FINAL FAILURE INVESTIGATION WESTCHESTER NORTH LAGOON BRIDGE. Anchorage, Alaska
|
|
|
- Shon Eric White
- 9 years ago
- Views:
Transcription
1 FINAL FAILURE INVESTIGATION WESTCHESTER NORTH LAGOON BRIDGE Anchorage, Alaska August 2014 Prepared for: Municipality of Anchorage Project Management and Engineering P.O. Box Anchorage, Alaska Prepared by: USKH Inc. now Stantec 2515 A Street Anchorage, Alaska Phone (907) Fax (907) USKH WO#
2 This page intentionally left blank.
3 TABLE OF CONTENTS USKH Inc. now Stantec Failure Investigation Final Report Westchester North Lagoon Bridge August 2014 ACRONYMS... II 1 EXECUTIVE SUMMARY INTRODUCTION DESCRIPTION SITE OBSERVATIONS ANALYSIS CONCLUSIONS... 8 FIGURES Figure 1 Vicinity and Location Map... 3 Figure 2 Bridge Elevation... 4 Figure 3 Bridge Cross Section APPENDICES Appendix A Original Construction Drawings Appendix B Calculations i
4 USKH Inc. now Stantec Failure Investigation Final Report Westchester North Lagoon Bridge August 2014 ACRONYMS AASHTO... American Association of State Highway and Transportation Officials DMV... Alaska Department of Motor Vehicles Glulam... glued laminated timber LRFD... Load and Resistance Factor Design MOA... Municipality of Anchorage NDS... National Design Specification for Wood Construction PM&E... Project Management and Engineering Psf... pounds per square foot UBC... Uniform Building Code USKH... USKH Inc. Now Stantec ii
5 1 EXECUTIVE SUMMARY USKH Inc. now Stantec Failure Investigation Final Report Westchester North Lagoon Bridge August 2014 The North Lagoon Bridge failed under vehicle load when a truck and chipper crossed the bridge. The failure was caused by a connection detail that allowed a constant influx of moisture into the main supporting glulam beam. The moisture kept the interior of the beam in a saturated condition and produced decay over time. The highly concentrated force from the chipper tire applied a significant shear load across a relatively small area of glulam beam. A local failure developed at one point in the decayed area, then like a zipper, the failure plane spread outward down the beam both sides from the initial point of failure. This bottom side of the beam, ledger, and decking tumbled into the wetland. Some summary points regarding the analysis site observation and analysis of cause of failure: While the new fiberglass decking added load to the bridge, it was not the cause of failure. Normal pedestrian loading could not have initiated this type of failure until the wood decay was significantly more advanced. The lag bolts allowed moisture to infiltrate the interior of the glulam beam causing decay and weakness to occur in the connection zone. The beams were preservative treated but the treatments penetrate wood only to a depth of 2 inches. The lag bolts created a path for water to penetrate into the untreated core of the beam. Had that connection zone not been decayed, the truck and chipper would not have caused failure. The ledger detail induced cross-grain tension in the main supporting member, which is not recommended in wood design. 2 INTRODUCTION The North Westchester Lagoon Bridge failed on June 16, 2014, as a truck towing a wood chipper crossed the bridge. The MOA Parks and Recreation Department contacted USKH Inc., now Stantec (USKH) Structural Engineers and requested an emergency evaluation. As part of the emergency evaluation, MOA requested an analysis and a determination of the cause of failure. The North Lagoon Bridge is located on the northwest end of Westchester Lagoon, see Figure 1. The bridge crosses over a wetland area between the lagoon and the railroad. Original contract documents were available for this investigation and reviewed (Appendix A). Site visits were conducted on June 16 and 17, DESCRIPTION The North Lagoon Bridge spans approximately 70 feet and is framed with glued laminated timber (glulam) beams and wood decking. The glulams are spaced 10 feet apart with the decking spanning in between supported by wood ledgers. The ledgers are inset into the glulam, and secured with lag bolts. The structure foundation is a shallow foundation system composed of timbers resting on a concrete leveling pad. A small utility conduit was attached to the bottom of the decking running along near the east glulam beam. It is our understanding that the bridge has not has any significant rehabilitation work or modifications except in 2013 when an overlay of fiberglass decking was secured to the decking and the guardrails were modified by adding another pipe railing. The original construction drawings were completed in 1987 as part of Phase 3 of the Coastal Trail construction. 1
6 USKH Inc. now Stantec Failure Investigation Final Report Westchester North Lagoon Bridge August 2014 The original construction drawings have a general notes section that lists design criteria and material specifications, see Figure 2. The design codes cited are the 1985 UBC and 1983 AASTHO Specifications. Pertinent design loading indicated is 85 per square foot (psf) uniform live load and an overload vehicle with 10,000-pound (lb) weight and 8,000 lb axle load. The glulams specified are 22F-V8 DF/DF and other lumber Douglas Fir No. 1. All lumber was specified to be pressure treated. 2
7
8
9 4 SITE OBSERVATIONS USKH Inc. now Stantec Failure Investigation Final Report Westchester North Lagoon Bridge August 2014 Site visits were conducted June 16 and June 17, The truck and chipper had been removed prior to the site visits and information regarding the equipment was supplied by the Municipality of Anchorage (MOA). The dimensions of the main bridge glulam beams, ledger, decking, and lag bolts were measured and compared to the construction document drawings. The glulam and lag bolts match the specific dimensions but the ledger connecting the decking to the glulam was slightly wider than called out. The called out ledger was a 4x6 which has actual dimensions of 3-1/2 by 5-1/2 inches. The measured depth matched the 5-1/2 inches but the measured width varies from 5 to 5-1/4 inches. The ledger inset dimension appeared to vary from 3/4- to 1-inch. This variation would not significantly change the capacity of this connection. The east side glulam beam failed when the bottom part of the beam split off from the main beam and came to rest in the wetlands. Most of the deck ledger was split. A portion remained connected to the glulam while other portions remained connected to the deck. The upper portion of the west glulam was still intact spanning the wetland. The east glulam appeared undamaged. The east ledger was rotated with the twisted surface of the decking and had a crack in line with the bolts at the points of maximum twisting. The surfaces of the glulam at the exposed failure plane were closely examined. The surfaces appeared moist and brown; stained from infiltrated moisture. The lag bolts were corroded, indicative of having been exposed to moisture. The darkest staining of the failure plane was near the point where the deck collapsed beneath the wood chipper, as shown in the newspaper photos. The outside both glulam beams were weathered and grey. There was some minor checking and cracking in the sides of the remaining beam. There was larger checking and splitting in the top of the beams in line with the lag bolts that secure handrail mounts. The east ledger has areas of water staining and moisture on the surface. The top of the wood decking could not observed because it was covered by the fiberglass deck overlay. Photos taken during the site visits follow: North Lagoon Bridge failure Cracked ledger and glulam 5
10 USKH Inc. now Stantec Failure Investigation Final Report Westchester North Lagoon Bridge August 2014 Splintered glulam Bolts in failure plane 1 Rotten wood at bolt locations Bolts in split ledger 5 ANALYSIS An analysis of the bridge was performed generally based on the American Association of State Highway and Transportation Officials (AASTHO) Load and Resistance Factor Design (LRFD) Guide Specification for the Design of Pedestrian Bridges, 2009; AASHTO LRFD Bridge Design Specifications, 6 th Edition with 2013 Interim Revisions, and the 2005 National Design Specification for Wood Construction (NDS). Only Limit State Strength I was checked to determine dead and live load capacity under the failure condition. Deflection and other serviceability limit states, seismic, wind, and foundations were not checked as they are not applicable to the failure. The current pedestrian bridge specification recommends 90 psf loading, non-reducible. Older versions of the pedestrian specifications recommend 85 psf, which was reducible when the area of deck supported exceeds a minimum threshold value. Given the area of the bridge deck for this bridge, the design live load could be reduced down to 69 psf under previous editions of the specification. The design documents reference 85 psf so it was assumed the bridge was designed for the reduced load. MOA provided information regarding the truck and the chipper crossing the bridge as it failed. The truck was a 2006 Ford F-550 with an Alaska Department of Motor Vehicles (DMV) registration weight of 7,099 lbs. The chipper was a 2005 Morbark Tornado 15 with a listed shipping weight of 7,300 lbs. The truck has single tires in front and dual tires in the rear. The truck was empty of tree chippings at the time of 6
11 USKH Inc. now Stantec Failure Investigation Final Report Westchester North Lagoon Bridge August 2014 crossing. The chipper has a single axle with single tires on each side. The truck appeared custom with a cargo section on the rear so an estimation of front-rear distribution of load and wheelbase of the truck was made by reviewing manufacturer specifications regarding the type of truck. The chipper was assumed to apply little tongue weight to the truck, so the weight of the chipper was fully applied to the single axle. The new handrail and fiberglass deck overlay added in the 2013 trail rehabilitation added approximately 7% weight to the bridge. Modifications made to structures that cause a load increase of less than 10% are usually not considered significant. Wood member allowable stresses were taken from the current AASHTO or NDS provisions based on the grades of wood noted in the general notes on the original construction documents. The analysis shows the capacity of the main glulam beams is limited by an overall uniform live load of approximately 72 psf. The main beams have adequate capacity for the design vehicle and actual truck plus chipper vehicle loading. The decking is limited by the point loading from vehicles. It is loaded to its maximum capacity by the vehicle that crossed the bridge. The ledger connection appears to have adequate capacity for both uniform load and concentrated vehicle load assuming a bearing limit state on the notched glulam. Full calculations are included in Appendix B. The failure mode, confirmed by analysis and site observations, appears to be cross-grain tension in the glulam beam. The ledger is set inboard of the glulam from 3/4- to 1-inch near the bottom of the glulam beams. The location means the bottom of the beam is loaded inducing cross-grain tension in the glulam. The NDS does not recognize this type of loading since wood is extremely weak in cross-grain tension, so designing connections that rely on cross-grain tension is not a recommended practice. The NDS gives recommendations for radial tension in curved glulam beams, which is basically the same as cross-grain tension. Using the allowable radial tension stress limitations given in NDS, and an assumption for length influenced by the tire loading, gives a Demand-Capacity Ratio of about 1.4. This means under the assumptions listed, the stress caused by the tire exceeds the allowable stress by about 40%. The code has a typical average factor of safety of 2, so in practice the vehicle loading did not cause failure until the plane was weakened when moisture infiltration and decay reduced the strength. Reference the figures below from American Institute of Timber Construction and American Panel Association addressing this type of connection. 1 AITC Typical Construction Details 1 AmericanInstituteofTimberConstruction(AITC).AITC TypicalConstructionDetails 7
12 USKH Inc. now Stantec Failure Investigation Final Report Westchester North Lagoon Bridge August Figure 8 Heavy Concentrated Loads Suspended from a Beam A review of the as-built drawings and site investigation shows how this plane of weakness developed. Water drains off the deck onto the ledger below and eventually migrates down to the lag bolts drilled into the glulams. While in the glulams, the moisture collects in the wood and although some moisture will dissipate through the wood and back to the surface, most will stay. This results in this location of the glulam remaining in a saturated condition over time causing decay. The black/brown stains and the moistness of the beams at this area confirm this decay zone. The ledger detail relies on cross-grain tension developed in the bottom of the beam to transfer the load. This load transfer detail is not recommended as wood is weakest in this loading condition. A calculation using some assumptions showed that this was the weak link of the design. The connection held until strength reduction from wood decay reduced this capacity gradually over time. 6 CONCLUSIONS The North Lagoon Bridge failed under vehicle load. The failure mechanism was cross-grain tension along the plane of the lag bolts attaching the deck support ledger to the main glulam beams. Although this was not a recommended detail, it did not fail until years of water infiltration and decay weakened a plane defined by a line of lag bolts through the ledger. 2 FormNo.EWST300H 2007EngineeredWoodSystems. 8
13 USKH Inc. now Stantec Failure Investigation Final Report Westchester North Lagoon Bridge August 2014 Water draining off the deck onto the ledger below and eventually migrated down the lag bolts drilled into the glulams. The constant influx of moisture into the glulam beam kept the plane in a saturated condition and decayed over time. The ledger detail relied on cross-grain tension developed in the bottom of the beam to transfer the load. The highly concentrated force from the chipper tire applied a significant shear load across a relatively small area of glulam beam. A local failure developed at one point, then like a zipper, the failure plane spread outward down the beam both sides from the initial point of failure. This bottom side of the beam, ledger, and decking tumbled into the wetland. Some summary points regarding the analysis site observation and analysis of cause of failure: While the new fiberglass decking added load to the bridge, it was not the cause of failure. Normal pedestrian loading could not have initiated this type of failure until the wood decay was significantly more advanced. The lag bolts allowed moisture to infiltrate the interior of the glulam beam causing decay and weakness to occur in the connection zone. The beams were preservative treated but the treatments penetrate wood only to a depth of 2 inches. The lag bolts created a path for water to penetrate into the untreated core of the beam. Had that connection zone not been decayed, the truck and chipper would not have caused failure. The ledger detail induced cross-grain tension in the main supporting member, which is not recommended in wood design. 9
14
15 Appendix A Original Construction Drawings
16
17
18
19
20 Appendix B Calculations
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
Residential Deck Safety, Construction, and Repair
Juneau Permit Center, 4 th Floor Marine View Center, (907)586-0770 This handout is designed to help you build your deck to comply with the 2006 International Residential Building code as modified by the
1997 Uniform Administrative Code Amendment for Earthen Material and Straw Bale Structures Tucson/Pima County, Arizona
for Earthen Material and Straw Bale Structures SECTION 70 - GENERAL "APPENDIX CHAPTER 7 - EARTHEN MATERIAL STRUCTURES 70. Purpose. The purpose of this chapter is to establish minimum standards of safety
Residential Decks. Planning and Development Services Department
Building Safety Division 8500 Santa Fe Drive Overland Park, KS 66212 (913) 895-6225 Fax (913) 895-5016 Email: [email protected] Planning and Development Services Department Residential Decks
This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.
Residential Decks Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org
FEBRUARY 2014 LRFD BRIDGE DESIGN 4-1
FEBRUARY 2014 LRFD BRIDGE DESIGN 4-1 4. STRUCTURAL ANALYSIS AND EVALUATION The analysis of bridges and structures is a mixture of science and engineering judgment. In most cases, use simple models with
Wood Decks Zoning and construction requirements for open non-sheltered wood decks for residential dwellings.
PLANNING, PROPERTY AND DEVELOPMENT DEPARTMENT Wood Decks Zoning and construction requirements for open non-sheltered wood decks for residential dwellings. September 2015 2 contents General Information
4.3.5 - Breakaway Walls
4.3.5 - Breakaway Walls Elevation of a structure on a properly designed foundation reduces the potential for water damage from flooding. When the space below the lowest elevated floor is maintained free
STANDARD OPEN PATIO COVER
STANDARD OPEN PATIO COVER BUILDING & SAFETY DIVISION 201 E. LA HABRA BLVD. LA HABRA, CA 90631 62-90-9710 Call Before You Dig 1-800-227-2600 PLEASE NOTE: This information Bulletin is made available to assist
Post and Beam Construction
Post and Beam Construction A Presentation By the Canadian Wood Council Canadian Conseil Wood canadien Council du bois Early settlers introduced the concept of post and beam construction in North America
RESIDENTIAL WOOD DECKS
RESIDENTIAL WOOD DECKS 1 A Building Permit is required for the construction of a wood deck where the deck is more than 600 mm above grade at any point. Definition: For the purposes of this pamphlet, a
Type of Force 1 Axial (tension / compression) Shear. 3 Bending 4 Torsion 5 Images 6 Symbol (+ -)
Cause: external force P Force vs. Stress Effect: internal stress f 05 Force vs. Stress Copyright G G Schierle, 2001-05 press Esc to end, for next, for previous slide 1 Type of Force 1 Axial (tension /
Building Construction. Lightweight construction. Conventional Construction
Ventilation 53 Building Construction The firefighter s ability to safely and efficiently ventilate a building through its roof will depend to some degree on the firefighter s understanding of roof construction.
MAXIMUM LEGAL TRUCK LOADINGS AND
Michigan Department Of Transportation T-1 ( ) MAXIMUM LEGAL TRUCK LOADINGS AND DIMENSIONS Regulations pertaining to the operation of trucks and trailers according to Act 300 P.A. of 1949, as amended. NOTE:
Wood Projects Outdoors. Post Hole Specifications. Deck Span Tables. www.jon Eakes.com
Wood Projects Outdoors Post Hole Specifications & Deck Span Tables www.jon Eakes.com Building Fences The depth of the fence posts into the ground must be at least one foot below the frost level for your
Uncovered Decks & Porches
Uncovered Decks & Porches Building Guides for Homeowners Why Do I need a Permit? D I D Y O U K N O W? As owner-builder you are the responsible party of record on such a permit. If your work is being performed
STRUCTURAL ASSESSMENT REPORT BOLINAS MARINE STATION - BOLINAS, CALIFORNIA
STRUCTURAL ASSESSMENT REPORT BOLINAS MARINE STATION - BOLINAS, CALIFORNIA College of Marin c/o Swinerton Management & Consulting P.O. Box 144003 835 College Avenue, Building MS-3 Kentfield, California
U.S. Department of Labor Occupational Safety and Health Administration Directorate of Construction. April 2015
Investigation of the November 13 and 14, 2014 collapses of two pedestrian bridges under construction at Wake Technical Community College Campus, Raleigh, NC U.S. Department of Labor Occupational Safety
SECTION 02845 GUARDRAILS
SECTION 02845 GUARDRAILS PART 1 - GENERAL 1.01 SCOPE OF WORK A. Furnish all labor, materials, equipment and incidentals necessary and repair, replace or install all types of guardrails as specified herein
Formwork for Concrete
UNIVERSITY OF WASHINGTON DEPARTMENT OF CONSTRUCTION MANAGEMENT CM 420 TEMPORARY STRUCTURES Winter Quarter 2007 Professor Kamran M. Nemati Formwork for Concrete Horizontal Formwork Design and Formwork Design
Project Report. Structural Investigations Hotel del Sol Yuma, Arizona
Project Report Structural Investigations Yuma, Arizona Prepared by: 2619 Spruce Street Boulder, CO 80302 303-444-3620 Prepared for: Principle Engineering Group, Inc. 833 East Plaza Circle, Suite 100 Yuma,
Safe & Sound Bridge Terminology
Safe & Sound Bridge Terminology Abutment A retaining wall supporting the ends of a bridge, and, in general, retaining or supporting the approach embankment. Approach The part of the bridge that carries
Chapter 3 Pre-Installation, Foundations and Piers
Chapter 3 Pre-Installation, Foundations and Piers 3-1 Pre-Installation Establishes the minimum requirements for the siting, design, materials, access, and installation of manufactured dwellings, accessory
Index 20010 Series Prestressed Florida-I Beams (Rev. 07/12)
Index 20010 Series Prestressed Florida-I Beams (Rev. 07/12) Design Criteria AASHTO LRFD Bridge Design Specifications, 6th Edition; Structures Detailing Manual (SDM); Structures Design Guidelines (SDG)
APPENDIX H DESIGN CRITERIA FOR NCHRP 12-79 PROJECT NEW BRIDGE DESIGNS
APPENDIX H DESIGN CRITERIA FOR NCHRP 12-79 PROJECT NEW BRIDGE DESIGNS This appendix summarizes the criteria applied for the design of new hypothetical bridges considered in NCHRP 12-79 s Task 7 parametric
6 RETROFITTING POST & PIER HOUSES
Retrofitting Post & Pier Houses 71 6 RETROFITTING POST & PIER HOUSES by James E. Russell, P.E. 72 Retrofitting Post & Pier Houses Retrofitting Post & Pier Houses 73 RETROFITTING POST AND PIER HOUSES This
General Approach. Structure Components. Is all lumber the same? Lumber Grades. Rafters Girders / Beams Columns. Sketch general structural layout
General Approach Sketch general structural layout Determine roof loading Determine required lumber dimensions Transfer load down the structure Structure Components Plants Structure Components Top Side
Residential Foundations and Basements
Residential Foundations and Basements Disclaimer All of the following information is based on the 2006 International Residential Code with Kentucky Amendments. As some information is paraphrased, article
CH. 2 LOADS ON BUILDINGS
CH. 2 LOADS ON BUILDINGS GRAVITY LOADS Dead loads Vertical loads due to weight of building and any permanent equipment Dead loads of structural elements cannot be readily determined b/c weight depends
Optimum proportions for the design of suspension bridge
Journal of Civil Engineering (IEB), 34 (1) (26) 1-14 Optimum proportions for the design of suspension bridge Tanvir Manzur and Alamgir Habib Department of Civil Engineering Bangladesh University of Engineering
Mobile Home Pre-Inspection Checklist
Mobile Home Pre-Inspection Checklist TWO (2) STEP INSPECTION PROCESS STEP ONE: CALL FOR THE FIRST INSPECTION WHEN THESE ITEMS ARE COMPLETE. 1. Septic tank installed and plumbing complete. (SEE PLUMBING
Page & Turnbull imagining change in historic environments through design, research, and technology
DCI+SDE STRUCTURAL EVALUATIONS OFFICE BUILDING, TOOL SHED & WATER TANK, AND BLACKSMITH & MACHINE SHOP BUILDINGS SAN FRANCISCO, CALIFORNIA [14290] PRIMARY PROJECT CONTACT: H. Ruth Todd, FAIA, AICP, LEED
REINFORCED CONCRETE. Reinforced Concrete Design. A Fundamental Approach - Fifth Edition. Walls are generally used to provide lateral support for:
HANDOUT REINFORCED CONCRETE Reinforced Concrete Design A Fundamental Approach - Fifth Edition RETAINING WALLS Fifth Edition A. J. Clark School of Engineering Department of Civil and Environmental Engineering
Report on. Wind Resistance of Signs supported by. Glass Fiber Reinforced Concrete (GFRC) Pillars
Report on Wind Resistance of Signs supported by Glass Fiber Reinforced Concrete (GFRC) Pillars Prepared for US Sign and Fabrication Corporation January, 2006 SUMMARY This study found the attachment of
POST AND FRAME STRUCTURES (Pole Barns)
POST AND FRAME STRUCTURES (Pole Barns) Post and frame structures. The following requirements serve as minimum standards for post and frame structures within all of the following structural limitations:
Walking and Working Surface Checklist:
Walking and Working Surfaces Purpose: This information is presented to improve the level of safety in our operations, and to inform you that we will comply with the OSHA Standard 29 CFR 1910.23. Responsibility:
Bolting: Attachment Of The Mudsill To The Foundation
Bolting: Attachment Of The Mudsill To The Foundation If the mudsill of a house (the pink area in the illustration at right) is not bolted, the lateral loads (back and forth motions) of an earthquake can
Timber Decks. Technical Note. March 2007
Timber Decks Technical Note. March 2007 This Technical Note contains general information for residential timber decks and floor frame structures for veranda s, patios etc which are exposed to the weather.
Design of Bridges. Introduction. 3 rd to 4 th July 2012. Lecture for SPIN Training at the University of Dar es Salaam
Design of Bridges Introduction 3 rd to 4 th July 2012 1 FUNCTION OF A BRIDGE To connect two communities which are separated by streams, river, valley, or gorge, etc. 2 EVOLUTION OF BRIDGES 1. Log Bridge
NAME: POWER UNIT ID: NAME OF APPLICANT (RESPONSIBLE MOTOR CARRIER) REGISTRATION/VIN STATE. Meet At: Meet Date: Meet Time:
M-936AM (7-06) OVERSIZE/OVERWEIGHT APPLICATION FOR SPECIAL HAULING PERMIT Miscellaneous Information Application ID: NAME: POWER UNIT ID: NAME OF APPLICANT (RESPONSIBLE MOTOR CARRIER) REGISTRATION/VIN STATE
Evaluation and Field Load Testing of Timber Railroad Bridge
Transportation Research Record 1696 Paper No. 5B0112 323 Evaluation and Field Load Testing of Timber Railroad Bridge Terry J. Wipf, Michael A. Ritter, and Douglas L. Wood Several spans of a 60-year-old
BRIDGES ARE relatively expensive but often are
Chapter 10 Bridges Chapter 10 Bridges Bridg Bridges -- usually the best, but most expensive drainage crossing structure. Protect bridges against scour. BRIDGES ARE relatively expensive but often are the
Chapter 6 ROOF-CEILING SYSTEMS
Chapter 6 ROOF-CEILING SYSTEMS Woodframe roof-ceiling systems are the focus of this chapter. Cold-formed steel framing for a roof-ceiling system also is permitted by the IRC but will not be discussed;
TYPICAL PATIO COVERS 111
City of Laguna Niguel Building Division 30111 Crown Valley Pkwy Laguna Niguel, CA 92677 (949) 362-4360 FAX 362-4369 www.cityoflagunaniguel.org TYPICAL PATIO COVERS 111 PLEASE NOTE: This information Bulletin
ESR-1190 Reissued December 1, 2009 This report is subject to re-examination in two years.
ICC-ES Evaluation Report ESR-90 Reissued December, 2009 This report is subject to re-examination in two years. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council
COMMONLY USED RESIDENTIAL BUILDING CODES
COMMONLY USED RESIDENTIAL BUILDING CODES INTERNATIONAL RESIDENTIAL CODE (2009) form revised 5/10 FOUNDATION 1. DESIGN OF FORMWORK. Section 1906.1 IBC 2009, Section R404.1.2.3.6 IRC 2009, ACI 318 Section
MOCK-UP TEST REPORT. Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up
MOCK-UP TEST REPORT Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up Report No: 85616.01-120-32 Test Completion Date: 01/15/09 Report Date: 02/11/09 Record Retention End Date: 01/15/13
Frequently Asked Questions and Common Mistakes to avoid when buying a pergola
Frequently Asked Questions and Common Mistakes to avoid when buying a pergola Pergolas are significant investments that add value and enjoyment to open spaces of all sizes and shapes. The choices are almost
Design of Steel Structures Prof. S.R.Satish Kumar and Prof. A.R.Santha Kumar. Fig. 7.21 some of the trusses that are used in steel bridges
7.7 Truss bridges Fig. 7.21 some of the trusses that are used in steel bridges Truss Girders, lattice girders or open web girders are efficient and economical structural systems, since the members experience
SUPERIOR FIRE RESISTANCE
AMERICAN INSTITUTE OF TIMBER CONSTRUCTION SUPERIOR FIRE RESISTANCE GLULAM Glulam Because of its beauty, strength and ease of construction, wood has long been in demand as a building material. Today, structural
DAMAGE TO FOUNDATIONS FROM EXPANSIVE SOILS
DAMAGE TO FOUNDATIONS FROM EXPANSIVE SOILS J. David Rogers, Robert Olshansky, and Robert B. Rogers Expansive soils in many parts of the United States pose a significant hazard to foundations for light
Ceiling Mounted Folding Attic Ladders Installation Instructions
Ceiling Mounted Folding Attic Ladders Installation Instructions WARNING Before you start installing your new Louisville Ceiling Mounted Folding Attic Ladder, you must read and understand the following:
Bridge Type Selection
Bridge Type Selection The major consideration for bridge type selection for bridges on the State Aid system is initial cost. Future maintenance costs, construction time, and location are considered when
Owner s Guide to Understanding Checks in Glued Laminated Timber
Owner s Guide to Understanding Checks in Glued Laminated Timber ENGINEERED WOOD SYSTEMS Checking In Glued Laminated Timber Glued laminated timber (glulam) is an engineered wood product that is used in
Analysis of the Interstate 10 Twin Bridge s Collapse During Hurricane Katrina
Analysis of the Interstate 0 Twin Bridge s Collapse During Hurricane Katrina By Genda Chen, Emitt C. Witt III, David Hoffman, Ronaldo Luna, and Adam Sevi The Interstate 0 Twin Span Bridge over Lake Pontchartrain
Technical Assignment 2 TABLE OF CONTENTS
2 TABLE OF CONTENTS Executive Summary...3 Introduction..5 Gravity Loads......6 Design Codes......7 Materials..8 Existing Structural System.. 10 Existing Floor System 15 Alternate Floor Framing Systems...17
Heating Load Calculation
Heating Load Calculation ME 425 Air Conditioning System Design Keith E. Elder, P.E. Heating Load Calculation The heating load calculation begins with the determination of heat loss through a variety of
Photo 2. View showing flour mill, machine shed, veranda and saw mill + storage shed.
May 7,2015 KSANDER & ASSOCIATES CONSULTING PROFESSIONAL ENGINEERS 130 HUINTER STREET, UNIT 103, PETERBOROUGH, ONTARIO K9H2K8 TELEPHONE (705) 743-9221 FAX 743-0904 Ontario Region Conservation Authority
National Council of Examiners for Engineering and Surveying. Principles and Practice of Engineering Structural Examination
Structural Effective Beginning with the April 2011 The structural engineering exam is a breadth and exam examination offered in two components on successive days. The 8-hour Vertical Forces (Gravity/Other)
CONCEPTUAL REHABILITATION ALTERNATIVE
Appendix D While federal law requires preservation/rehabilitation of historic bridges be considered, there is no standard procedure to determine when rehabilitation is appropriate and when replacement
`Fall Protection Guidelines in Construction
`Fall Protection Guidelines in Construction A Publication Provided by: 1681 Campus Delivery Fort Collins, Colorado 80523 (970) 491-6151 email: [email protected] web: http://www.bernardino.colostate.edu/public/
Chapter 3 DESIGN AND CONSTRUCTION FEATURES IMPORTANT TO SEISMIC PERFORMANCE
Chapter 3 DESIGN AND CONSTRUCTION FEATURES IMPORTANT TO SEISMIC PERFORMANCE To satisfy the performance goals of the NEHRP Recommended Seismic Provisions, a number of characteristics are important to the
What is Seismic Retrofitting?
What is Seismic Retrofitting? SEISMIC RETROFITTING A Seismic Retrofit provides existing structures with more resistance to seismic activity due to earthquakes. In buildings, this process typically includes
CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION
CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION SPECIFICATION EO-5023 REVISION 3 MARCH 2003 REQUIREMENTS FOR
Ohio Department of Transportation Division of Production Management Office of Geotechnical Engineering. Geotechnical Bulletin PLAN SUBGRADES
Ohio Department of Transportation Division of Production Management Office of Geotechnical Engineering Geotechnical Bulletin GB 1 PLAN SUBGRADES Geotechnical Bulletin GB1 was jointly developed by the Offices
Chapter 4 SUBSURFACE INVESTIGATION GUIDELINES
Chapter 4 SUBSURFACE INVESTIGATION GUIDELINES Final SCDOT GEOTECHNICAL DESIGN MANUAL August 2008 Table of Contents Section Page 4.1 Introduction...4-1 4.2 Subsurface Investigation...4-2 4.2.1 Preliminary
SPECIFICATIONS FOR PRECAST MODULAR BLOCK RETAINING WALL SYSTEM (revised 11/5/13)
Page 1 of 7 STONE STRONG SYSTEMS SPECIFICATIONS FOR PRECAST MODULAR BLOCK RETAINING WALL SYSTEM (revised ) PART 1: GENERAL 1.01 Description A. Work includes furnishing and installing precast modular blocks
March 19, 2014. Ms. Jean McDonald CAP Management 910 16th Street, Suite 1010 Denver, Colorado 80202
Ms. Jean McDonald CAP Management 910 16th Street, Suite 1010 Denver, Colorado 80202 Re: Prospector s Point Walkway/Façade Repairs Martin/Martin, Inc Project No.: 13.0358.S.02 Ms. McDonald: Per your request
Featuring TJ Rim Board and TimberStrand LSL
#TJ-8000 SPECIFIER S GUIDE TRUS JOIST RIM BOARD Featuring TJ Rim Board and TimberStrand LSL Multiple thicknesses, grades, and products to cover all your rim board needs 1¼" Thickness matches lateral load
Tension Development and Lap Splice Lengths of Reinforcing Bars under ACI 318-02
ENGINEERING DATA REPORT NUMBER 51 Tension Development and Lap Splice Lengths of Reinforcing Bars under ACI 318-02 A SERVICE OF THE CONCRETE REINFORCING STEEL INSTITUTE Introduction Section 1.2.1 in the
DESIGN OF SLABS. 3) Based on support or boundary condition: Simply supported, Cantilever slab,
DESIGN OF SLABS Dr. G. P. Chandradhara Professor of Civil Engineering S. J. College of Engineering Mysore 1. GENERAL A slab is a flat two dimensional planar structural element having thickness small compared
CONFER ABOVE GROUND CURVE STEP / ABOVE GROUND CURVE STEP SYSTEM ASSEMBLY AND INSTALLATION MANUAL
SAVE THESE INSTRUCTIONS DEALER/INSTALLER: GIVE TO HOMEOWNER CONFER ABOVE GROUND CURVE STEP / ABOVE GROUND CURVE STEP SYSTEM ASSEMBLY AND INSTALLATION MANUAL Model CCX-AG Note: 40 lbs. of sand required!
2015 ODOT Bridge Design Conference May 12, 2014. DeJong Rd Bridge High- Seismic Zone Case Study: Bridge Rehab vs. Replacement.
2015 ODOT Bridge Design Conference May 12, 2014 DeJong Rd Bridge High- Seismic Zone Case Study: Bridge Rehab vs. Replacement Mary Ann Triska 2015 HDR, all rights reserved. Presentation Outline Project
Proposed Minimum Subterranean Termite Treatment Standards
Proposed Minimum Subterranean Termite Treatment Standards Introduction This document is intended to serve as a model for states considering the adoption of standards for soil application of termiticides.
Section 9315. Operations Section Organizational Guidance
Section 9315 Operations Section Organizational Guidance T able of Contents Section Page 9315 Operations Section Organizational Guidance... 9315-1 9315.1 Minor Inland Spill Scenario... 9315-1 9315.2 Minor
Engineered, Time-Tested Foundation Repairs for Settlement in Residential and Light Commercial Structures. The Leading Edge.
TM TM Engineered, Time-Tested Foundation Repairs for Settlement in Residential and Light Commercial Structures. SM The Leading Edge. 10 One Major Causes of foundation settlement or more conditions may
Development Services Department Building Permit & Inspection Services Shed and Garage Construction Guide for Detached and Semi-Detached Dwellings
Development Services Department Building Permit & Inspection Services Shed and Garage Construction Guide for Detached and Semi-Detached Dwellings H:/forms/handouts/bldg071.docx Shed and Garage Construction
Engineers, Civil Structural Survey
Engineers, Civil Structural Survey 317 STREET 0 6 3 6 0 886-1966 886-9165 FAX. September 1 1 Mr. Alan Bergren City Manager City of Norwich Broadway, Floor Norwich, 06360 Re: Limited Structural Condition
14 September 2015. Sarah Zorn Planning and Economic Development 25 West Fourth Street, Ste. 1100 St. Paul, MN 55102
Sarah Zorn Planning and Economic Development 25 West Fourth Street, Ste. 1100 St. Paul, MN 55102 Project No.: 15538.00 Re: Structural Condition Review of the building at 700 4 th St. E. Dear Sarah: We
Attached/Detached Patio Cover/Carport
CITY OF MANTECA COMMUNITY DEVELOPMENT DEPARTMENT 1001 West Center Street Manteca, CA 95337 FAX (209) 923-8955 Building Safety Division (209) 456-8550 Community Development/Planning Division (209) 456-8500
The Analysis of Open Web Steel Joists in Existing Buildings
PDHonline Course S117 (1 PDH) The Analysis of Open Web Steel Joists in Existing Buildings Instructor: D. Matthew Stuart, P.E., S.E., F.ASCE, F.SEI, SECB, MgtEng 2013 PDH Online PDH Center 5272 Meadow Estates
Envelope INSULATION BATT (2) Avoid Using Batt Insulation With Metal Framing. Pressure or Friction Fit
R-H-DI1 INSULATION BATT NR-E-IB1 Avoid Using Batt Insulation With Metal Framing Batt insulation should not be used with metal framing systems. Although it is common to see fiberglass batt insulation installed
PART E SPECIFICATIONS
PART E SPECIFICATIONS Page 1 of 5 PART E - SPECIFICATIONS GENERAL E1. APPLICABLE SPECIFICATIONS, STANDARD DETAILS AND DRAWINGS E1.1 The City of Winnipeg Works and Operations Division Standard Construction
TOWNSHIP OF TOMS RIVER ZONING OFFICE DECK CONSTRUCTION
TOWNSHIP OF TOMS RIVER ZONING OFFICE DECK CONSTRUCTION The information contained herein serves as a general guideline and may not be all encompassing. Applicants are cautioned that additional Federal,
Chapter 3: Fall Protection/ Scaffolding Safety
Chapter 3: Fall Protection/ Scaffolding Safety Learning Objectives In this chapter you will learn to: recognize the hazards commonly associated with work on or around scaffolds; be aware of common scaffold-related
HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES
HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES 101 Retrofits Required. Pursuant to Section 553.844 553.884, Florida Statutes, strengthening of existing site-built,
US 51 Ohio River Bridge Engineering and Environmental Study
US 51 Ohio River Bridge Engineering and Environmental Study ITEM NOS. 1-100.00 & 1-1140.00 Prepared by: Michael Baker Jr., Inc. 9750 Ormsby Station Rd Louisville, KY 40223 August 16, 2013 Table of Contents
Report on Sanctuary/Chancel Crawl Space Inspection. St. John in The Wilderness, 2896 Old Lakeshore Road Bright s Grove. Project No.
Report on Sanctuary/Chancel Crawl Space Inspection St. John in The Wilderness, 2896 Old Lakeshore Road Bright s Grove Project No. E112056 1. Background St. John in the Wilderness (SJITW) is considering
The Homeowner s Building Application Checklist for Constructing a Residential Sundeck
This checklist provides homeowners a summary of the Building Permit submission requirements for constructing a residential sundeck. Regardless of the deck s walking surface area, if the deck is adjacent
STRUCTURAL ASSESSMENT
STRUCTURAL ASSESSMENT Project: 1432-1434 East Commerce St. Job. No: 122200 Location: San Antonio, TX Date: Dec. 10, 2012 Weather: Sunny, Windy,60 deg Performed by: Jeff Haughton and Frank Lamas, Alpha
9.8.1.1. General (1) This Section applies to the design and construction of interior and exterior stairs, steps, ramps, railings and guards.
Section 9.8. Stairs, Ramps, Handrails and Guards 9.8.1. Application 9.8.1.1. General (1) This Section applies to the design and construction of interior and exterior stairs, steps, ramps, railings and
Prepared For San Francisco Community College District 33 Gough Street San Francisco, California 94103. Prepared By
Project Structural Conditions Survey and Seismic Vulnerability Assessment For SFCC Civic Center Campus 750 Eddy Street San Francisco, California 94109 Prepared For San Francisco Community College District
Perforated Shearwall Design Method 1
Perforated Shearwall Design Method 1 Philip Line, P.E., Bradford K. Douglas, P.E., American Forest & Paper Association, USA Abstract Wood frame shearwalls are traditionally designed using full-height shearwall
Summary of ET Plus Guardrail End Treatment Inspections
Summary of ET Plus Guardrail End Treatment Inspections 12/16/2015 Maine Department of Transportation Prepared by Brian Burne, Atlee Mousseau, Clark Sulloway, Doug Gayne, Ulrich Amoussou Guenou & Dale Peabody
ENGINEERING SPECIFICATION FIBERGRATE MOLDED GRATING. January 24, 2014 06610-1
ENGINEERING SPECIFICATION FIBERGRATE MOLDED GRATING January 24, 2014 06610-1 SECTION 06610 FIBERGLASS REINFORCED PLASTICS (FRP) FABRICATIONS MOLDED GRATING PART 1 - GENERAL 1.1 SCOPE OF WORK A. The CONTRACTOR
PERFORMANCE RATED I-JOISTS
PERFORMANCE RATED I-JOISTS ENGINEERED WOOD SYSTEMS 2 WOOD The Miracle Material Wood is the right choice for a host of construction applications. It is the earth s natural, energy efficient and renewable
Fifteen years experience of design, production and assembling of prestressed Bridge decks in Timber
Fifteen years experience of design, production and assembling of pre-stressed Bridge decks in Timber P. Jacobsson 1 Fifteen years experience of design, production and assembling of prestressed Bridge decks