Drying of brick walls after impregnation
|
|
|
- Gwendolyn Charles
- 10 years ago
- Views:
Transcription
1 Drying of brick walls after impregnation H.M. Künzel and K. Kießl Fraunhofer-Institute of Building Physics (Director: Prof. Dr.-Ing. habil. Dr. h.c. Dr. E.h.mult. Karl Gertis) Abstract Elevated moisture due to driving rain impact on unrendered brick walls can lead to frost damage or accelerated decay of the exposed facade. Additionally, in the case of monolithic exterior walls which are often encountered in historic buildings, a high water content reduces the already low thermal resistance of the wall, thus leading to poor hygienic indoor conditions. Since the appearance of the facade should in general remain unaltered for esthetical reasons, the obvious measure to improve the moisture protection and thermal quality of brick masonry is the impregnation with water repellent agents, possibly combined with an interior insulation. In field test, the effect of siloxane impregnation on the moisture behaviour of exposed brick masonry with and without cracks was examined in comparison with untreated as well as with sheltered facades. In all cases the impregnation of exposed wall elements with elevated moisture led to a drying process which resulted in low water contents, similar to the moisture conditions of sheltered facades. The drying of the impregnated wall elements with a thickness of 24 cm takes about one year. Since monolithic brick walls of historic buildings are mostly thicker, complementary heat and moisture transport calculations were carried out for representative walls. Depending on the interior finish (e.g. insulation) of such brick walls, the drying time after impregnation ranges from 2 to 7 years. In order to avoid frost damage or a long dry-out time, an interior insulation is best applied some time after impregnation. Key words: Brick wall, frost damage, impregnation, water repellent agents, water content, heat and moisture transport. Drying of brick walls after impregnation 1
2 1. Introduction Single layer brick walls of old buildings often lack sufficient protection against driving rain and may thus exhibit elevated moisture contents, especially on the weather side. This further reduces the mostly low thermal resistance of these walls, which may in some cases even fall below the minimum heat insulation required for hygienic reasons. Additionally, an elevated moisture content entails the danger of frost damage close to the facade. Installing an interior heat insulation, e.g. to increase thermal comfort, aggravates this danger since the drying process of the wall is slowed down and its mean temperature reduced. Prerequisite for a better thermal quality and a better protection against moisture of these walls is therefore an increased rain protection. In the case of unrendered masonry, which should retain its appearance for esthetical reasons, the only way to improve rain protection is repointing the facade and treating it with water repellent agents. In this paper the performance of siloxane impregnation is examined in a field test and the consequences of such a treatment for the hygrothermal behaviour of single layer brick walls with and without interior insulation is analysed by experimentally verified heat and moisture transfer calculations. The drying time of representative walls after impregnation is assessed by assuming an effective long term rain protection by the water repellent treatment. 2. Experimental and numerical investigations 2.1 Combination of field tests and calculations It has been shown in [1] that a combination of field tests and heat and moisture transport calculations can enhance the interpretation and transferability of experimental results concerning the hygrothermal behaviour of building components. If the measured and calculated results for a certain construction element correspond well, it can be assumed that the dominant factors for the hygrothermal behaviour of the considered construction are correctly implemented in the calculation model. This means that further conclusions can be drawn by a numerical study without additional costly and time consuming field tests. Drying of brick walls after impregnation 2
3 2.2 Experimental set-up In a test hall which is conditioned during wintertime of 20 C and 50 % R.H., masonry elements with a surface of 60x60 cm 2 and a thickness of 24 cm have been exposed with one side facing to the wet and to the east, respectively [2]. The western facade of the hall faces a plain without any obstructions. The amount of driving rain hitting the facade varies between about 400 to 500 l/m 2 a year. The eastern facade is sheltered by a overhanging roof, so that hardly any rain water hits it. The masonry in the wall elements is made of solid brick (format: 24x11.5x5 cm 3 ) and lime-cement mortar. The mortar gaps have a thickness of about 15 mm. At some elements, artificial cracks were introduced with a thin wire while the mortar was still soft, which led to cracks of up to 1 mm in thickness between the mortar and the brick. After exposing the wall elements to the natural climate in Holzkirchen (Bavaria), the water content was monitored by weighing the elements about once a month. Due to unusually dry weather at the beginning of the observation period, the elements facing west were sprayed by a lawn sprinkler in the end of May 1993 in order to obtain a representative water content. Five days later, half of the wall elements were treated with siloxane in organic solvent while the other half of the elements remained untreated. The impregnation was applied twice with the aid of a paint brush by wetting the surface thoroughly. The total amount of solution taken up by the masonry was about 0.3 kg/m 2. After the treatment, the moisture behaviour of the wall elements was registered by discontinuous weighing for a period of more than two years. Towards the end of the observation period, the rain protection of one element was blemished by drilling holes (diameter 3 cm) in the facade and filling them with untreated lime-cement mortar, thereby producing an unimpregnated area of less than 2 % of the facade element. 2.3 Heat and moisture transfer calculations The calculations are done with the PC-program WUFI, a one-dimensional version of the calculation model described in [3]. Although this model has been validated by comparison with experimental results several times, a verification of the calculations for this case is necessary because the material parameters of the masonry have to be approximated from standard material properties as listed in table 1. The resulting liquid diffusivities for water absorption and liquid redistribution, res. drying, are shown in Fig. 1. The retention curve is approximated from the sorption moisture at 80 % R.H. and the capillary saturation according to [3]. As boundary conditions for the comparison, the Drying of brick walls after impregnation 3
4 Table 1: Hygrothermal parameters of brick masonry and the interior insulation materials. material brick masonry expanded polystyrene mineral wool insulating plaster density [kg/m 3 ] thermal conductivity [W/mK] moisture related increase of λ [%/M.-%] vapour diffusion resistance factor [-] sorption moisture at 80 % R.H. [Vol.-%] capillary saturation [Vol.-%] Fig. 1: Liquid diffusivity of the brick masonry for water absorption during rain periods and the redistribution respectively drying process. Drying of brick walls after impregnation 4
5 measured meteorological data, i.e. temperature, relative humidity, driving rain and solar radiation of the test period, are used in form of hourly mean values. The initial moisture content assumed for this calculation is the water content after the spray-wetting of the wall elements assuming a uniform distribution. The effect of the water repellent impregnation is simulated by a non water-absorbing surface and an additional surface diffusion resistance of 0.2 m which was measured by a wet-cup test. The thickness of the tested wall elements is not representative for single layer brick walls found in old buildings, which are mostly at least 40 cm thick. The same holds for the precipitation load in Holzkirchen which is classified in driving rain group III according to [4]. Unrendered brick walls cannot bear such a high load and are therefore uncommon in areas classified in group III. Therefore, the driving rain load in the outdoor boundary conditions taken from an average year in Holzkirchen has been reduced to one third of the measured amount. The interior temperatures and relative humidities are approximated by sine waves with mean value of 22 C and 50 % relative humidity and amplitudes of 2 K and 10 % R.H., respectively. The maximum values are reached in July. In contrast to [5], where the moisture distribution in an exposed wall was derived from the measured distribution in a rendered brick wall, the conditions in untreated walls without insulation and with 6 cm of interior insulation using different insulation materials (material parameters are given in table 1) is determined by calculating over several years applying the same meteorological data until no changes from one year to another are observed anymore. From the thus obtained moisture distribution, the drying behaviour of the walls after impregnation is calculated assuming a perfect rain protection, i.e. without water absorption of the exposed surface. 3. Results 3.1 Performance of siloxane impregnation in the field test The course of the change in water content of the exposed wall elements during the observation period is shown in Fig. 2. Prior to the siloxane impregnation, which was applied in the beginning of June 1993 shortly after the spray wetting of the west facing elements, the moisture change of the west facing elements are very similar. After the impregnation however, the untreated masonry elements are becoming increasingly wet until they reach a dynamic equilibrium, whereas the siloxane impregnated masonry Drying of brick walls after impregnation 5
6 elements dry out continuously. As expected, the drying process is faster in summer than in winter. There appears to be no influence of the cracks on the moisture behaviour of the masonry since the changes in water content with and without cracks between the bricks and the mortar are almost equal for the treated and the untreated wall elements. The effect of the untreated mortar areas in the impregnated facade without cracks introduced in autumn 1995 (hollow circles in Fig. 2 above) seems, however, quite important. The increase in water content compared to the unaltered impregnated masonry element (full circles in Fig. 2) has to be carefully observed in future. The eastward facing sheltered wall elements show no difference in the moisture behaviour for the treated and untreated masonry. The slight increase in material moisture during winter time due to vapour diffusion from the inside and a higher relative humidity on the outside is equal in both cases. That means that the siloxane impregnation has only a minor effect on the vapour diffusion and sorption behaviour of the masonry. 3.2 Comparison of calculation and experiment The calculated and measured courses of the mean water content of an impregnated and an untreated west facing wall element after the artificial wetting are compared in Fig. 3. The agreement between the calculated results and the measurements is quite good which means that the approximated material parameters are sufficiently accurate in order to obtain realistic calculation results. It also shows that rain water penetration of the impregnated facade is very low because the measured water content hardly deviates from the calculated course where zero water absorption is assumed. 3.3 Calculated moisture behaviour of a representative wall The annual mean moisture profiles (solid lines) and the annual variation range (hatched areas) in the masonry of a 40 cm thick untreated brick wall with and without interior insulation are shown in Fig. 4. In all cases, the exterior surface shows the highest variation in water content but the annual mean water content there is rather low. The variations are decreasing rapidly towards the interior of the wall, whereas the mean water content increases steeply. While the annual mean moisture reaches a peak of about 8 Vol.-% in the masonry without insulation, the maximum with interior insulation lies above 10 Vol.-%. This means that the frost damage risk of a brick facade is considerably increased by applying an interior insulation. Compared with the uninsulated wall, the influence of the type of insulation on the moisture behaviour of the masonry is not significant. This shows that there is no risk-free interior insulation measure, because the reduction in masonry temperature seems to be more important Drying of brick walls after impregnation 6
7 for the drying process than the vapour permeability of the insulation layer. A low vapour diffusion resistance leads to better drying conditions during summer time which are almost compensated by interstitial condensation during the heating period. Fig. 2: Moisture behaviour of the exposed masonry elements over a period of approximately three years. The roman numbers indicate the quarters of a year. The impregnation of the exterior surface of the elements was done shortly after the spray wetting. Drying of brick walls after impregnation 7
8 Fig. 3: Comparison of the calculated and the measured variation in water content of 24 cm thick brick masonry under natural conditions. The initial water content (marked with an arrow) was reached by artificial spray wetting of the facade elements. Fig. 4: Annual mean profiles (solid lines) and annual variations (hatched areas) of the water content in the masonry of a west oriented wall without and with different types of interior insulation. Drying of brick walls after impregnation 8
9 If the moisture content in the masonry shown in Fig. 4 is regarded to be too high, an impregnation of the facade may be considered. However, an immediate change of the moisture conditions after application of the water repellent agent should not be expected. Fig. 5 shows the development of the mean water content in the masonry with and without insulation starting from the calculated moisture profiles analogous to those in Fig. beginning of July after facade impregnation. While the uninsulated masonry reaches the practical moisture content of 1.5 Vol.-% in less than two years, it takes more than five years for the insulated walls to dry out completely. Fig. 5: Drying behaviour of unrendered brick walls without and with different types of interior insulation after impregnation. The initial water content in the walls corresponds to the respective condition at the beginning of July without impregnation. 4. Discussion of the results and conclusion The field test shows that a siloxane impregnation, if properly applied, can repel rain water to such an extent that a complete drying of the masonry is possible. The question remains, however, whether the experience from rather small test elements even with artificial cracks which were impregnated by experts can be translated into the application on a real building. It seems possible that in inappropriate impregnation can Drying of brick walls after impregnation 9
10 even increase the moisture content and hence the danger of frost damage as stated in [6]. The quality of workmanship and the preparation of the facade, for example by repointing it, appear to be of major importance. If the quality conditions are met, an impregnation can be considered as an effective rain protection. Small cracks up to 1 mm wide do not affect the rain protection if they are thoroughly impregnated and if the wall is of sufficiently low air permeability, e.g. by the application of a plaster on the inside. A similar result for cracks up to 0.5 mm has been obtained by laboratory simulations [7]. The drying time of the masonry even after an effective impregnation should not be underestimated. It is recommendable to install an interior insulation after the impregnation and leaving some time for the excessive moisture in the masonry to dry out. Finally, it should be noted that a high accumulation of salt in the brickwork may impede the drying process or even prevent it altogether [8]. Under these circumstances, impregnation measures may fail to have the desired effect or even worse, salt crystallisation behind the impregnated surface layer may lead to spalling effects at the facade. If the moisture in the wall is not due to ran but to rising damp, an impregnation can result in a further rise of the water front. Literature [1] Künzel, H.M. und Krus, M.: Beurteilung des Feuchteverhaltens von Natursteinfassaden durch Kombination von rechnerischen und experimentellen Untersuchungsmethoden. Bauinstandsetzen 1, 5-19 (1995). [2] Riedl, G. und Kießl, K.: Untersuchungen zum Feuchteverhalten von Ziegelmauerwerk mit unterschiedlichen Imprägnier- und Beschichtungssystemen unter natürlicher Bewitterung. Report of the Fraunhofer-Institut für Bauphysik FtB- 31 (1994). [3] Künzel, H.M.: Simultaneous Heat and Moisture transport in Building Components. IRB-Verlag, Stuttgart (1995). [4] DIN 4108, Teil 3: Wärmeschutz im Hochbau. Klimabedingter Feuchteschutz. August [5] Künzel, H.M. and Kießl, K.: Hydrophobing historical facade for rain protection and thermal quality purposes. Proceedings of the International Symposium on Moisture Problems in Building Walls. Porto, Sept., pp 1-14 (1995). [6] Franke, L. und Bentrup, H.: Schädigung von Mauerwerksbauten durch Umwelteinflüsse; Beurteilung und Instandsetzung. Bauphysik 13, (1991). [7] Franke, L. und Bentrup, H.: Einfluß von Rissen auf die Schlagregensicherheit von hydrophobiertem Mauerwerk und Prüfung der Hydrophobierbarkeit. Bautenschutz + Bausanierung 14, and (1991). [8] Künzel, H.: Trocknungsblockade durch Mauerversalzung. Bautenschutz + Bausanierung 14, (1991). Drying of brick walls after impregnation 10
Frost Damage of Masonry Walls A hygrothermal Analysis by Computer Simulations
Frost Damage of Masonry Walls A hygrothermal Analysis by Computer Simulations K. SEDLBAUER, H.M. KÜNZEL INTRODUCTION AND OBJECTIVES Frost damage occurs especially if damp building elements are subjected
Long-Term Hygrothermal Performance of Green Roofs
Long-Term Hygrothermal Performance of Green Roofs D. Zirkelbach B. Schafaczek H. Künzel, PhD Member ASHRAE ABSTRACT Green roofs are becoming more and more popular because their thermal inertia, combined
Frost Damage of Roof Tiles in Relatively Warm Areas in Japan
Frost Damage of Roof Tiles in Relatively Warm Areas in Japan Influence of Surface Finish on Water Penetration Chiemi IBA Hokkaido Research Organization, Japan Shuichi HOKOI Kyoto University, Japan INTRODUCTION
Martin Krus, Klaus Sedlbauer, Herbert Sinnesbichler
Martin Krus, Klaus Sedlbauer, Herbert Sinnesbichler Artificial thermal bridge with a dew point switch to accomplish an appropriate control of the ventilation for the prevention of mould growth in buildings
Moisture Content in Insulated Basement Walls
Moisture Content in Insulated Basement Walls Peter Blom,PhD, SINTEF Building and Infrastructure; [email protected], www.sintef.no/byggforsk Sverre B. Holøs M.Sc. SINTEF Building and Infrastructure;
WUFI-ORNL/IBP A North American Hygrothermal Model
WUFI-ORNL/IBP A North American Hygrothermal Model Achilles Karagiozis, Ph.D. Hartwig Künzel Andreas Holm ABSTRACT Building envelope designers and architects provide expert advice during the selection of
Influence of rain water leakage on the hygrothermal performance of exterior insulation systems
Influence of rain water leakage on the hygrothermal performance of exterior insulation systems Hartwig M. Künzel, Dr.-Ing. Department of Hygrothermics, Fraunhofer Institute for Building Physics; [email protected]
Mold Preventing I nterior System
interior insulation and renovation boards A system of components that have been designed to work perfectly together to repair damage caused by mold. The system consists of boards, insulation wedges, reveal
Technical Data Sheet Art. No. 1810. Kiesol. applications. Shelf-life. rate depending on application. Characteristic data of the product
Page 1 of 5 Technical Data Sheet Art. No. 1810 Kiesol Deep protection silicification for waterproofing and refurbishing old and new buildings in the Kiesol System according to WTA Code of Practice 4-4-04/D
Coupling Forced Convection in Air Gaps with Heat and Moisture Transfer inside Constructions
Coupling Forced Convection in Air Gaps with Heat and Moisture Transfer inside Constructions M. Bianchi Janetti 1, F. Ochs 1 and R. Pfluger 1 1 University of Innsbruck, Unit for Energy Efficient Buildings,
FIXIT.CH. Aerogel Insulating Plaster System. Handling Guidelines. Easy to use. Mineral based. 0.028 W/mK BAUSTOFFE MIT SYSTEM
FIXIT.CH Aerogel Insulating Plaster System Handling Guidelines BAUSTOFFE MIT SYSTEM λ 0.028 W/mK Mineral based Easy to use Efficient building insulation using space technology Aerogel high-performance
Hygrothermal Simulations and Analysis of Solar- Driven Inward Water Vapor
ROXUL Hygrothermal Simulations and Analysis of Solar- Driven Inward Water Vapor January 2014 Prepared by: Building Science Consulting Inc. 167 Lexington Court, Unit 5 Waterloo, Ontario Canada N2J 4R9 www.buildingscienceconsultinginc.com
Moisture risk in prefabricated wooden wall elements (TES-elements) with a vapour retarder of OSB/3
Passivhus Norden 2013 Moisture risk in prefabricated wooden wall elements (TES-elements) with a vapour retarder of OSB/3 Silje Korsnes Author, SINTEF Building and Infrastructure, 7465 Trondheim, [email protected]
Development of conservation compatible new materials for envelope retrofitting of historic buildings
Development of conservation compatible new materials for envelope retrofitting of historic buildings Carsten Hermann, Senior Technical Officer, Historic Scotland Glasgow is one of seven EFFESUS case study
Basements are Changing. Basements Part of the Enclosure. Basements. Energy Efficient, Durable, Healthy. Below grade enclosure
Basements are Changing John Straube, Ph.D., P.Eng Basements: New & Retrofit Energy Efficient, Durable, Healthy Increasingly used as living space Not a root /coal cellar anymore! High quality space expected
Improving the flood resistance of your home. Advice sheet 4: Flood-resilient walls.
Improving the flood resistance of your home Advice sheet 4: Flood-resilient walls. This sheet provides guidance on identifying different types of wall, and reducing the flow of floodwater through them
Post-insulation of cellar ceiling and cellar walls
WP5 Education and Economic Promotion Post-insulation of cellar ceiling and cellar walls Educational product: New lecture material for training modules dealing with knowledge and skills how to apply suitable
Sustainable construction criteria to evaluate the thermal indoor climate - further development of the BNB assessment tool and practical implementation
Fraunhofer Institute for Building Physics IBP Directors Univ. Prof. Dr. Ing. Gerd Hauser Univ. Prof. Dr. Ing. Klaus Sedlbauer Holzkirchen Branch Fraunhoferstrasse 10 83626 Valley / Germany IBP-Abstract
WATERPROOFING OF WET ROOMS
WATERPROOFING OF WET ROOMS Waterproofing under tiles For longterm enjoyment of a wetroom area a complete and resistant waterproofing system is an important precondition. Most tiles are by themselves waterproof
orizontal BarrierS PATENTED SYSTEM
orizontal BarrierS Against rising damp IN MASONRY PATENTED SYSTEM Why is rising damp a concern for building owners? Rising damp is among the most frequently encountered causes of damage to masonry walls.
ROOFS, SNOW AND ICE DAMS
ROOFS, SNOW AND ICE DAMS The Problem Ice dams are a common roof performance problem in cold climate buildings. Simply put, they are ridges of ice and icicles caused by melt water from further up the roof
Basement Insulation: Best Practices for Efficient, Durable, & Healthy Homes
Basement Insulation: Best Practices for Efficient, Durable, & Healthy Homes Midwest Regional Energy Codes Conference October 3, 2012 Indianapolis, IN Patrick H. Huelman Cold Climate Housing Coordinator
HEALTHY LIVING WITH WOOD FIBRE INSULATING MATERIALS
HEALTHY LIVING WITH WOOD FIBRE INSULATING MATERIALS HIGH-QUALITY INSULATION. SUSTAINABLE LIVING. www.homatherm.com Preamble THE EXAMPLE OF NATURE Sustainable living to us means harnessing the forces of
Moisture-Safe Unvented Wood Roof Systems
building science.com 2010 Building Science Press All rights of reproduction in any form reserved. Moisture-Safe Unvented Wood Roof Systems Research Report - 1001 April-2010 John Straube, Jonathan Smegal
EPSRC Research Project EP/G00028X/1. Environmental Assessment of Domestic Laundering. Final Modelling Report
ESRU Report EPSRC Research Project EP/G00028X/1 Environmental Assessment of Domestic Laundering Final Modelling Report Kelly N J K, Markopoulos A and Strachan P A March 2012 Energy Systems Research Unit
NANSULATE NANOTECHNOLOGY BASED SOLUTIONS TO REDUCE HEAT LOSS THROUGH WINDOWS
NANSULATE NANOTECHNOLOGY BASED SOLUTIONS TO REDUCE HEAT LOSS THROUGH WINDOWS NANSULATE ENERGY PROTECT INSULATION AND PROTECTIVE COATING The science of nanotechnology is behind the innovation of Nansulate
3 Masonry and Manufactured Stone (Interior and Exterior)
3 Masonry and Manufactured Stone (Interior and Exterior) 3.1 Efflorescence (a whitish crystalline powder) is present on masonry surfaces. Efflorescence commonly occurs on masonry surfaces. This is not
Water Vapor Permeance of Wood Structural Panels and Wood Wall Construction
T e c h n i c a l n o t e Water Vapor Permeance of Wood Structural Panels and Wood Wall Construction Number J450 February 2009 Controlling against moisture damage in structures depends upon proper system
European technical approval
Authorised and notified according to Article 10 of the Council Directive 89/ 106/EEC of 21 December 1988 on the approximation of laws, regulations and administrative provisions of Member States relating
Baumit Renders for Porotherm Masonry. Application Guidelines. n Light and easy application n Tried and tested
Renders for Porotherm Masonry Application Guidelines n Light and easy application n Tried and tested Porotherm is a Wienerberger Group brand Ideas with a future Renders for Porotherm Masonry International
bout your HOUSE before you start Repairing And Replacing Materials Exterior Walls
A bout your HOUSE before you start Repairing And Replacing Materials Exterior Walls CE 28 h Exterior finish materials are expected to protect the house from the elements while providing an attractive appearance.
Salt Weathering of Masonry Walls The Venice Experience. By M. Collepardi, S. Collepardi and R. Troli
Salt Weathering of Masonry Walls The Venice Experience By M. Collepardi, S. Collepardi and R. Troli Synopsis: All the buildings in Venice insist on foundation immersed in sea water and then are permanently
WUFI 2D. Calculation Example Step by Step. D. Zirkelbach Th. Schmidt H.M. Künzel M. Kehrer Ch. Bludau
WUFI 2D Calculation Example Step by Step D. Zirkelbach Th. Schmidt H.M. Künzel M. Kehrer Ch. Bludau WUFI 2D Short Introduction PREFACE This introduction will show you how to model a building component
Molds and mildew are fungi that grow
Appendix C: Moisture, Mold and Mildew Molds and mildew are fungi that grow on the surfaces of objects, within pores, and in deteriorated materials. They can cause discoloration and odor problems, deteriorate
Module 3.7. Thermal bridging
Module 3.7 Thermal bridging Learning Outcomes On successful completion of this module learners will be able to - Describe construction details which influence thermal bridging. 2 Introduction to thermal
Crawl space heat and moisture behaviour
Crawl space heat and moisture behaviour Miimu Airaksinen, Dr., Technical Research Centre of Finland, VTT [email protected], www.vtt.fi KEYWORDS: crawl space, moisture, evaporation from ground, ground
Signs of insulation problems In the winter. In the summer. conditioning system
about your house CE 19 While previous generations may have been content to live in drafty houses, most people now want comfortable warm houses. A healthy house today is well sealed, well insulated and
201 WATER STREET FORWARDERS MUSEUM AND VISITORS INFORMATION CENTRE
STRUCTURAL INSPECTION REPORT DRAFT 201 WATER STREET FORWARDERS MUSEUM AND VISITORS INFORMATION CENTRE TOWN OF PRESCOTT Date: November 2013 GENIVAR No.: 131-20617-00 2611 Queensview Drive, Suite 300, Ottawa,
PERFORMANCE GUIDELINES
1. Foundation/Basement 17 PERFORMANCE GUIDELINES 1. FOUNDATION/BASEMENT 1.1 Efflorescence on concrete or masonry surfaces Efflorescence is the formation of a white crystalline or powdery deposit on the
Climate and Energy Responsive Housing in Continental Climates. The Suitability of Passive Houses for Iran's Dry and Cold Climate. Farshad Nasrollahi
Climate and Energy Responsive Housing in Continental Climates The Suitability of Passive Houses for Iran's Dry and Cold Climate Farshad Nasrollahi Table of Contents Abstract German Abstract Introduction
Interior Walls below and above ground OLDROYD THE ULTIMATE WATERPROOF MEMBRANE SYSTEM
P r o d u c t a p p l i c a t i o n s a n d t e c h n i c a l i n f o r m a t i o n 2 below and above ground V OLDROYD THE ULTIMATE WATERPROOF MEMBRANE SYSTEM V The flexible, fast and cost-effective answer
Exemplary Retrofitting of an Old School in Stuttgart - EROS -
Exemplary Retrofitting of an Old School in Stuttgart - EROS - City of Stuttgart, Summary The objective of the project was to demonstrate the potentials of a retrofitting process for a typical school in
Garver Feed Mill Condition Evaluation
Garver Feed Mill Condition Evaluation OUTLINE Brick masonry overview Condition assessment & methodology Project overview Existing conditions Stabilization Probable costs Summary BRICK MASONRY OVERVIEW
Water Damage & Repair
Water Damage & Repair Chinatown Preservation Talks 2015 James Engler, P.A Glenn Mason, AIA Mason Architects Program Outline Terminology & Waterproofing Basics Discussion of why this is important Below
Waterproofing System for Wastewater Tanks in Petrochemical Industries and Refineries
Waterproofing System for Wastewater Tanks in Petrochemical Industries and Refineries Introduction Wastewater of petrochemical industries and refineries contains high amounts of emulsified aliphatic or
Infrared Moisture Detection
What it can do for you... what it can t and why 1. Infrared camera basics 2. Examples Lew Harriman MoistureDM.com 3. Summary - The 4 most important facts about infrared moisture detection 1 of 19 Infrared
Sealing & Bonding Sika solutions for Window Installation
Sealing & Bonding Sika solutions for Window Installation Sika s Comprehensive Fenestration Competence Benefit of our solution Globally, growing requirements to save energy and to utilize natural resources
Repair of Spalling and Leaking Clay Brick Building Walls
B etter buildings Repair of Spalling and Leaking Clay Brick Building Walls Overview A few years after being built in Waterloo in 1980, a condominium of three, six-storey buildings showed severe spalling
European Technical Approval ETA 13/0526
European Technical Approval ETA 13/0526 Trade Name Holder of the approval Website Generic type and use of construction product DOLCEA i3 PCIM S.A. Rue du Péquet 54 5590 Achene (Ciney) Belgium www.isoproc.eu
Chimney systems ICOPAL WULKAN C/CI/C-eko/CI-eko
INSTALLATION MANUAL Chimney systems ICOPAL WULKAN C/CI/C-eko/CI-eko Ventilated Notified entity Building Technical and Research Institute Prague notification no. 1020 This instruction refers to double-layer
research highlight Highly Energy Efficient Building Envelope Retrofits for Houses
research highlight June 2012 Technical Series 12-103 Highly Energy Efficient Building Envelope Retrofits for Houses introduction In Canada approximately 30% of all energy is consumed in buildings, with
Insulating Basements: Part 3 Basement Wall Systems
The Pennsylvania Housing Research Center Insulating Basements: Part 3 Basement Wall Systems Builder Brief: BB0710 Brian Wolfgang, PHRC Fellow INTRODUCTION The perception of a basement has changed significantly
Aalborg Universitet. Reduction of moisture problems in old basements Brandt, Erik; Møller, Eva B.; Vesterløkke, Michael
Aalborg Universitet Reduction of moisture problems in old basements Brandt, Erik; Møller, Eva B.; Vesterløkke, Michael Published in: Proceedings 5th International Conference on Building Physics (IBPC)
*Trademark of The Dow Chemical Company A business unit of The Dow Chemical Company and its subsidiaries Copyright 2003 The Dow Chemical Company.
Dow Chemical is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned on completion of this program will be reported to CES Records for AIA members.
BUREAU OF ENVIRONMENTAL HEALTH Emergency Response/Indoor Air Quality Program
BUREAU OF ENVIRONMENTAL HEALTH Emergency Response/Indoor Air Quality Program Use of Moisture Measuring Devices in Evaluating Water Damage in Buildings July 2007 The evaluation of mold colonization of building
WATERPROOFING SYSTEMS IN BUILDING CONSTRUCTION
WATERPROOFING SYSTEMS IN BUILDING CONSTRUCTION Ar. Soma Anil Mishra Ar. Prakool Soni Dr.R.K. Pandit Asso. Professor Practising Architect Professor & Head I.P.S Academy, Indore (M.P) M.I.T.S, Gwalior (M.P)
National Building Code of Canada 2010
National Building Code of Canada 2010 Emergency Change Issued by the Canadian Commission on Building and Fire Codes The table that follows lists two emergency changes that apply to the National Building
Building envelope and heat capacity: re-discovering the thermal mass for winter energy saving
346 2nd PALENC Conference and 28th AIVC Conference on Building Low Energy Cooling and Building envelope and heat capacity: re-discovering the thermal mass for winter energy saving S. Ferrari Politecnico
In accordance with the Department of Labor and Industry s statute 326.0981, Subd. 11,
In accordance with the Department of Labor and Industry s statute 326.0981, Subd. 11, This educational offering is recognized by the Minnesota Department of Labor and Industry as satisfying 1.5 hours of
ETAG 004 EXTERNAL THERMAL INSULATION COMPOSITE SYSTEMS WITH RENDERING
European Organisation for Technical Approvals Europäische Organisation für Technische Zulassungen Organisation Européenne pour l Agrément Technique Edition March 2000 Amendment June 2008 GUIDELINE FOR
Understanding BS EN 771-3: Aggregate concrete masonry units
60 Charles Street, Leicester LE1 1FB Tel: 0116 253 6161 Fax: 0116 251 4568 Email: [email protected] Website: www.cba-blocks.org.uk February 2006 Understanding BS EN 771-3: Aggregate concrete
Chapter D9. Irrigation scheduling
Chapter D9. Irrigation scheduling PURPOSE OF THIS CHAPTER To explain how to plan and schedule your irrigation program CHAPTER CONTENTS factors affecting irrigation intervals influence of soil water using
Solar air collectors for industry and larger halls S Ø. Efficient dehumidification and air heating for free...
Solar air collectors for industry and larger halls N S Ø Efficient dehumidification and air heating for free... This booklet contains information about SolarVenti Industrial air solar system. The system
High performance thermal insulation materials
thermal insulation materials Reducing energy use in buildings Civil and Environmental Engineering Building Technology Different materials Thermal conductivity (mw/mk) 45 40 35 30 25 20 15 10 5 0 Aerogel
Models and Methods in Applied Sciences
Energy consumption and energy saving in Malaysian office buildings S.Sadrzadehrafiei, K.Sopian S.Mat, C.Lim Solar Energy Research Institute University Kebangsaan Malaysia 43600, Bangi, Malaysia [email protected],
The Influence of Low-Permeance Vapor Barriers on Roof and Wall Performance
The Influence of Low-Permeance Vapor Barriers on Roof and Wall Performance J.F. Straube, Ph.D. ABSTRACT Low-permeance vapor barriers are widely used on the interior of wall and roof systems in large parts
TEXTILE FABRICS AS THERMAL INSULATORS
TEXTILE FABRICS AS THERMAL INSULATORS Zeinab S. Abdel-Rehim 1, M. M. Saad 2, M. El-Shakankery 2 and I. Hanafy 3 1 Mechanical Engineering Department of the National Research Center, Dokki, Giza, Egypt 2
SOUND INSULATION FOR EXTERIOR WALLS AND FACADE SYSTEMS
NOISE TECHNICAL FACT SHEET FACT SHEET 5 SOUND INSULATION FOR EXTERIOR WALLS AND FACADE SYSTEMS The sound insulation of exterior walls and roof-ceiling systems refers to their ability to reduce external
Solar Homes Catch the Sun. Are you planning a new house? Discover how you can apply solar architecture principles to:
PASSIVE Solar Design Solar Homes Catch the Sun Are you planning a new house? Discover how you can apply solar architecture principles to: keep your heating bills to a minimum enjoy the comfort of a warm
Foundation. Foundation
Moisture Aside from structural concerns, the most important consideration for foundation design is moisture. No client wants a wet basement. No client wants a damp basement. No client wants mold in their
CONDENSATION. Section Break (Next Page)
CONDENSATION Elimination of condensation on or within walls and floors is as important as reducing the heat loss through the wall or floor. In addition to the moisture damage caused to buildings by condensation,
BEST PRACTICE GUIDE. Fibrelime Premixed Universal Plaster and Render
BEST PRACTICE GUIDE Fibrelime Premixed Universal Plaster and Render Contents: Fibrelime description Fibrelime suitability Preparation before application Application Aftercare Painting General Recommended
Cavity Drain R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high.
CI/SfB Tn6 L6813 September 2013 RIW CAVITY DRAIN R20 R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high. Other systems are available for specific uses,
Mineral waterproof coating PCI Dichtschlämme
Mineral waterproof coating PCI Dichtschlämme 305 for basement walls, swimming pools and potable water tanks With official test certificate. FIELDS OF For indoor and outdoor use. For walls and floors. For
EXPERT OPINION on the applicability of the construction technology "GRÈMOUND non-tectonic system on grounds of the documentation submitted
ÉMI Építésügyi Minőségellenőrző Innovációs Nonprofit Kft. [ÉMI Non-Profit Limited Liability Company for Quality Control and Innovation in Building; ÉMI Non-Profit Ltd.] Address: 1113 Budapest, Diószegi
CHAPTER 3. The sun and the seasons. Locating the position of the sun
zenith 90 summer solstice 75 equinox 52 winter solstice 29 altitude angles observer Figure 3.1: Solar noon altitude angles for Melbourne SOUTH winter midday shadow WEST summer midday shadow summer EAST
Wall Moisture Problems in Seattle
Wall Moisture Problems in Seattle Andre O. Desjarlais Achilles N. Karagiozis Michael A. Ki-Kramer ABSTRACT In the past few years, major moisture-related problems have appeared in the northwestern U.S.
Energy savings in the residential area are essential in
Overheating and insufficient heating problems in low energy houses up to now call for improvements in future Requirements for improved energy performance have shifted major focus on energy calculations
Introduction. 1. Heat Transfer. In Townsville s climate it is essential to choose building materials that perform well in our local conditions.
In Townsville s climate it is essential to choose building materials that perform well in our local conditions. Choosing the correct materials and insulation will improve the overall thermal performance
AND MEMBRANES ROOFING UNDERLAYS. www.fakro.com
AND MEMBRANES 010 ROOFING UNDERLAYS 1 HO DOES YOUR ROOF BREATHe? MEMBRANES THE WAY to A WARM AND DRY ROOF HO HO HO HO HO HO WATERTIGHTNESS The FAKRO Company offers a wide range of membranes and underlays
How To Test Water Penetration On Concrete Block And Mortar
WATER PENETRATION TEST ON CONCRETE BLOCK MASONRY Vilató, Rolando Ramirez 1 1 PhD, Prof., Mackenzie Presbyterian University, School of Engineering, São Paulo, [email protected] This paper considers
Water Permeability vs Waterproof
ASCE Met Section Construction Group, Cooper Union Student Chapter, May 25, 2000 Water Permeability vs Waterproof by Patrick F. McGrath, Ph.D. Xypex Chemical Corporation, Richmond, B.C., Canada The paper
ELASTOCEM. Technical features. Applications. Two-component flexible, waterproofing and protective cementitious grout.
Two-component flexible, waterproofing and protective cementitious grout. 1504-2 PI-MC-IR Technical features Two-component grout, based on cements, selected aggregates, special additives and synthetic polymers
Article. Protecting the Building Envelope from Water Damage. MemBrain Smart Vapor Retarder & Air Barrier Film
Article Protecting the Building Envelope from Water Damage Vapor Retarders Play a Crucial Role in Moisture Management Whether we like it or not, moisture in the form of water vapor diffusion and humid
Comparison of two calculation methods used to estimate cooling energy demand and indoor summer temperatures
Comparison of two calculation methods used to estimate cooling energy demand and indoor summer temperatures Kai Sirén and Ala Hasan Helsinki University of Technology, Finland Corresponding email: [email protected]
DETERMINATION OF WOOD MOISTURE PROPERTIES USING CT- SCANNER IN A CONTROLLED ENVIRONMENT
DETERMINATION OF WOOD MOISTURE PROPERTIES USING CT- SCANNER IN A CONTROLLED ENVIRONMENT Cherepanova, E. 1 & Hansson, L. 2 ABSTRACT The aim of the present work was to examine the existing algorithm for
Building Condition Assessment: 215-219 West Lexington Street Baltimore, Maryland
KPA The Joint Venture of EBA Engineering, Inc. and Kennedy Porter & Associates, Inc. 4813 Seton Drive, Baltimore, MD 21215 Phone: (410-358-7171) Fax: (410)358-7213 Building Condition Assessment: Baltimore,
Fire 2This Technical Bulletin has been commissioned by the UK SIP Association in
REV 1-12.12.11/TB002 Technical Bulletin Fire 2This Technical Bulletin has been commissioned by the UK SIP Association in conjunction with TRADA Technology and is intended to provide the reader with introductory
TECH BULLETIN. Roofing No. Impact of Temperature on Polyiso R-value. Subject: Impact of Temperature on the R-value for Polyisocyanurate Insulation
TECH BULLETIN Roofing No. 3016 Subject: Impact of erature on the R-value for Polyisocyanurate Insulation Date: February 2014 (Revised May 2015) The blowing agents used in polyisocyanurate (polyiso) foam
Tunnels & Arches OLDROYD THE ULTIMATE WATERPROOF MEMBRANE SYSTEM
P r o d u c t a p p l i c a t i o n s a n d t e c h n i c a l i n f o r m a t i o n 5 Tunnels & Arches V OLDROYD THE ULTIMATE WATERPROOF MEMBRANE SYSTEM V Create dry usable space with the original X pattern
Metropolitan Builders Association Masonry & Concrete Standard
Metropolitan Builders Association Masonry & Concrete Standard Background Masonry and concrete work in residential construction often provides the base structure upon which the house is built or as a veneer.
Weather Resistive Barriers: Building Science Makes a Case for Two Layers by Dave Olson Technical Services Manager, Fortifiber Building Systems Group
Weather Resistive Barriers: Building Science Makes a Case for Two Layers by Dave Olson Technical Services Manager, Fortifiber Building Systems Group Since water intrusion is among the most damaging problems
Sika Membran System For Sealing and Waterproofing Construction Gaps in Building Façades
Construction Sika For Sealing and Waterproofing Construction Gaps in Building Façades Waterproof and Airtight Flexible Seal Controlled Vapour Diffusion Bonds to any Building Substrate Prevents Interstitial
Garden Bothy, Cumnock
Refurbishment Case Study 8 DRAFT Garden Bothy, Cumnock Upgrades to walls, floors, windows & door The views expressed in commissioned case studies are those of the authors and do not necessarily represent
THERMAL STORAGE WITH PCM VS. THERMAL INSULATION IN WARM AND HOT CLIMATES
THERMAL STORAGE WITH PCM VS. THERMAL INSULATION IN WARM AND HOT CLIMATES G. C HRISTOPH SPAEH, PE, LEED BD+C SUTTON KENNERLY & ASSOC., INC. 300 Pomona Dr., Greensboro, NC 27403 Phone: 336-855-0993 Fax: