Vapour barrier and moisture response of wood-frame stucco wall results from hygrothermal simulation. Mukhopadhyaya, P.; Kumaran, K.; van Reenen, D.

Similar documents
Moisture Content in Insulated Basement Walls

Window Sill Details for Effective Drainage of Water

research highlight Water Penetration Resistance of Windows - Study of Codes, Standards,Testing, and Certification

research highlight Highly Energy Efficient Building Envelope Retrofits for Houses

Water Vapor Permeance of Wood Structural Panels and Wood Wall Construction

Evaluation Report CCMC R MemBrain

The Influence of Low-Permeance Vapor Barriers on Roof and Wall Performance

Wall Moisture Problems in Seattle

National Building Code of Canada 2010

Hygrothermal Simulations and Analysis of Solar- Driven Inward Water Vapor

How To Control Water Penetration In A Window

Determination of equilibrium moisture content of building materials: some practical difficulties

Influence of rain water leakage on the hygrothermal performance of exterior insulation systems

Article. Protecting the Building Envelope from Water Damage. MemBrain Smart Vapor Retarder & Air Barrier Film

Field Performance of Different Interior Basement Insulation Systems

Vapor Permeability Provides No Performance Benefit for in Ventilated Attics

Maintenance Matters. Window and Door Replacement

Frost Damage of Roof Tiles in Relatively Warm Areas in Japan

Presented by: Jennifer Doyle, P.E., RRC, LEED AP

Crawl space heat and moisture behaviour

WUFI-ORNL/IBP A North American Hygrothermal Model

Technical Series

Long-Term Hygrothermal Performance of Green Roofs

CFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER

Consumer Guide to window and Door Replacement

Optimal Drying of Flooded Brickwork Masonry

BEST 2 WB 3 4 SIX WAYS FOR CONDENSATION IN BUILDINGS. Wagdy Anis, FAIA, LEED ap*

Mario D. Gonçalves, Patenaude-Trempe 1 Pierre Gendron, Patenaude-Trempe 2 Tony Colantonio, PWGSC 3. Abstract

DuPont Tyvek Commercial Air Barrier Assemblies Exceed Air Barrier Association of America, ASHRAE 90.1

Moisture risk in prefabricated wooden wall elements (TES-elements) with a vapour retarder of OSB/3

*Trademark of The Dow Chemical Company A business unit of The Dow Chemical Company and its subsidiaries Copyright 2003 The Dow Chemical Company.

CONDENSATION IN REFRIDGERATED BUILDINGS

Frost Damage of Masonry Walls A hygrothermal Analysis by Computer Simulations

bout your HOUSE before you start Repairing And Replacing Materials Exterior Walls

R-VALUES AND U-FACTORS OF SINGLE WYTHE CONCRETE MASONRY WALLS. TEK 6-2C Energy & IAQ (2013) Related TEK: 2-5B, 6-1C, 6-4B, 6-11A, 6-12C, 6-12D, 6-12E

Testing Water Penetration Resistance of Window Systems Exposed to Realistic Dynamic Air Pressures

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION

Infrared Moisture Detection

Basements are Changing. Basements Part of the Enclosure. Basements. Energy Efficient, Durable, Healthy. Below grade enclosure

Molds and mildew are fungi that grow

Evaluating the Field Performance of Windows and Curtain Walls of Large Buildings

Specifying Treated Wood Paul I Morris, Group Leader Durability and Protection

NANSULATE NANOTECHNOLOGY BASED SOLUTIONS TO REDUCE HEAT LOSS THROUGH WINDOWS

10DBMC International Conference On Durability of Building Materials and Components LYON [France] April 2005

Coupling Forced Convection in Air Gaps with Heat and Moisture Transfer inside Constructions

TECH BULLETIN. Roofing No. Impact of Temperature on Polyiso R-value. Subject: Impact of Temperature on the R-value for Polyisocyanurate Insulation

1/9/2013. Terminology Calculating Heat Transfer Code Requirements Design Examples and Sustainability

Building Owners Guide to a Duro-Last System!

Moisture-Safe Unvented Wood Roof Systems

Underwriters Laboratories Testing Information

Water Damage & Repair

Natatorium Building Enclosure Deterioration Due to Moisture Migration

ROOFS, SNOW AND ICE DAMS

2014 British Columbia Building Code Changes

DESIGN OF NATURAL VENTILATION WITH CFD CHAPTER SEVEN. Qingyan Chen. difficult to understand and model, even for simple

Insulation Technologies and Materials Technologies, Systems and Tools in the U.S.

Basement Insulation: Best Practices for Efficient, Durable, & Healthy Homes

Asphalt Shingle Application Requirements

CONVENTIONAL ROOFS: MEASURING IMPACTS OF INSULATION STRATEGY & MEMBRANE COLOUR IN CANADA

Before You Start an Energy Efficiency Retrofit The Building Envelope

Eco Pelmet Modelling and Assessment. CFD Based Study. Report Number R1D1. 13 January 2015

The Optimum Basement Wall

Window Thermal Performance Optimization in Governmental Emirati Housing Prototype in Abu Dhabi, UAE

Cost effective basement wall drainage alternatives employing exterior insulation basement systems (EIBS)

Impact-Resistant Windows and Sliding Glass Doors

Predicting Moisture Problems in Low-Slope Roofing

The Influence Of Window Type And Orientation On Energy-Saving In Buildings Application To A Single Family Dwelling

STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM

Weather Resistive Barriers: Building Science Makes a Case for Two Layers by Dave Olson Technical Services Manager, Fortifiber Building Systems Group

Mold Preventing I nterior System

The Influence of Insulation Styles on the Air Conditioning Load of Japanese Multi- Family Residences

Performance of 8 Passive House Envelopes in Cold Climates

Continuous Insulation Using Polyiso Wall Sheathing

Answers to Your Questions from the Webinar

AND MEMBRANES ROOFING UNDERLAYS.

APPENDIX C - Florida Energy Code Standard Reference Design Auto-Generation Tests

Selecting Energy-Efficient Windows

Signs of insulation problems In the winter. In the summer. conditioning system

EPSRC Research Project EP/G00028X/1. Environmental Assessment of Domestic Laundering. Final Modelling Report

CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C Date of issue , Updated July 1, 2011

Avoiding Air Barrier Pitfalls

New Developments in Mitigation of Thermal Bridges Generated by Light Gage Steel Framing Components

EXPLANATION OF WEATHER ELEMENTS AND VARIABLES FOR THE DAVIS VANTAGE PRO 2 MIDSTREAM WEATHER STATION

Hovedindtryk som Tommy Odgaard oplevede dem

CHAPTER 3. The sun and the seasons. Locating the position of the sun

CONDENSATION. Section Break (Next Page)

Effects of Solar Photovoltaic Panels on Roof Heat Transfer

Key energy-efficient features of your new home

Open-cell spray foam & what every contractor

The Influence of Sweating on the Heat Transmission Properties of Cold Protective Clothing Studied With a Sweating Thermal Manikin

NUMERICAL ANALYSIS OF THE EFFECTS OF WIND ON BUILDING STRUCTURES

Hygrothermal Performance of Basement Foundation Systems

IEA-SHC Task 27: Setting Window Energy Efficiency Levels in Canada

Energy Efficient Building Design College of Architecture Illinois Institute of Technology, Chicago. Ceiling/Airspace

R-VALUES AND U-FACTORS OF SINGLE WYTHE CONCRETE MASONRY WALLS. TEK 6-2B Energy & IAQ (2009) Related TEK: 6-1B, 6-11, 6-12C INTRODUCTION

2.18 INTERIOR & EXTERIOR FINISHES VAPOR & AIR BARRIERS

keep moisture in check by getting fairly hot and facilitating downward time the sun came out, Then, after installation roof no longer got very

SELECTIVE GLAZING FOR SUN CONTROL

Drying of brick walls after impregnation

THERMAL STORAGE WITH PCM VS. THERMAL INSULATION IN WARM AND HOT CLIMATES

Transcription:

Vapour barrier and moisture response of wood-frame stucco wall results from hygrothermal simulation Mukhopadhyaya, P.; Kumaran, K.; van Reenen, D. NRCC-46864 A version of this document is published in / Une version de ce document se trouve dans : CIB World Building Congress 2004, Toronto, Ontario, May 2-7, 2004, pp. 1-10 http://irc.nrc-cnrc.gc.ca/ircpubs

Vapour Barrier and Moisture Response of Wood-frame Stucco Wall Results from Hygrothermal Simulation Authors: Phalguni Mukhopadhyaya 1,Ph.D, Kumar Kumaran 2,Ph.D & David van Reenen 3, BS ABSTRACT This paper investigates the role of the vapour barrier in a wood-frame stucco wall with the help of twodimensional hygrothermal simulation tool, hygirc-2d, developed at the Institute for Research in Construction of the National Research Council Canada. For this purpose, the wall is subjected to the exterior weather conditions of Vancouver, Canada. Three different interior climatic conditions and seven different vapour diffusion strategies, generated by varying the water vapour permeance of the vapour barrier, installed outboard of the interior finish, have been considered in this study. The outputs from the simulations have been analysed with the help of a novel moisture response indicator called RHT index. Simulation results indicate that the vapour permeance characteristics of the vapour barrier, in terms of water vapour permeance, plays a very important role in the overall moisture response of the wood-frame stucco wall. A very high or low vapour permeance of the vapour barrier does not produce the optimum moisture management strategy for the wood-frame stucco wall subjected to a climate as exists in Vancouver, Canada. Moreover, simulation results indicate that the removal of vapour barrier from the wall system can result in a heightened moisture response and a considerable accumulation of moisture in the interior gypsum board that may lead to severe consequences in particular, the premature deterioration of the interior facing board. It has also been observed from the simulation outputs that the optimum vapour diffusion strategy, that of limiting the vapour permeance of the vapour barrier, is not a function of interior climatic conditions considered in this study. It is hoped that the results reported in this paper will shed some light on a number of concerns raised in recent years on the role of vapour barrier in wood-frame stucco wall construction. 1 Research Officer, Institute for Research in Construction, National Research Council Canada, Ottawa, ON, K1A OR6 2 Principal Research Officer & Group Leader, Institute for Research in Construction, National Research Council Canada, Ottawa, ON, K1A OR6 3 Technical Officer, Institute for Research in Construction, National Research Council Canada, Ottawa, ON, K1A OR6 Page 1

1.0 INTRODUCTION The moisture design of exterior walls in a building envelope is becoming more complex in modern buildings. The functional variation, presence of different ventilation systems and use of new materials in construction have all contributed to this complexity. Without a proper vapour diffusion strategy, the short and long-term performance or durability of the wall can be seriously affected. In absence of any air leakage, moisture in the form of water vapour diffuses through the wall assembly due to water vapour pressure and/or temperature gradient across the wall cross section. The direction of water vapour movement depends on the exterior climate and indoor environment. During the heating season (i.e. winter) almost all the time moisture moves toward the exterior face of the building envelope and during the cooling season (i.e. summer) most of the time moisture moves towards the inside of the building envelope. Condensation of this moisture inside the wall assembly is highly undesirable as it may lead to premature deterioration of the wall component on which it is deposited. Water vapour condensation takes place always in the part of the wall that is moist and cold. The role of the vapour barrier in the wall assembly is to control the moisture movement from the warmer part of the wall assembly to the colder part of the wall. For this precise reason, it is a requirement in the National Building Code of Canada (NBC, 1995) to install a vapour barrier protection on the warmer side of the insulation. However in real life the colder side of the insulation is not always static, particularly in geographical locations with fluctuating weather. The role of the vapour barrier in building envelope construction is an issue that has been investigated and debated in Canada for over sixty years (Hutcheon, 1989; Swinton 1990). The complexity of the issue and the lack of definitive research mean, that for many smaller low-rise buildings, moisture diffusion continues to be governed by simple prescriptive requirements that are not particularly casesensitive. Water vapour permeance for vapour barriers in these buildings, determined by ASTM E96 Procedure A, must not exceed 15 ng/(pa.s.m 2 ) or 60 ng/(pa.s.m 2 ) depending on the permeance of other materials in the assembly. For other buildings where professionals are expected to be involved in the design, the National Building Code of Canada (NBC) provides more general performance-based requirements that allow for greater case-sensitivity. Although there is no evidence of problems as a result of compliance with the NBC prescriptive requirements, questions remain regarding the specific limits prescribed. However, the exact influence of these prescriptive values on the overall moisture response of the wall due to climatic moisture load is still not very clear. Experimental data are needed to critically examine this issue but such experiments are time consuming, expensive and on occasions practically difficult to perform. In such a situation, the use of computer aided numerical modelling can be a realistic scientific option. However, this option is only useful if the model is benchmarked. The study undertaken in this paper uses a two-dimensional (2-D) modelling tool, hygirc-2d, to assess the effect of vapour permeance characteristics of the vapour barrier on the overall moisture response of a wood-frame stucco wall exposed to various interior climatic conditions in Vancouver, Canada. 2.0 RESEARCH BACKGROUND A two-dimensional numerical modeling study, carried out by Karagiozis and Kumaran (1993), questioned the necessity of specific water vapour permeance characteristics of the vapour barrier, as prescribed in the National Building Code of Canada (1990), installed at the interior side of the wall assembly in certain Canadian locations to achieve optimum moisture management. The results from this study indicated the necessity of location and specific water vapour permeance values for the vapour barrier. It was also suggested that it might not be necessary to install a vapour barrier for a wall built in Vancouver, Canada. However, these studies were done using constant interior boundary conditions (20 C and 38.5% relative humidity) and the presence of exterior cladding was not modelled. Moreover, Page 2

the study neglected entirely the effect of driving rain, solar radiation and wind velocity on the water vapour movement through the wall assembly. Further to the aforementioned study, Mukhopadhyaya et al. (2001) conducted a number of simulations for wood-frame stucco walls for locations of Ottawa and Vancouver, using a more advanced two dimensional modelling tool that takes into account the effect of driving rain, solar radiation, wind velocity and also the presence of exterior cladding. A single interior boundary condition was assumed to be variable and functionally related to the exterior climate. The results from this simulation study indicated that a vapour barrier having a higher water vapour permeance results in greater drying and wetting of the wall assembly in terms of total moisture content. This study did not look into the localized moisture response of the wall assembly. The investigation reported in this paper analyses the localized response of the wood-frame stucco wall assembly, built with seven different vapour barrier systems and exposed to three different interior boundary conditions. The exterior climatic condition of Vancouver, Canada, is taken as the exterior boundary condition. A two dimensional (2-D) heat, air and moisture (hygrothermal) transport numerical simulation tool, hygirc-2d, has been used for this study. 3.0 hygirc-2d AND HYGROTHERMAL SIMULATION The hygrothermal simulation tool used in this study is a computer aided numerical model, hygirc-2d, that can predict the moisture response of building envelopes (Hens 1996). hygirc-2d is continuously evolving as a research tool, developed by a group of researchers at the Institute for Research in Construction (IRC) of the National Research Council (NRC), Canada. Interested readers can refer to the publications by Karagiozis (1997) and Djebbar et al., (2002) for further details. These documents outline the formulation of the combined heat, air and moisture transport equations used in hygirc-2d and the techniques used to solve them numerically. The reliability of hygirc-2d outputs has been established through laboratory measurements and benchmarking exercises (Maref et al. 2002). The effective use of hygirc-2d to analyse and obtain meaningful results, however, demands a proper physical understanding of the problem, an appropriate definition of input parameters and the ability to judiciously interpret the outputs from the simulation tool (Mukhopadhyaya and Kumaran, 2001; Mukhopadhyaya et al. 2001; and Mukhopadhyaya et al. 2002). hygirc-2d accommodates many advanced features, such as transient heat, air and moisture (liquid and vapour) transport, 2-dimensional spatial formulation, variable material properties with moisture content and temperature, air flow through building materials, wind driven rain penetration, effect of solar radiation, presence of moisture source inside the material, freeze-thaw effects, as well as many other useful features. To define the construction of the wall system, hygirc-2d has a pre-processor that allows the user to divide a wall into a number of layers, in both the horizontal and vertical directions. There are a number of major input parameters required for hygirc-2d simulation, such as wall construction details, material properties, boundary conditions, exposure duration, initial moisture content and temperature. The detailed descriptions of these parameters, as required for this study, are given in the following paragraphs. 3.1 Wall Construction Details A wood-frame stucco wall has been considered in this study. The basic details of the construction of the wood-frame stucco wall are shown in Figure 1. The wall remains the same for all the simulations done in this study, and only the vapour permeance value of the vapour barrier is varied, as shown in Table 1, for the parametric study. 3.2 Material Properties for hygirc-2d hygirc-2d simulation requires eight sets of material properties. These properties are air permeability, thermal conductivity, dry density, heat capacity, sorption characteristics, suction pressure, liquid diffusivity and water vapour permeability. These materials properties, for the wall construction Page 3

shown in Figure 1, were obtained from the IRC/NRC's database and were determined in the IRC's Thermal and Moisture Performance Laboratory. 3.3 Boundary Conditions and Geographic Location The outdoor climatic condition required for hygirc-2d simulations has seven major weather components (i.e., temperature, relative humidity, wind velocity, wind direction, rain fall, solar radiation and cloud index) recorded on an hourly basis. In this study, the weather conditions for Vancouver (year 1969), representative of climatic conditions (i.e. average weather year) in the lower mainland of coastal British Columbia, Canada (i.e., temperate oceanic cool) is taken as exterior climate. The total exposure or simulation duration of two years (same weather year repeated) is used for the simulation. The hourly indoor climatic condition (i.e., temperature, relative humidity) is considered here as a subject of parametric variation, details of which are described in section 4.0. Three different sets of data are used as shown in Table 1. 3.4 Initial Moisture Content In this study, the initial moisture content of each wall component is assumed to be equivalent to the corresponding relative humidity of 50 percent, derived from the sorption isotherm of the respective materials. 4.0 PARAMETRIC VARIATION The primary objective of this study is to find out the effect of different vapour permeance values of the vapour barrier on the overall long-term moisture response of the wood-frame stucco wall assembly exposed to different indoor boundary or climatic conditions. Hence, two parameters under investigation in this study are the variation of vapour permeance values of vapour barrier, installed outboard of the interior finish, and different climatic conditions as described in the following paragraphs. 4.1 Vapour Barrier Seven cases of different vapour resistances, offered by vapour barrier and interior gypsum board, are considered in this study, as shown in Table 1 with the values of vapour permeance of vapour barrier and interior facing (i.e. gypsum board) together. The total vapour permeance values varied between 14.7 ng/m 2.s.Pa and 2753.3 ng/m 2.s.Pa. 4.2 Indoor Condition Three different indoor conditions are considered in this study. These conditions include: (i) Constant 40% relative humidity (RH) and 22 C temperature (T) condition (Table 1), (ii) Controlled indoor condition (RH and T) according to ASHRAE Handbook of Fundamentals, Chapter 3 and criteria specified for winter and summer in "Specifications to the National (Canada) Energy Code for Houses (Swinton & Sander, 1994) (Figure 2), and (iii) Indoor climatic conditions (Figure 3) that is derived from outdoor climatic data using the weather analysis tool Weathersmart (Djebbar et al. 2001) developed at the IRC/NRC. In this particular case, the indoor RH conditions have been derived using a model proposed by Jones (1995) with the indoor temperature 21 C (both for summer and winter), moisture load 7.5 litre/day, air leakage 1.44cm 2 /m 2, volume 192m 3, air exchange rate (ACH) 0.3, and indoor maximum RH cap of 75%. Page 4

2400 Top Plate ht. [76 mm] Gypsum [12mm] Vapour Barrier Insul Space [89 mm] Sheathing Board [11mm] Sheath Memb [0 23mm] Stucco Cladding [19 mm] Relative Humidity (%) 80 70 60 50 40 30 20 10 0 Indoor Condition - ASHRAE CIB 2004, Toronto, Canada 20 0 2000 4000 6000 8000 10000 Time (hours) FIGURE 2 Relative Humidity (%) Temperature (deg C) Indoor climate ASHRAE 40 35 30 25 FIGURE 1 Area [650x1.5 mm 2 ] of the sheathing board selected for RHT index calculation Bott. Plate ht. [76 mm] Basic wall construction details Relative Humidity (%) 80 70 60 50 40 30 20 10 0 Indoor Condition - Weathersmart Relative Humidity (%) Temperature (deg C) 20 0 2000 4000 6000 8000 10000 Time (hours) FIGURE 3 Indoor climate Weathersmart 40 35 30 25 Simulation ID TABLE 1. Parametric variations considered Vapour barrier permeance (ng/pa.s.m 2 ) + Interior facing Total vapour permeance of vapour barrier and interior facing (ng/pa.s.m 2 ) Indoor condition Seven different vapour barriers with ASHRAE specified indoor condition VA15-A 15+Coated Gypsum 14.7 ASHRAE (Figure 2) VA60-A 60+Coated Gypsum 54.8 ASHRAE (Figure 2) VA100-A 100+Coated Gypsum 86.0 ASHRAE (Figure 2) VA500-A 500ng+Coated Gypsum 271.9 ASHRAE (Figure 2) VA1000-A 1000ng+Coated Gypsum 372.5 ASHRAE (Figure 2) VANC-A No vapour barrier+coated Gypsum 591.3 ASHRAE (Figure 2) VANUC-A No vapour barrier+uncoated Gypsum 2753.3 ASHRAE (Figure 2) Seven different vapour barriers with Weathersmart generated indoor condition VA15-B 15+Coated Gypsum 14.7 Weathersmart (Figure 3) VA60-B 60+Coated Gypsum 54.8 Weathersmart (Figure 3) VA100-B 100+Coated Gypsum 86.0 Weathersmart (Figure 3) VA500-B 500ng+Coated Gypsum 271.9 Weathersmart (Figure 3) VA1000-B 1000ng+Coated Gypsum 372.5 Weathersmart (Figure 3) VANC-B No vapour barrier+coated Gypsum 591.3 Weathersmart (Figure 3) VANUC-B No vapour barrier+uncoated Gypsum 2753.3 Weathersmart (Figure 3) Seven different vapour barriers with constant indoor condition VA15-C 15+Coated Gypsum 14.7 Constant (21 C, 40% RH) VA60-C 60+Coated Gypsum 54.8 Constant (21 C, 40% RH) VA100-C 100+Coated Gypsum 86.0 Constant (21 C, 40% RH) VA500-C 500ng+Coated Gypsum 271.9 Constant (21 C, 40% RH) VA1000-C 1000ng+Coated Gypsum 372.5 Constant (21 C, 40% RH) VANC-C No vapour barrier+coated Gypsum 591.3 Constant (21 C, 40% RH) VANUC-C No vapour barrier+uncoated Gypsum 2753.3 Constant (21 C, 40% RH) Page 5

5.0 hygirc-2d OUTPUT AND ANALYSIS OF RESULTS A significant amount of data were generated from hygirc-2d and subsequently post-processed for the detailed evaluation of the simulated hygrothermal response of the various walls through parametric analyses. The results obtained from the typical hygirc-2d output have been further analysed as described in the following paragraphs. 5.1 Typical hygirc-2d Output The basic outputs from hygirc-2d simulations are the relative humidity (RH) and temperature (T) contour plots (Figure 4) across the wall assembly cross-section (vertical). In this study, these contour plots were generated at midnight, at every 10-day interval for the entire duration of the simulation/exposure period (i.e. 2 years). In order to make quantitative sense of the long-term moisture response of the wall assembly from these outputs, a novel hygrothermal performance indicator called RHT index, derived from the RH and T distribution patterns over a period time as defined in the following paragraphs, has been used. Wall Height (m) 2 1.5 1 Stucco Stheathing board Relative Humidity Contour Region of focus RH 0.9346 0.8723 0.8100 0.7477 0.6854 0.6231 0.5608 0.4985 0.4362 0.3739 0.3115 0.2492 0.1869 0.1246 0.0623 Wall Height (m) 2 1.5 1 Temperature Contour T 18.8822 17.6151 16.3480 15.0808 13.8137 12.5465 11.2794 10.0123 8.7451 7.4780 6.2109 4.9437 3.6766 2.4094 1.1423 0.5 0.5 0.05 0.1 Wall Width (m) - Expanded FIGURE 4 Typical outputs from hygirc-2d 0.05 0.1 Wall Width (m) - Expanded 5.2 RHT Index The RHT Index (Kumaran et al. 2003; Mukhopadhyaya et al. 2002; Mukhopadhyaya 2003) can be used to quantify and compare the localized hygrothermal response of any part of the wall component (i.e., region of focus, see Figure 4). The region of focus is that part of the wall cross-section where hygrothermal response is the most severe and critical for the long-term moisture performance of the wall assembly. Relative humidity (RH) and temperature (T) at different time steps are the values required to obtain the RHT index. The generic definition of RHT index at the 'region of focus' is: n RHT Index = ( RH ) ( T ) t= 1 RH (1) X T X where RH = relative humidity (%); RHx = threshold RH; T = temperature; Tx = threshold temperature ( C); t = time step or interval when RH and T values are recorded. During any time step when either or both RH RH X % and T T X C, the RHT value for that time step is zero. The RHT index brings out the long-term localized combined moisture and temperature response of the selected area of the material (i.e. region of focus ). The part of the wall component selected in this study for the RHT index calculation, by visual inspection of the relative humidity contour plot (Figure 4), is a thin layer (height 650mm; width 1.5mm) of sheathing board facing the exterior stucco cladding above Page 6

the bottom plate (Figure 1). User-defined threshold values for RH X = 95%, T X = 5 C and a time step or interval of 10 days over the period of two years have been chosen for this study. 6.0 DISCUSSION ON RESULTS The RHT indices, indicating the long-term moisture response of the wall assembly, calculated for 21 simulations (Table 1) are shown in Table 2 and in Figures 5 to 7. A higher value of RHT index points out a relatively severe moisture response compared to a lower RHT index value. In addition total moisture content of the interior gypsum board for various cases are also plotted in Figures 8 to 10. The significance of these results is to be discussed in the following paragraphs. Table 2 Parametric variations considered Simulation ID RHT Index Simulation ID RHT Index Simulation ID RHT Index VA15-A 675 VA15-B 708 VA15-C 675 VA60-A 276 VA60-B 272 VA60-C 268 VA100-A 265 VA100-B 265 VA100-C 257 VA500-A 249 VA500-B 264 VA500-C 240 VA1000-A 247 VA1000-B 266 VA1000-C 238 VANC-A 422 VANC-B 547 VANC-C 338 VANUC-A 377 VANUC-B 497 VANUC-C 290 RHT Index 1000 800 600 400 200 0 RHT95 - ASHRAE 0 500 1000 1500 2000 2500 3000 Vapour Permeance (ng/pa.s.m 2 ) FIGURE 5 RHT Index variation due to different permeance of vapour barrier (ASHRAE indoor condition) RHT Index 1000 800 600 400 200 0 RHT95 - Weathersmart 0 500 1000 1500 2000 2500 3000 Vapour Permeance (ng/pa.s.m 2 ) FIGURE 6 RHT Index variation due to different permeance of vapour barrier (Weathersmart indoor condition) RHT Index 1000 800 600 400 200 0 RHT95-Constant 0 500 1000 1500 2000 2500 3000 Vapour Permeance (ng/pa.s.m 2 ) FIGURE 7 RHT Index variation due to different permeance of vapour barrier (Constant Indoor) Page 7 Moisture Content (kg/m) 2.2 2.0 1.8 1.6 1.4 1.2 1.0 0.8 0.6 15ng 100ng 1000ng No VB-Uncoat-GB ASHRAE 60ng 500ng No-VB 0 100 200 300 400 500 600 700 800 Time (days) (hours) FIGURE 8 Moisture content in interior gypsum facing (ASHRAE Indoor)

2.2 Weathersmart 1.9 Constant Moisture Content (kg/m) 2.0 1.8 15ng 60ng 1.6 100ng 500ng 1000ng No-VB NoVB-Uncoat GB 1.4 0 100 200 300 400 500 600 700 800 Time (days) (hours) FIGURE 9 Moisture content in interior gypsum facing (Weathersmart Indoor) Moisture Content (kg/m) 1.8 1.7 1.6 15ng 60ng 1.5 100ng 500ng 1000ng No-VB 1.4 No VB-Uncoat-GB 0 100 200 300 400 500 600 700 800 Time (hours) (days) FIGURE 10 Moisture content in interior gypsum facing (Constant Indoor) 6.1 Effect of Vapour Permeance of Vapour Barrier The vapour permeance values of the vapour barriers alone, and the total vapour permeance of the vapour barrier and interior facing for each of the 21 cases are shown in Table 1. The lowest value of the vapour permeance (14.7ng/Pa.s.m 2 ) is associated with a vapour barrier permeance value of 15ng/Pa.s.m 2 and the highest value of the vapour permeance (2753ng/Pa.s.m 2 ) is with the case where there is no vapour barrier and the interior facing of the wall is made of uncoated gypsum board. As shown in Figures 5 to 7, the vapour permeance of the vapour barrier influences the overall moisture response of a wood-frame stucco wall subjected to Vancouver climate. The vapour barrier with the lowest vapour permeance (15ng/Pa.s.m 2 ), used in this study, produces the most severe moisture response (i.e. the highest value of RHT index). A more vapour permeable vapour barrier can reduce the intensity of the moisture response. However, it is interesting to note that the optimum moisture management (i.e. the lowest RHT index) for the wall assembly cannot be achieved either with the use of the most permeable vapour barrier nor when vapour barrier is entirely removed +. The optimum moisture management in this study is obtained when the vapour barrier permeance is between 60 and 1000ng/Pa.s.m 2, and interior gypsum facing board is coated with a primer and latex paint. In fact, the complete removal of the vapour barrier and further reduction of vapour resistance by using uncoated interior gypsum board produces a much higher level of moisture response than the optimum case. Hence, it can be said, as shown in Figures 5 to 7, a vapour barrier with too high or too low vapour resistance would not be a choice that would lead to an optimum moisture management strategy in stucco wall assemblies of the type represented in this study. In Vancouver, as the simulation results show, a vapour barrier that has a vapour permeance value between 60 and 1000ng/Pa.s.m 2 would produce an optimum moisture management. At this stage, the authors are conducting similar studies for other geographic locations in Canada and results from these studies will be reported in due course. 6.2 Effect of Different Interior Climatic Conditions Results from the simulations (Figures 5 to 7) indicate that the interior conditions (RH and T) considered in this study have very little or no influence on the overall vapour diffusion strategy for optimum moisture management. However, in presence of a vapour barrier with higher vapour permeance or in absence of any vapour barrier, the level of moisture load in the interior climate has a greater influence on the overall moisture response of the wall. + There is a proposed change to the NBC (1995) to remove the requirement for vapour barriers with a minimum 15 ng/(pa.s.m 2 ) permeance where there are other low permeance materials in the assembly; only the 60 ng/(pa.s.m 2 ) limit would remain. Page 8

6.3 Moisture Content in Interior Gypsum Board It is to be mentioned that the interior facing (gypsum board) also offers some vapour resistance, though not very high, to water vapour moving across the wall assembly. In the presence of a vapour barrier with lower vapour resistance (i.e. providing higher vapour permeance) or in absence of any vapour barrier in the wall assembly, the role and moisture response of the interior facing becomes more critical. In order to investigate this phenomenon the moisture content of the interior gypsum board was varied with time for the entire period of simulation (2 years), the results of which are shown in Figures 8 to 10. These results show that the removal of vapour barrier can significantly increase the moisture content of the interior gypsum board facing. 7.0 SUMMARY OF OBSERVATIONS The results and discussion presented in this paper on the role of vapour barrier in optimum moisture management can be summarised with several observations as stated below. However, it is to be noted that the observations made in this study are useful, practical and applicable only for the input conditions stated in the paper. 1. Vapour permeance characteristics of the vapour barrier plays an important role in the overall moisture management for the wood-frame stucco wall. 2. Simulation results indicate that an acceptable range of vapour permeance of the vapour barrier to obtain optimum moisture management in the wood-frame stucco wall assembly could be much wider that the prevailing practices. Further studies are required on this issue and in particular the performance of the wall at other geographic locations (other than Vancouver). 3. Removal of the vapour barrier in Vancouver does not produce optimum moisture management in the wood-frame stucco wall. 4. Removal of the vapour barrier from the wall assembly significantly increases the moisture content in the interior gypsum board facing. 8.0 REFERENCES 1. ASHRAE Applications Handbook, 1999. Chapter 3 - Commercial and Public Buildings. 2. ASTM : E96-00 2000. Standard test methods for water vapour transmission of materials. Annual Book of ASTM Standards. 3. Djebbar, R., Kumaran, M.K., Van Reenen, D. and Tariku, F. 2002. Hygrothermal modelling of building envelope retrofit measures in multi-unit residential and commercial office buildings. IRC/NRC, National Research Council, Ottawa, Canada, Client Final Report B-1110.3, pp. 187. 4. Djebbar, R., van Reenen, D. and Kumaran, M. K. 2001. Environmental boundary conditions for long-term hygrothermal calculations. 8th International Conference on Building Envelopes, Clearwater Beach, Florida, USA, p. 13. 5. Hens, H., 1996. Heat, air and moisture transport, Final Report, Vol. 1, Task 1: Modelling, International Energy Agency Annex 24, Laboratorium Bouwfysica, K. U.-Leuven, Belgium. 6. Hutcheon, N. B. 1989. Forty years of vapour barriers, water vapour transmission through building materials and systems: mechanisms and measurement. ASTM, STP 1039. 7. Jones, R. 1995. Indoor humidity calculation procedures, Building Services Engineering Research & Technology, Volume 16, No. 3, pp 119-126. Page 9

8. Karagiozis, A. 1997. Analysis of the hygrothermal behaviour of residential high-rise building components. Client Report A-3052.4, IRC/NRC, National Research Council Canada, Ottawa. 9. Karagiozis, A. N. and Kumaran, M. K. 1993. Computer model calculations The performance of vapour barriers in Canadian residential buildings. ASHRAE Transactions, Vol. 99, Part 2. 10. Kumaran M. K., Mukhopadhyaya P., Cornick S. M., Lacasse, M. A., Maref W., Rousseau M., Nofal M., Quirt J. D. & Dalgliesh W. A. 2003. An integrated methodology to develop moisture management strategies for exterior wall sys-tems. 9th Conference on Building Science and Technology, Vancouver, Canada, pp. 16. 11. Maref, W., Kumaran, M. K., Lacasse, M. A. Swinton, M. C. & van Reenen, D. 2002. Advanced hygrothermal model- hygirc: Laboratory measurements and benchmarking. 12th International Heat Transfer Conference, Grenoble, pp. 1-6. 12. Mukhopadhyaya, P. 2003. MEWS project produces long-term moisture response indicator Construction Innovation, Volume 8, No. 1, pp. 6-7. 13. Mukhopadhyaya, P. and Kumaran, M. K. 2001. Prediction of moisture response of wood frame walls using IRC s advanced hygrothermal model (hygirc). 2nd Annual Conference on Durability and Disaster Mitigation in Wood-Frame Housing. pp. 221-226. 14. Mukhopadhyaya, P., Goudreau, P., Kumaran, M. K. and van Reenen, D. 2002. Influence of material properties on the hy-grothermal response of an ideal stucco wall - Results from hygrothermal simulations. 6th Nordic Building Physics Symposium 2002, Trondheim, Norway, pp. 611-618. 15. Mukhopadhyaya, P., Kumaran, M. K., Rousseau, M., Tariku, F., van Reenen, D. and Dalgliesh, A. 2003. Application of hygrothermal analyses to optimise exterior wall design, 2nd International Conference on Research in Building Physics, Leuven, Belgium, pp. 417-426. 16. Mukhopadhyaya, P., Kumaran, M.K., van Reenen, D. and Tariku, F. 2001. Influence of sheathing membrane and vapour barrier on hygrothermal response of stucco walls, International Conference on Building Science and Technology (ICBEST), Ottawa, Canada, pp. 6. 17. Mukhopadhyaya, P., Kumaran, M.K., Tariku, F., and van Reenen, D. 2003. Long-term performance: Predict the moisture management performance of wall systems as a function of climate, material properties, etc. through mathematical modelling, Research Report, Institute for Research in Construction, National Research Council Canada, 132, pp. 384, February 01, (IRC- RR-132). 18. National Building Code (NBC) of Canada. 1995. Part 9, National Research Council Canada, Ottawa. 19. Swinton, M.C. and Sander, D.M. 1994. Trade-off compliance for houses: specifications for calculation procedures for demonstrating compliance to the National Energy Code for Houses, National Research Council Canada (NRCC-39861), pp. 46. 20. Swinton, M.C. and Mitalas, G.P. 1990. The effect of separating the air and vapour barriers on moisture movement in walls - A discussion paper, Fifth Conference on Building Science and Technology, Toronto, Ontario, Canada, pp. 133-155, (NRCC-42507). Page 10