Introduction System Schematic ADDRESSABLE SPUR CIRCUIT LOOP 1 ADRRESSABLE LOOP ~ CONVENTIONAL SOUNDERS LOOPS 2-4 ~ CONVENTIONAL SOUNDERS MODBUS OUTPUT TO BMS SYSTEM BACNET OUTPUT TO BMS SYSTEM SITE MONITOR SYSTEM SITE GRAPHICS SYSTEM CF3000 ~ CW9000 ~ CTPR3000 ~ EC700 LON-FO CFSFL01 EC200 EXT 24V EC650 EXT 24V ECO232 ECO232 NC NC NC FIBRE OPTIC ~ NC LOCAL AREA NETWORK NC ~ UP TO MAX 126 NETWORK NODES EXT 24V EC400 EC400 EC540 CF1100/1200 CF3000
Introduction Network Schematic Max 126 nodes Control Panels, Network Repeaters, Network Modules Topology Fire rated RS485 screened twisted pair, ie, Draka 910234 1000m cable max of copper network between boosters Data Available Panel Number, Loop Number, Device No. / Desc / type, Zone No. / desc MODBUS OUTPUT TO BMS SYSTEM BACNET OUTPUT TO BMS SYSTEM SITE MONITOR SYSTEM SITE GRAPHICS SYSTEM CF3000 ~ CW9000 ~ CTPR3000 ~ EC700 LON-FO CFSFL01 EC200 EXT 24V EC650 EXT 24V ECO232 ECO232 NC NC NC FIBRE OPTIC ~ NC LOCAL AREA NETWORK NC ~ UP TO MAX 126 NETWORK NODES EXT 24V EC400 EC400 EC540 CF1100/1200 CF3000
Introduction Advanced Network Modules Range NCDR Dual Redundancy Network Card (V2) CFSFL01/02 LON (network) to Fibre Optic interface, max 15K FO length EC400 LON (network) to TCP/IP interface EC540 LON (network) booster, splits network and resends data to increase range ECO232 LON (network) to RS232: Site Graphics & Site Monitor EC200 LON (network) to BMS Gateway EC650 LON (network) to BACnet interface EC700 BMS Gateway to ModBus interface
Standard Hardware Standard Network Card Connections Cable Enhanced fire rated data cable, Max 1000m length Draka 910234 2 core twisted pair with screen Screening Connect screen to ground at one end only Termination Resistor termination 102 (2 x 51 ) per card Radial Network Remove resistors at all network cards except the two ends 102 at each end = 51 across network Ring Network Remove resistors at all network cards except one Link out 1 resistor leaving 51 across network EC540 Booster: treat the network either side as separate networks NETWORK CONNECTIONS A-X, B-Y OUT IN Y X B A TERMINATION RESISTORS RIBBON CABLE TO CONTROL PANEL
Standard Hardware Standard Network Termination Radial Network Remove resistors at all network cards except the two ends 102 at each end = 51 across network PANEL 1 OF 4 PANEL 2 OF 4 PANEL 3 OF 4 PANEL 4 OF 4 102 NONE NONE 102
Standard Hardware Standard Network Termination Radial Network with Booster Remove resistors at all network cards except the two ends 102 at each end = 51 across network PANEL 1 OF 4 PANEL 2 OF 4 PANEL 3 OF 4 EC540 BOOSTER 24V SUPPLY 102 NONE 102 102 TO NEXT PANEL ETC
Standard Hardware Standard Network Termination Ring Network Remove resistors at all network cards except one Link out 1 resistor leaving 51 across network PANEL 1 OF 4 PANEL 2 OF 4 PANEL 3 OF 4 PANEL 4 OF 4 51 NONE NONE NONE
Standard Hardware Standard Network Termination Resistor Termination on network card 102 (2 x 51 resistor) To give 51 reading across network pair at any point Radial Network Remove resistors at all network cards except the two ends 102 at each end = 51 across network Ring Network Remove resistors at all network cards except one Link out 1 resistor leaving 51 across network A B 51 51 All () None (no resistor) One (51 ) Terminal Mounted A B A 51 51 B O/C A B 51 S/C 102 LEAVE ALL RESISTORS INTACT CUT HERE TO REMOVE FROM CIRCUIT SOLDER LINK ACROSS ONE RESISTOR SOME DEVICES MAY NOT HAVE INBUILT RESISTORS
NCDR: Network Card Dual Redundancy Dual Network Channels Cable Enhanced fire rated data cable, Max 1000m length Draka 910234 2 core twisted pair with screen Screening Connect screen to ground at one end only Termination As per standard network card, but for each channel NETWORK 2 CONNECTIONS IN-OUT SCREEN CONNECTIONS OUT IN NETWORK 1 CONNECTIONS IN-OUT OUT IN Y X B A TERMINATION RESISTORS RIBBON CABLE TO CONTROL PANEL
NCDR: Network Card Dual Redundancy Dual Network Channels Network 1 and Network 2 Automatic Switching in event of fault Network Protocol V2 option must be selected PANEL 1 OF 4 PANEL 2 OF 4 PANEL 3 OF 4 PANEL 4 OF 4 51 51 NONE NONE NONE NETWORK CHANNEL 1 NETWORK CHANNEL 2
CFSFL01/02: Lon (Network) to Fibre Optic Interface Single or Dual Channel Requires 2 for a dual network Fibre Single Mode x 2 (Tx & Rx) 9/125 micron 15Km max SC Type connectors FIBRE CONNECTIONS 0V SCREEN NETWORK A NETWORK B
CFSFL01: Lon (Network) to Fibre Optic Interface Single Channel network Radial, ring or part network PANEL 1 OF 4 PANEL 2 OF 4 PANEL 3 OF 4 PANEL 4 OF 4 NONE NONE 2 x SINGLE MODE FIBRE
CFSFL01: Lon (Network) to Fibre Optic Interface Single Channel network Radial, ring or part network PANEL 1 OF 4 PANEL 2 OF 4 PANEL 3 OF 4 PANEL 4 OF 4 NONE 1021 2 x SINGLE MODE FIBRE
CFSFL02: Lon (Network) to Fibre Optic Interface Dual Channel network Radial, ring or part network PANEL 1 OF 4 PANEL 2 OF 4 PANEL 3 OF 4 PANEL 4 OF 4 2 x SINGLE MODE FIBRE
CFSFL01/2: Lon (Network) to Fibre Optic Interface Many possible combinations PANEL 3 OF 7 PANEL 5 OF 7 PANEL 1 OF 7 PANEL 2 OF 7 PANEL 4 OF 7 PANEL 6 OF 6 PANEL 7 OF 7 CFSFL01 or CFSFL02 CFSFL02 CFSFL02 CFSFL02 CFSFL01 or CFSFL02 2 x SINGLE MODE FIBRE
EC400: Lon (Network) to TCP/IP Interface Network via PC network / internet / etc Requires 2 for a dual network Use Hyper Terminal for configuration IP address Inbuilt Web Server for IP configuration IP address Passwords PROGRAMMING NETWORK CONNECTION ETHERNET CONNECTION 24V DC
EC400: Lon (Network) to TCP/IP Interface Requires fixed IP address Useful for facilities management PANEL 3 OF 3 PANEL 1 OF 3 PANEL 2 OF 3 NETWORK NETWORK
EC540: Lon (Network) Booster Extend radial network length Effectively splits a network into multiple networks Requires 2 for a dual network Max 5 per network Any more may cause transmission delays NETWORK CONNECTION
EC540: Lon (Network) Booster Radial Network Terminate network either side of booster PANEL 1 OF 3 PANEL 2 OF 3 PANEL 3 OF 3 NONE 1000M MAX 1000M MAX
EC0232: Lon (Network) to RS232 Interface PC connection No network address required Versions EC0232: Site Monitor, Site Graphics, EC0232PAVA: EVAX HMX PAVA EC0232PAVA3D: EVAX HMX PAVA 3 minute time delay
EC0232: Lon (Network) to RS232 Interface Typical Example PANEL 1 OF 2 PANEL 2 OF 2 SITE GRAHICS OR SITE MONITOR EC0232 1000M MAX
EC200: Lon (Network) to BMS Gateway Translation for BMS connection Requires EC700
EC700: BMS Gateway to MODbus interface Translation for BMS connection Requires EC700 Verify requirement spec as protocol implementation may vary
MODbus Interface Typical Example PANEL 1 OF 2 PANEL 2 OF 2 EC200 EC700 MODBUS SYSTEM 1000M MAX
EC650 to BACnet interface Translation for BMS connection Direct network connection Verify requirement spec as protocol implementation may vary
BACnet Interface Typical Example PANEL 1 OF 2 PANEL 2 OF 2 EC650 BACNET SYSTEM 1000M MAX
Network Standard Network Setup At each control panel Number of panels on network Panel Address E.g., Panel 1 of 4 Network Response (to commands received) Silence Reset Evacuate Fire Fault Pre Alarm Network Filter Select which Panels to respond to
Operation Fault Finding a Network Lon Network Error Check panel address and totals settings Check network termination Check network cable insulation and continuity readings Misc Hard reset panel, then clear watchdog fault with soft reset Generate fire or fault and check transmission and reset