6424 Projected Beam Type Smoke Detector

Similar documents
FIRERAY 2000 Installation Guide

Wireless Indoor/ Outdoor Thermometer

Detector transparent with Color Inserts. FAA 500 TR P Trim Ring transparent with Color Inserts. FCA 500 / FCA 500 E Detector Bases

D7050/D7050TH. Installation Instructions. Multiplex Photoelectric Smoke Detectors

LED Security Spotlight User Manual

Indoor/Outdoor Color Camera with Built-in 2.4 GHz Wireless Transmitter, plus X10 controlled power supply, and Video Receiver.

This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules.

Installer Guide smart connect

BroadBand PowerShield. User Manual

SCREENLOGIC INTERFACE WIRELESS CONNECTION KIT

NFC Communication Tray Model: HHX-IT3-Z

CMD-8000 rev. A COMMANDER SERIES REMOTE CONTROL ENTRY SYSTEM

4.3-inch Back-Up Camera

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE

E-PDD Duct Smoke Detector Installation Sheet

USB/VGA Cat 5 UTP Console Extender

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

PC Tab Security System INSTRUCTION MANUAL

Daily use. Never use alcohol or other solvents to clean any part of the loudspeakers!

ADSL Modem Installation Guide. Model # 36R515 Part # Rev. D Revision Date 12/2000. ADSL Modem Installation Guide

Model Owner s Manual. Español - P. 19 Français - P. 39

LF-IRX. Limited Warranty LF-IRX. Remote Control Extender OWNER S MANUAL

ScreenLogic Wireless Connection Kit. Installation Guide. pool/spa control system

e-ask electronic Access Security Keyless-entry

Table of Contents Function Keys of Your RF Remote Control Quick Setup Guide Advanced Features Setup Troubleshooting

Installation & Operation Manual

FCC COMPLIANCE STATEMENT

StructureScan HD Module. Installation Guide ENGLISH

INSTALLATION GUIDE ConnectLine TV Adapter Getting started

Wireless Alarm System. Panic Button. User s Manual. Choice ALERT. Control all sensors, accessories and remote transmitters from one location

Alarm Clock USER GUIDE

WIRELESS STATUS MONITOR

When you switch off your system, or mute the sound, the red indicator light appears immediately, indicating that the subwoofer is not in use.

Part I - Installation

PrintPAD CN3/4/3e/4e. User Guide

Dialog Telephone Interface Module Installation Sheet

AXIS T81B22 DC 30W Midspan

Dome Security Camera with IR night vision

Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide

Installation and Operation Manual. Digital Remote Meter for Monitoring System Performance. Version: RM-1

Model 70A00-1. GSM Cellular Communications Center

Wireless Base Station Single and Multiple Headsets

RI-215A Operator s Manual. Part Number: RK Revision 0 Released: 10/3/05

PUSH BUTTON START INSTALLATION MANUAL

User Guide for the Kidde RemoteLync. Remote Notification Device

XTEND 900 MHZ WIRELESS MODEM For use with VEEDER-ROOT EMR³ DATALINK INSTALLATION INSTRUCTIONS Manual , Rev. B

ATS Overhead Table Shelf System INSTRUCTION MANUAL

Model: Manual DC: WIRELESS COLOR FORECAST STATION

BeoLab 1. User s guide

Andersen Electric Window Opener for Andersen Awning and Roof Windows

SP1790JK 900MHz Wireless Indoor/Outdoor Speakers. User Manual INTRODUCTION FEATURES IMPORTANT SAFETY INFORMATION

Wireless Alarm System. Wireless Keypad. User s Manual. Choice ALERT. Control all sensors, accessories and remote transmitters from one location

INSTALLATION/PROGRAMMING INSTRUCTIONS 928 ENTRYCHECK

Intelli-Time Alarm Clock model 13027

LevelOne IFE Port PoE + 1-Port TP Industrial Fast Ethernet Switch User Manual

NX-591NE-GSM NetworX GSM 3G HSPA+ Module Installation Sheet

INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930

FN2001-A1 Network module (SAFEDLINK) Mounting Installation

Installation & Operation Manual HANDS-FREE BLUETOOTH MEDIA INTEGRATION KIT. Perfect for ANDROID TM

ANT1750F Multi-Directional Slim Digital Antenna / Antena multidireccional plana para interiores / Antenne numérique mince multidirectionnelle

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W

Manual. Simrad StructureScan LSS-1 Sonar Module. English

25 Code GTO Digital Keypad

TWIN EAGLES ALL WEATHER ELECTRIC RADIANT HEATER

Advantium 2 Plus Alarm

SECTION FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

CINEMATE 1 SR DIGITAL HOME THEATER SPEAKER SYSTEM. Operating Guide Guía del usuario Guide d utilisation

On/Off Relay Switch and 3-Way Switch Kit

DTM04 TANK MONITOR DTM08 TANK MONITOR Dtm12 TANK MONITOR. Installation and Operation Manual

VARIO PROX CARD READER INSTALLATION MANUAL

SATA and SAS Hard Drive Backplane

e-4 AWT07MLED 7 Q TFT LCD MONITOR (LED Backlighted) USER MANUAL

user s manual Battery Case model #: SPB3200 Battery Case Charger for Samsung Galaxy S 4

Operating Instructions

BOSE. Link AL8 HOMEWIDE WIRELESS AUDIO LINK

Business Audio System: Music & Messaging MP3 Player. by Grace Digital Audio. User Guide. Model No. GDI-USBM10

Rev E October 2004 ZZZ*(6HFXULW\FRP. Part No: R. CareGard. User Guide

RC8021 Indoor Camera Installation Guide

For the US-market only! CAUTION: To reduce the risk of electric shock, do not remove cover (or back). No User-serviceable parts

Square D Clipsal C-Bus Network Analyzer

Residential Gateway (RG) Battery Backup REV B

Radiant Temperature Sensor TY7321

7 High-Resolution Digital Photo Frame

Conference Phone UserÕs Manual. Part No R1 Printed in Korea Bogen Communications, Inc.

BeoLab 7-1 BeoLab 7-2. Guide

Manual for Fire Suppression & Methane Detection System

Application and Instruction Manual Motion Activated Solar Powered LED Security Light with Camera MODEL: XP-2H38WC

16/32 Channel 1U Rack Mount CCTV Power Supply

Utility Distribution Systems

Weather Radio Alarm Clock

Wireless Alarm System. Window/Door Sensor. User s Manual. Choice ALERT. Control all Sensors & accessories from one location

3.5 mm Audio Jack. Manual innoxplore ix B24 A2DP Stereo Bluetooth Audio Adapter Dongle 3.5mm Audio Jack [ix B24] Contents

Installation Manual. Features SMART SWITCH OCCUPANCY SENSOR. Maximum Energy savings

Caller-ID on your TV!

Model SRMD Setra Remote Monitoring Display

TS93 EMR T/PT/TDE. Surface applied door closer

EF-S18-55mm f/ IS II COPY ENG. Instruction

PASSIVE INFRARED INTRUSION DETECTOR PASSIVE INFRAROOD DETECTOR DETECTEUR D INTRUSION PASSIF INFRAROUGE

DCMT-2500 Wireless Transmitter. Owner s Manual

ALPHA Meter Installation Information

Transcription:

INSTALLATION AND MAINTENANCE INSTRUCTIONS 6424 Projected Beam Type Smoke Detector A Division of Pittway 3825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 630-377-6495 Specifications General Range: 30 to 330 Feet Sensitivity: 30% ± 5% Total Obscuration, or 55% ± 5% Total Obscuration Response Time: Alarm: 15 Seconds Max. Trouble: 15 Seconds Max. Trouble Condition: 95% or More Obscuration Improper Initial Alignment Self-compensation limit reached (service needed) Test/Reset Features: Obscuration Filters (ALARM/NO ALARM) Local Alarm Reset Switch Remote Test and Reset Switch Capability (compatible with RTS451 Test Station with Magnet) Indicators: Alarm: Remote Output, Local LED (red) Trouble: Remote Output, Local LED (yellow) Normal Operation: Local LED (flashing green) Alignment Aid: LED Bar Graph (4 red LEDs) Relays: Alarm; Trouble Environmental Temperature: 30 C to 55 C ( 22 F to 131 F) Humidity: 10% to 93% RH Noncondensing Mechanical Weight: Receiver: 1.5 lbs (663 g) Transmitter: 1.3 lbs (598 g) Mounting: Ceiling or Wall, Separate Mounting Brackets Provided Wiring: Plug with Attached Cable Adjustment Angle: Ceiling: ± 30 Horizontal/60 Vertical Wall: ± 90 Horizontal/60 Vertical Electrical (Receiver) Voltage: 20 to 32 VDC Maximum Ripple Voltage: 6.0 volts (Peak-to-peak) Current (24 VDC): Avg. Standby: 10mA Max. Avg. Alarm: 28.4mA Max. Avg.Trouble: 27.1mA Max. Start-up Surge: 19mA Max. Relay Contacts:.5A at 30 VAC/DC Reset Time:.6 Seconds Max. Start-up Time (after 5 min. reset): 1 Minute Maximum Power Loss: Retain Memory for 5 Minute Minimum Electrical (Transmitter) Voltage: 18.8 to 32 VDC Maximum Ripple Voltage: 5.6 volts (Peak-to-Peak) Avg. Current (24 VDC): 10mA Max. D400-18-00 1 I56-494-11R

Before Installing Please thoroughly read this manual and applicable sections of System Sensor s Manual I56-506, Guide for Proper Use of Projected Beam Detectors. Copies of this manual are available from System Sensor. General Description System Sensor Model 6424 is a long range projected beam smoke detector designed to provide open area protection. It is to be used with UL-listed, separately supplied power (4- wire) control panels only. The detector consists of a separate transmitter and receiver. Smoke entering the area between the transmitter and receiver causes a reduction in signal at the receiver. When the obscuration reaches one of two predetermined thresholds (chosen with a switch in the receiver), the detector generates an alarm signal. Complete blockage of the beam causes a trouble signal to avoid false alarms. Slow changes in obscuration due to a build up of dirt or dust on the lens of the detector are compensated for by a microcontroller which continuously monitors the signal strength and periodically updates the alarm and trouble thresholds. When the self-compensation circuit reaches its limit, the detector generates a trouble signal, indicating the need for service. Three LEDs at the receiver indicate the status of the detector: a red LED for alarm, a yellow LED for trouble, and a pulsed green LED for standby operation. The alarm signal latches and can be reset by a momentary power interruption, by using the remote reset input to the receiver if using the remote test/reset station model RTS451, or with the local reset button located behind the rear door in the receiver. A trouble signal automatically resets upon removing the cause of trouble. In addition to these indicators, there are four LEDs on both the receiver and the transmitter which are used as a beam alignment aid. No additional equipment is needed for alignment of the beam. Each detector contains one Form A (normally open) contact for alarm signals and one Form B (normally closed) contact for trouble signals. Supervision of power is accomplished by installing a Power Supervisory End-of-Line Relay Module (model A77-716) at the end of the detector power loop. When power is applied to and through the detectors, the EOL Power Supervisory Module is energized. The relay contacts, along with the detector s trouble relay contacts, can provide a closed series circuit in the control panel s alarm-initiating loop. A loss in power or a trouble condition at the detector causes the respective EOL or trouble relay to open, resulting in a trouble signal at the control panel. Parts List Description Quantity Receiver Unit 1 Transmitter Unit 1 Receiver Wiring Cable 1 Transmitter Wiring Cable 1 Wall Mounting Bracket 2 Ceiling Mounting Bracket (inside part) 2 Ceiling Mounting Bracket (outside part) 2 Wall Bracket Screw 2 Ceiling Bracket Screw 2 Washers 4 Allen Wrench 1 Instruction Manual 1 Test Filter 1 Cable Exit Plug 1 Hole Plug 1 Detector Placement This section of the manual discusses the placement of projected beam detectors. Though this information is based upon industry expertise, it is intended to be used only as a technical guide. Always comply with the requirements of applicable codes and standards such as, NFPA 72, National Fire Alarm Code, as well as directives of the Authority Having Jurisdiction (AHJ). For general information on the placement of detectors, read System Sensor s Manual I56-506, Guide for Proper Use of Projected Beam Detectors. Projected beam detectors are usually located with their beams parallel to the ceiling. However, they can be mounted vertically or at any angle to protect the area involved. Since beam detectors sense the smoke buildup over a distance, they are ideal for locations with high ceilings. They can also be mounted on a wall or ceiling below the level of a spot type detector, reducing the effects of air stratification. Some typical locations would include large areas with high ceilings such as atriums, warehouses, and factories. NOTE: Projected beam smoke detectors should always be mounted to stable mounting surfaces. See the MOUNTING LOCATION section for details. Some fire codes specify spacing on a given center-to-center distance between detectors under ideal conditions. These spacings are based on rooms with smooth ceilings and no physical obstructions between the contents being protected and the detectors. Moreover, they are also based on a maximum ceiling height, and on the assumption that the value and the combustible nature of the contents of the room being protected do not warrant greater protection or closer spacing. D400-18-00 2 I56-494-11R

In a room with a smooth ceiling, detectors should be spaced between 30 and 60 feet. One-half that spacing between the beam and the sidewall may be used as a guide. See Figure 1. The beam detector can be mounted with the receiver on one wall and the transmitter on the opposite wall, or both suspended from the ceiling, or any wall/ceiling combination. In the case of the ceiling mount, the distance from the end walls should not exceed one-quarter of the selected spacing (7.5 ft. maximum if the spacing is 30 ft.). See Figure 2. Figure 3. Sloped ceiling (shed type): 3 FT. MAX. S S 1/2 S MAX. Tx Rx Figure 1. Spacing for smooth ceiling (side view): 1/2 S S Figure 4. Sloped ceiling (peaked type): A78-2036-01 1 FT. MOUNT DETECTOR ANYWHERE IN THIS AREA WALL Tx Rx A78-2037-00 Figure 2. Spacing for smooth ceiling (top view): 1/4 S MAX. TX 1/2 S MAXIMUM RX 3 FT. MAX. S 1/2 S 1/2 S S 3 FT. MAX. S A78-2035-01 TX RX 30 FEET MINIMUM 330 FEET MAXIMUM A78-2039-00 In the case of peaked or sloped ceilings, codes may specify spacing of detectors by using horizontal spacing from the peak of the roof or ceiling. Figures 3 and 4 show the spacing for both the shed type and peaked type sloped ceilings. Mounting Locations Beam detectors require a stable mounting surface for proper operation. A surface which moves, shifts, vibrates, or warps over time will cause false alarm or trouble conditions. Initial selection of a proper mounting surface will eliminate false alarms and nuisance trouble signals. Mount the detector on a stable mounting surface, such as brick, concrete, a sturdy load-bearing wall, support column, structural beam, or other surface that is not expected to experience vibration or movement over time. DO NOT MOUNT the beam detector on corrugated metal walls, sheet metal walls, external building sheathing, external siding, suspended ceilings, steel web trusses, rafters, nonstructural beam, joists, or other such surfaces. D400-18-00 3 I56-494-11R

Figure 5. Good and poor mounting surfaces: Poor Mounting Surface Sheet Metal Poor Mounting Surface ;Concrete or Brick Good Mounting Surface Good Mounting Surface Mounting Brackets Install a ceiling or wall bracket for both the receiver and transmitter so that when mounted, the receiver and the transmitter will be at approximately the same height. Each ceiling bracket is composed of two parts that should be assembled with inside part between the ceiling and outside part as shown in Figure 5. The brackets should be mounted so that the slot in the front of each bracket is facing the other bracket. Mount the brackets only on solid structures of the building. To avoid unwanted alarms due to wall movement, do not mount to flexible walls, such as sheet metal walls (see MOUNTING LOCATIONS). Mount brackets with a separation of at least 30 feet but not more than 330 feet. Figure 6. Ceiling mouting bracket assembly: CEILING INSIDE PART SLOT IN FRONT OF BRACKET OUTSIDE PART A78-2652-00 Wiring Installation Guidelines Always install all wiring in compliance with the National Electrical Code, and/or the applicable local codes, and any special requirements of the local authority having jurisdiction. Proper wire gauges and suitable means for strain relief should be used. The conductors used to connect beam smoke detectors to control panels and accessory devices should be color-coded to reduce the likelihood of wiring errors. Improper connections can prevent a system from responding properly in the event of a fire. Installation wire used for the beam detector shall be no smaller than 18 gauge (1.0 square mm). For best system performance, all wiring should be twisted pair and installed in separate grounded conduit. Do NOT mix fire system wiring in the same conduit as any other electrical wiring. Shielded cable may be used to provide additional protection against electrical interference. When installing the beam smoke detector in applications where flexible conduit will be used the BMB Beam Mounting Bracket kit must be installed with the cable before wiring the unit, as per the instructions supplied with the kit. For applications that require flexible conduit to be mounted to the beam smoke detector, the model BMB kit can be ordered separately. In those applications where the model BMB kit is not used, the two connectors with attached cable (6 conductor for the transmitter and 16 conductor for the receiver) can be wired before the detector is mounted. CEILING SCREWS A78-2041-01 For wiring, first remove the pre-cut insulation from the conductor to be connected, then use a wire nut to connect the detector wire to the field wire. If the insulation has been removed from any unused conductors, make sure they are terminated properly to avoid short circuits. The transmitter can be wired in one of two ways. Figure 7 shows the transmitter permanently connected to the receiver. In this case the transmitter receives its power along with communication for the alignment aid through the connecting pair of D400-18-00 4 I56-494-11R

wires. Figure 8 shows an alternative wiring configuration in which the transmitter receives its power from a remote power source. Temporary wiring can be installed for the communication needed for transmitter alignment aid. If the remote power configuration is used, the remote power source must comply with all codes and directives of the Authority Having Jurisdiction. NOTE: The transmitter should be permanently wired to the receiver (Figure 7) whenever possible to allow the alignment LEDs on the transmitter to be used during the alignment procedure. Figure 9 shows the remote outputs for trouble and alarm, while Figure 10 shows the connection necessary for using the remote test station (RTS451 or RTS451KEY). Figure 7. Transmitter permanently wired to receiver: CLASS A RETURN LOOP YELLOW RED YELLOW RED INITIATING LOOP POWER TO DETECTORS BLACK WHITE RED-WHITE BLACK ORANGE RECEIVER GRAY VIOLET VIOLET BROWN BLACK WHITE RED-WHITE GRAY BLACK BROWN RECEIVER ORANGE VIOLET VIOLET EOL RESISTOR LISTED EOL POWER SUPERVISION RELAY MODULE (SHOWN ENERGIZED) LISTED PANEL BLUE BLUE NOTE: FOR PROPER SUPERVISION, AN EOL RELAY MUST BE USED. A78-2043-00 TRANSMITTER TRANSMITTER Figure 8. Transmitter powered separately: CLASS A RETURN LOOP YELLOW RED YELLOW RED INITIATING LOOP POWER TO DETECTORS BLACK WHITE RED-WHITE BLACK ORANGE RECEIVER GRAY VIOLET VIOLET BROWN BLACK WHITE RED-WHITE BLACK ORANGE RECEIVER GRAY VIOLET VIOLET EOL RESISTOR BROWN LISTED EOL POWER SUPERVISION RELAY MODULE (SHOWN ENERGIZED) OPTIONAL TEMPORARY WIRING FOR TRANSMITTER ALIGNMENT AID. BLACK RED BLACK RED LISTED PANEL LISTED REMOTE POWER SOURCE BLUE POWER TRANSMITTER INPUTS TO TRANSMITTER ARE NONPOLAR WHITE BROWN BLUE TRANSMITTER NOTE: FOR PROPER SUPERVISION, AN EOL RELAY MUST BE USED. A78-2042-00 D400-18-00 5 I56-494-11R

NOTE: The test coil which is shipped with the RTS451 and RTS451KEY is not used on the 6424 Beam Smoke Detector. Figure 9. Remote annunciators: POWER (+) POWER ( ) ALARM SIGNAL TROUBLE SIGNAL AUX ( ) 6424 REMOTE OUTPUTS Figure 10. Remote Test Station: ALARM SIGNAL AUX ( ) BROWN ORANGE BROWN ORANGE 1 2 A78-2040-00 2. Mount brackets and connect cables properly as detailed above. (In any applications where the BMB Beam Mounting Bracket kit is used, the kit should be installed before the detector is mounted. Instructions for mounting the BMB are included in the BMB kit.) 3. Insert the flange of the detector mounting bracket into the keyed hole of the wall or ceiling mounting bracket. Slide the detector forward into position. The detector should now hang from the bracket. 4. Insert the correct screw and washer combination (either wall or ceiling mount) through the slot and into the hole of the mounting bracket flange. Tighten the screw until almost snug. The detector should still turn easily in both directions. 5. Open the sliding access door on the back of the unit. 6. Plug cable connector into slot in metal barrier, observing proper orientation (see Figures 14 and 15). 7. Repeat for the other unit. 8. IMPORTANT: If the detector spacing is between 30 and 60 feet, the additional filter (included) must be attached to the receiver lens. Peel the protective backing off the filter and install as shown in Figure 11. Figure 11. Additional filter required for installations with 30 to 60 Ft. spacing only: 4 RESET YELLOW 3 Additional Lens TEST BLUE 5 6424 RTS451 OR RTS451KEY REMOTE TEST STATION A78-2038-01 Installation Reference Figures 11 through 17 for installation, alignment, and maintenance. Receiver A78-2651-00 WARNING Disconnect the power from the initiating device circuits before installing the detectors. 1. The clear protective film and warning label on the smoked lens of both the receiver and transmitter MUST be removed before they can operate. To remove them, grasp a free corner of the clear protective film and pull so that both the film and the warning label are peeled from the smoked glass lens. D400-18-00 6 I56-494-11R

Figure 12. Wall mounting: HORIZONTAL ADJUSTMENT SCREW (#10-24 x 1-3/8 in.) METAL WASHER PLASTIC WASHER MOUNTING HOLE MOUNTING HUB WALL MOUNTING BRACKET ALIGNMENT LEDs U BRACKET VERTICAL ADJUSTMENT SCREWS (2) STATUS LEDs (RECEIVER ONLY) CABLE EGRESS HOLE PLUG. USED TO PLUG UNUSED HOLE. BEAM LENS ALIGNMENT ADJUST POTENTIOMETER (RECEIVER ONLY) HOLE PLUG A78-2034-01 Figure 13. Ceiling mounting: HORIZONTAL ADJUSTMENT SCREW (#10-24 x 2-1/4 in.) METAL WASHER PLASTIC WASHER CEILING MOUNTING BRACKET MOUNTING HUB MOUNTING HOLES ALIGNMENT LEDs U BRACKET VERTICAL ADJUSTMENT SCREWS (2) STATUS LEDs (RECEIVER ONLY) CABLE EGRESS HOLE PLUG. USED TO PLUG UNUSED HOLE. BEAM LENS ALIGNMENT ADJUST POTENTIOMETER (RECEIVER ONLY) HOLE PLUG A78-2033-01 D400-18-00 7 I56-494-11R

Figure 14. Rear view receiver: ACCESS DOOR SENSITIVITY SELECT SWITCH 30 55 ALIGNMENT MODE SWITCH 16 CONDUCTOR CABLE N A RESET SWITCH CONNECTOR A78-2032-01 Figure 15. Rear view transmitter: ACCESS DOOR ALIGNMENT MODE SWITCH A N 6 CONDUCTOR CABLE SW1 CONNECTOR RANGE SELECT SWITCH L S SW2 A78-2031-01 D400-18-00 8 I56-494-11R

Alignment Figure 16. Front View Transmitter and Receiver RECEIVER: ING LOCATIONS) and alignment procedures are executed properly, false alarms and nuisance trouble signals will be avoided. The alignment procedure is best accomplished by two individuals. This allows the adjustment of the gain pot on the receiver during alignment of the transmitter without the need for several trips back and forth between the transmitter and receiver. NOT USED TRANSMITTER: : FLASHES APPROXIMATELY EVERY 2 SECONDS IF POWERED UP AND SENSING A SAFE CONDITION. YELLOW: TURNS ON WHILE A TROUBLE CONDITION EXISTS. RED: TURNS ON IF AN ALARM CONDITION IS SENSED. LATCHES ON UNTIL RESET. 4 RED LEDs USED FOR ALIGNMENT A) ALIGNMENT SETUP: 1) At the transmitter, select the proper range using the range selection switch (SW2) on the transmitter. Short Range (S): 30 to 100 feet Long Range (L): 100 to 330 feet 2) If the transmitter is directly wired to the receiver (Figure 7), slide the alignment switch (SW1) on the transmitter to the A (align) position (see Figure 15). Point the transmitter directly at the receiver, then go to step 5. A78-2320-00 Figure 17. Alignment adjust pot (receiver only): ALIGNMENT LEDs 3) If the transmitter is wired directly to a power supply, it should be temporarily wired to the receiver if possible (see Figure 8). NOTE: Temporarily wiring the transmitter to the receiver is beneficial because it activates the alignment LEDs on the transmitter to allow alignment of the transmitter without having to look at the alignment LEDs on the receiver. MAX. MIN. 4) If the transmitter is not wired directly to the receiver, make sure the SW1 switch remains in the N (normal) position (see Figure 15) before going to step 5. Point the transmitter directly at the receiver. ALIGNMENT ADJUST POT (RECEIVER ONLY) 5) At the receiver, select the proper sensitivity using the switch on the back of the receiver (see Figure 14). The sensitivity selected depends on the separation of the transmitter and receiver. The sensitivities and ranges shown are in accordance with UL standard 286, Smoke Detectors for Fire Protective Signaling Systems. CAUTION A78-2339-00 The clear protective film and warning label on the smoked lens of both the receiver and transmitter MUST be removed before they can operate. The alignment of the 6424 is divided into three steps: alignment setup, alignment of the transmitter, and alignment of the receiver. It is necessary for all three steps to be executed properly to ensure proper alignment of the product. If the 6424 is mounted to a recommended surface (see MOUNT- SENSITIVITY DISTANCE 30% 30 to 92 feet 30% or 55% 92 to 178 feet (30% is more sensitive) 55% 178 to 330 feet 6) Using a small standard screwdriver, make sure the alignment adjust pot on the receiver (see Figure 17) is turned fully counterclockwise, looking at it from the bottom (maximum gain). The alignment adjust pot changes the gain of the amplifier to compensate for differences in separation between the receiver and transmitter and has no effect on the detector sensitivity. D400-18-00 9 I56-494-11R

7) Turn on power to the system. 8) Slide the alignment switch on the receiver to A (see Figure 14). The yellow trouble LED should light to indicate alignment mode, but the trouble relay will not activate. If the receiver is left in the alignment mode for more than an hour, the trouble relay will activate. 9) Point the receiver directly at the transmitter. B) RECEIVER ALIGNMENT PROCEDURE: 1) Align the receiver by slowly moving it back and forth, and up and down until all four LEDs light. (NOTE: If it is impossible to get all four LEDs to light, the transmitter may need to be adjusted. Go to the transmitter and align it so that all four LEDs light, and then go back to the receiver and continue with step 2.) 2) Adjust the alignment adjust pot until only three alignment LEDs are lit. 3) Further align the receiver by slowly moving it back and forth, and up and down, trying to get all four LEDs to light. REPEAT STEPS 2 AND 3 UNTIL IT IS IMPOSSIBLE TO GET MORE THAN THREE LEDs TO LIGHT. (NOTE: If steps 2 and 3 are carefully executed, it should take two to five tries to align the receiver.) 4) Carefully tighten the horizontal adjustment screws first and then the two vertical adjustment screws on the receiver bracket, making sure all three alignment LEDs remain lit. C) TRANSMITTER ALIGNMENT PROCEDURE: 1) Slowly move the transmitter back and forth, and up and down, trying to get all four LEDs to light. 2) If four LEDs light, adjust the alignment adjust pot on the receiver until only three alignment LEDs are on. REPEAT STEPS 1 AND 2 UNTIL IT IS IMPOSSIBLE TO GET MORE THAN THREE LEDs TO LIGHT. (NOTE: If steps 1 and 2 are carefully executed, it should take between two and five tries to achieve this.) 3) When it is impossible to get more than three LEDs to light, carefully tighten the horizontal adjustment screws and then the vertical adjustment screws on the transmitter bracket, making sure all three alignment LEDs stay lit. 4) Slide the alignment switch on the transmitter to the NORMAL MODE (N) position (see figure 15) and disconnect any temporary wiring. Carefully close the door on the transmitter and go to the receiver. 5) Verify that three alignment LEDs are lit and switch back to NORMAL MODE (N) at the receiver. It is important that three alignment LEDs are on (not four) when leaving alignment mode. This ensures that the amplifier is not saturated with signal and will be capable of detecting smoke within its sensitivity limits. Wait at least one minute before continuing. Do not block or disturb the beam while it is calibrating. Any interference could cause a trouble signal. If there is a trouble signal during this period, switch the receiver back to ALIGN MODE to make sure that only three LEDs are lit. Switch back to NORMAL MODE and wait again. If three alignment LEDs are not on, repeat the transmitter alignment procedure. 6) When the detector has completed it s self-calibration, the green (normal) operation LED will flash every two or three seconds. Alignment is now complete. Sensitivity Total obscuration can be converted to percent per foot, assuming uniform smoke density for the entire length of the beam. The chart below converts total obscuration to percent per foot at both 30% and 55% sensitivity settings. OBSCURATION (%/FT) 1.3 1.2 1.1 1 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 SENSITIVITY IN %/FT VS DISTANCE ASSUMING UNIFORM SMOKE DISTRIBUTION 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250 260 270 280 290 300 310 320 330 DISTANCE (FEET) = 30% Sensitivity Setting = 55% Sensitivity Setting A78-2321-00 D400-18-00 10 I56-494-11R

Sensitivity Testing NOTE: Before testing, notify the proper authorities that the smoke detector system is undergoing maintenance, and therefore the system will be temporarily out of service. Disable the zone or system undergoing maintenance to prevent unwanted alarms. Detectors must be tested after installation and following periodic maintenance. The sensitivity of the 6424 may be tested as follows: NOTE: Before testing the detector, check for the presence of the flashing green LED at the receiver, making sure not to disturb or block the beam. If it does not flash and the detector is not in trouble or alarm, power has been lost to the detector (check the wiring). A. Calibrated Test Filter 1. Test the detector at the receiver. 2. Use the proper side of the test card depending on the sensitivity setting (55 or 30) of the detector. Maintenance NOTE: Before cleaning the detector lenses, notify the proper authorities that the smoke detector system is undergoing maintenance, and therefore the system will be temporarily out of service. Disable the zone or system undergoing maintenance to prevent unwanted alarms. 1. Carefully clean the lenses of both the receiver and the transmitter. A damp soft cloth with a mild soap may be used. Avoid products with solvents or ammonia. 2. After the lenses are clean, switch the receiver to the align mode. If three and only three alignment LEDs turn on, slide the align switch back to normal mode and wait approximately one minute for self calibration. The green LED should pulse after the calibration time. If more or fewer LEDs turn on in align mode, see the Beam Alignment Instructions on page 9 for realignment. 3. Notify the proper authorities that the system is back on line. 3. Place the NO ALARM section of the test filter over the receiver lens. The green LED should continue to pulse and the detector should not alarm after 15 seconds. 4. Place the ALARM section of the test filter over the lens. The detector should alarm within 15 seconds. 5. The detector can be reset with the local reset, remote reset, or by momentarily interrupting the power. 6. Notify the proper authorities that the system is back on line. Detectors that fail to alarm should be returned for repair. Units that alarm during the non-alarm test (step 3) should be cleaned and tested again before being returned. Follow the maintenance instructions for cleaning. B. Remote Test Switch The remote test station, RTS451, can be used with the 6424 beam smoke detector. Follow instructions included with the test station for proper use. See Figure 9 (Remote Test Station) for wiring diagram. If the detector is not in trouble and the unit fails to alarm, check all related wiring. Once the proper wiring is confirmed, perform the above calibrated test filter procedure. If the unit still fails to alarm it should be returned for repair. D400-18-00 11 I56-494-11R

Please refer to insert for the Limitations of Fire Alarm Systems Three-Year Limited Warranty System Sensor warrants its enclosed smoke detector to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this smoke detector. No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company s obligation of this Warranty shall be limited to the repair or replacement of any part of the smoke detector which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. After phoning System Sensor s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defective units postage prepaid to: System Sensor, Repair Department, RA #, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to repair or replace units which are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company s negligence or fault. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state. FCC Statement This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: Reorient or relocate the receiving antenna. Increase the separation between the equipment and receiver. Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. Consult the dealer or an experienced radio/tv technician for help. D400-18-00 12 I56-494-11R 2000 System Sensor