord Behavior in Large Flexible Diaphragms

November 20, Heather Sustersic Dear Professor Sustersic,

Expected Performance Rating System

FINAL FAILURE INVESTIGATION WESTCHESTER NORTH LAGOON BRIDGE. Anchorage, Alaska

CONCRETE FLOOR SLAB & CASTING BED CONSTRUCTION

research report Residential Hip Roof Framing Using Cold-Formed Steel Members RESEARCH REPORT RP06-2 American Iron and Steel Institute

PC-Concrete Injectable Concrete Anchoring and Repair System

Chapter 3 Pre-Installation, Foundations and Piers

EUROPEAN ORGANISATION FOR TECHNICAL APPROVALS

Foundations 65 5 FOUNDATIONS. by Richard Chylinski, FAIA and Timothy P. McCormick, P.E. Seismic Retrofit Training

Optimum proportions for the design of suspension bridge

Guidelines for Earthquake Bracing of Residential Water Heaters

16. Beam-and-Slab Design

Timber Frame Construction

How to Design Helical Piles per the 2009 International Building Code

Residential Deck Safety, Construction, and Repair

Shaft- Mounted Speed Reducers

SECTION 7 Engineered Buildings Field Investigation

CHAPTER 7. Connections. 7.1 General. The objectives of connection design are

CITY OF LOS ANGELES CALIFORNIA

Designing a Structural Steel Beam. Kristen M. Lechner

Section 5A: Guide to Designing with AAC

Steel Design Guide Series. Column Base Plates

Standard from CSI Part Section Format For Wood Framing For Metal Framing For Gypsum Sheathing

Detailing of Reinforcment in Concrete Structures

Handling, Erection and Bracing of Wood Trusses

INTRODUCTION TO LIMIT STATES

CONSTRUCTION DETAILS & LOAD DESIGN CHARTS

SECTION 5 ANALYSIS OF CONTINUOUS SPANS DEVELOPED BY THE PTI EDC-130 EDUCATION COMMITTEE LEAD AUTHOR: BRYAN ALLRED

APPENDIX H DESIGN CRITERIA FOR NCHRP PROJECT NEW BRIDGE DESIGNS

Transcription:

Anchorage of Wood Shear Walls to Concrete for Tension and Shear 2009 IBC brings about several changes from 2006 IBC By Shane Vilasineekul, P.E. Since the publication of the 2006 International Building Code (IBC), new research and testing related to wood shear walls and concrete anchorage have led to significant changes in the 2009 IBC, codereferenced material standards, product evaluation criteria and industry practice. The first change engineers will likely encounter is the removal of much of the wood shear wall design information from Section 2305 of the IBC. The code now requires the use of AF&PA s 2008 Special Design Provisions for Wind and Seismic (SDPWS-08) to design the lateral-force-resisting system. Since the format of the SDPWS-08 is different from the IBC, some of the other changes are not quite as apparent yet they will impact the way wood shear walls are designed and constructed. The SDPWS-08, however, does not contain everything needed to complete the design. After engineers determine the connections required at the base of the shear wall, they must then use the IBC and ACI 318-08 to design the anchorage into the concrete. If proprietary connectors or anchors are implemented, designers will need to ensure the products are approved for the application by the authority having jurisdiction. Most building departments and designers rely on research reports issued by an accredited product certification body, such as ICC-ES or IAPMO-ES, to evaluate code compliance. Designing the anchorage of shear walls is a multi-step process. Understanding the purpose of each step is important to ensure the finished product performs as expected. The process begins with determining the magnitude and location of the shear wall anchorage using the SDPWS-08. Wood Shear Wall Mechanics and Anchor Forces Figure 1 shows an idealized force diagram for the shear wall framing when a shear load is applied at the top. The shear force is transferred into the sheathing by nailing the panel into the top plate and transferred out of the sheathing by nailing the panel to the sole plate. Nails into the vertical edges of the sheathing panel prevent the panel from rotating, which results in tension and compression at the shear wall end posts. The shear wall must be anchored to resist uplift due to overturning and shear due to sliding. The overturning forces for a shear wall are given in SDPWS-08 Equation 4.3-7 for Individual Full Height Shear Wall Segments, and Equation 4.3-8 for Perforated Shear Wall Segments: Eqn. 4.3-7: T = C = vh Eqn. 4.3-8: T = C = (Vh) / (C o L i ) Where: T = tension force (lbs.) C = compression force (lbs.) h = shear wall height (ft.) v = induced unit shear (lbs./ft.) V = induced shear force (lbs.) C o = shear capacity adjustment factor L i = sum of perforated shear wall segment lengths (ft.) Simpson Strong-Tie Company Inc. 800.999.5099 www.strongtie.com Page 1

Designers should be cautioned that these equations do not include several factors that impact the design of the framing members and connections. For multi-story applications, overturning forces from shear walls above are cumulative and require careful detailing for load path. In addition, dead load above the shear wall end posts can reduce the tension force and increase the compression force. Finally, for narrow shear walls (aspect ratio, h:b, greater than 1:1 as a general rule), using a moment arm measured from center of tension (hold-down anchor) to center of compression (end post) can significantly increase the overturning forces compared to Eqn. 4.3-7, which uses a moment arm equal to the full length of shear wall (b). Figure 1: Idealized Force Diagram on Full-Height Shear Wall Segment The shear anchorage of the sole plate for an Individual Full Height Shear Wall Segment must be designed to transfer the induced unit shear force (v). For Perforated Shear Wall Segments, the sole plate anchorage must be designed to resist the maximuminduced unit shear from Equation 4.3-9. Eqn. 4.3-9: v max = (V) / (C o L i ) In addition, sole plates in Perforated Shear Wall Segments must be anchored to resist a uniform tension force equal to v max, resulting in anchorage designed for combined shear and tension. Figure 2: Idealized Force Diagram on Shear Wall Resisting Combined Shear and Uplift from Wind The SDPWS-08 introduced a new design procedure that permits certain shear wall sheathing materials to simultaneously resist shear and uplift from wind forces. Figure 2 shows a force diagram for the wall framing under combined shear and uplift. In this application, the sole plate anchorage must be designed for combined shear and tension and spaced no more than 16 in. on center to prevent sole plate splitting along the sheathing nails. Additional design and construction requirements can be found in Section 4.4. Simpson Strong-Tie Company Inc. 800.999.5099 www.strongtie.com Page 2

Overturning Uplift Restraint There are numerous proprietary products for resisting shear wall overturning uplift but they can generally be broken down into three types as shown in Figure 3: 1) embedded hold-downs, 2) hold-downs fastened to the end post and connected to a threaded anchor, and 3) threaded rods that pass through the shear wall and secure the end post down with a bearing plate above. Figure 3: Methods of Providing Overturning Restraint For embedded hold-downs, a new ICC-ES Acceptance Criteria was developed for code report coverage under the 2009 IBC: Acceptance Criteria for Cast-in-Place Cold-Formed Sheet Steel Connectors in Concrete for Light-Frame Construction (AC398). AC398 is based on a philosophy similar to ACI 318-05 Appendix D and results in separate allowable loads for cracked and uncracked concrete as well as wind and seismic forces. Hold-downs fastened to the end post and connected to a threaded anchor are typically tested and load rated in accordance with ICC-ES Acceptance Criteria for Hold-Downs Attached to Wood Members (AC155). AC155 became effective in 2006 and significantly changed how hold-downs are tested and load rated by requiring additional testing on wood posts and limiting deflection to ¼-in. at the strength design level. The design of the threaded anchor into the concrete will be discussed later in this article. Threaded rods and bearing plates used to resist overturning uplift are designed using AISC s 360-05 standard for the rod and plate components, and AF&PA s NDS-05 for bearing and bending of the wood members. Rod systems are often used in multi-story shear walls, which require special attention be paid to the effects of cumulative overturning and wood shrinkage. Shrinkage compensating devices can be evaluated using ICC-ES Acceptance Criteria for Shrinkage Compensating Devices (AC316). The design of the threaded anchor into the concrete will be discussed later in this article. Sole Plate Shear Restraint Plate washers and 3x sole plates have been used in high seismic regions since the 1997 UBC in an attempt to limit splitting along the length of the sole plate at shear-resisting anchor rods (see Figure 4). Recent cyclic testing has led to important changes to the sole plate and shear anchorage requirements under the 2009 IBC. The first change deals with the size of the sole plate. Section 2305.3.11 of the 2006 IBC required the use of a 3x sole plate for certain seismic conditions. This entire section was removed in the 2009 IBC which now references the SDPWS-08. Based on tests of both 2x and 3x sole plates, the SDPWS-08 permits a 2x sole plate for all applications but requires the sheathed edge of the sole plate to be supported with a plate washer regardless of the sole plate size. This leads to the second important change. Simpson Strong-Tie Company Inc. 800.999.5099 www.strongtie.com Page 3

The required use of a plate washer is no longer limited to high seismic regions. The SDPWS-08 requires the use of a plate washer for anchor rods resisting in-plane shear forces from wind or seismic loads. Based on observations from testing, exceptions are given that permit a standard cut washer for certain applications that are correlated to the strength of the sheathing assembly and the relative stiffness expected for the overturning uplift restraint. The failure limit state for low-strength, nailed wood structural panel (WSP)-sheathed assemblies tends to be ductile fastener yielding. Higher-strength, nailed WSP-sheathed assemblies can cause the sole plate to experience brittle splitting due to cross-grain bending when it is pulled up by the sheathing. This occurs when the sheathing panel rotates and is intensified when the overturning uplift restraint system permits the end post and sheathing to lift up off of the sole plate. To encourage a ductile limit state, the SDPWS-08 requires plate washers unless one of the following two conditions is met: Figure 4: Shear Wall Failures from Oregon State University Testing 1. The allowable unit shear capacity of the sheathing assembly does not exceed 200 plf. 2. The foundation anchor rods are designed to resist shear only and all of the following conditions are met: a. The shear wall is an Individual Full-Height Wall Segment (not a Perforated or Force- Transfer shear wall) b. Dead load stabilizing moment is neglected when sizing the overturning uplift restraint c. Shear wall aspect ratio, h:b, does not exceed 2:1 d. The allowable unit shear capacity of the sheathing assembly does not exceed 490 plf. for seismic or 685 plf. for wind (unit shear based on 7/16" OSB with 8d nails at 3" on center edge spacing into DF lumber) When a plate washer is required, it must be a minimum of 0.229"x3"x3" and must extend to within ½-in. of the sheathed edge of the sole plate. Slots are permitted in the plate washer to allow for a tolerance in anchor rod placement. The 3x3 plate washer size works well with a 2x4 sole plate but when used with a 2x6 sole plate, it requires the anchor rod to be offset toward the sheathed edge and a staggered bolt pattern if the wall is sheathed on both sides. The SDPWS-08 commentary suggests simply using larger plate washers when anchor rods are centered on 2x6 sole plates. See Figure 5 for various assembly details. Simpson Strong-Tie Company Inc. 800.999.5099 www.strongtie.com Page 4

As an alternative to anchor rods with or without plate washers, anchor straps may be used when installed on the sheathed side of the sole plate provided they are approved for use in the shear wall application. Power-driven fasteners are often used in lightly loaded shear wall assemblies. ICC-ES Acceptance Criteria for Fasteners Power-Driven into Concrete, Steel and Masonry Elements (AC70) limits their use to Seismic Design Categories A and B. Since AC70 does not require the fasteners to support the sheathed edge of the sole plate, power-driven fasteners are not recommended to replace anchor rods when plate washers are required. Overturning Anchorage into Concrete If the overturning tension force does not include earthquake loads or effects and the shear wall was designed using ASD methodology (SDPWS-08 supports both ASD and LRFD), then cast-in-place headed anchors may be designed using IBC Table 1911.2. The tabulated values in the IBC must be reduced when near edges, may be increased by 1/3 for wind when using the Alternative Basic Load Combinations of IBC Section 1605.3.2 and may be doubled when special inspection is provided (tension loads only). If the shear wall does not qualify to use IBC Table 1911.2, then the concrete anchorage must be designed using the strength design provisions of ACI 318-08 Appendix D. A wide variety of proprietary products are available for post-installed anchors that have been evaluated using ICC-ES AC193 for mechanical anchors and AC308 for adhesive anchors. Cast-in-place proprietary bolts can be evaluated using ICC-ES Acceptance Criteria for Cast-in-Place Proprietary Steel Bolts in Concrete for Light-Frame Construction (AC399) and can provide high-tension capacities in near-edge conditions. Figure 5: Plate Washer Assembly Details Simpson Strong-Tie Company Inc. 800.999.5099 www.strongtie.com Page 5

Shear Anchorage into Concrete As is the case with overturning anchor design, if the anchor force does not include earthquake loads or effects and the shear wall was designed using ASD methodology then cast-in-place headed anchors may be designed using IBC Table 1911.2 for the concrete and AF&PA s NDS-05 for the wood. Otherwise, the concrete anchorage must be designed using the strength design provisions of ACI 318-08 Appendix D. ACI 318-08 Appendix D requires shear wall sole plate anchors that are resisting earthquake forces in Seismic Design Category C-F to be governed by either a ductile steel element or a ductile connection to the structure or have a 50% reduction in their design strength (overturning anchors face a 60% reduction). Recent testing performed by the Structural Engineers Association of California has shown most wood sole plate anchors used for shear will be governed by ductile yielding in the wood plate. The 2012 IBC will reflect this for wood sole plate anchorage (and cold-formed steel track anchorage) that meets the following conditions: 1. Shear strength of anchors is determined using AF&PA s NDS Table 11E (AISI s S100 Section E3.3.1 for CFS) 2. Anchor diameter does not exceed 5/8 in. 3. Minimum anchor embedment of 7 in. 4. Minimum anchor edge distance is 1¾ in. 5. Minimum anchor end distance is 15 in. 6. 2x or 3x sole plate (33-68 mils for CFS) Design Methodology for Different Standards When dealing with different material standards it may be necessary to convert design loads between Allowable Stress Design (ASD) and Strength Design (LRFD) methodologies. For example, if the wood shear wall was designed using ASD, the design loads must be converted to LRFD to design the anchorage using ACI 318-08 because 318-08 exclusively uses Strength Design. The code does not provide explicit instruction for converting loads, but engineers generally compare 2009 IBC load combination equations 16-6, 16-7, 16-14, and 16-15 to convert ASD wind loads to LRFD by multiplying by 1.6 and convert ASD seismic loads to LRFD by dividing by 0.7. Conclusion The 2009 IBC, material design standards and product evaluation criteria have been updated to reflect our ever-growing understanding of light-frame building performance under lateral loads. These new provisions will have an impact on the design and installation of wood shear wall anchorage. Understanding the changes and the reasons behind them will help engineers design safe, economical and code-compliant shear wall anchorage. Shane Vilasineekul, P.E., is a branch engineering manager for Simpson Strong-Tie in Columbus, Ohio. He can be reached at svilasineekul@strongtie.com. Simpson Strong-Tie Company Inc. 800.999.5099 www.strongtie.com Page 6