Design and Development of the Middle-Frequency Isolation Transformer for the High-Voltage DC/DC Converter

Similar documents
Iron Powder Cores for Switchmode Power Supply Inductors. by: Jim Cox

Design of an Auxiliary Power Distribution Network for an Electric Vehicle

Selecting IHLP Composite Inductors for Non-Isolated Converters Utilizing Vishay s Application Sheet

Power supplies. EE328 Power Electronics Assoc. Prof. Dr. Mutlu BOZTEPE Ege University, Dept. of E&E

Chapter 14: Inductor design

A bidirectional DC-DC converter for renewable energy systems

ABSTRACT 1. INTRODUCTION

Hybrid Power System with A Two-Input Power Converter

The full wave rectifier consists of two diodes and a resister as shown in Figure

TOPOLOGIES FOR SWITCHED MODE POWER SUPPLIES

High Power Density Capacitor Charging Power Supply Development for Repetitive Pulsed Power

INDUCTOR DESIGN IN SWITCHING REGULATORS

EMI in Electric Vehicles

VICOR WHITE PAPER. The Sine Amplitude Converter Topology Provides Superior Efficiency and Power Density in Intermediate Bus Architecture Applications

Current Ripple Factor of a Buck Converter

Power Supplies. 1.0 Power Supply Basics. Module

Modeling and Analysis of DC Link Bus Capacitor and Inductor Heating Effect on AC Drives (Part I)

Principles of Adjustable Frequency Drives

CHAPTER 4 DESIGN OF INTEGRAL SLOT AND FRACTIONAL SLOT BRUSHLESS DC MOTOR

Line Reactors and AC Drives

A MULTILEVEL INVERTER FOR SYNCHRONIZING THE GRID WITH RENEWABLE ENERGY SOURCES BY IMPLEMENTING BATTERY CUM DC-DC CONERTER

WIND TURBINE TECHNOLOGY

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

AN2228 APPLICATION NOTE

Toroids. Toroids. Design Considerations

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies

Designers Series XII. Switching Power Magazine. Copyright 2005

Philosophy of Topology and Components Selection for Cost and Performance in Automotive Converters.

Variable Frequency Drives - a Comparison of VSI versus LCI Systems

CURRENT TRANSFORMERS FOR ELECTRONIC WATTHOUR METERS ADVANCED MATERIALS THE KEY TO PROGRESS

DC-DC Converter Basics

Improved PFC Boost Choke using a Quasi-Planar Winding Configuration Dave Shonts Schott Corporation 1000 Parkers Lake Road Wayzata, MN 55391

High Voltage Power Supplies for Analytical Instrumentation

Chapter 15: Transformer design

SELECTION GUIDE. Nominal Input

Application Note AN-1070

Improvement of Charging Resource in Repetitive Pulsed Power by High Power Density Capacitor

Design, Analysis, and Implementation of Solar Power Optimizer for DC Distribution System

Planar versus conventional transformer

Design Considerations for an LLC Resonant Converter

Power supply output voltages are dropping with each

ALLOY POWDER CORE SERIES INTRODUCTION

Application Note AN- 1095

Application Note. So You Need to Measure Some Inductors?

FREQUENCY CONTROLLED AC MOTOR DRIVE

A Simple Current-Sense Technique Eliminating a Sense Resistor

Novel Loaded-Resonant Converter & Application of DC-to-DC Energy Conversions systems

The leakage inductance of the power transformer

DC/DC BUCK Converter for Renewable Energy Applications Mr.C..Rajeshkumar M.E Power Electronic and Drives,

Control Development and Modeling for Flexible DC Grids in Modelica

Introduction to Power Supplies

Homework # Physics 2 for Students of Mechanical Engineering

2012 San Francisco Colloquium

Design and Simulation of Soft Switched Converter Fed DC Servo Drive

A Zero-Voltage Switching Two-Inductor Boost Converter With an Auxiliary Transformer

AN3022. Establishing the Minimum Reverse Bias for a PIN Diode in a High-Power Switch. 1. Introduction. Rev. V2

Chapter 16. Current Transformer Design. Copyright 2004 by Marcel Dekker, Inc. All Rights Reserved.

Output Ripple and Noise Measurement Methods for Ericsson Power Modules

1ED Compact A new high performance, cost efficient, high voltage gate driver IC family

Design of Four Input Buck-Boost DC-DC Converter for Renewable Energy Application

Bridgeless PFC Implementation Using One Cycle Control Technique

Fundamentals of Power Electronics. Robert W. Erickson University of Colorado, Boulder

Drive circuit basics + V. τ e. Industrial Circuits Application Note. Winding resistance and inductance

Design a Phase Interleaving PFC Buck Boost Converter to Improve the Power Factor

SWITCHING REGULATORS

Tape-Wound Cores for Magnetic Amplifier Chokes VITROVAC 6025 Z

AN ISOLATED GATE DRIVE FOR POWER MOSFETs AND IGBTs

UNDERSTANDING AND CONTROLLING COMMON-MODE EMISSIONS IN HIGH-POWER ELECTRONICS

Comparison of an Efficient Buck Converter Configuration for the DC Power Distribution Of Future Green Data Centers

3.3 kv IGBT Modules. Takeharu Koga Yasuhiko Arita Takatoshi Kobayashi. 1. Introduction. 2. Specifications of 3.3 kv IGBT Module

Welcome to the combined product training module of Linear Technology and Wurth Electronics about their efficient design solution for DC/DC Flyback

EMI and t Layout Fundamentals for Switched-Mode Circuits

PRECISION CAPACITOR CHARGING SWITCHING POWER SUPPLIES

Reset Circuits With Energy Recovery for Solid-State Modulators

Switched Mode Power Supplies

Implementation of High Step-Up Solar Power Optimizer for DC Micro Grid Application

CMR Series Isolated 0.75W Single and Dual Output Isolated DC/DC Converters

International Journal of Science and Research (IJSR) ISSN (Online): Index Copernicus Value (2013): 6.14 Impact Factor (2014): 5.

FILM CAPACITORS FOR ELECTRONIC LIGHTING

Chapter 2 Application Requirements

Chapter 6: Converter circuits

Modeling Grid Connection for Solar and Wind Energy

Development of High Frequency Link Direct DC to AC Converters for Solid Oxide Fuel Cells (SOFC)

Cree PV Inverter Tops 1kW/kg with All-SiC Design

Solar Inverters. Ferrites in Renewable Energies: Solar Inverters. customer requirements. Support and flexibility to design custom product to fulfill

Design of Solar Power Optimizer And Eliminating Leakage Current In Multi-Level Inverter For PV Systems

Design of High Voltage Low Power Supply Device

Switch Mode Power Supply Topologies

Case Studies in On-Line Measurement of PD in Motors Fed by Voltage Source PWM Drives

An Isolated Multiport DC-DC Converter for Different Renewable Energy Sources

Which is the best PFC stage for a 1kW application?

Design Optimization of Printed Circuit Board Embedded Inductors through Genetic Algorithms with Verification by COMSOL

Application Notes. Magnetics. Determining L min for Buck/Boost Converters

Power Electronics for Renewable Energy Integration into Hybrid AC/DC Microgrids Kai SUN Aug 27, 2015

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Inductor and Magnetic Product Terminology

Understanding Power Impedance Supply for Optimum Decoupling

New Pulse Width Modulation Technique for Three Phase Induction Motor Drive Umesha K L, Sri Harsha J, Capt. L. Sanjeev Kumar

Contactless Power Transfer : Inductive charging of EV

Chapter 10. AC Inductor Design. Copyright 2004 by Marcel Dekker, Inc. All Rights Reserved.

Transcription:

Proceedings of the 6 th ICEENG Conference, 27-29 May, 2008 EE014-1 Military Technical College Kobry El-Kobbah, Cairo, Egypt 6 th International Conference on Electrical Engineering ICEENG 2008 Design and Development of the Middle-Frequency Isolation Transformer for the High-Voltage DC/DC Converter By D. Vinnikov T. Lehtla R. Strzelecki I. Galkin Abstract: Among the performance requirements of railway equipment applied to the 3.0 kv DC catenary-fed auxiliary power supplies (APS), the most significant one is compliance with electric safety requirements. It provides the specific feature for the power circuit topology of APS converter, requiring an isolation transformer to decouple input and output sides (with the isolation voltage at least 12 kv). Since the isolation transformer in switching-mode power supplies contributes about 25 30 % of the overall volume and more than 30 % of the overall weight, the design of a compact and lightweight system will be a great challenge for the designer [1]. This paper is mainly addressed to some specific design issues that are encountered during the development of isolation transformers for the rolling stock APS. For the middle-frequency (500...3000 Hz) highpower transformers, the optimal transformer design rule of the copper and core loss equalization will not work. Main attention here must be paid to select proper material for the magnetic core and to define an optimal operating flux density to minimize the dimensions and to improve operability and efficiency of the transformer, respectively. For the isolation transformers designed for the APS converters with high input voltage and load variations, threat related to magnetic core saturation caused by transient conditions should be considered. These and some other specific design issues (minimization of leakage inductance and parasitic capacitances, high-voltage isolation, etc.) make the design of such devices very challenging. Keywords: Isolated DC/DC converters, auxiliary power supplies for rail vehicles, transformers Tallinn University of Technology, Tallinn, Estonia Gdynia Maritime Academy, Gdynia, Poland Riga Technical University, Riga, Latvia

Proceedings of the 6 th ICEENG Conference, 27-29 May, 2008 EE014-2 1. Introduction: In 2007 during the R&D project an experimental high-voltage half-bridge isolated DC/DC converter based on innovative high-voltage (HV) 6.5 kv IGBT transistors was developed in the Department of Electrical Drives and Power Electronics of Tallinn University of Technology. The layout of the experimental converter power scheme and its general specifications are presented in Fig. 1 [2]. Parameter Continuous minimal input voltage U in(min) Continuous maximal input voltage U in(max) Nominal output voltage U O Rated output power P O Primary inverter switches (TT, TB) Primary inverter switching frequency f sw Value 2400 VDC 4000 VDC 350 VDC 50 kw 2 x IGBT 6.5 kv 200 A (EUPECFZ200R65KF1) 1000 Hz (a) Figure (1): Experimental high-voltage half-bridge isolated DC/DC converter topology (a) and the general specifications of the experimental converter (b) HV IGBT implementation is attractive since it provides an excellent opportunity to simplify a power scheme, avoiding the series connection of conventional IGBTs used to achieve proper voltage blocking capability. Using a single 6.5 kv IGBT module instead of several series-connected IGBTs helps to achieve a more reliable, efficient, compact and lightweight design than ever. However, the limited switching dynamics of HV IGBTs (switching frequency range is 500...3000 Hz) imposes some challenges in the converter design, especially in terms of magnetics. First of all, the isolation transformers and output filter inductors in such applications can be regarded as the bulkiest components in the whole converter stack. For such middle-frequency (MF) operation range, the highest possible values of permeability (µ н ) and saturation magnetic induction (В max ) of the isolation transformer magnetic core material is essential, because it gives an additional advantage for weight-space optimization of the transformer. Other possible problems are connected to the behavior of the isolation transformer in transient conditions, i.e. during the rapid change of the input voltage or/and load within the defined ranges, where the threat of transformer saturation is arising. Finally, the designer must provide the most cost-effective solution at high efficiency to meet the end-user requirements. (b)

Proceedings of the 6 th ICEENG Conference, 27-29 May, 2008 EE014-3 2. Isolation Transformer Operating Parameters: The input side of the experimental converter is directly connected to the traction supply grid with the voltage tolerances from 2400 VDC up to 4000 VDC (see Fig. 1). Due to the capacitors C1 and C2 providing a mid-voltage point, the isolation transformer during the operation sees a positive and negative voltage with the amplitude value U Ia of only half the input voltage (see Fig. 2). This results in twice the desired peak flux value of the core, because the transformer core is operated in the first and third quadrant of the B-H loop and experiences twice the flux excursion of a similar forward converter core. This is an advantage of the half-bridge topology over the double-ended forward topologies, where the half-bridge primary transformer winding has half the turns for the same input voltage and power. Figure (2): Simulated isolation transformer primary voltage and current waveforms The most demanding operation point is at the minimum input voltage and at the rated load conditions (i.e., maximum duty cycle operation). It is essential to prevent even short-time simultaneous conduction of TT and TB switches in these demanding conditions - it leads to the short circuit across the supply voltage and to the destruction of the converter. It means that the maximum on-state time t on(max) of each switch in the half-bridge must be set at 80 % of a half-period (T sw ) to ensure that this does not happen. Pulse width at the maximum input voltage is minimal and may be determined as U in(min) 2400 Tsw t = t = t = 0.44. (1) on(min) on(max) on(max) U 4000 2 in(max)

Proceedings of the 6 th ICEENG Conference, 27-29 May, 2008 EE014-4 Thus the isolation transformer must operate normally in the wide supply voltage range (1100...2000 V) with the constantly changing duty cycle. Simulated waveforms of isolation transformer primary voltage in the boundary operating points are presented in Fig. 3. (a) (b) Figure (3): Isolation transformer primary voltage waveforms for maximum (a) and minimum (b) duty cycle operation For the described application, the converter output voltage must be carefully regulated to 350 V DC despite the voltage fluctuations on the input side. Considering the voltage drop in the output rectifier and filter assembly (U drf ), the required amplitude value of the transformer secondary voltage U IIa in the most demanding applications (i.e. minimum input voltage and the rated load conditions - operation with the maximum duty cycle) can be estimated as Tsw U IIa = U O + U drf. (2) 2 t on 3. Specific Problem Areas and Design Considerations: For such low operating frequency (i.e., 500...3000 Hz) the higher possible values of permeability (µ н ) and saturation magnetic induction (В max ) of the magnetic core material is essential, because it gives an additional advantage of transformer weight-space optimization. Table 1 provides a comparison of different soft magnetic materials. The basic field of choice in such operation frequency range is iron steel and Permalloy. However, despite its good magnetic properties the latter has a drawback of increased magnetostriction. Another drawback of Permalloy type alloys is associated with their softness in that flat particles are liable to deform by stresses induced during milling to form a coating composition, also resulting in a loss of magnetic properties. Ferrites are

Proceedings of the 6 th ICEENG Conference, 27-29 May, 2008 EE014-5 not considered for such high-power low-frequency operation because of their relatively low permeability and saturation magnetic induction. Table (1): Magnetic properties of some soft magnetic materials В MAX, T µ Н µ MAX Permalloy 0.70...0.75 14000...50000 60000...300000 Silicon steel 2 200...600 3000...8000 Ferrites 0.18...0.40 100...6000 3000...10000 Iron 2.16 250 7000 GAMMAMET 0.8...1.12 7000...20000 40000...600000 For this project, advanced GAMMAMET toroidal magnetic cores made from 25 μm thick ribbon of soft magnetic nanocrystalline alloy on Fe-basis were investigated. The real advantages of the selected toroidal magnetic cores Gm14DC are their high initial permeability and very low core losses [3], [4]. Typical specifications of Gm14DC magnetic cores are presented in Fig. 4. Saturation magnetic induction 0.8 T Saturation magnetostriction 1.5 10-6 Initial permeability 20000 Maximum permeability 50000 Coercive force 2.5 A/m Electrical resistivity 1.25 10-6 Ω m Density 5200 kg/m 3 Specific core losses (f < 3 khz) P = 1.4 1.7 D( core) 0. 75 f BM (a) (b) Figure (4): B-H loop (a) and typical magnetic and physical properties (b) of GAMMAMET 14 DC magnetic cores In general, the design approach for the half-bridge converter isolation transformer is relatively simple. The primary winding is used for both half-cycles of operation (using both quadrants of the B-H loop, see Fig. 4, a), providing extremely good transformer core and copper utilization. The pulse transformer core volume V m should be selected to meet the power requirements and temperature rise for the selected operating frequency: A k ADD k T P Vm = 1.5, (3) 1 k U 4 f ΔT where P is the transformer rated power, k T is the temperature coefficient of winding resistance, k U is the window utilization factor, ΔT is transformer temperature rise and A

Proceedings of the 6 th ICEENG Conference, 27-29 May, 2008 EE014-6 is the specific core loss factor: 3 α 2 β 2 α β D(core) f Bm (f ) (Bm ) A = P. (4) Figure 5 gives an overview of specific core losses and minimal required core volume vs. operating flux density for the different operating frequencies for the 50 kw isolation transformer with GAMMAMET 14DC toroidal core. Specific Core Losses [W/cm 3 ] 40 35 30 25 20 15 10 5 0 500 1000 1500 2000 2500 3000 Operating Frequency [Hz] Bm=0.3 Bm=0.4 Bm=0.5 Bm=0.6 Bm=0.7 Bm=0.8 (a) Core Volume [cm 3 (x10 3 )] 17,5 15 12,5 10 7,5 5 2,5 Temperature rise ℵT=50 C, window utilization K U =0.25 0 500 1000 1500 2000 2500 3000 Operating Frequency [Hz] Bm=0.3 Bm=0.4 Bm=0.5 Bm=0.6 Bm=0.7 Bm=0.8 Figure (5). Specific core losses (a) and minimal required core volume (b) vs. operating flux density as a function of operating frequency for the 50 kw isolation transformer with GAMMAMET 14DC magnetic core (b) In the isolated DC/DC converters with a wide input voltage and load variations with the increase of input voltage, the on-state time (pulse width) of the switch will normally decrease in the same ratio to maintain the output voltage constant. Under these conditions the peak flux density of the isolation transformer core remains constant at some certain designed value. However, under several transient conditions (rapid load changes, unstable supply from the contact line, etc.), it is possible for the pulse width to increase to its maximum irrespective of the input voltage. This can occur at maximum input voltage. The increase in the flux density at maximum input voltage will follow the same ratio as the increase in voltage. The operating flux density would abruptly increase to 30...50% from the predefined value, thus overcoming the saturation limit. For the saturation prevention, the isolation transformer for such applications must be designed for the lower flux level. However, such conservative design approach results in a lowerefficiency transformer, because more turns are required (see Fig. 5, a). Another issue to be taken into account during the design procedure is that the operating flux excursion ΔB in a non-ideal case may not always be 2B [5]. Thus, during the converter turn-on the operation point of the core flux density is normally lies between two remanent flux values. Hence, for the first half-cycle, the flux doubling effect could occur, i.e. a flux change of 2B may take the core into saturation. The isolation transformer core

Proceedings of the 6 th ICEENG Conference, 27-29 May, 2008 EE014-7 saturation will also occur in a half-bridge converter due to the mid-voltage point shift, which can be caused by the input capacitor mismatch. The solution to these problems is to reduce the operating flux range ΔB and use more turns in the primary winding in order to provide a good working margin. The margin required depends on how well the above effects have been controlled. 1100 99,7 880 99,3 Losses [W] 660 440 220 98,9 98,5 98,1 Efficiency [%] 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 Operating flux density [T] Core losses Copper losses Transformer efficiency 97,7 Figure (6): 1 khz isolation transformer losses and efficiency as a function of operating flux density 4. Experimental Verification: During the project the experimental toroidal transformer based on above presented approach was assembled and tested. General view of the developed transformer is presented in Fig. 7. Figure (7): General view of the developed 50 kw 1 khz isolation transformer Measured waveforms of isolation transformer primary voltage in the boundary operating points are presented in Fig. 8.

Proceedings of the 6 th ICEENG Conference, 27-29 May, 2008 EE014-8 1 > 1 1 > 1 1) Ch 1: 2: 0.41 kvolt 250us us 1) Ch 1: 2: 0.61 kvolt 250us us Figure (8): Isolation transformer supply voltage measured waveforms for maximum (a) and minimum (b) duty cycle operation 5. Conclusions: Considering the above assumptions, the design of middle- or high-frequency isolation transformers for the high-power high-voltage converters is always a tradeoff between operability, flexibility and efficiency. In the current project the average core power dissipation for the 1 khz 50 kw isolation transformer is about 35 W with the assumed maximum flux density of 0.6 T. Estimated winding losses for this particular design (special litz wire was used in both windings) are not higher than 190 W. Magnetic core losses; 35W (16% ) Primary winding losses ; 105W (46% ) Secondary winding losses; 85W (38%) Figure (9): Power loss distribution in the developed isolation transformer With the total power dissipation of 225 W (Fig. 9), the efficiency of the developed 1 khz 50 kw transformer is 99.5 %, which is a quite good result for such a demanding application.

Proceedings of the 6 th ICEENG Conference, 27-29 May, 2008 EE014-9 Acknowledgement: Authors thank Estonian Science Foundation (Grant No. 7572) for financial support of this study. References: [1] R. Petkov, Optimum design of a high-power, high-frequency transformer, IEEE Transactions on Power Electronics, vol. 11, issue 1, pp. 33-42, 1996. [2] T. Jalakas, D. Vinnikov, J. Laugis, Development of 50-kW Isolated DC/DC Converter with High-Voltage IGBTs, in Proc. of IEEE Compatibility in Power Electronics Conference CPE '07, pp.1-6, 2007. [3] Y. N. Starodubtsev, V. I. Keilin, V. Y. Belozerov, Cores of Fast-Quenched GAMMAMET alloys with a linear magnetization curve, Russian Electrical Engineering, ISSN1068-3712, ETATS-UNIS, 1993. [4] Magnetic Properties of Tape Wound Encapsulated Cores GAMMAMET 14DC, GAMMAMET Research & Production Enterprise, 2007. [5] K. H. Billings, Switchmode Power Supply Handbook. McGraw-Hill, 1989. [6] J.C. Fothergill, P.W. Devine, P.W. Lefley, A novel prototype design for a transformer for high voltage, high frequency, high power use, IEEE Transactions on Power Delivery, vol. 16, issue 1, pp. 89-98, 2001. [7] Gunewardena, S.; Archer, W.E.; Sanchez, R.O.: High voltage miniature transformer design. In. Proc. Electrical Insulation Conference and Electrical Manufacturing & Coil Winding Conference, pp.:141-147, 2001. Nomenclatures: µ н...permeability В max...saturation magnetic induction t on(max)..switch maximum on-state time t on(min)..switch minimum on-state time T sw...switching period U Ia...Amplitude value of isolation transformer primary voltage U drf...voltage drop in the output rectifier and filter assembly U IIa...Amplitude value of isolation transformer secondary voltage P...Rated power of the transformer k T...Temperature coefficient of winding resistance k U...Window utilization factor ΔT...Transformer temperature rise A...Specific core loss factor