How To Clean Water From An Ammonia Refrigeration System



Similar documents
Refrigeration Basics 101. By: Eric Nelson

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.

How To Understand Evaporator

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.

Centrifugal Water Chillers. Scott Meyerkord

Flushing and Cleaning the A/C System

VACUUM REFRIGERATION SYSTEMS

How To Clean Up A Reactor Water Cleanup

CONTAMINANT REMOVAL FROM CENTRIFUGAL SYSTEMS

Nirvana. Cycling Refrigerated Dryers

Specific Volume of Liquid (Column 7). The volume per unit of mass in cubic feet per pound.

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS

A discussion of condensate removal systems for clarifier and thickener drives for water and wastewater facilities.

Rusty Walker, Corporate Trainer Hill PHOENIX

C. starting positive displacement pumps with the discharge valve closed.

Table Z. Troubleshooting Chart for Air Conditioners. Cause

MAC-120HE-01 Air-Cooled Chiller

UNIT 2 REFRIGERATION CYCLE

Engineering Recommendation on: Accumulators Revised Issued January 10, 1979 Page 1 of 7

Refrigeration Installation 101

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers

How much do you know about HVAC? Try testing yourself with the following questions and then take a look at the answers on the following page.

SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS

EJECTOR AIR REMOVAL SYSTEMS ENGINEERING DATA BULLETIN # PVS ARS PAGE 1 OF 5

How To Design A Refrigeration System

TRAINING, EXAMINATION AND CERTIFICATION

Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur

Cryogenic Vacuum Pumps

Mechanical Seal Piping Plans

Steam Jet Vacuum Pumps

UNDERSTANDING REFRIGERANT TABLES

How To Calculate The Performance Of A Refrigerator And Heat Pump

Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures

ThermoStar Refrigeration Air Dryers

POLICY BULLETIN Tecumseh Compressor Company Compressor Group

AIR CONDITIONER GENERAL 1. SPECIFICATIONS AIR CONDITIONER REXTON

Troubleshooting an Air Conditioning system. R D Holder Eng. Roger D Holder MSME

REFRIGERANT 410A. Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois Information compiled by Frank Prah, CMS

A/C refrigerant system, overview

Maintenance for Energy Efficiency

Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions

Condensate Treatment Solutions. CTS Series Eliminator II Oil-Water Separators

Any Service Technician Can Fix It A Good Service Technician Can Figure Out What s Wrong With It.

Glossary of Heating, Ventilation and Air Conditioning Terms

HOW HVAC WORKS. How HVAC. Works PAGE 1

Water Fired Chiller/Chiller-Heater. WFC-S Series: 10, 20 and 30 RT Cooling

CPX/HT Series. REFRIGERATED AND HIGH TEMPERATURE DRYER 12 to 2400 CFM. High-performance products. Designed for you!

2B.1 Chilled-Water Return (and Supply) Temperature B.3 Cooling-Water Supply Temperature / Flow

DESIGN STANDARDS SECTION

Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications

Vacuum. How It Relates to Refrigeration And Air Conditioning Service

Open Cycle Refrigeration System

Recommended Compressor Installation Practices

Contents and Nomenclature

2A.1 Features of Chiller Control Components A.3 Chilled-Water Supply Temperature Control A.4 Cooling-Water Supply Control...

ARP Food Industry, Portugal

Refrigeration Air Dryers ADQ. Capacity: m 3 /h

New Trends in the Field of Automobile Air Conditioning

AIR CONDITIONING TECHNOLOGY

Understanding ejector systems necessary to troubleshoot vacuum distillation

GAS HANDLING SYSTEMS VACUUM INSTRUMENT CORPORATION

Air Conditioning 101. STN Presentation AC101

Chilled Water HVAC Systems

MAINTENANCE INSTRUCTIONS. Thermia Robust heat pump

Oil and Coolant Circulating Heating System. Model - OCSM

REFRIGERATED COMPRESSED AIR DRYERS

MUELLER FALLING FILM CHILLERS

Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions

ThermoSorb Desiccant Dryers

Testing methods applicable to refrigeration components and systems

Increasing the evaporation temperature with the help of an internal heat exchanger

Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, Table of Contents

HVAC-02, Air Conditioning Troubleshooting and Repair

Thermal Coupling Of Cooling and Heating Systems

Attachment J-C18.1. HVAC Work Instructions

Holdover Plates Transport Refrigeration Systems

DEVELOPMENT OF A TWIN SCREW EXPRESSOR AS A THROTTLE VALVE REPLACEMENT FOR WATER-COOLED CHILLERS

THE CASE FOR A REFRIGERATION PREVENTATIVE MAINTENACE PROGRAM

Element D Services Plumbing

DIRECT STEAM INJECTION HOT WATER SYSTEMS FOR JACKETED HEATING

Condensing unit type EPSILON-ECHOS LE Technical information manual

Air-sourced 90 Hot Water Supplying Heat Pump "HEM-90A"

Product Data Bulletin

ON-VEHICLE INSPECTION

Dry-out Design Considerations and Practices for Cryogenic Gas Plants

OUR PRODUCTS TRH-TRS-TRM-TRV. LIQUID RING VACUUM PUMPS AND COMPRESSORS Capacity up to 2100 ACFM Vacuum to 29 Hg. Our Other Products.

Performance Evaluation of a Heat Pump System for Simultaneous Heating and Cooling

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014

FLASH TANK ECONOMIZER PRODUCT GUIDE

Ground-breaking conversion of critical Data Room WaterChiller from R22 to R422D / MO29

HYDRYER TYPE P Heat Regenerative Dryers ISO 9001 CERTIFIED

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,

Training Manual SUPER SEAL. Simplifying AC/R Repair. Inside Your Guide PROFESSIONAL FORMULA. Page

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

VAD. Variable Area Desuperheaters

2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units

Defining Quality. Building Comfort. Heating and Cooling Coils

Characteristics of Evaporators

On request of Akzo Nobel Dynamo Project Team we ve surveyed the energy efficiency of the compressed air system in the Barcelona Deco & A/AS plant.

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

Transcription:

Water Contamination and Water Removal in Industrial Ammonia Refrigeration Systems By Ray Ficker, PE Effects of Water Contamination Water contamination in an industrial ammonia refrigeration system can lower system efficiency, and increase the electrical costs required to run the system s refrigeration compressors. For a given pressure, the addition of water to the ammonia will raise its temperature. At typical suction pressures, the addition of 10% water by weight will increase the evaporator temperature by about 4 F (2 C). Stated another way, for a given required evaporator temperature, the addition of water to the ammonia will require a lower suction pressure. For example, pure ammonia at -4 F (-20 C) has a saturation pressure of 12.9 psig (0.90 barg). An ammonia-water solution of 10% water and 90% ammonia by weight, at the same -4 F (-20 C) has a saturation pressure of 10.2 psig (0.72 barg). Therefore to maintain an evaporator temperature of -4 F (-20 C) in a system with 10% water contamination, the suction pressure would have to be run at 12.9 10.2 = 2.7 psi (0.18 bar) lower than if the water were not present. Hansen Technologies Corporation Tel 630.325.1565 Fax 630.325.1572 Email info@hantech.com www.hantech.com

Ammonia / Water Solutions Suction Pressure Penalty of Water 30 25 +14 F Evaporator 4.1 psid = 4.4 F 9.0 psid = 10.4 F 20 Suction Pressure, psig 15 10-4 F Evaporator 2.7 psid = 4.2 F 5.9 psid = 9.7 F 5 0-22 F Evaporator 1.7 psid = 3.8 F 3.8 psid = 9.0 F 10" Hg -40 F Evaporator 1.0 psid = 3.4 F 2.3 psid = 8.3 F 20" Hg 0% 5% 10% 15% 20% Water Concentraion by Weight The requirement to maintain a lower suction pressure than would be necessary if the water could be removed is a waste of electrical energy. As an example, consider a booster compressor operating with -40 F (-40 C) evaporating and +20 F (-7 C) condensing. At -40 F (-40 C), sizing software from a major compressor 2

manufacturer calculates that the power required is 1.44 hp/ton (COP=3.266). At -44 F (-42 C), it calculates that the power required is 1.55 hp/ton (COP=3.043). The 4 F (2 C) difference represents a water concentration of slightly more than 10%. Therefore, the extra energy required due to the 10% water concentration is (1.55-1.44)/1.44 = 7.6%. 25% Energy Savings - Water Removal (-40 F evaporating, +20 F condensing) 20% Energy Penalty Due to Excess Water 15% 10% 5% 0% 0% 5% 10% 15% 20% Water Concentration by Weight To calculate the energy savings that could be achieved if the water were removed, consider a total system operating at 1500 tons (3500 kw), a compressor run time of 6500 hours per year, and an electricity rate of $.06/kW-hr. Then the excess energy to run the compressors at the lower suction pressure due to 10% water for 3

this example is: (.076)(1500tons)(1.44hp/ton)(.746kW/hp)(6500hr/yr)($.06/kW-hr) = $48,000 per year potential energy savings if the water is removed. The effect of air contamination in industrial refrigeration systems has been well documented over many years. Like water contamination, air contamination lowers system efficiency and increases electrical costs due to the higher compressor discharge pressure caused by the presence of the air. When the air is removed with a non-condensible gas purger (for example, a Hansen Auto-Purger) the discharge pressure is reduced, system efficiency is restored, and electrical costs are reduced. The energy savings quickly pay for the cost of installing the non-condensible gas purger. Typically, there is a 6% savings in energy cost for every 10 psi (0.7 bar) of excess pressure due to non-condensible air that is removed from the refrigeration system. Compressor Power kw per ton 4.00 3.00 2.00 1.00-40 F suction temperature - 20 F suction temperature 0 F suction temperature 6% decrease in kw per ton for each 10 psi decrease in condensing pressure 60 100 140 180 220 Condensing Pressure (psig) NH3 4

Other Benefits of Proper Maintenance of Refrigerant Quality Removing air and water from ammonia refrigeration systems certainly saves energy, but there are other benefits that improve system operation. On the high side of the system, operating at the lowest condensing pressure permissible means less wear and tear on compressor bearings and other mechanical parts. The lower discharge temperatures also reduce oil and refrigerant breakdown, and extend gasket life. Air removal means there is less oxygen in the system, which is sometimes associated with corrosion of piping and vessels. In the same way, removing water from the refrigeration system may reduce corrosion. Means of Water Entry into a System The most common way that water enters a system is with the air that enters the system. The air that enters the system has a certain relative humidity. Therefore, as air enters a system, a certain amount of moisture also enters the system. The moist air enters the system in two common ways. 1.) For systems that operate in a vacuum, system leaks will pull moist air into the system through the leak path. 2.) For all systems, regardless of whether they operate in a vacuum, if maintenance is performed on a portion of the system, and if this portion is not pulled into a strong vacuum before restoring it to service, that moist air remains in the system. Non-condensible gas purgers are very effective at removing the air from the system. They are however, less effective at removing the moisture from the system. Another means of water entry into a system is when a water chiller develops a tube leak, and water from the tube side mixes with the ammonia on the shell side, or vice versa. This can introduce large amounts of water to a system, and drastic measures may be required, including replacement of the entire refrigerant charge. 5

Location Where Water Typically Collects The ammonia, air, water, and oil circulate through the refrigeration system. Water will tend to collect on the low side of the system. Only gas can leave the low side of the system. Therefore water, for the most part, can not leave the low side and will collect here. (Some water can leave as water vapor, but most will stay in the low side.) In two or more stage systems, the water will eventually collect in the lowest stage vessel. The oil, also not being a gas, collects in the low side of the system, and must be routinely drained. Alternatively, only liquid can exit the high side of the system, so air collects in the high side. This is typically near the outlet of evaporative condensers or in the coolest, low velocity section of receivers and water cooled condensers. Removal of Water and Air from the Refrigeration System Hansen Technologies pioneered the automatic, non-condensible gas purger over two decades ago. Hansen Auto-Purgers efficiently remove air from the high side of the system where air collects. Now Hansen Technologies has improved on the Auto-Purger to add water removal capability. Auto-Purger models that have both water and air removal capabilities are model Auto-Purger Plus. 6

½" FOUL GAS LINE ½" LOW-PRESSURE PUMPED LIQUID LINE ½" LIQUID RETURN LINE ¾" SUCTION LINE VAPOR TRAP FLOAT SWITCH LIQUID DRAINER STRAINER/ ORIFICE LIQUID LEVEL CONTROL SENSOR EVAPORATOR CHAMBER AIR SEPARATOR CHAMBER EVAPORATOR SHELL THERMOCOUPLE WATER CONCENTRATION SENSOR Figure 1, Collecting Non-Condensible Gases The Auto-Purger Plus removes air the same as the familiar Auto-Purger model. An ammonia gas and air mixture (foul gas) is taken from various locations in the high side. This gas is brought into the tube side of a shell and tube heat exchanger with cold ammonia liquid on the shell side. The ammonia gas in the tube condenses to liquid. The air being non-condensible remains a gas. When enough air is collected, it is released. See figure 1. 7

Liquid Ammonia and Water in ½" FOUL GAS LINE ½" LOW-PRESSURE PUMPED LIQUID LINE ½" LIQUID RETURN LINE ¾" SUCTION LINE Only Ammonia Gas Out VAPOR TRAP FLOAT SWITCH LIQUID DRAINER STRAINER/ ORIFICE LIQUID LEVEL CONTROL SENSOR EVAPORATOR CHAMBER AIR SEPARATOR CHAMBER Water Concentration Gradually Increases EVAPORATOR SHELL THERMOCOUPLE WATER CONCENTRATION SENSOR Figure 2, Collecting Water In the familiar Auto-Purger models, the liquid comes from the high side receiver and from condensed foul gas and is expanded into the shell side of the heat exchanger which is maintained at suction pressure. In the new Auto-Purger Plus model, the liquid is taken from the pump discharge of the lowest pressure recirculator. This is where we expect the water to collect. Only ammonia gas can exit the shell side of the heat exchanger. The concentration of water gradually increases over time as liquid ammonia and water are brought in, and only ammonia gas leaves. See figure 2. 8

½" FOUL GAS LINE ½" LOW-PRESSURE PUMPED LIQUID LINE ½" LIQUID RETURN LINE ¾" SUCTION LINE VAPOR TRAP LIQUID DRAINER LIQUID LEVEL CONTROL SENSOR EVAPORATOR CHAMBER AIR SEPARATOR CHAMBER EVAPORATOR SHELL THERMOCOUPLE WATER CONCENTRATION SENSOR ELECTRIC HEATERS PLATE THERMOCOUPLE LIQUID THERMOCOUPLE Highly Concentrated Water LOW LEVEL SAFETY CUTOUT Figure 3, Concentrating Water Using foul gas as a heat source for concentrating the water can only bring the concentration to about 50% water and 50% ammonia depending on the evaporating pressure and the condensing temperature. In order to concentrate the water much more, a water concentration sensor (pressure/temperature transducer) in the shell side of the heat exchanger monitors the mixture. When the concentration of water in the shell side of the heat exchanger gets to about 20%, the AP Plus stops collecting air, isolates the mixture of ammonia and water, and energizes two electric heaters to heat the ammonia water solution even hotter, and to much more 9

effectively concentrate the water. The heaters remain energized until the ammonia water solution is heated to 185 F (85 C). This corresponds to a concentration of about 80% to 90% water and 10% to 20% ammonia, depending on the suction pressure. This concentrated water is then drained to a customer supplied container. See figure 3. After the water is drained, the Auto-Purger Plus goes back to normal operation collecting air and water. If no air or water is present, there are no releases to atmosphere. Specifications For non-condensible gas (air) removal, the AUTO-PURGER PLUS is suitable for systems up to 1500 tons (5300 kw) nominal system capacity when the system operates above a vacuum. It is suitable for systems up to 750 tons (2600 kw) nominal system capacity when the system operates in a vacuum. For water removal, the AUTO-PURGER PLUS has the following capacities: 5% system water concentration 3 gallons per day, 10% system water concentration 5 gallons per day, 20% or more system water concentration 7 gallons per day. Conclusion Many industrial ammonia refrigeration systems contain significant amounts of water which reduces their efficiency. The removal of this water has not received sufficient attention in our industry. Removing the water with a Hansen model Auto-Purger Plus can restore system efficiency, reduce electrical costs, and save money. 10